Eaton Ampgard 720A Instructions For Installation, Operation And Maintenance

Instruction Booklet IB48066
Effective November 2010
Instructions for Installation, Operation and Maintenance of the Ampgard 720A Reduced Voltage Soft Starter
Contents
Description Page
Purpose ................................. 2
Introduction .............................. 2
1.1 Basic Description of a Single Unit ........ 2
1.2 Main Cell ........................... 3
1.3 Bypass Cell .......................... 4
1.4 RVSS Cell ........................... 4
Operation ................................ 5
Instruction Booklet IB48066
Effective November 2010
Instructions for Installation, Operation and Maintenance
of the Ampgard 720A Reduced Voltage Soft Starter
Read and understand these instructions before attempting any installation, operation or maintenance of the Ampgard Reduced Voltage Soft Starter.
This equipment shall be installed and serviced only by qualified electrical personnel.
Retain this document for future use.
DANGER
HAZARDOUS VOLTAGE
ALL POWER SOURCES MUST BE ISOLATED AND LOCKED OUT BEFORE SERVICING THE EQUIPMENT.
READ AND UNDERSTAND THESE INSTRUCTIONS IN THEIR ENTIRETY BEFORE INSTALLING, OPERATING, OR MAINTAINING THIS EQUIPMENT. ONLY QUALIFIED PERSONS SHOULD INSTALL, MAINTAIN, ADJUST OR REPAIR THESE UNITS. A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE EQUIPMENT AND THE HAZARDS ASSOCIATED WITH IT.
Purpose
This instruction book is to insure the safe and successful installation, operation and maintenance of the Ampgard 720A Reduced Voltage Soft Starter (RVSS). This equipment may be installed as an individual structure or may be part of a lineup of Ampgard products.
Section 1: Introduction
1.1 Basic Description of a Single Unit
The Ampgard RVSS is designed to start medium voltage motors at reduced voltages with specific ramp times and amperages. An individual unit is 72 in wide x 30 in deep and 92 in tall, including the main bus. An additional structure for incoming line cables may also be supplied. The left structure is referred to as the main structure and the right structure is the RVSS cell. The upper portion of the main structure is referred to as the main cell and the lower portion is the bypass cell. (See Fig. 1.)
Main
Structure
RVSS Cell
Main
Cell
Bypass
Cell
Figure 1. Ampgard 720A RVSS Unit
2
EATON CORPORATION www.eaton.com
Instructions for Installation, Operation and Maintenance of the Ampgard 720A Reduced Voltage Soft Starter
Instruction Booklet IB48066
Effective November 2010
1.2 Main Cell
The upper cell consists of a full voltage starter with a non-load break isolation switch, medium voltage current limiting fuses, an SL contractor, and current transformers. The low voltage control com­partment is located on the front of the medium voltage door. (See Fig. 2.) Refer to IB48043 (Instructions for Ampgard 720A Ampere Medium Voltage Starter) for operating and maintenance instructions on the main cell.
Low Voltage
Compartment
Main Fuses
Isolation
Switch
The following components are located on the front of the low volt­age door of the main cell. (See Fig. 3)
Bypass Mode LED – After the motor is started and reaches
speed, the bypass contactor closes to bypass the SCRs in the soft starter. The Bypass Mode Indicating Light will illuminate when the SCRs are bypassed.
RVSS Fault LED – In the event of a soft starter failure, the RVSS
Fault LED will illuminate.
RVSS Fault Reset Pushbutton – In the event of a soft starter fail-
ure, the RVSS Fault Reset pushbutton must be depressed to clear the fault.
Optional start-stop pushbuttons and runstopped indicating lights
are supplied when specified.
Figure 2. Main Cell
Main
Contactor
Figure 3. Low Voltage Components
EATON CORPORATION www.eaton.com
3
Loading...
+ 5 hidden pages