Eaton 93PM 150 kW SIAC-B Three-Wire, 93PM 150 kW SIAC-B Four-Wire, 93PM 200 kW SIAC-B Four-Wire, 93PM 200 kW SIAC-B Three-Wire Installation And Operation Manual

Eaton® 93PM Sidecar Integrated Accessory Cabinet-Bypass
150 kW SIAC-B Three-Wire 150 kW SIAC-B Four-Wire 200 kW SIAC-B Three-Wire 200 kW SIAC-B Four-Wire Installation and Operation Manual
Eaton® 93PM Sidecar Integrated Accessory Cabinet-Bypass
150 kW SIAC-B Three-Wire 150 kW SIAC-B Four-Wire 200 kW SIAC-B Three-Wire 200 kW SIAC-B Four-Wire Installation and Operation Manual
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter entièrement ces instructions avant de faire fonctionner l'équipement et conserver ce manuel afin de pouvoir vous y reporter ultérieurement.
Eaton is registered trademarks of Eaton or its subsidiaries and affiliates. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies.
©Copyright 2013-2016 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.

Table of Contents

1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Installation Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.3 Model Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.4 Using This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.5 Conventions Used in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.6 Symbols, Controls, and Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.7 For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.8 Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
2 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
SECTION 1 — INSTALLATION
3 INSTALLATION PLAN AND UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Preparing the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.1 Environmental and Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.2 Floor Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3.2.3 SIAC-B Power Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.2.4 SIAC-B Interface Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.3 Inspecting and Unpacking the SIAC-B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
4 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Preliminary Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Unloading the Field Installed SIAC-B from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.3 Mechanically Joining the UPS Cabinet and SIAC-B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.4 Electrically Connecting the UPS Cabinet and SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.4.1 Installing SIAC-B Internal Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.4.2 Installing SIAC-B Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4.5 Removing and Reinstalling the Factory Installed SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
4.5.1 Electrically Disconnecting the UPS Cabinet and SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
4.5.2 Mechanically Disconnecting the UPS Cabinet and SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
4.5.3 Mechanically Rejoining the UPS Cabinet and SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.5.4 Electrically Reconnecting the UPS Cabinet and SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.6 Unloading the Factory Installed SIAC-B from the Pallet and Mechanical Installation . . . . . . . . . . . . . . . . . . 4-19
4.7 Two-Hole Barrel Lug Terminations to Bus Bar Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
4.8 Installing SIAC-B External Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
4.9 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
4.10 Completing the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
SECTION 2 — OPERATION
5 ONELINES AND SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 Onelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 System Onelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.3 Three Wire Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.4 Four Wire Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality i
Table of Contents
6 SIAC-B OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1 Sidecar Integrated Accessory Cabinet-Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.1 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.2 Using the UPS when an SIAC-B is Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.3 Transferring the UPS to Maintenance Bypass using an SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.1.4 Transferring the UPS from Maintenance Bypass using an SIAC-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
7 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1 Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2 Performing Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.1 DAILY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.2 PERIODIC Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.3 ANNUAL Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.3 Maintenance Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
8 PRODUCT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.3 Environmental and Safety Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W-1
ii Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality

