Eaton ATC-600 Instructions For Installation, Operation And Maintenance

Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Description Page
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . 7
Appendix A: Status Display Messages . . . . . . . . . . . . . 27
Appendix B: Historical Display Information . . . . . . . . . . 28
Appendix C: Time/Date Display Information . . . . . . . . . 30
Appendix D: ATC-600 Menu Tree . . . . . . . . . . . . . . . 31
Appendix E: Operational Flowcharts . . . . . . . . . . . . . . . 33
IB ATS-1005 For more information visit: www.eaton.com
Instructional Booklet
Page 2 Effective: March 2010
CAUTION
THE ATC-600 IS FACTORY PROGRAMMED FOR A SPECIFIC TRANS­FER SWITCH. DO NOT ATTEMPT TO INTERCHANGE ATC-600 CON­TROL DEVICES WITHOUT CONSULTING THE FACTORY.
All possible contingencies which may arise during installation, operation, or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of his equipment, the local Eaton representative should be contacted.
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
Section 1: Introduction
1.1 Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects associ­ated with the installation, application, operation and maintenance of the ATC-600. It is provided as a guide for authorized and quali­fied personnel only in the selection and application of the ATC-
600. Please refer to the specific WARNING and CAUTION in Sec­tion 1.1.2 before proceeding. If further information is required by the purchaser regarding a particular installation, application or maintenance activity, a Eaton representative should be contacted.
NOTICE
DURING CONVERSATIONS WITH EATON CONCERNING TROUBLE­SHOOTING OR PRODUCT RETURN, THE CUSTOMER MAY BE ASKED FOR INFORMATION PERTAINING TO THE SOFTWARE VERSION AND OPTIONS INCLUDED IN THE SPECIFIC UNIT. REFER TO THE “NOTE” UNDER THE TOPIC “HELP PUSHBUTTON” IN PARAGRAPH 3.4 FOR INSTRUCTIONS ON HOW TO OBTAIN THIS INFORMATION.
1.1.1 Warranty and Liability Information
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WAR­RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF MER­CHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CON­TAINED HEREIN. In no event will Eaton be responsible to the pur­chaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or conse­quential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its cus­tomers resulting from the use of the information and descriptions contained herein.
1.1.2 Safety Precautions
All safety codes, safety standards and/or regulations must be strictly observed in the installation, operation and maintenance of this device.
WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO­CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEADING IS SHOWN IN REVERSE TYPE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTA­TION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW.
CAUTION
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRE­SENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL­LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMA­NENT EQUIPMENT DAMAGE.
For more information visit: www.eaton.com IB ATS-1005
Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Effective: March 2010 Page 3
1.2 Background
Transfer switches are used to protect critical electrical loads against loss of power. The load’s normal power source is backed up by a secondary (emergency) power source. A transfer switch is connected to both the normal and emergency sources and sup­plies the load with power from one of these two sources. In the event that power is lost from the normal source, the transfer switch transfers the load to the secondary source. Transfer can be automatic or manual, depending upon the type of transfer switch equipment being used. Once normal power is restored, the load is transferred back to the normal power source.
In automatic transfer switch equipment, the switch’s intelligence system initiates the transfer when normal power fails or falls below a preset voltage. If the emergency source is a standby gen­erator, the transfer switch initiates generator starting and trans­fers to the emergency source when sufficient generator voltage is available. When normal power is restored, the transfer switch automatically transfers back and initiates engine shutdown.
An automatic transfer switch consists of three basic elements:
1. Main contacts to connect and disconnect the load to and from
the source of power
2. A transfer mechanism to affect the transfer of the main con-
tacts from source to source
3. Intelligence/supervisory circuits to constantly monitor the con-
dition of the power sources and thus provide the intelligence necessary for the switch and related circuit operation
This manual deals with the third basic element of the automatic transfer switch, the required intelligence/ supervisory circuits. Prior to the introduction of ATC-600, this function was performed by a door mounted logic panel. The logic panel could be the relay logic type or the solid state logic type. In either case, the panel consisted of a number of individually mounted and wired devices offering a limited amount of system flexibility, especially in the case of the relay logic design. ATC-600 brings intelligence, super­visory and programming capabilities, never before available, to automatic transfer switch equipment.
1.3 Product Overview
The ATC-600 is a comprehensive, multi-function, microprocessor based automatic transfer switch controller. It is a compact, self­contained, panel mounted device designed to replace traditional relay and solid state logic panels (Figures 1 and 2).
