Eaton Arrow Hart AHAWC-DT-120W Installation Instructions Manual

Hot
Arrow Hart
Installation Instructions
Dual Technology Wall/Corner Mounted Low Voltage Occupancy Sensor
9850-000550-00
General Information
• Read all instructions on both sides of this sheet first
• Install in accordance with ALL local codes
• For indoor use only
• For Use with Eaton Switchpacks & Systems Only
• Do not run any Eaton Low Voltage Wiring in the same conduit as power conductors
Specifications
Technology: Passive Infrared (PIR) and Ultrasonic (US) Power Requirements:
Input:
• 10-30 VDC from Eaton Switchpack or Eaton system. Maximum current needed is 25mA per sensor
Output:
• Open collector output to switch up to ten Eaton Switchpacks. BAS with Isolated Form C Relay (-R model) Isolated Form C Relay Ratings: 1A 30VDC/VAC
Time Delays: Self-Adjusting, 15 seconds/test (10 min Auto) or Selectable 5, 15, 30 minutes
Coverage: 1200 sq. ft. Light Level Sensing: 0 to 300 foot-candles (-R model) Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: up to 90% non-condensing
Housing:
• Medium impact injection molded housing
• Polycarbonate resin complies with UL 94V0
Size: 4.4" x 3.4" x 2" (112 mm x 86.4 mm x 50.8 mm) LED Indicators: Red indicates PIR detection; Green
indicates Ultrasonic detection
Description
The AHAWC-DT Wall/Corner Mount Low Voltage Occupancy Sensor is a Passive Infrared (PIR) and Ultrasonic (US) motion sensing lighting control, used for energy savings and convenience. PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON. When motion is detected, the blue wire is electronically connected to the red wire, energizing the relay in the switchpack to turn ON the load. If vacancy is detected, the blue wire is disconnected from the red, causing the relay to open turning OFF the load. The red lead is 10-30 VDC supply, the black lead is common and the blue is the relay control.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and time delay in real-time.
The Daylighting feature (-R model only) prevents lights from turning ON when the room is adequately illuminated by natural light.
The Walk-Through feature maximizes energy savings by not leaving the lights ON after momentary occupancy. The sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect motion 30 seconds following the initial activation, it will automatically go to a shorter 2 minute time delay.
In Automatic ON Mode, the lights turn ON when a person enters the room. In Manual On Mode, the lights are turned ON by activating a momentary switch that is connected to the sensor. When used with 2 level lighting (-R model only), bi-level Automatic ON can be achieved which allows Zone 1 to come ON automatically upon occupancy. Zone 2 does not come ON unless the occupant presses the optional momentary switch.
Coverage
(7.3 mm) 20’
(6 mm)
12’
(3.7)
8’
(2.4 mm)
8’
(2.4 mm)
12’
(3.7)
0
Minor Motion, IR
Major Motion, IR
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Location
the presence of obstacles. Follow the coverage diagram concerning major and minor motion coverage. Decrease total coverage area by 15% for “soft” rooms (for example, heavy draperies or heavy carpeting). The sensor must have a clear view of the area to be controlled. The sensor will not “see” through glass. Mounting height should not exceed 12 feet. Optimum mounting height is 10 feet. Mount the sensor so the grilles face the open portion of the room and are not facing a nearby wall, door, window or other obstructing object. Avoid pointing into hallways. To prevent false activation, the sensor should be mounted away from the air supply duct a minimum of 4 to 6 feet. Mounting at fixture height is most effective. For typical placement refer to Location Diagram.
Installation
The maximum coverage area may vary somewhat according to room shape and
Location Diagram
The AHAWC-DT-120W can be mounted to the wall, ceiling, junction box, or round fixture with raceway.
Occupancy Sensor Mounted to Wallboard
Occupancy Sensor Mounted to Drop Ceiling
Occupancy Sensor Mounted to Octagon Box
Model # AHAWC-DT-120W
Occupancy Sensor Mounted to Round Fixture with Raceway
Wiring
CAUTION: Before installing or performing any service on a Eaton system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by
frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. (Use twist-on wire connectors for all connections) CAP ALL UNUSED WIRE LEADS.
3. Mount unit to wall, ceiling, junction box or round fixture with raceway.
4. Turn power back ON at the branch circuit breaker and wait two minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
One Sensor, One Switchpack
SENSOR WIRE LEAD LEGEND
Black (Common) Red (10-30 VDC) Blue (Control) Yellow (Control) Brown (Switch-Blue Lead Control) Brown/White (Switch-Yellow Lead Control) Sensor’s Isolated Relay Orange (Normally Open) Gray (Common) Purple (Normally closed)
Line
Neutral
**Use Black Lead for 120 VAC Use Orange Lead for 277 VAC Cap Unused Lead
Black Red Blue Yellow Brown Brown/White Orange Gray Purple
Black (Common)
Red (15 VDC)
Blue (Control)
**Hot
White
Blue
Blue
Switchpack
To Additional Sensors. Maximum of 5 sensors per switchpack.