List of Figures

Figure 1-1. Eaton 93PM SIAC-B (Three or Four Wire) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Figure 1-2. Eaton 93PM 150 kW SIAC-B (Three or Four Wire) attached to a
93PM 150 kW Capacity UPS (Three or Four Wire) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Figure 1-3. Eaton 93PM 200 kW SIAC-B (Three or Four Wire) attached to a
93PM 200 kW UPS (Three or Four Wire) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Figure 3-1. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with
93PM 150 kW SIAC-B (Three or Four Wire) Dimensions (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-2. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with
93PM 150 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom Views) . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-3. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with
Left-Mounted 93PM 150 kW SIAC-B (Three or Four Wire) – Center of Gravity . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-4. Eaton 93PM 200 kW UPS (Three or Four Wire) with
93PM 200 kW SIAC-B (Three or Four Wire) Dimensions (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-5. Eaton 93PM 200 kW UPS (Three or Four Wire) with
93PM 200 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom Views) . . . . . . . . . . . . . . . . . . . 3-8
Figure 3-6. Eaton 93PM 200 kW UPS (Three or Four Wire) with
Left-Mounted 93PM 200 kW SIAC-B (Three or Four Wire) – Center of Gravity . . . . . . . . . . . . . . . . . . . . . . 3-9
Figure 3-7. Eaton 93PM 150 kW Capacity UPS Cabinet with
SIAC-B Front and Rear Floor Mounting Bracket Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Figure 3-8. Eaton 93PM 200 kW UPS Cabinet with
SIAC-B Front and Rear Floor Mounting Bracket Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Figure 3-9. Eaton 93PM 150 kW SIAC-B (Three or Four Wire) attached to a
93PM 150 kW Capacity UPS (Three or Four Wire) as Shipped on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Figure 3-10. Eaton 93PM 200 kW SIAC-B (Three or Four Wire) attached to a
93PM 200 kW UPS (Three or Four Wire) as Shipped on Pallet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Figure 3-11. Eaton 93PM Field Installed SIAC-B as Shipped on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM Field Installed SIAC-B . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-2. Cabinet Attaching Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Figure 4-3. Left-Mounted SIAC-B – RIB, BIB, and MIS Breaker Terminal Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Figure 4-4. Right-Mounted SIAC-B – RIB, BIB, and MIS Breaker Terminal Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Figure 4-5. 93PM SIAC-B MIS Input Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Figure 4-6. 93PM SIAC-B BIB Output Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Figure 4-7. 93PM SIAC-B RIB Output Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Figure 4-8. 93PM 150 kW Three-Wire SIAC-B and 93PM 150 kW Four-Wire SIAC-B Interface Terminal Location . . . . 4-12
Figure 4-9. 93PM 200 kW Three-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B Interface Terminal Location . . . . 4-13
Figure 4-10. SIAC-B Interface Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Figure 4-11. 93PM 150 kW Three-Wire SIAC-B and 93PM 150 kW Four-Wire SIAC-B
UPS MBP Interface Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Figure 4-12. 93PM 200 kW Three-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B
UPS MBP Interface Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Figure 4-13. UPS MBP Interface Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Figure 4-14. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Figure 4-15. 93PM 150 kW Three-Wire SIAC-B and 93PM 150 kW Four-Wire SIAC-B
Conduit Landing Wire Entry Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Figure 4-16. 93PM 200 kW Three-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B
Conduit Landing Wire Entry Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
Figure 4-17. 93PM 150 kW Three-Wire SIAC-B and 93PM 150 kW Four-Wire SIAC-B
Left-Mounted Bypass Power Input, Power Output, and Ground Terminal Locations. . . . . . . . . . . . . . . . . . 4-24
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality iii
List of Figures
Figure 4-18. 93PM 150 kW Three-Wire SIAC-B and 93PM 150 kW Four-Wire SIAC-B
Right-Mounted Bypass Power Input, Power Output, and Ground Terminal Locations. . . . . . . . . . . . . . . . . . 4-25
Figure 4-19. 93PM 200 kW Three-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B
Left-Mounted Bypass Power Input, Power Output, and Ground Terminal Locations. . . . . . . . . . . . . . . . . . . 4-26
Figure 4-20. 93PM 200 kW Three-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B
Right-Mounted Bypass Power Input, Power Output, and Ground Terminal Locations. . . . . . . . . . . . . . . . . . 4-27
Figure 4-21. 93PM SIAC-B RIB Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
Figure 5-1. Two-Breaker SIAC-B Internal Oneline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-2. Three-Breaker SIAC-B Internal Oneline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-3. Four-Breaker SIAC-B Internal Oneline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 5-4. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with
Two-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online. . . . . 5-5
Figure 5-5. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with
Three-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online . . . 5-6 Figure 5-6. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with
Four-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online . . . . 5-7
Figure 5-7. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with
Two-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online. . . . . . . 5-8
Figure 5-8. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with
Three-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online . . . . . 5-9
Figure 5-9. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with
Four-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online . . . . . . 5-10
Figure 5-10. Eaton 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B Two-Breaker Schematic . . . 5-11 Figure 5-11. Eaton 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B Three-Breaker Schematic . . 5-12 Figure 5-12. Eaton 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B Four-Breaker Schematic . . . 5-13
Figure 5-13. Eaton 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B Two-Breaker Schematic . . . . . 5-14
Figure 5-14. Eaton 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B Three-Breaker Schematic . . . . 5-15
Figure 5-15. Eaton 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B Four-Breaker Schematic . . . . . 5-16
Figure 6-1. Eaton 93PM 150 kW SIAC-B (Three or Four Wire) or
Eaton 93PM 200 kW SIAC-B (Three or Four Wire) Breakers – Left-Mounted SIAC-B . . . . . . . . . . . . . . . . . . 6-2
Figure 6-2. Eaton 93PM 150 kW SIAC-B (Three or Four Wire) or
Eaton 93PM 200 kW SIAC-B (Three or Four Wire) Breakers – Right-Mounted SIAC-B . . . . . . . . . . . . . . . . . 6-3
iv Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality

List of Tables

Table 3-1. SIAC-B Cabinet Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Table 3-2. External Power Wiring Requirements for the Eaton 93PM 150 kW Three-Wire SIAC-B and
93PM 200 kW Three-Wire SIAC-B – Two and Three Breaker Maintenance Bypass. . . . . . . . . . . . . . . . . . . 3-15
Table 3-3. External Power Wiring Requirements for the Eaton 93PM 150 kW Three-Wire SIAC-B and
93PM 200 kW Three-Wire SIAC-B – Four Breaker Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Table 3-4. External Power Wiring Requirements for the Eaton 93PM 150 kW Four-Wire SIAC-B and
93PM 200 kW Four-Wire SIAC-B – Two and Three Breaker Maintenance Bypass. . . . . . . . . . . . . . . . . . . . 3-17
Table 3-5. External Power Wiring Requirements for the Eaton 93PM 150 kW Four-Wire SIAC-B and
93PM 200 kW Four-Wire SIAC-B – Four Breaker Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Table 3-6. External Input Power Cable Terminations for the Eaton 93PM 150 kW Three-Wire SIAC-B . . . . . . . . . . . . 3-19
Table 3-7. External Input Power Cable Terminations for the Eaton 93PM 150 kW Four-Wire SIAC-B . . . . . . . . . . . . . 3-19
Table 3-8. External Input Power Cable Terminations for the Eaton 93PM 200 kW Three-Wire SIAC-B . . . . . . . . . . . . 3-20
Table 3-9. External Input Power Cable Terminations for the Eaton 93PM 200 kW Four-Wire SIAC-B . . . . . . . . . . . . . 3-20
Table 3-10. Supplied External Wiring Terminal Hardware Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Table 3-11. Recommended Installation Parts and Tools (Not Supplied by Eaton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Table 4-1. SIAC-B Interface Wiring Terminal Block Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Table 4-2. SIAC-B MBP Interface Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality v
List of Tables
This page intentionally left blank.
vi Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality

Chapter 1 Introduction

The Eaton® 93PM 150 kW and 200 kW Three-Wire Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) is designed for use with the 93PM 150 kW and 200 kW Three-Wire UPS systems. The 93PM 150 kW and 200 kW Four-Wire SIAC-B is designed for used with the 93PM 150 kW and 200 kW Four-Wire UPS systems. The SIAC-B provides maintenance bypass functions with configurable features, enabling adaptation and expansion without costly electrical rework.
NOTE Startup and operational checks must be performed by an authorized Eaton

1.1 Features

The following descriptions provide a brief overview of the SIAC-B functions:
l
Two breaker configuration: The bypass sidecar contains only a Maintenance Bypass (MBP) and Maintenance Isolation (MIS) breaker. This allows Maintenance bypass for system repair or maintenance. The critical load is NOT protected in the Maintenance bypass mode.
l
Three breaker configuration (used with single-feed systems): Maintenance Bypass (MBP) and Maintenance Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely bypass the UPS. The UPS can then be safely serviced or replaced without interrupting power to critical systems.
l
Four breaker configuration (used with dual-feed systems): Maintenance Bypass (MBP) and Maintenance Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely bypass the UPS. A Rectifier Input Breaker (RIB) provides a convenient method for removing power from the UPS when using the maintenance bypass to supply the load. The UPS can then be safely serviced or replaced without interrupting power to critical systems.
Figure 1-1shows the SIAC-B. Figure 1-2 and Figure 1-3 show the SIAC-B mounted to the UPS cabinet.
Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date.