Designed to meet the needs of markets worldwide, ATC-600:
Is a UL Recognized Component
Meets Seismic Requirements of Uniform and California Building
Codes (exceeding requirements of worst case Zone 4 levels)
Complies with UL 991 environmental tests
Complies with IEC 61000-4-2, 61000-4-3, 61000-4-4, and
61000-4-5
Complies with CISPR 11, Class A
Complies with FCC Part 15, Subpart B, Class A
ATC-600 provides an unmatched degree of programmed flexibility to address the needs of any system. It operates from most system voltages available worldwide at 50 or 60 Hertz. In addition, a period of no control power operation is provided. ATC-600 moni­tors the condition of the 3-phase line-to-line voltage and frequency of both the Normal and Emergency sources. It can also be pro­grammed for single phase operation. ATC-600 provides the neces­sary intelligence to insure that the switch operates properly through a series of programmed sensing and timing functions.
A standard ATC-600 will:
Monitor Normal and Emergency source voltages and frequen-
cies
Provide undervoltage monitoring of Normal and Emergency
sources
Permit customer programming
Display real time and historical information
Permit system testing
Offer Help Screen assistance
Store customer/factory established parameters in nonvolatile
memory
Communicate using a PONI
Provide faceplate source/load status indications
A wide array of additional features are available to address the most sophisticated system requirements, such as:
Previously unavailable Load Monitoring and Delayed Transition
In-phase Transition
1.4 Functions/Features/Options
The primary function of ATC-600 is to accurately monitor power sources and provide the necessary intelligence to operate a trans­fer switch in an appropriate and timely manner. In addition, ATC-600 provides useful present and historical data, reliable two­way communications, and programming through the device’s face­plate or communications option. ATC-600 features proprietary microprocessor technology to provide and maintain superior preci­sion and versatility during both programming and data access.
1.4.1 Operational Simplicity
From installation to programming to usage, ATC-600 was designed with operational simplicity in mind. Only one style needs to be considered, regardless of input/output requirements or sys­tem voltages and frequencies. ATC-600 provides the functionality of numerous other devices combined in one package that mounts in less than 7 by 11 inches of panel space.
The user friendly front panel interface simplifies routine operation, programming, data presentation and setting adjustments. An LED based display provides the flexibility of large character displays for enhanced visibility. The operation of front panel membrane push­buttons moves the ATC-600 display from function to function or step to step within a function. Three LEDs at the top of the face­plate provide an immediate indication as to the device’s operational mode. An integral Help Mode provides immediate user assistance in the form of English language message displays through the use of a front panel Help pushbutton.
With a Product Operated Network Interface (PONI), the ATC-600 is communications ready and compatible with other devices in the IQ Family of products. The Communication Module (PONI) is avail­able in three versions, the INCOM PONI, RS-232 PONI and PONI Modem. Reliable two-way communications can be provided over a twisted pair communications network. With the INCOM PONI, ATC-600 is compatible with the Eaton IMPACC system.
1.4.2 Standard and Optional Features
A variety of programmable features are available to meet a wide variety of application requirements. Individual features or feature combinations provide the intelligence required to tailor switches to individual needs.
IB ATS-1005 For more information visit: www.eaton.com
Instructional Booklet
Page 4 Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
The features are factory activated, depending upon customer requirements. The specific variable setpoints associated with stan­dard and factory activated features are stored in a nonvolatile memory. Activated feature setpoints are available for customer adjustment. Any feature not selected and factory activated cannot be viewed or adjusted.
NOTICE
WITH RESPECT TO THEIR USE IN THIS DOCUMENT AND AS THEY RELATE TO AUTOMATIC TRANSFER SWITCH OPERATION, THE FOL­LOWING WORDS OR PHRASES ARE DEFINED:
Available
A source is defined as available when it is within its undervoltage/ overvoltage/underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting.
Fails
A source is defined as failed when it is outside of its undervoltage/ overvoltage/underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting.
Normal Source
The Normal Source is defined as the source that is preferred. The Preferred Source setting allows the operator to select Source 1, Source 2 or NONE as the Preferred Source. If NONE is chosen, the Preferred Source or the Normal Source will be the source that is presently attached to the load. If the Preferred Source feature is not available from the factory, the default is set as being Source 1 as the Preferred and Normal Source.
