Eaton Ampgard 400 Instruction Manual

Instructional Leaflet IB48041
Effective December 2009
Instructions for AMPGARD 400A medium voltage starter
DANGER
READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY BEFORE INSTALLING OR OPERATING THE CONTROLLER. INSTALLATION, ADJUSTMENT, REPAIR, AND MAINTENANCE OF THESE CONTROLLERS MUST BE PERFORMED BY QUALIFIED PERSONNEL. A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS INVOLVED.
Introduction
This instruction book is intended to cover the handling, installation, operation, and mainte­nance of AMPGARDT 400A, 7.2 kV starters and associated equipment. The function of these controllers is to start, stop, and protect medium voltage motors, transformers, capacitors, and other loads. Controllers may be of full voltage, reduced voltage reactor, reduced voltage autotransformer, reduced voltage solid-state, or two-speed type. They may control induction or synchronous machines, and they may be non-reversing or reversing.
While this instructional leaflet is dedicated primarily to full-voltage starting, the other applications listed are an expansion of the principles identified in this leaflet. This leaflet does not purport to cover all possible contingencies, variations, and details that may arise during operation or maintenance of this equipment. If further information is desired regarding this product, contact your local Eaton sales office.
Identification
A rating nameplate is located on the door of each controller. Contained on this nameplate are the controller type and ratings as required by industry standards. Also contained on this nameplate is the factory’s general order number. This number should be given to the Eaton sales office if a question should arise concerning the equipment or if renew­al parts are required. Refer to Figure 1 for typical location of rating nameplates.
Instructional Leaflet IB48041
Effective December 2009
Low Voltage Door
Figure 1. Starter with Rating Nameplate
Instructions for AMPGARD 400A
medium voltage starter
DANGER
EXCEEDING THE NAMEPLATE RATINGS OF AN AMPGARD CONTROLLER MAY CAUSE EQUIPMENT DAMAGE, SEVERE INJURY, OR DEATH.
Do not apply an AMPGARD controller beyond its nameplate ratings.
Rating Nameplate
Medium Voltage Door
Table 1. Contractor Ratings
Rated Utilization Voltage 2200–2500V 3000–3600V 3800–4800V 6000–6900V
Interrupting rating NEMAT unfused (E1) NEMA fused (E2)
Application table Induction motor Synchronous motor (0.8 PF) Synchronous motor (1.0 PF) Transformer Capacitor three-phase
8.5 kA 50 kA 200 MVA at 2400V
1750 hp 1750 hp 2000 hp 1500 kVA 1200 kVAR
8.5 kA 50 kA 295 MVA at 3300V
2250 hp 2250 hp 2500 hp 2000 kVA 1650 kVAR
8.5 kA 50 kA 400 MVA at 4600V
3000 hp 3000 hp 3500 hp 2500 kVA 2100 kVAR
8.5 kA 50 kA 570 MVA at 6600V
4500 hp 4500 hp 5500 hp 4000 kVA 3300 kVAR
Maximum insulation voltage: 7200V
Maximum interrupting current (3 operations) Rated current IEC make-break capability-AC1 Make Break Short-time current 30 seconds 1 second
8.6 milliseconds (0.5 cycle) Standard service altitude Optional service altitude
Mechanical life Electrical life BIL Dielectric strength (60 Hz) Closing time (energization to contact touch) Operating time
Time-rated cycles on 60 Hz base.