1.2 Installation Features

The SIAC-B is housed in a single cabinet factory or field attached to and directly integrated with the UPS cabinet and can be ordered mounted on either the left or right side of the UPS, or shipped separately. The SIAC-B matches the UPS cabinet in style and color. It has safety shields behind the removable front panel for hazardous voltage protection and 2-hole bus bar lug input and output terminals reduce installation time. Power wiring between the UPS and SIAC-B are factory installed. Output power wiring to the critical load is routed using external conduit.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 1-1
Introduction

1.3 Model Configurations

The following model configurations are available:
l
Eaton 93PM 150 kW Three-Wire SIAC-B, Eaton 93PM 150 kW Four-Wire SIAC-B, Eaton 93PM 200 kW Three-Wire SIAC-B, and Eaton 93PM 200 kW Four-Wire SIAC-B
- Right-mounted two breaker configuration containing a MBP with auxiliary contacts and MIS
- Right-mounted three breaker configuration containing a MBP with auxiliary contacts, a MIS, and a BIB
- Right-mounted four breaker configuration containing a MBP with auxiliary contacts, a MIS, a BIB, and a RIB
- Left-mounted two breaker configuration containing a MBP with auxiliary contacts and MIS
- Left-mounted three breaker configuration containing a MBP with auxiliary contacts, a MIS, and a BIB
- Left-mounted four breaker configuration containing a MBP with auxiliary contacts, a MIS, a BIB, and a RIB
Figure 1-1. Eaton 93PM SIAC-B (Three or Four Wire)
1-2 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Introduction
Left-Mounted SIAC-B
Right-Mounted SIAC-B
SIAC-B
UPS
UPS
SIAC-B
Figure 1-2. Eaton 93PM 150 kW SIAC-B (Three or Four Wire) attached to a 93PM 150 kW Capacity UPS (Three or Four Wire)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 1-3
Introduction
Left-Mounted SIAC-B
Right-Mounted SIAC-B
SIAC-B
UPS
UPS
SIAC-B
Figure 1-3. Eaton 93PM 200 kW SIAC-B (Three or Four Wire) attached to a 93PM 200 kW UPS (Three or Four Wire)
1-4 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality

1.4 Using This Manual

This manual describes how to install the SIAC-B and is divided into chapters. Read and understand the procedures described to ensure trouble-free installation and operation.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the UPS system being installed or operated.

1.5 Conventions Used in This Manual

This manual uses these type conventions:
l
Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or represents a command or option that you type or enter at a prompt.
l
Italic type highlights notes and new terms where they are defined.
l
Screen type represents information that appears on the screen or LCD.
Icon Description
Note Information notes call attention to important features or instructions.
[Keys] Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system – the UPS cabinet, an external battery system, and options or accessories installed.
Introduction
The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS. The term standalone refers to accessory cabinets that are located separate from the UPS.

1.6 Symbols, Controls, and Indicators

The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 1-5
Introduction

1.7 For More Information

Refer to the Eaton 93PM UPS (20–150 kW, 480V – 150 kW Capacity Frame) Installation and Operation Manual, the Eaton 93PM UPS (20–150 kW, 480V Four Wire – 150 kW Capacity Frame) Installation and Operation
Manual, the Eaton 93PM Emergency Lighting UPS (20–40 kW, 480V Four Wire – UL 924) Installation and Operation Manual, the Eaton 93PM UPS (20–200 kW, 480V – 200 kW Frame) Installation and Operation Manual, or the Eaton 93PM UPS (20–200 kW, 480V Four Wire – 200 kW Frame) Installation and Operation Manual for the following additional information:
l
UPS, optional components, and accessory installation instructions, including site preparation, planning for installation, and wiring and safety information. Detailed illustrations of cabinets and optional accessories with dimensional and connection point drawings are provided.
l
UPS operation, including UPS controls, functions of the UPS, standard features and optional accessories, procedures for starting and stopping the UPS, and information about maintenance and responding to system events.
l
Communication capabilities of the UPS system.
Refer to the Eaton 93PM Integrated Accessory Cabinet-Distribution (50 kW, 100 kW, 150 kW, and 200 kW IAC-D) Installation and Operation Manual for the following additional information:
l
Installation instructions, including site preparation, planning for installation, wiring and safety information, and detailed illustrations of cabinets with dimensional and connection point drawings
l
Operation, including breakers, standard features and optional accessories, procedures for using the tie and bypass functions, and information about maintenance
Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain copies of these manuals.