Emergency Source
The Emergency Source is defined as the source that is not pre­ferred. If NONE is chosen for the Preferred Source setting, the Emergency Source will be the source that is presently not attached to the load. Therefore, in this condition after a transfer, what was the Normal and Emergency Sources will switch between Source 1 and 2. If the Preferred Source feature is not available from the factory, the default is set with Source 2 as the Emergency Source.
Option #
For personnel who are familiar with previous transfer switch con­troller option specifications, an attempt at equivalence to some of the features is made.
ATC-600 features with a brief description follow. The actual pro­grammable setpoints for each feature are covered in Section 5.
Standard Feature: Time Delay Engine Start (TDES)
TDES is used where the source is an engine generator. It delays initiation of the engine start circuit in order to override momentary power outages and/or fluctuations. This timer and the associated engine start circuit will operate with or without control power. There are two separate start circuits, one for each source when applications of two generators are selected, although the same TDES timer value is used for both. When one generator is selected, this timer’s engine start circuit will operate on generator 2 for source 2. If the source that is being transferred to has a gen­erator and that source is already available, the TDES timer is bypassed.
Standard Feature: Time Delay Normal to Emergency (TDNE)
TDNE delays the transfer to the Emergency Source to permit sta­bilization of the Emergency power source before the transfer is made. This timer will begin the countdown from its setting value when the Emergency Source becomes available. If the Normal Source should become available during the countdown of this timer, the timer will be aborted.
Standard Feature: Time Delay Emergency to Normal (TDEN)
TDEN delays the transfer to the Normal Source to permit stabiliza­tion of the Normal power source before the transfer is made. This timer will begin the countdown from its setting value when the Normal Source becomes available. During the countdown of this timer, if the Normal Source should become unavailable, the timer will be aborted. If the Preferred Source is available and the Emer­gency Source fails while the TDEN timer is counting down, the TDEN timer will be bypassed.
Standard Feature: Time Delay for Engine Cool-Off (TDEC)
TDEC permits the generator to run under a no-load condition after a transfer from the generator source has been made. Countdown timing begins when the transfer is completed. In applications where two generators are selected, the same cool-off timer set­ting value is used for both.
Standard Feature: Time Delay Emergency Failure (TDEF)
TDEF is used where at least one source is an engine generator. TDEF will delay an available source from being declared unavail­able in order to override momentary generator fluctuations. This time delay is only implemented when the load is connected to a generator source. TDEF is not displayed when the number of gen­erators is zero.
CAUTION
CHANGING THE SYSTEM NOMINAL VOLTAGE OR FREQUENCY SET­POINTS WILL CAUSE PICKUP AND DROPOUT SETPOINTS TO CHANGE AUTOMATICALLY TO NEW DEFAULT VALUES.
Standard Feature : System Nominal Frequency (NOMF)
There are only two choices for system nominal frequency of the distribution system, 50 or 60 Hertz. The dropout/pickup, underfre­quency and overfrequency upper and lower setting limits are based on the nominal frequency value.
Standard Feature: System Nominal Voltage (NOMV)
This refers to the standard system nominal RMS line to line volt­age. A wide range (120 to 600) of sensing voltage is available to be programmed. The dropout/pickup, undervoltage and overvolt­age upper and lower setting limits are based upon the nominal voltage value.
Standard Feature: Undervoltage Monitoring for Source 1 (1UVD, 1UVP)
This feature constantly monitors Source 1 for an undervoltage condition. When the Source 1 voltage drops to a value equal to or below the undervoltage dropout setting, the source will become unavailable. The source’s voltage will then have to rise to a value that is equal to or above the pickup setting to become available again.
Standard Feature: Undervoltage Monitoring for Source 2 (2UVD, 2UVP)
This feature functions the same as Standard Feature (1UVD, 1UVP), except for Source 2 instead of Source 1.
Standard Feature: Underfrequency Monitoring for Source 2 (2UFD, 2UFP)
This feature functions the same as Optional Feature 26E, except for Source 2 instead of Source 1.
For more information visit: www.eaton.com IB ATS-1005
Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Effective: March 2010 Page 5
Standard Feature: Commit to Transfer During TDNE Timing (CTDNE)
This feature provides for selection as to whether or not commit­ment to transfer is desired when Time Delay Normal to Emergency countdown has begun. If no commitment is chosen and the Nor­mal Source returns to availability when the TDNE timer is counting down, the transfer is aborted and the engine generator (if applica­ble) is cooled down.