Optional momentary switch­Blue control lead-manual ON/OFF
Recommended Wire: 18-3 AWG stranded non-shielded
Load 1
(3 mm)
24’
(7.3 mm)
20’
(6 mm)
10 ft
6 ft
(1.7 mm)
15 ft
(4.6 mm)
24 ft
(7.3 mm)
50 ft
(15.3 mm)
Occupancy Sensor Mounted to Octagon Box with Mud Ring
Printed in Malaysia
Eaton Wiring Devices
203 Cooper Circle Peachtree City, GA 30269 United States Eaton.com Eaton.com/arrowhart
Electrical Sector Canada Operations 5925 McLaughlin Road Mississauga, Ontario, L5R 1B8 EatonCanada.ca
Mexico Operations Carr. Tlalnepantla ­Cuautitlan Km 17.8 s/n Col. Villa Jardin esq. Cerrada 8 de Mayo Cuautitlan, Mexico CP 54800 Eaton.mx
DIP Switch Settings
Hot
Neutral
Line
Load 1
Black Red
Blue
Purple
Gray
Orange
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC Cap Unused Lead
White
Hot
Neutral
Line
Load 2
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC Cap Unused Lead
White
Yellow Brown Brown/White
Optional momentary switch­Blue control lead- manual ON/OFF
Red (15VDC)
Black(Common)
Blue (Control)
SENSOR WIRE LEAD LEGEND
Black (Common) Red (10-30VDC) Blue (Control) Yellow (Control) Brown (Switch-Blue Lead Control) Brown/White(Switch-Yellow Lead Control)
Sensor's Isolated Relay Orange (Normally Open) Gray (Common) Purple (Normally Closed)
Red (15VDC)
Black(Common)
Blue (Control)
To Additional Switchpacks 10 switchpacks Maximum
Power Pack One
Power Pack Two
(-R model only)
(-R model only)
Time Delay Activation Activation PIR Sensitivity Walk-Through Mode LEDs Override Daylighting ModeLighting Sweep
DIP Switch
12345678 910
One Sensor, Multiple Switchpacks
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP switch 5 UP.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50% by moving DIP switch 5 UP.
2. Adjust Ultrasonic Sensitivity.
Daylight Adjustments (-R model only)
If this feature is not needed, leave the light level at maximum (fully clockwise).
The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light in the room, the sensor will allow the lights to turn ON when occupied.
Full and Half Logic Modes (See DIP switch legend):
In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy activation,
should the ambient light level exceed the preset foot-candle level.
After activation:
Full Logic Mode – should the ambient light level exceed the preset foot-candle level, the lights connected to the yellow
control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.
Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after occupancy activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn the lights OFF while occupancy is being detected.
Note: Set the light level when the ambient light is at the level where no artificial light is needed. In order for this feature to function, the yellow control lead must be wired.
1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP switch 10 out of its current position,
wait 3 seconds and then back in to its original position.
2. Set DIP switch 10 to Full or Half Logic Mode.
3. Set the light level to minimum (fully CCW).
4. Leave the room and let the sensor time-out so lights are OFF. Enter the space and lights should remain OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small increments
until the lights are ON. (Pause 5 seconds between each adjustment)
6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current illumination.
Troubleshooting
Issue Possible Causes Suggestions
Wall Switch OFF Turn Wall Switch ON
Lights
Will Not
If low voltage switch option is used, lights
may have been turned-off manually
Turn ON
automatically
Daylighting Feature Enabled
Power interruption Check incoming voltage and/or wiring
Lights
Will Not
Daylighting Feature Enabled
Turn ON
manually
Power interruption Check incoming voltage and/or wiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Override Make sure sensor is not in Override Mode (DIP Switch 8 up)
Ultrasonic Sensitivity set High
Sensor installed close to an air vent
Sensors should be installed minimum 4 - 6 feet away
from any air vent and out of path of heavy airflow
Sensor installed close to indirect lighting Sensors should be mounted away from indirect lighting.
Lights
Will Not
Turn OFF
Self-adjust
It may be possible for the unit to have self-adjusted the time delay to a 30 minute delay. If the lights do
not turn OFF after 30 minutes follow next step
automatically
Maximum time delay is 30 Minutes. Check DIP
30 Minute Delay
Switches to verify DIP Switch settings. If lights do
not turn OFF at the set time delay, check next step
Press low-voltage switch
If all lights are required to turn ON adjust DIP
Switch 10 and/or daylight potentiometer
If all lights are required adjust DIP switch
10 and/or daylight potentiometer
Lower sensitivity by turning green
potentiometer CCW in small decrements
Checkout and Adjustment
Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.
Self-Adjust
Sensor is shipped in the Self-Adjust Mode. This applies to time delay, US, and PIR sensitivity. In preparation for the Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the unit will time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching the Green (US) and Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs. LEDs should only turn ON for one second with each motion. (If LEDs do not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)
2. Stand still six to eight feet away from the sensor for five seconds. LEDs should not turn ON. (If any LED turns ON, note LED and go to Installer Adjustments – Sensitivity Adjustment section)
3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer Adjustments Section)
4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 5 minutes then automatically exit Test Mode and go for 10 min. Time Delay User Mode setting.