1.8 Getting Help

If help is needed with any of the following:
Scheduling initial startup
Regional locations and telephone numbers
A technical question about any of the information in this manual
A question this manual does not answer
Please call the Customer Reliability Center at:
United States: 1-800-843-9433 Canada: 1-800-461-9166 ext 260 All other countries: Call your local service representative
Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual:
E-ESSDocumentation@eaton.com
1-6 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality

Chapter 2 Safety Warnings

This manual contains important instructions that should be followed during installation and maintenance of the UPS system and batteries. Read all instructions before operating the equipment and save this manual for future reference.
The UPS system is designed for industrial or computer room applications, and contains safety shields behind the door and front panels. However, the UPS system is a sophisticated power system and should be handled with appropriate care.
This UPS system contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
l
The UPS system is powered by its own energy source (batteries). The output terminals may carry live voltage even when the UPS is disconnected from an AC source.
l
To reduce the risk of fire or electric shock, install this UPS system in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40C (104F). Do not operate near water or excessive humidity (95% maximum). The system is not intended for outdoor use.
l
As a result of the connected loads high leakage current is possible. Connection to earth ground is required for safety and proper product operation. Do not check UPS system operation by any action that includes removal of the earth (ground) connection with loads attached.
l
Ensure all power is disconnected before performing installation or service.
l
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS system or battery wiring or connectors. Attempting to alter wiring can cause injury.
l
Installation or servicing should be performed by qualified service personnel knowledgeable of UPS and battery systems, and required precautions. Keep unauthorized personnel away from equipment. Consider all warnings, cautions, and notes before installing or servicing equipment.
l
Keep the Accessory cabinet doors closed and front panels installed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit.
l
Do not install or operate the UPS system close to gas or electric heat sources.
l
The operating environment should be maintained within the parameters stated in this manual.
l
Keep surroundings uncluttered, clean, and free from excess moisture.
l
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 2-1
Safety Warnings
This page intentionally left blank.
2-2 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Section 1
Installation

Chapter 3 Installation Plan and Unpacking

This chapter includes planning for the Eaton 93PM 150 kW and 200 kW Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B).
NOTE The SIAC-B is attached to and directly integrated with the UPS cabinet at the factory
or after field installation on sight. This section must be used along with the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
1.7, during installation planning and unpacking.
Use the following basic sequence of steps to install the SIAC-B:
1. Create an installation plan for the SIAC-B.
2. Prepare your site for the SIAC-B.
3. Inspect and unpack the SIAC-B (refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for inspection and unpacking instructions).
4. Unload and install the SIAC-B (refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for inspection and unpacking instructions).
5. Externally wire the SIAC-B.
6. Complete the Installation Checklist.
7. Have authorized service personnel perform preliminary operational checks and start up the system.
NOTE Startup and operational checks must be performed by an authorized Eaton
Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.

3.1 Creating an Installation Plan

Before installing the SIAC-B, read and understand how this manual applies to the system being installed. Use the procedures and illustrations in this section to create a logical plan for installing the SIAC-B.

3.2 Preparing the Site

For the UPS system to operate at peak efficiency, the installation site should meet the environmental parameters outlined in this manual. The operating environment must meet the weight, clearance, and environmental requirements specified for the applicable accessory cabinet. Specifications subject to change.