Standard Feature: Engine Test Mode (TMODE)
This feature provides selection of the type of test that can be initi­ated by the front panel Engine Test pushbutton. An engine test without transferring the load to it, or an engine test with a full transfer of the load to the engine can be chosen. Load testing is fail-safe. If the generator fails during testing for any reason, the ATC-600 will signal the transfer switch to return to normal. If dis­able test mode is chosen, the front panel pushbutton cannot be used to initiate a test.
Standard Feature: Test Engine Run (TER)
This feature provides selection of the length of time in hours and minutes that the ATC-600 will enable the generator contacts dur­ing an Engine Test that was initiated from the front panel pushbut­ton or for the plant exerciser feature, if applicable.
Standard Feature 5C: Overfrequency Monitoring for Source 2 (2OFD, 2OFP)
This feature constantly monitors Source 2 for an overfrequency condition. When the Source 2 frequency rises to a value equal to or above the overfrequency dropout setting, the source will become unavailable. The source’s frequency will then have to drop to a value that is equal to or below the pickup setting to become available again.
Standard Feature 5E: Overvoltage Monitoring for Source 2 (2OVD, 2OVP)
This feature constantly monitors Source 2 for an overvoltage con­dition. When the Source 2 voltage rises to a value equal to or above the overvoltage dropout setting, the source will become unavailable. The source’s voltage will then have to drop to a value that is equal to or below the pickup setting to become available again.
Standard Feature 8C/8D: Transfer Time Delay Bypass
This feature allows an external pushbutton input to be used to bypass the timer for Standard Feature (TDNE) or Standard Feature (TDEN) individually, or both simultaneously. This feature is usually used in testing when it is not desirable to wait for completion of the timing sequence.
Standard Feature 23: Plant Exerciser (EXER)
This feature provides for the automatic test operation of the gen­erator for a pre-selected weekly interval. When the test is running, pressing and releasing the Engine Test pushbutton will cancel the test. The day of the week, hour, and minute that exercising is desired can be programmed into the ATC-600. The type of test, whether a load transfer or just an engine test, can also be selected. Load testing is fail-safe. If the generator fails during test­ing for any reason, the ATC-600 will signal the transfer switch to return to normal.
Standard Feature 26C: Overvoltage Monitoring for Source 1 (1OVD, 1OVP)
This feature constantly monitors Source 1 for an overvoltage con­dition. When the Source 1 voltage rises to a value equal to or above the overvoltage dropout setting, the source will become unavailable. The source’s voltage will then have to drop to a value that is equal to or below the pickup setting to become available again.
Standard Feature 26D: Go To Emergency
This feature enables an external contact closure to initiate a trans­fer from the Normal Source to the Emergency Source. If the external contact is closed and the Emergency Source fails, the ATC-600 will transfer the load back to the Normal Source.
Standard Feature 26E: Underfrequency Monitoring for Source 1 (1UFD, 1UFP)
This feature constantly monitors Source 1 for an underfrequency condition. When the Source 1 frequency drops to a value equal to or below the underfrequency dropout setting, the source will become unavailable. The source’s frequency will then have to rise to a value that is equal to or above the pickup setting to become available again.
Standard Feature 26F: Overfrequency Monitoring for Source 1 (1OFD, 1OFP)
This feature constantly monitors Source 1 for an overfrequency condition. When the Source 1 frequency rises to a value equal to or above the overfrequency dropout setting, the source will become unavailable. The source’s frequency will then have to drop to a value that is equal to or below the pickup setting to become available again.
Optional Feature 9B: Maintenance Selector Switch (MSS)
Marked “OFF”, “ON”. This feature provides selector switch dis­connection of control to the transfer motor thus allowing testing of the transfer switch control logic circuitry without initiating load transfer. Manual disconnection is standard on all Eaton transfer switches. Positioning the MSS in the “OFF” position isolates the control circuit from the transfer motor, permitting manual opera­tion of the transfer switch or testing of logic circuitry without load transfer.
Optional Feature 10: Preferred Source Selection (PRF SRC)
This feature permits the selection of either source (1 or 2) as the Preferred or Normal Source. The Normal Source is the source that the switch always looks to for availability so that it can transfer to it. When two generators are selected and the switch has trans­ferred to the Emergency Source, the ATC-600 will constantly be waiting and attempting to start the generator on the Preferred Source so that it may return to it. IF NONE is chosen, the Pre­ferred Source or the Normal Source will be the source that is pres­ently attached to the load.
