Eaton 9PX6KIRTN Product Data Sheet

Technical
Specifications
Eaton 9PX UPS technical specifications (5 and 6 kVA models*)
Model overview
Catalog number
208V output, 50/60 Hz bundles
9PX5K 5000/4500 L6-30P*** 9PX6K 6000/5400 L6-30P***
9PX6KG 6000/5400 Hardwired (2) C19, (8) C13, Hardwired 5.1 (3U) x 17.3 x 27.0 106 120/208V output, 50/60 Hz bundles
9PX5KTF5 5000/4500 L6-30P*** 9PX5KP1 5000/4500 L6-30P
9PX5KP2 5000/4500 Hardwired Hardwired 10.2 (6U) x 17.3 x 28.4 201 9PX6KTF5 6000/5400 L6-30P*** 9PX6KP1 6000/5400 L6-30P
9PX6KP2 6000/5400 Hardwired Hardwired 10.2 (6U) x 17.3 x 28.4 201
**Each module of every 9PX bundle ships with a 4-post rail kit. ***Terminal block with L6-30P cord.
Battery backup times (in minutes)****
Load (watts)
5400 3.0 16 28 47 58 4050 4.5 24 45 62 90 2700 8.5 38 71 104 133 1350 22.0 85 147 214 287
540 57.0 203 399 554 755
****Runtimes are shown at full load with maximum power factor, are approximate and may vary with equipment, configuration, battery age, temperature, etc. View interactive runtime graphs at www.eaton.com/9PX.
Additional specifications
General
Topology Double-conversion online Configuration Rack/tower Color Black and silver Diagnostics Full system self test at power up Warranty 2 years Rail kit 4-post rail kit and tower pedestals included; Optional 2-post rail kit available, part
Remote emergency power off (REPO) Contents (Ships with the following items)
(2) L6-30R, (2) L6-20R, Hardwired 5.1 (3U) x 17.3 x 28.4 106 (2) L6-30R, (2) L6-20R, Hardwired 5.1 (3U) x 17.3 x 28.4 106
(1) L6-30R, (2) L6-20R, (18) 5-20R, Hardwired 10.2 (6U) x 17.3 x 28.4 201 (1) L14-30R, (1) L6-30R, (6) 5-20R 10.2 (6U) x 17.3 x 28.4 203
(1) L6-30R, (2) L6-20R, (18) 5-20R, Hardwired 10.2 (6U) x 17.3 x 28.4 201 (1) L14-30R, (1) L6-30R, (6) 5-20R 10.2 (6U) x 17.3 x 28.4 203
Dimensions (HxWxD, in.)**
Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
number: RK2PC ROO and RPO: Rear deck emergency stop connectors (for remote on/off and power off) UPS Network-MS Web/SNMP card 4-post rail kit User manual Quick start guide Tower pedestals Intelligent Power Software Suite CD RS-232 serial cable
Weight (lb.)
Eaton.com/9PX TD153001EN February 2013
Page 2 of 2
USB cable Cable gland for hardwire conection
Phillips head screw driver Electrical input Input voltage range Full load: 176-276V, Derating: 100-276V Nominal voltage 200/208/220/230/240V Default voltage 9PX5K and 9PX6K: 208V. 9PX6KG: 230V Frequency 50/60 Hz Frequency range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz Input power factor >.99 Input current distortion <5% Circuit breaker (2) 20A for L6-20R Electrical output Power ratings NEMA 5 kVA 200/208/220/230/240V: 5000 VA/4500 watts Power ratings NEMA 6 kVA 230/240V: 5400 watts
220V: 5100 watts
208V: 4800 watts
200V: 4600 watts Power ratings IEC 6 kVA 200/208/220/230/240V: 6000 VA/5400 watts Nominal voltage 208V default (200/208/220/230/240V) Output voltage regulation ±1% steady-state Voltage THD <2% for linear loads Power factor 0.9 Efficiency 93% with resistive load Transfer time 0 ms Battery Optional extended battery module (EBM) Maximum number of EBMs Add up to 4 EBMs Battery description Sealed, lead-acid; maintenance free
Battery management ABM technology; 3-stage charging extends battery service life by 50% and Battery replacement Hot-swappable internal batteries and EBMs
Start on battery Cold-start enabled; first cold start is always forbidden Communications User interface Graphical display. UPS status in a single view. LEDs 4 status-indicating LEDs Communication ports RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables
Communications card slot Network Card-MS included Power management software Eaton Intelligent Power Software Suite CD (included) Environmental & standards RoHS compliance Yes Surge protection IEEE ANSI C62.41 Cat B2 Heat dissipation (BTU/hr; battery full charged, resistive load) Audible noise <45 dB at 1 meter Operating temperature 0 to 40°C (32°F to 104°F) Safety conformance CE / cULus / NOM EMC markings IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A Storage temperature 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F) Relative humidity 0 to 95% non-condensing Altitude <1,000 meters for nominal power; 10% power derating every 1000 meters (up to
*Due to continuing product improvement programs, specifications are subject to change without notice.
9PXEBM180RT
provides advance warning for battery replacement
included
9PX5K: Online: 1150. Battery: 1560
9PX6K, 9PX6KG: Online: 1245. Battery: 1895
3000 meters) at 40°C
Eaton.com/9PX TD153001EN February 2013