3.2.1 Environmental and Installation Considerations

The UPS system installation, including the SIAC-B, must meet the following guidelines:
l
The system must be installed on a level floor suitable for computer or electronic equipment.
l
The system must be operated at an altitude no higher than 1500m (5000 ft) without derating. For additional assistance with high altitude operation, contact an Eaton service representative (see paragraph 1.8).
l
The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
Failure to follow guidelines may void your warranty.
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 3-1
Installation Plan and Unpacking
The basic environmental requirements for operation of the SIAC-B are:
l
Ambient Temperature Range: 5–40C (41–104F)
l
Recommended Operating Range: 5–40C (41–104F)
l
Maximum Relative Humidity: 95%, noncondensing
The SIAC-B operating environment must meet the weight requirements shown in Table 3-1. The SIAC-B size requirements are shown in Figure 3-1 through Figure 3-3 or Figure 3-4 through Figure 3-6. Dimensions are in millimeters (inches).
Table 3-1. SIAC-B Cabinet Weights
Weight
kg (lb)
Model
Eaton 93PM-150-1 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 572 (1259) 541 (1192) 8 at 68 (149)
Eaton 93PM-150-2 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 635 (1399) 604 (1332) 8 at 76 (167)
Eaton 93PM-150-3 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 699 (1540) 668 (1473) 8 at 84 (184)
Eaton 93PM-150-1 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 585 (1289) 554 (1222) 8 at 69 (153)
Eaton 93PM-150-2 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 649 (1430) 618 (1363) 8 at 77 (170)
Eaton 93PM-150-3 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 713 (1570) 682 (1503) 8 at 85 (188)
Shipping Installed Point Loading
Eaton 93PM-150-1 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 600 (1322) 569 (1255) 8 at 71(157)
Eaton 93PM-150-2 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 664 (1462) 633 (1395) 8 at 79 (174)
Eaton 93PM-150-3 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 727 (1603) 696 (1536) 8 at 87 (192)
Eaton 93PM-150-1 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 614 (1352) 583 (1285) 8 at 73 (161)
Eaton 93PM-150-2 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 677 (1492) 646 (1425) 8 at 81 (178)
Eaton 93PM-150-3 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 741 (1633) 710 (1566) 8 at 89 (196)
Eaton 93PM-200-1 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 624 (1374) 593 (1307) 8 at 74 (163)
Eaton 93PM-200-2 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 687 (1514) 656 (1447) 8 at 82 (181)
Eaton 93PM-200-3 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 751 (1655) 720 (1588) 8 at 90 (199)
Eaton 93PM-200-4 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker) 815 (1795) 784 (1728) 8 at 98 (216)
Eaton 93PM-200-1 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 637 (1404) 606 (1337) 8 at 76 (167)
Eaton 93PM-200-2 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 701 (1544) 670 (1477) 8 at 84 (185)
Eaton 93PM-200-3 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 765 (1685) 734 (1618) 8 at 92 (202)
Eaton 93PM-200-4 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker) 828 (1825) 797 (1758) 8 at 100 (220)
Eaton 93PM-200-1 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 658 (1449) 627 (1382) 8 at 78 (173)
Eaton 93PM-200-2 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 721 (1589) 690 (1522) 8 at 86 (190)
Eaton 93PM-200-3 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 785 (1730) 754 (1663) 8 at 94 (208)
Eaton 93PM-200-4 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker) 849 (1875) 818 (1808) 8 at 102 (288)
