Datasheet Eaton 9PX UPS 5-11 kVA
Eaton 9PX UPS
5/6 /8/11 k VA
Rack/Tower versatile
9PX 11kVA with Maintenance ByPass
Advanced protection for:
• Small&mediumdatacenter
• IT,Networking,StorageandTelecom
• Infrastucture,IndustrialandMedical
Energy efficient power protection
Performance and Efficiency
• Double conversion topology. The Eaton 9PX constantly monitors power conditions and regulates voltage and frequency.
• With up to 95% efficiency in online double conversion mode
and 98% in high-efficiency mode the 9PX provides the
highest efficiency level in its class to reduce energy &
cooling costs.
• With a 0.9 power factor the 9PX delivers 28% more power
than UPS in its class. It powers more servers than other UPSs
with equivalent VA ratings and lower power factors.
• With a RT (Rack/tower) versatile form factor the 9PX is the
most compact solution in its class delivering up to 5400W in
only 3U and 10kW in only 6U.
Manageability
• The new graphical LCD provides clear information on the
UPS’s status and measurements on a single screen (in seven
languages). LCD display position can be adjusted to offer the
best viewable angle for tower and rack usage.
• The 9PX can meter energy consumption. kWh values can
be monitored using the LCD or Eaton’s Intelligent Power®
Software Suite.
• Load segment control enables prioritised shutdowns of
nonessential equipment to maximise battery runtime for
critical devices. It can also be used to remotely reboot lockedup network equipment or to manage scheduled shutdowns
and sequential start-ups.
• The 9PX offers Serial, USB and relay connectivity, plus an extra
slot for an optional card (Network card delivered as standard
on Netpack version). Eaton’s Intelligent Power® Software Suite
compatible with all major OS including virtualization software
such as VMware and Hyper-V is included with each UPS.
Availability and Flexibility
• The internal bypass allows service continuity in case of
internal fault, a Maintenance ByPass is also available (as standard on HotSwap version) for easy replacement of the UPS
without powering down critical systems.
• The Eaton 9PX can be paralleled to achieve twice the power of
unitary product using HotSync technology, without extra cost
on the initial purchase (available in Q4 2013)
• Stronger, longer battery life: Eaton ABM® battery management technology uses an innovative three-stage charging technique that extends battery life by up to 50%.
• More runtime can be added with up to 12 external hotswappable battery modules, able to run systems for hours if
necessary. The additional battery modules are automatically
recognized by the UPS.

Eaton 9PX UPS
1 Remote Off/On and Remote
Power Off connectors
5 8 IEC 10A sockets (2 groups
of 4 manageable sockets)
with cable retention system
2 Slot for Network-MS,
ModBus-MS or Relay-MS cards
6 2 IEC 16A sockets
with cable retention system
3 Parallel operation
port (DB15)
4 External battery module
7 DB 9 with output contacts
8 USB and serial ports
(EBM) connector with
automatic detection (RJ11)
Technical Specifications 5kVA 1:1 6kVA 1:1 6kVA 3:1 8kVA 1:1 or 3:1 11kVA 1:1 or 3:1
Rating (kVA/kW) 5kVA/4.5kW 6kVA/5.4kW 6kVA/5.4kW 8kVA/7.2kW 11kVA/10kW
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Input voltage 200/208/220/230/240V 1:1 200/208/220/230/240V/250V 1:1, 380/400/415 3:1
Input voltage range 176-276V without derating (up to 100-276V with derating) 1:1, 305V-480V without derating (up to 175V-480V with derating) 3:1
Output voltage/THDU 200/208/220/230/240V +/– 1%; THDU <2%
Input frequency range/THDI 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency Up to 94% in Online mode, 98% in Hi-Efficiency mode Up to 95% in Online mode, 98% in Hi-Efficiency mode
Short circuit current 90A 90A 90A 120A 150A
Overload capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Connections
Input Terminal block (up to 10 mm
Outputs
Outputs with HotSwap Maintenance Bypass Terminal block + 3 IEC C13 (10A) + 2 IEC C19 (16A) Terminal block + 4 IEC C19 (16A)
Batteries
Typical backup times at 50 and 70% load*
9PX 13/10 min 11/8 min 30/20min 20/15 min 13/9min
9PX + 1 EBM 60/40 min 48/34 min 70/45min 48/32 min 32/21 min
9PX + 4 EBM 220/150 min 170/120 min 210/140 min 140/100 min 100/70 min
Battery management ABM
Communication
Communication ports
Communication slot 1 slot for Network-MS card (included in Netpack versions), ModBus-MS or Relay-MS cards.