Note: To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To force
into 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position,
seconds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.
wait 3
Installer Adjustments
Sensitivity Adjustments Ultrasonic Sensitivity (Green LED) – Using a small flathead screw driver turn the green potentiometer so that the arrow
points UP.
1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning the green potentiometer clockwise in small increments. Repeat Step 1.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the US sensitivity by turning the green potentiometer counter-clock-wise in small decrements. Repeat Step 3.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 minutes. As long as Auto is enabled, the sensor will respond to each pair of false-OFFs with no normal OFF in between, by alternately making slight adjustments to either time delay (by 2 minute increments) or sensitivity, so there should be no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP switch legend.
Reset sensor time delay to factory settings by moving DIP switches 1 and 2 down. (If DIP switches 1 and 2 are already down, toggle DIP switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Automatic Mode
In Automatic ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage switches are used along with Automatic ON Mode, activating the switch(es) while the load is ON turns the load OFF. When the load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After the time delay expires, the lights stay OFF and the sensor goes back to Automatic ON Mode. For wiring information for the optional momentary low voltage switch(es), please see the wiring section of the installation instructions.
Manual Mode
In Manual ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated the sensor will maintain the lights ON until motion ceases and the time delay expires. While the room is occupied the BAS relay remains active. After the time delay expires, the load(s) will automatically be turned OFF and the switch(es) must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.
Lighting Sweep Option
If selected, this DIP switch option forces an initial 60 second delay upon “power-up” to prevent false activation in buildings with computer control systems.
1. Move DIP switch 9 UP.
Override
The Override setting allows the lights to remain ON in the unlikely event of sensor failure.
1. Move DIP switch 8 UP.
While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).
Printed in Malaysia
PIR activated by heat
source other than occupant
Bypass
Move DIP Switch 5 up
Check wiring to make sure sensor or
switchpack are not bypassed
Lights Will Not
Turn OFF
Override Make sure sensor is not in Override Mode (DIP Switch 8 up)
automatically
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Eaton Wiring Devices LIMITED 5 YEAR WARRANTY
Eaton Wiring Devices warrants its Sensors to be free of defects in materials and workmanship in normal use and service for a period of five years from date of original purchase. THIS FIVE (5) YEAR LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, OBLIGATIONS, OR LIABILITIES, EXPRESSED OR IMPLIED (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT IS IN DURATION IN EXCESS OF FIVE YEARS FROM THE DATE OF ORIGINAL CONSUMER PURCHASE). NO AGENT, REPRESENTATIVE, OR EMPLOYEE OF Eaton Wiring Devices HAS AUTHORITY TO INCREASE OR ALTER THE OBLIGATIONS OF Eaton Wiring Devices UNDER THIS WARRANTY. To obtain warranty service for any properly installed Eaton Wiring Devices Sensors that proves defective in normal use send the defective Sensors prepaid and insured to Quality Control Dept., Eaton Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269; in Canada: Eaton Wiring Devices, 5925 McLaughlin Road, Mississauga, Ontario L5R 1B8. Eaton Wiring Devices will repair or replace the defective unit, at its option. Eaton Wiring Devices will not be responsible under this warranty if examination shows that the defective condition of the unit was caused by misuse, abuse, improper installation, alteration, improper maintenance or repair of damage in shipment to Eaton Wiring Devices. EATON WIRING DEVICES SHALL HAVE NO RESPONSIBILITY FOR INSTALLATION OF THE SENSORS, OR FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR ANY SPECIAL, INCIDENTAL, CONTINGENT, OR CONSEQUENTIAL DAMAGES OF ANY KIND, RESULTING FROM DEFECTS IN THE SENSORS OR FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY ON THIS PRODUCT. THE EXCLUSIVE REMEDY FOR BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE REPAIR OR REPLACEMENT OF THE DEFECTIVE PRODUCT AT EATON WIRING DEVICES’ OPTION. IMPLIED WARRANTIES (IF ANY) INCLUDING, BUT NOT LIMITED TO IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABIITY, ARE LIMITED IN DURATION TO A PERIOD ENDING FIVE YEARS FROM THE DATE OF ORIGINAL CONSUMER PURCHASE. IN NO CASE SHALL EATON WIRING DEVICES’ LIABILITY UNDER ANY OTHER REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. Some states do not allow the exclusion or limitation of incidental or consequential damages or allow disclaimers or modifications of or limitations on how long an implied warranty lasts, so the above limitations may not apply to you. Some Canadian provinces do not allow exclusion or variance of implied warranties so that some or all of the above limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state and province to province. Read enclosed instructions carefully. If you have any questions concerning use or care of this product, please write: Consumer Service Division, Eaton Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269.
Eaton Wiring Devices
203 Cooper Circle Peachtree City, GA 30269 United States Eaton.com Eaton.com/arrowhart
Electrical Sector Canada Operations 5925 McLaughlin Road Mississauga, Ontario, L5R 1B8 EatonCanada.ca
Mexico Operations Carr. Tlalnepantla ­Cuautitlan Km 17.8 s/n Col. Villa Jardin esq. Cerrada 8 de Mayo Cuautitlan, Mexico CP 54800 Eaton.mx
Loading...