Eaton 93PM-200-1 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 871 (1479) 640 (1412) 8 at 80 (226)
Eaton 93PM-200-2 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 735 (1619) 704 (1552) 8 at 88 (194)
Eaton 93PM-200-3 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 799 (1760) 768 (1693) 8 at 96 (212)
Eaton 93PM-200-4 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker) 862 (1900) 831 (1833) 8 at 104 (229)
The clearances required around the SIAC-B are the same as the attached UPS.
3-2 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Installation Plan and Unpacking
Dimensions are in millimeters [inches]
UPS with Left-Mounted SIAC-B UPS with Right-Mounted SIAC-B
Figure 3-1. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with 93PM 150 kW SIAC-B (Three or Four Wire) Dimensions (Front View)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 3-3
Installation Plan and Unpacking
UPS with Left-Mounted SIAC-B
UPS with Right-Mounted SIAC-B
Bottom View
Bottom View
Top View
Front
Front
Front
Front
Top View
Dimensions are in millimeters [inches]
Figure 3-2. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with 93PM 150 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom Views)
3-4 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Installation Plan and Unpacking
Dimensions are in millimeters [inches]
NOTE The 93PM 150 kW Capacity UPS (three or four wire) is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image.
Figure 3-3. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with Left-Mounted 93PM 150 kW SIAC-B (Three or Four Wire) – Center of Gravity
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 3-5
Installation Plan and Unpacking
Weight and Center of Gravity with Left-Mounted 150 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 3-3)
Eaton 93PM-150-1 Capacity UPS with 2-Breaker SIAC-B 862 (33.9) 508 (20.0) 501 (19.7) 541 (1192)
Eaton 93PM-150-2 Capacity UPS with 2-Breaker SIAC-B 913 (35.9) 510 (20.1) 518 (20.4) 604 (1332)
Eaton 93PM-150-3 Capacity UPS with 2-Breaker SIAC-B 985 (38.8) 512 (20.2) 531 (20.9) 668 (1473)
Eaton 93PM-150-1 Capacity UPS with 4-Breaker SIAC-B 870 (34.3) 507 (20.0) 494 (19.4) 554 (1222)
Eaton 93PM-150-2 Capacity UPS with 4-Breaker SIAC-B 819 (36.2) 509 (20.0) 510 (20.1) 618 (1363)
Eaton 93PM-150-3 Capacity UPS with 4-Breaker SIAC-B 989 (38.9) 511 (20.1) 524 (20.6) 682 (1503)
Weight and Center of Gravity with Right-Mounted 150 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 3-3)
Eaton 93PM-150-1 Capacity UPS with 2-Breaker SIAC-B 862 (33.9) 508 (20.0) 437 (17.2) 541 (1192)
Eaton 93PM-150-2 Capacity UPS with 2-Breaker SIAC-B 913 (35.9) 510 (20.1) 420 (16.5) 604 (1332)
Eaton 93PM-150-3 Capacity UPS with 2-Breaker SIAC-B 985 (38.8) 512 (20.2) 407 (16.0) 668 (1473)
Eaton 93PM-150-1 Capacity UPS with 4-Breaker SIAC-B 870 (34.3) 507 (20.0) 445 (17.5) 554 (1222)
Eaton 93PM-150-2 Capacity UPS with 4-Breaker SIAC-B 819 (36.2) 509 (20.0) 428 (16.9) 618 (1363)
Eaton 93PM-150-3 Capacity UPS with 4-Breaker SIAC-B 989 (38.9) 511 (20.1) 414 (16.3) 682 (1503)
A
mm (in)Bmm (in)Cmm (in)
A
mm (in)Bmm (in)Cmm (in)
Installed Weight
kg (lb)
Installed Weight
kg (lb)
Weight and Center of Gravity with Left-Mounted 150 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 3-3)
A
mm (in)Bmm (in)Cmm (in)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 853 (33.6) 552 (21.7) 501 (19.7) 569 (1255)
Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B 903 (35.5) 550 (21.7) 517 (20.3) 633 (1395)
Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B 973 (38.3) 548 (21.6) 529 (20.8) 696 (1536)
Eaton 93PM-200-1 UPS with 4-breaker SIAC-B 861 (33.9) 553 (21.8) 494 (19.4) 583 (1285)
Eaton 93PM-200-2 UPS with 4-breaker SIAC-B 909 (35.8) 551 (21.7) 510 (20.1) 646 (1425)
Eaton 93PM-200-3 UPS with 4-breaker SIAC-B 977 (38.5) 549 (21.6) 523 (20.6) 710 (1566)