Operating conditions, standards and approvals
Operating temperature 0 to 40°C continuous
Noise level <45dB <45dB <48db <48db <50db
Safety IEC/EN 62040-1, UL 1778 (1:1 version)
EMC, performance IEC/EN 62040 -2, FCC Class A (1:1 version), IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV), UL (1:1 version)
Dimensions H x W x D/Weight
UPS Dimensions 440(19’’)*130(3U)*685mm 440(19’’)*130(3U)*685mm 440(19’’)*260(3U+3U)*700mm 440(19’’)*260(3U+3U)*700mm 440(19’’)*260(3U+3U)*700mm
UPS Weight 48kg 48kg 88kg 84kg (1:1), 88kg (3:1) 86kg (1:1), 88kg (3:1)
EBM Dimensions 440(19’’)*130(3U)*645mm 440(19’’)*130(3U)*645mm 440(19’’)*130(3U)*680mm 440(19’’)*130(3U)*680mm 440(19’’)*130(3U)*680mm
EBM Weight 68kg 68kg 65kg 65kg 65kg
Power Module Dimensions - - 440(19’’)*130(3U)*700mm 440(19’’)*130(3U)*700mm 440(19’’)*130(3U)*700mm
Power Module Weight - - 23kg 19kg (1:1), 23kg (3:1) 21kg (1:1), 23kg (3:1)
Customer Service and Support
Warranty 2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Terminal block +
2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
®
and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off,
1 DB15 for parallel operation.
2
) Terminal block (up to 16mm2)
Eaton 9PX 6kVA 1:1
Terminal block
9 Input/Ouput connection
Parts Numbers 9PX 5kVA 1:1 9PX 6kVA 1:1 9PX 8kVA 1:1 9PX 11kVA 1:1 9PX 6kVA 3:1 9PX 8kVA 3:1 9PX 11kVA 3:1
UPS with HotSwap Maintenance Bypass 9PX5KiBP 9PX6KiBP 9PX8KiBP 9PX11KiBP 9PX6KiBP31 9PX8KiBP31 9PX11KiBP31
UPS with Network Card and Rack Kit 9PX5KiRTN 9PX6KiRTN – – – – –
UPS with HotSwap MBP, Network Card
and Rack Kits
EBM 9PXEBM180 9PXEBM180 9PXEBM240 9PXEBM240 9PXEBM240 9PXEBM240 9PXEBM240
Power Module – – 9PX8KiPM 9PX11KiPM 9PX6KiPM31 9PX8KiPM31 9PX11KiPM31
HotSwap Maintenance Bypass MBP6Ki MBP6Ki MBP11Ki MBP11Ki MBP11Ki31 MBP11Ki31 MBP11Ki31
Transformer Module single phase TFMR11Ki TFMR11Ki TFMR11Ki TFMR11Ki TFMR11Ki TFMR11Ki TFMR11Ki
Supercharger with Rack Kit – – SC240RT SC240RT SC240RT SC240RT SC240RT
1.8m Battery Connection Cable EBMCBL180 EBMCBL180 EBMCBL240 EBMCBL240 EBMCBL240 EBMCBL240 EBMCBL240
Battery Integration System BINTSYS BINTSYS BINTSYS BINTSYS BINTSYS BINTSYS BINTSYS
Rack Kit 9RK 9RK 9RK 9RK 9RK 9RK 9RK
In the interests of continuous product improvement all specications are subject to change without notice.
– – 9PX8KiRTNBP 9PX11KiRTNBP 9PX6KiRTNBP31 9PX8KiRTNBP31 9PX11KiRTNBP31
© 2013 Eaton Corporation, All Rights Reserved, Eaton 9PX Rev C, June 2013.
Due to continuing product improvement programmes, specifications are subject to change without notice.