8500A 400A enclosed
4000A 3200A
2400A 6000A
63 kA peak –1000 to +2000 meters –3500 to –1001 meters +2001 to +5000 meters
2.5 million operations 300,000 operations 60 kV (1.2 x 50 microseconds) 20 kV (1 minute) 90 milliseconds
30 to 330 milliseconds (selectable)
Arcing time Pickup voltage Dropout voltage Control voltages AC DC Control circuit burden Closing (AC/DC) Holding (AC/DC) Auxiliary contact rating Voltage (maximum) Continuous current Making capacity (AC) Making capacity (DC) Breaking capacity (AC) Breaking capacity (DC) Latch (when specified) Mechanical life Trip voltages (DC) Trip voltages (DC) Minimum trip voltage Trip burden (24 Vdc) (125 Vdc) (110/125 Vac) Trip Time Weight
12 milliseconds (3/4 cycle) or less 90% rated coil voltage 60% rated coil voltage
110/120/220/240 (50/60 Hz) 125
— 30 VA
600V 10A 7200 VA 125 VA 720 VA 125 VA
250,000 operations 24/120V 110/120V 90% rated coil voltage
— — — 30 milliseconds 60 lbs (27 kg) (rollout)
2
EATON CORPORATION www.eaton.com
Instructions for AMPGARD 400A medium voltage starter
Description
Controller
The AMPGARD 400A, 7.2 kV controller consists of a non-loadbreak isolation switch, medium voltage current-limiting fuses, one or more Type SL vacuum-break contactors, a set of current transform­ers, plus control and protection devices. The isolating switch has a limited make and break rating, suitable only for closing and opening limited transformer magnetizing currents. The controller is designed to start, stop, and protect a three-phase medium voltage motor within the ratings shown in Table 1. The controller may also be used to switch transformer windings or capacitor loads as shown. For applications other than those indicated, consult the factory. Each AMPGARD controller occupies all or a portion of a steel structure that may also enclose a horizontal bus system to distribute power to two or more sections and a vertical bus system to connect individual starters to the horizontal bus. The controllers are configured for full­voltage or reduced-voltage starting, reversing or non-reversing, in single-speed or two-speed applications.
Starters are available with bolt-in or clip-in main fuses. Contactors may have bolted connections or stab-in connections to the starter cell.
The flow of current through a starter with bolted fuses and a stab-in contactor can be described as follows: The line finger assembly mounted at the back of the enclosure serves to connect the isolation switch moving stabs to the controller line terminals when the switch is closed. Power flows from the switch moving stabs through a flexible shunt to the upper fuse mountings. The fuses are connected to the lower fuse mountings that contain the line-side stab connections to the line finger assemblies for the main contactor. With the main contactor energized, power flows through the contactor’s vacuum interrupters to the contactor load fingers, which are engaged on to the contactor load-side stabs. Medium voltage cables connect the load-side stabs to the motor load connections. The contactor is held in place by a set of rails mounted in the lower part of the cell. Current transformers are typically mounted immediately behind the main contactor, under the load-side stabs. The motor load connections are mounted to the left of the main fuses in the rear of the compartment, facing forward.
Instructional Leaflet IB48041
Effective December 2009
Isolation Switch Position View Window
Figure 3. Low Voltage Compartment
Isolation switch
The controller isolation switch is a non-loadbreak device. Mechanical and electrical interlocks are provided to ensure that the main contactor is de-energized before the switch can be operated. In the open position, the switch isolates medium voltage from the main controller compartment, allowing access to the controller for inspection and maintenance. For standard applications, the isolation switch includes ground fingers that ground the line side of the power fuses when the switch is in the open position. The isolation switch has a mechanical endurance rating of 10,000 operations. Isolation switches in starters with double-barrel fuses are supplied with additional phase barriers that must be installed to maintain the proper dielectric rating of the starter.
DANGER
AMPGARD CONTROLLERS ARE SOMETIMES ENERGIZED BY A BACK-FED CONDITION THAT ALLOWS THE MEDIUM VOLTAGE COMPARTMENT TO BE ENERGIZED WITH THE ISOLATION SWITCH IN THE OPEN POSITION. STUDY THE PLANT SINGLE LINE DIAGRAMS TO MAKE CERTAIN THAT NO BACK­FEED SITUATION EXISTS BEFORE ENTERING THE MEDIUM VOLTAGE COMPARTMENT.
Figure 2. Medium Voltage Compartment
Low voltage components
The low voltage components consisting of a protective relay, interposing relay, test power circuit, terminal blocks, and optional equipment are mounted in the low voltage control compartment located on the front of the controller medium voltage door. The low voltage compartment is fabricated from steel sheets to provide iso­lation from the medium voltage components mounted behind the low voltage compartment. A window is provided in the low voltage compartment to allow the user to view the position of the isolation switch before entering the medium voltage compartment. See the “Isolation Switch” section for further details.
All power sources must be isolated and locked out before servicing the equipment.