Weight and Center of Gravity with Right-Mounted 150 kW Four-Wire SIAC-B (letters A, B, and C map to Figure 3-3)
A
mm (in)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 853 (33.6) 552 (21.7) 421 (16.6) 569 (1255)
Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B 903 (35.5) 550 (21.7) 407 (16.0) 633 (1395)
Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B 973 (38.3) 548 (21.6) 395 (15.5) 696 (1536)
Eaton 93PM-200-1 UPS with 4-breaker SIAC-B 861 (33.9) 553 (21.8) 429 (16.9) 583 (1285)
Eaton 93PM-200-2 UPS with 4-breaker SIAC-B 909 (35.8) 551 (21.7) 414 (16.3) 646 (1425)
Eaton 93PM-200-3 UPS with 4-breaker SIAC-B 977 (38.5) 549 (21.6) 402 (15.8) 710 (1566)
B
mm (in)Cmm (in)
Installed Weight
kg (lb)
Installed Weight
kg (lb)
3-6 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Installation Plan and Unpacking
Dimensions are in millimeters [inches]
UPS with Left-Mounted SIAC-B UPS with Right-Mounted SIAC-B
Figure 3-4. Eaton 93PM 200 kW UPS (Three or Four Wire) with 93PM 200 kW SIAC-B (Three or Four Wire) Dimensions (Front View)
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 3-7
Installation Plan and Unpacking
Dimensions are in millimeters [inches]
UPS with Left-Mounted SIAC-B
UPS with Right-Mounted SIAC-B
Bottom View
Bottom View
Top View
Front
Front
Front
Front
Top View
Figure 3-5. Eaton 93PM 200 kW UPS (Three or Four Wire) with 93PM 200 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom
3-8 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality
Views)
Dimensions are in millimeters [inches]
NOTE The 93PM 200 kW UPS is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image.
Installation Plan and Unpacking
Figure 3-6. Eaton 93PM 200 kW UPS (Three or Four Wire) with Left-Mounted 93PM 200 kW SIAC-B (Three or Four Wire) – Center of Gravity
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality 3-9
Installation Plan and Unpacking
Weight and Center of Gravity with Left-Mounted 200 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 3-6)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 855 (33.7) 564 (22.2) 580 (22.8) 593 (1307)
Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B 866 (34.1) 561 (22.1) 587 (23.1) 656 (1447)
Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B 908 (35.7) 559 (22.0) 593 (23.3) 720 (1588)
Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B 968 (38.1) 557 (21.9) 598 (23.5) 784 (1728)
Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B 864 (34.0) 575 (22.6) 574 (22.6) 606 (1337)
Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B 873 (34.4) 571 (22.5) 582 (22.9) 670 (1477)
Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B 914 (36.0) 568 (22.4) 588 (23.1) 734 (1618)
Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B 973 (38.3) 566 (22.3) 594 (23.4) 797 (1758)
Weight and Center of Gravity with Right-Mounted 200 kW Three-Wire SIAC-B (letters A, B, and C map to Figure 3-6)
Eaton 93PM-200-1 UPS with 2-Breaker SIAC-B 857 (33.7) 566 (22.3) 593 (23.3) 593 (1307)
Eaton 93PM-200-2 UPS with 2-Breaker SIAC-B 868 (34.2) 563 (22.2) 563 (22.2) 656 (1447)
Eaton 93PM-200-3 UPS with 2-Breaker SIAC-B 909 (35.8) 561 (22.1) 538 (21.2) 720 (1588)
Eaton 93PM-200-4 UPS with 2-Breaker SIAC-B 970 (38.2) 559 (22.0) 517 (20.4) 784 (1728)
Eaton 93PM-200-1 UPS with 4-Breaker SIAC-B 864 (34.0) 575 (22.6) 599 (23.6) 606 (1337)
Eaton 93PM-200-2 UPS with 4-Breaker SIAC-B 874 (34.4) 571 (22.5) 568 (22.4) 670 (1477)
Eaton 93PM-200-3 UPS with 4-Breaker SIAC-B 914 (36.0) 568 (22.4) 543 (21.4) 734 (1618)
Eaton 93PM-200-4 UPS with 4-Breaker SIAC-B 974 (38.3) 566 (22.3) 522 (20.6) 797 (1758)
A
mm (in)Bmm (in)Cmm (in)
A
mm (in)Bmm (in)Cmm (in)
Installed Weight
kg (lb)
Installed Weight
kg (lb)
3-10 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality