Eaton AtLite Sure-Lites SELDWA29SD, AtLite Sure-Lites ATLELDWA100SD Installation Instructions Manual

AtLite
Sure-Lites
Installation Instructions for the Sure-Lites SELDWA29SD/ATLELDWA100SD Emergency Light with Self Diagnostics
WARNING
Risk of Fire / Electric Shock
If not qualifi ed, consult an electrician.
Important Safeguards
When using electrical equipment, basic safety precautions should always be observed including the following:
Do not use in hazardous locations, or near gas or elec-
tric heaters.
Do not let power supply cords touch hot surfaces.
Use caution when servicing batteries. Battery acid can
cause burns to skin and eyes. If acid is spilled on skin or in eyes, fl ush acid with fresh water and contact a physician immediately.
Do not use this equipment for other than the intended use.
Installation is to be performed only by quali ed person­nel.
Install in accordance with National Electric Code and local regulatory agency requirements.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tamper­ing by unauthorized personnel.
SAVE THESE INSTRUCTIONS
Maximum Mounting Height: 8.6 ft.
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before installing or servicing.
INSTALLATION
1. De-energize the circuit at the junction box (J-box) where the emergency light is to be installed.
2. Open the emergency light by inserting a fl at screw- driver in the two slots on the side of the unit, then turning to separate housing from the backplate.
3. To mount to a junction box ­mounting pattern and the wire pass hole in the back­plate and the back gasket to fi t the J-box being used.
4. To mount to conduit – Unscrew the ½” NPT plug locat­ed at the top of the fi xture and screw in the user-sup- plied conduit hub.
5. Once the backplate is secured, the housing can be held in place during installation with the help of the grounding wire
6. Connect the incoming wires to the SELDWA29SD/
ATLELDWA100SD power supply wires using the wire nuts provided. housing. connect the black wire to the hot lead. If using 277V, connect the orange wire to the hot lead. Cap the unused lead. Secure the emergency light to the wall and/or junction box using installer supplied hardware.
7. Complete the battery connection and snap the cover onto the backplate.
8. Energize AC supply. The test button should illuminate, and LED heads will illuminate briefl y when the test button is pushed.
9. Adjust the heads as needed. The SELDWA29SD/
ATLELDWA100SD lenses utilize a highly directional beam, and the lenses can be rotated to adjust the beams to the
front or sides of the fixture (see Fig. 2 next page).
(see Fig. 1 next page).
Connect the green grounding wire for the
Connect the white wire to neutral. If using 120V,
Knock out/drill out
the appropriate
ACTIVATING TIME DELAY
OPERATION
The SELDWA29SD/ATLELDWA100SD has an integrated time delay circuit that allows them to remain in emergency mode 15 minutes after power is restored.
To activate the time delay, remove the jumper on the circuit board labeled TDI/J1.
Figure 1
Green(Grounding wire)
Figure 2
The Sure-Lites Eagle Eye Self Diagnostics is continuous­ly monitoring your emergency fi xture, and will signal any failure through the 3 color indicator LED.
INITIAL OPERATION
When the unit is fi rst powered up, it will go into a 24 hour fast charge, indicated by the indicator LED pulsing green. Once the unit has fully charged, it will perform a self cali­bration, after which the LED will change to steady green, indicating the unit is fully charged and fl oat charging the battery to maintain readiness.
AUTOMATIC TESTING
The unit will perform a battery capacity, lamp/LED, and charge circuit test every 30 days for 30 seconds. During this time, the indicator LED will change to a steady yellow. It will perform a full battery capacity (90 minute) test once per year. During this time, the indicator LED will change to a blinking yellow.
MANUAL TESTING
10 Second “Installation” test – Press and release the test button once during fast charge (blinking green) to initiate a 10 second quick test. The sign will switch to emergency mode for 10 seconds allowing the installer to verify proper installation of the unit, and the LED indicator will turn solid yellow.
30 Second Test - Press and release the test button once during fl oat charge (steady green). The indica- tor LED will turn steady yellow to indicate the unit is performing a 30 second test of the batteries and lamps/ LEDs.
90 Minute Test - Press and release the test button a second time during a 30 second test (steady yellow) to change to a 90 minute test. During this test, the LED indicator will change to blinking yellow, and the circuit will perform a full battery capacity, charge circuit, and LED test.
Canceling Test – Press and release the test button during the 90 minute test (fl ashing yellow) to return the
xture to its original state (fast charge or fl oat charge).
LASER TEST:
The SELDWA29SD/ATLELDWA100SD is equipped with a Laser Test function, that allows the unit to be manually tested without the need to physically press the test button. Shining a laser pointer in the hole marked “LASER TEST” on the bottom of the unit has the same effect as a press and release of the test button.