Optional Feature 16: Overcurrent Protection
When integral overcurrent protection is provided for either one or both sources, the need for separate upstream overcurrent protec­tion, in most instances, is eliminated. With this factory installed feature in the ATC-600, further automatic transfer operation is locked-out until the appropriate source breaker is reset.
Optional Feature 29G: Type of Operation (Selectable Automatic or Manual)
This feature provides a two position selector switch marked Auto/ Manual which permits the selection of automatic or manual opera­tion. It includes devices for manual operation when the selector switch is in the manual position.
Optional Feature 29J: Type of Operation (MANTR)
This feature provides for a selection between an automatic trans­fer and re-transfer mode or a manual pushbutton re-transfer to Normal from the Emergency Source mode. If this option is not selected the factory default selection is automatic.
IB ATS-1005 For more information visit: www.eaton.com
Instructional Booklet
Page 6 Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
Optional Feature 32A: Time Delay Neutral (TDN)
This feature provides a time delay in the transfer switch Neutral position when both breakers are open. This delay takes place when the load is transferred in either direction to prevent exces­sive in-rush currents due to out-of-phase switching of large motor loads. This feature is not available with the Neutral Load Sense Delay (TDNLD) feature.
Optional Feature 32B: Load Voltage Decay (LDCY)
This feature utilizes the load voltage measurements to sense back EMF that is generated when the transfer switch is in the Neutral position. It provides a delay in transfer in either direction if an unacceptable level is sensed as established by a customer pro­grammed level. The transfer will not take place until the back EMF decays below the acceptable programmed level. This feature has a separate setting of enabling or disabling the operation. If disabled, the transfer switch will not delay in the Neutral position and will transfer between the sources as fast as possible. This feature is not available with the Time Delay Neutral (TDN) Feature 32A.
Optional Feature 32C: In-Phase/Load Voltage Decay
In-phase transition is a feature that will allow a transfer between two live sources only when the phase difference between the two sources is near zero. This is an open transition transfer that pre­vents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Load Voltage Decay utilizes the load voltage measurements to sense back EMF that is generated when the transfer switch is in the Neutral position. It provides a delay in transfer in either direc­tion if an unacceptable level is sensed as established by a cus­tomer programmed level. The transfer will not take place until the back EMF decays below the acceptable programmed level. This feature has a separate setting of enabling or disabling the opera­tion. If disabled, the transfer switch will not delay in the Neutral position and will transfer between the sources as fast as possible. This feature is not available with the Time Delay Neutral (TDN) Feature 32A.
Optional Feature 32D: In-Phase/Time Delay Neutral
In-phase transition is a feature that will allow a transfer between two live sources only when the phase difference between the two sources is near zero. This is an open transition transfer that pre­vents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Time Delay Neutral provides a time delay in the transfer switch Neutral position when both breakers are open. This delay takes place when the load is transferred in either direction to prevent excessive in-rush currents due to out-of-phase switching of large motor loads. This feature is not available with the Neutral Load Sense Delay (TDNLD) feature.
Optional Feature 35: Pre-Transfer Signal (TPRE)
Typically associated with elevator controls, this feature provides for the control of an addressable relay to remotely signal an eleva­tor that a re-transfer is about to take place. A permissive report­back signal from the elevator, telling the ATC-600 that the eleva­tor has reached the floor and opened its doors, is also recognized to facilitate faster transfer operation. Should the permissive signal not be used or does not occur, the ATC-600 has a programmed overriding pre-transfer delay timer that can be set from 0 to 5 min­utes.
Optional Feature 36: Emergency Inhibit
This feature enables the Emergency Inhibit control input to inhibit transfers to the Emergency Source. See Control Inputs section for more information.
Optional Feature 37: Service Equipment
This factory programmed feature makes the transfer switch suit­able for a service equipment rating by responding to a Go-To-Neu­tral input.
Optional Feature 45: Load Sequencing Capability (TSEQ)
This feature provides the sequential closure of up to 10 remote relays after a transfer. A customer programmed time delay is available to delay closure between each of the relays.
Optional Feature 46: Potential Transformer (PT) Ratio
This feature allows external voltage transformers to be used on the ATC-600’s source and load sense inputs. Once this option is enabled, the PT Ratio setpoint can be adjusted in steps of 1, between 2:1 and 500:1. Also when this option is enabled the Nominal System Voltage setting will be fixed at 120 or 110 volts, depending upon the Nominal System Frequency setting. If the Nominal System Frequency setting is 60Hz then the Nominal Sys­tem Voltage will be fixed at 120 volts and all voltage pick-up and drop-out setpoints will be based upon the 120 volt level. The same is true of a Nominal System Frequency of 50Hz whose Nom­inal System Voltage will be fixed at 110 volts. The metering dis­play will use the PT ratio value to calculate and display the load and source voltages with up to three significant digits. There will be four possible types of displays, as an example they could dis­play 999K, 99.9K, 9.99K, or 999 volts.
48: Communication Modules
Provides communications modules for the ATC-600 and ATC-800 transfer switch controllers. These controllers are PowerNet and Modbus compatible devices. A separately mounted communica­tions module will enable the automatic transfer controller to be remotely monitored controlled and programmed via the network.
48F: RS-232 and RS-485 with Modbus
Provides communications for the ATC-600 via RS-232 or Modbus through an RS-485 port. Registers are available to read back sta­tus, voltages, frequencies, and historical data. Registers are also available for transfer switch control. Setpoints may be read back and/or programmed via a pass-through command.
For more information visit: www.eaton.com IB ATS-1005
Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Effective: March 2010 Page 7
Section 2: Hardware Description
2.1 General
The purpose of this section is to familiarize the reader with ATC­600 hardware, its nomenclature, and to list the unit’s specifica­tions. The information presented is divided into the following four parts:
Operator Panel
Rear Access Area
External Hardware
Specification Summary
2.2 Operator Panel
The operator panel, which is normally accessible from the outside of a panel or door, provides a means for:
Being alerted to specific conditions
Receiving functional help
Programming
Parameter Monitoring/Selection/Metering
LEDs, a display window, pushbuttons, and a mimic bus make up the front accessible operator panel (Figure 1).
Seventeen individual LEDs are lit when performing or indicating a specific function. For detailed information on individual LEDs refer to Paragraph 3.2.
The LED type display window is used to display all ATC-600 mon­itored parameters, setpoints and messages in easy to read for­mats. The alpha numeric display is approximately 0.75 by 4.25 inches and is able to display up to eight characters at a time. For details concerning the kind of information that can be viewed in the display window refer to Paragraph 3.3.
The front operator panel supports six long-life membrane pushbut­tons. Pushbuttons accomplish their function when pressed and released. Refer to Paragraph 3.4 for information concerning the function of specific pushbuttons.
2.3.2 Right Rear of Chassis
The right rear of the chassis provides a port that will accept the D-sub male connector of the optional Communication Module (PONI). A self locking female connector J7 is provided for Sources 1 and 2 control power input.
Customer programming is provided through the Program/Run Tog­gle Switch. While the switch is in the Program position, the ATC-600 continues to operate in keeping with previously pro­grammed setpoints.
Terminal block J5 provides dry relay contacts for primary control outputs. Physically these relays are comprised of two latching Form A relays for generator start contacts, and seven conven­tional coil Form C relays necessary to complete the electrical con­trol function.
2.3 Rear Access Area
The rear access area of the ATC-600 is normally accessible from the rear of an open panel door (Figure 2).
All wiring connections to the ATC-600 are made at the rear of the chassis. For the sake of uniform identification, the frame of refer­ence when discussing the rear access area is facing the back of the ATC-600 with the panel door open. The communication module port, for example, is located on the upper right rear of the unit. The Run/Program Switch, used to determine the ATC-600 Mode, is located in the lower right near the control power inputs. Detailed information relative to any connection made to the rear access area is presented in Section 4 entitled “Operation.”
2.3.1 Left Rear of Chassis
The left rear of the chassis provides self locking female connec­tors J1, J2 and J3 for voltage monitoring of Source 1 (S1), Source 2 (S2) and the Load respectively. Terminal block J4 pro­vides DC wetted connections for various functional inputs. See Paragraph 4.3 for more information on input functionality.