For applications where the controller is back fed, the grounding fingers should be removed from the isolation switch.
The switch consists of a fixed rear portion and a removable front portion. Refer to Figures 5 and 6. The fixed portion includes the controller line fingers and a moveable shutter that isolates the line fingers when the switch is in the open position. The removable portion is operated by a handle mechanism that extends through the controller medium voltage door. With the handle in the up position, the switch is closed and medium voltage is available for connection to the controller load. With the handle in the down position, the switch is open and medium voltage is isolated from the controller and the controller load.
An isolation switch viewing window is provided in the upper rear corner of the low voltage control compartment. After opening the isolation switch and before opening the medium voltage door, the switch should be visually examined through the viewing window to verify that it is in the open position. Three green and white “barber poles” will be visible when the switch is in the open position and the shutter assembly is in the isolating position. See Figure 4 for location of barber poles. The use of a flashlight will help in verifying the position of the barber poles.
EATON CORPORATION www.eaton.com
3
Instructional Leaflet IB48041
Effective December 2009
Barber Poles Indicating Shutter Closed
Phase Barriers (4) for Double­Barrel Fuses
Figure 4. Shutter Closed
DANGER
DO NOT ENTER THE MEDIUM VOLTAGE STARTER COMPARTMENT WITH­OUT VISUALLY VERIFYING THAT THE ISOLATION SWITCH IS OPEN AND THE ISOLATING SHUTTER IS IN PLACE. ENTERING A COMPARTMENT WITHOUT THE ISOLATING SHUTTER IN PLACE MAY RESULT IN SEVERE INJURY OR DEATH.
Instructions for AMPGARD 400A
medium voltage starter
Vacuum contactor
400A AMPGARD medium voltage controllers are supplied with 400A vacuum contactors. The contactors are supplied with one of two interrupting ratings: The standard contactor has an interrupting rating of 4500A, while the high-interrupting contactor has an interrupting rating of 8500A. The standard contactors are typically supplied on controllers with single-barrel main fuses (<188 FLA). They are also supplied when auxiliary contactors are required, such as start and run contactors on autotransformer starters and run contactors on reactor starters. High-interrupting contactors are supplied on controllers with double-barrel fuses. A code plate is provided in cells originally equipped with high-interrupting contactors to prevent the inadvertent installation of standard interrupting contactors into those cells.
Figure 5. Fixed Portion—ISO Switch
Figure 6. Removable Portion—ISO Switch
Power fuses
AMPGARD controllers are supplied with Eaton Type CLS, CLE, or HLE current-limiting power fuses. Fuses may be either bolt-in type or clip-in type. All fuses include an indicator that pops up when the fuse has blown. An optional blown fuse trip bar may be supplied with bolt-in fuses. The mechanism is mounted on the controller isolation switch and may be wired to trip the controller off-line in the event of a blown fuse.
Figure 7. SL Vacuum Contactor
Contactors are typically three-pole devices except in the case of the start contactor on autotransformer starters, which are normally two­pole devices.
Refer to Instruction Book IB48018N for further details on the operation and maintenance of the vacuum contactors.
Controllers supplied as transformer feeders, or for other specialized applications, are sometimes supplied with contactors that include a mechanical latch device. Refer to Instruction Book IB48020 for further details on the operation and maintenance of the latch mechanism.
Safety interlocks
AMPGARD controllers are manufactured with several built-in inter­lock provisions and safety features to reduce hazards and provide proper operating sequences:
•
A mechanical interlock prevents opening the medium voltage door with the switch in the closed position. Ensure that the medium voltage door is fully closed and latched using the two latches on the right side of the door to prevent damage to the interlock bracket on the back of the door
•
An additional interlock prevents closing of the switch unless the medium voltage door is closed (see MV door interlock plunger in Figure 8). On controllers that require two structures (reduced voltage starters, for example), the door to the second structure will also be interlocked with the switch-operating mechanism. The second door must be closed before the main door is closed. Both doors must be closed before the switch operator can be moved to the closed position
ote:N Attempting to close the switch with the door open can cause damage
to the operating mechanism.
4
EATON CORPORATION www.eaton.com
Loading...
+ 8 hidden pages