Eaton 945U-E Installation Manual

Instruction Leaflet IL032045EN
Effective Febuary 2016 Version 2.0
945U-E wireless Ethernet modem installation guide
Installation steps
This guide provides installation drawings and instructions appropriate for most applications. For more information, refer to the user manual.
1. Connect the GND terminal on the back of the 945U-E to earth/ground.
2. Install the antenna.
3. Connect the 945U-E to a DC power supply and power on.
NOTE
This equipment is suitable for use in ClassI Division 2 groups A, B, C and D hazardous locations, or nonhazardous locations only.
Antenna installation
When selecting an antenna, consider radio proximity. For short distance paths, check the receive signal level. If it exceeds –40dBm, a 20 dBm you must fit an attenuator in-line with the coaxial cable. Do not use demonstration antennas for the final installation.
Use Figure 1 as a guide for installing an antenna and attaching it to the 945U-E.
Figure 1. Antenna Installation
945U-E
to your computer via Ethernet and
945U-E
. Refer to the user manual for
WARNING
EXPLOSION HAZARD
Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations. Substitution of any component may impair suitability for Class I Division 2.
Statutory requirements
FCC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. .
945U-E
M4 x 5 mm
Module
Connection
Wavelength: 13" (33 cm)
Surge Arrestor (recommended)
at least 11 AWG (4 mm
Provide good ground connection to mast, module, and surge arrestor.
If ground conditions are poor, use more than one stake.
Coaxial Cable
GND
GND
Antenna* 1 Wavelength
Stress Relief Loop
2
)
Earth Stake
(minimum)
Weatherproof Connections (recommended:
3M
23 self-
bonding tape)
Mast
Earth Conductor at least 5 AWG
2
(16 mm
)
*
For maximum range, install above local obstructions.
Instruction Leaflet IL032045EN
RS-485
SUPPLY
ETHERNET
(HUB)
100M
LINK
B A
-
B A
SUPPLY
+
-
DIO
COM
B A
B A
B A
+
DIO
COM
B A
RS-485
SUPPLY
B A
+
-
DIO
COM
B A
B A
RS-485
SUPPLY
B A
+
-
DIO
COM
B A
Effective Febuary 2016
Version 2.0
945U-E wireless Ethernet modem installation guide
EATON_945U-E Install Guide
NOTE
All connections must be SELV <50 Vac and <120 Vdc.
If the wireless Ethernet modem is installed as Category 3 equipment, it must be installed in an enclosure that maintains an ingress protection rating of IP54 and meets the enclosure requirements of EN50014 or EN60079-0.
If the wireless Ethernet modem is installed in a hazardous environment, coaxial cable must be installed in a metallic conduit, per NEC requirements.
Digital Output will activate for approximately 5 seconds during the device power up sequence.
WARNING
The wireless Ethernet modem enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. This must be taken into account during installation. The non-metallic cover of the wireless Ethernet modem constitutes an electrostatic discharge hazard. Clean only with a damp cloth.
The following illustration shows the ports and switches on the 945U-E. The Ethernet port is wired for a hub or switch.
Factory Default Switch
100M LINK
RUN
SETUP
ETHERNET
(HUB)
RJ-45 Ethernet Port (connects to hub)
Power supply wiring
The device power supply –Ve terminal is not isolated from earth/ ground.
* Connect the negative
( – ) supply terminal and the GND screw (located on the rear of the module) to earth/ ground as close to the device as possible.
Do not connect the
positive ( + ) supply terminal to earth/ ground.
RS-232 Port
RS-232
(DCE)
B A RS-485 SUPPLY
+-
COM
+-
DIOCOM
RS-485 Resistor Termination Switch
B A
B A
RS-485 connections
Use shielded twisted pair cable to interconnect modules to reduce potential RFI.
Maintain the polarity of the two RS-485 wires.
B A
RS-485
Terminate each end of the network with a 120-ohm resistor. An on-board terminating resistor is provided in the modem and can be
115S-xx 115S-xx
engaged by setting the DIP switch on the end plate to ON.
B A B A
+
RS-232 connections
RS-232
(DCE)
945U to DTE (Host)
2
RD
3
TD
5
SG
7
RTS
8
CTS
6
DSR
4
DTR
1
DCD
DB-9 MALE
(945U is Female)
DB-9 FEMALE
(DTE is Male)
2
RD
3
TD
5
SG
7
RTS
8
CTS
6
DSR
4
DTR
1
DCD
945U to DCE (Modem)
2
3
5
7
8
6
4
1
2
RD
3
TD
5
SG
7
RTS
8
CTS
6
DSR
4
DTR
1
DCD
DB-9 MALE
(DCE is Female)
RD
TD
SG
RTS
CTS
DSR
DTR
DCD
DB-9 MALE
(945U is Female)
Digital input and output wiring
The digital input/output (DIO) channel can be wired as either input or output.
COM DIO
Digital InputDigital Output
COM DIO
9-30 Vdc
Supply
CAUTION! Avoid ground loops.
Eaton
1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
Eaton’s wireless business
www.eaton.com/wireless
2A Fuse or
Circuit Breaker
Connect to Ground as close to the module as possible
© 2015 Eaton All Rights Reserved Printed in USA Publication No. IL032045EN Febuary 2016
Max.
30 Vdc
0.5A
DC Load
(relay)
Voltage-Free Contact or Transistor Device
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Loading...