IB ATS-1005 For more information visit: www.eaton.com
Instructional Booklet
1. ATC-600 Faceplate (UV Resistant)
2. Operational Mode LEDs (highlighting ATC-600’s
present operational condition)
3. System Status Mimic Bus (easy to read and under­stand LED type)
4. Display Window (easy to read monitored parameters, setpoints and messages)
5. Display LEDs (seven LEDs to identify the Display Win­dow Information)
6. Help Pushbutton (provides English language help information in any operational mode)
7. Increase/Decrease Pushbuttons (used individually, pushbuttons move displayed information/setting up or down through all possibilities – used simultaneously while viewing historical logged values, values reset to zero)
8. Step Pushbutton (used to step through different avail­able information within the category being displayed)
9. Display Select Pushbutton (used to move the display through the categories represented by the 7 LEDs under the display)
10. Engine Test Pushbutton (pushed and released twice to initiate a self test in Run or Program Modes
Page 8 Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
Figure 1. ATC-600 Operator Panel.
For more information visit: www.eaton.com IB ATS-1005
Instructions for Installation, Operation and Maintenance of the
LEFT SIDE VIEW
Communication Module
Connector
J4 (Inputs) Terminal Block
(DC Wetted Contact)
J5 (Outputs) Terminal
Block (Dry Relay Contacts)
J1, J2, J3 Source/Load Connectors
Program/Run
Toggle Switch
J7 Sources 1 and 2
Control Power
Connector
RIGHT SIDE VIEW
ATC-600 Controller - Breaker Type (CAT#8160A00G41)
Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Effective: March 2010 Page 9
Figure 2. ATC-600 (Left and Right Side Views).
2.4 External Hardware (Communication Module)
External hardware is viewed as any optional device mounted directly to or remotely from the ATC-600, such as a communica­tion module. Communications is made possible by mounting a small, addressable communication module (PONI) to the back of the ATC-600 (Figure 3) or in a remote location. Since the ATC­600 is always supplied with a communications port, a PONI can be easily retrofitted to the ATC-600 at any time. It is recom-
mended that the control power to the ATC-600 be removed prior to connecting or disconnecting a PONI. When using the INCOM
PONI on the ATC-600, the PONI function switches should be set to either of the Standard PONI modes (PONI 9600 Baud or PONI 1200 Baud). Refer to the instruction details supplied with the PONI for details.
IB ATS-1005 For more information visit: www.eaton.com
Figure 3. Communication Module - PONI (mounted).
Instructional Booklet
Page 10 Effective: March 2010
2.5 Specification Summary
Refer to Table 1.
Table 1. ATC-600 Specifications
PARAMETER SPECIFICATION
Control Power: • 120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Power Consumption: • 18VA
Environmental Conditions:
Operating Temperature • -20° to 70°C
Operating Humidity • up to 90% Relative Humidity (non-condensing)
Enclosure Compatibility: • NEMA 12 (standard mounting)
System Voltage Application: • 120 to 600 Vac (50/60 Hz) (single or three phase)
Voltage Measurements: • Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System)
Voltage Measurement Range: • 0 to 700 Vac
Voltage Measurement Accuracy: • ±1% of Full Scale
Frequency Measurements: • Source 1 and Source 2
Frequency Measurement Range: • 40 to 80 Hz
Frequency Measurement Accuracy: • ±0.1 Hz
Undervoltage Dropout Range (Volts)
Breaker Switch Style ATS 50 to 97% of Nominal System Voltage
Undervoltage Pickup Range (Volts)
Breaker Switch Style ATS (Dropout +2%) to 99% of Nominal System Voltage
Overvoltage Dropout Range (Volts)
Breaker Switch Style ATS 105 to 120% Nominal System Voltage
Overvoltage Pickup (Volts)
Breaker Switch Style ATS 103% to (Dropout-2%) of Nominal System Voltage
Underfrequency Dropout (Hertz)
Breaker Switch Style ATS 90 to 97% of Nominal System Frequency
Underfrequency Pickup (Hertz)
Breaker Switch Style ATS (Dropout +1 Hz) to 99% of Nominal System Frequency
Overfrequency Dropout (Hertz)
Breaker Switch Style ATS 103 to 110% of Nominal System Frequency
Overfrequency Pickup (Hertz)
Breaker Switch Style ATS 101% to (Dropout -1 Hz) of Nominal System Frequency
Applicable Testing: • UL Recognized Component
• NEMA 4/4X (mounted with gasket between panel and device faceplate)
• NEMA 3R (outdoor)
• UV Resistant ATC-600 Faceplate
• Meets Seismic Requirements of Uniform and California Building Codes (exceeding requirements of worst case Zone 4 levels)
• Complies with UL 991 environmental tests
• Complies with IEC 61000-4-2, 61000-4-3, 61000-4-4, and 61000-4-5
• Complies with CISPR 11, Class A
• Complies with FCC Part 15, Subpart B, Class A
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
For more information visit: www.eaton.com IB ATS-1005
Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller
Instructional Booklet
Effective: March 2010 Page 11
Section 3: Operator Panel
3.1 General
The operator panel, which is normally accessible from the outside of a panel or door, provides a means for being alerted to specific conditions, receiving functional help, programming, and parameter monitoring/selection (Figure 1). For the purpose of familiarization, the panel is divided into three sub-sections and discussed individ­ually:
LEDs
Pushbuttons
Display Window
NOTICE
WITH RESPECT TO THEIR USE IN THIS DOCUMENT AND AS THEY RELATE TO AUTOMATIC TRANSFER SWITCH OPERATION, THE WORDS “CYCLE” AND “EVENT” ARE DEFINED AS FOLLOWS:
CYCLE –A COMPLETE OPERATION FROM NORMAL TO EMERGENCY TO NORMAL.
EVENT –A FAILURE RESULTING IN SOM E T YP E OF SWITC H AND/OR SWITCH INTELLIGENCE ACTION.
NOTICE
REFER TO APPENDIX D FOR AN OVERALL VIEW OF ATC-600 OPER­ATIONS IN THE FORM OF A MENU TREE.
3.2 LEDS
LEDs are used to indicate the device’s mode of operation, the status of the system, and the operations and/or conditions of displayed functions. Three LEDs at the top of the ATC-600 provide a quick snapshot of the unit’s status (Mode). Seven LEDs, just above the display window, indicate which portions of the mimic bus are active, and the actual status of both sources and load. The remain­ing seven LEDs, just below the display window, are lit to indicate the identity of information being displayed.
Automatic Mode LED
This LED blinks green indicating that the ATC-600 is operating and providing the transfer switch control function in keeping with programmed setpoints. If the LED is not lit or is on continuously, a problem may be indicated.
Test Mode LED
This LED is lit red upon entering the Test Mode. The Test Mode can only be entered with the LEDs below the display window not lit. When a test is initiated, the Status LED lights. Both LEDs will turn off upon the successful completion of a test cycle.
Program Mode LED
This LED is lit red when the Run/Program switch on the rear of the chassis is in the Program position. This condition permits pro­gramming of control setpoints. When the setpoints LED is lit indi­cating that existing setpoints can be changed, the Program Mode LED blinks.
Source 1 Available - Status LED
This LED is lit amber if Source 1 meets the criteria for pro­grammed Source 1 setpoints.
Source 1 Preferred - Status LED
This LED is lit red if Source 1 is the preferred source choice.
Source 1 Connected - Status LED
This LED is lit green if Source 1 is connected. This is accom­plished by sensing the Source 1 breaker via the S1 closed auxil­iary contact.
Source 2 Available - Status LED
This LED is lit amber if Source 2 meets the criteria for pro­grammed Source 2 setpoints.
Source 2 Preferred - Status LED
This LED is lit red if Source 2 is the preferred source choice.
Source 2 Connected - Status LED
This LED is lit red if Source 2 is connected. This is accomplished by sensing the Source 2 breaker via the S2 closed auxiliary con­tact.
Load Energized - Status LED
This LED is lit red if the load is connected to a source that is avail­able.
CAUTION
LOAD ENERGIZE LED IS NOT A POSITIVE INDICATION THAT VOLT­AGE IS NOT PRESENT ON THE LOAD TERMINALS.
Status - Display LED
This LED is lit red when action is occurring, such as a timer timing down, and one of the other display categories has not been selected. When the action is completed, the display goes blank and the LED turns off. The Status position is the default position of the display.
Source 1 - Display LED
This LED is lit green when displaying Source 1 voltage, frequency, and status information. The LED also lights when displaying spe­cific Source 1 setpoint information.
Source 2 - Display LED
This LED is lit red when displaying Source 2 voltage, frequency, and status information. The LED also lights when displaying spe­cific Source 2 setpoint information.
Load - Display LED
This LED is lit red when load voltage is being displayed.
History - Display LED
This LED is lit red when displaying historical information.
Time/Date - Display LED
This LED is lit red when displaying the time or date.
Setpoints - Display LED
This LED is lit red when displaying the programmed setpoints of the ATC-600. When a specific displayed setpoint is associated with one of the sources, the specific source LED will also be lit.
IB ATS-1005 For more information visit: www.eaton.com
Loading...
+ 25 hidden pages