Product Introduction
Product Snapshot
Technology:
Power Rating:
Input Voltage:
Output Voltage:
Frequency:
Dimensions:
Configuration:
Battery Backup:
Split-phase double-conversion
online UPS
8 kVA, 10 kVA, 12 kVA and 15 kVA
at 0.9 power factor
200–240 Vac with Neutral or with
optional input isolation transformer
100/200, 110/220, 120/240 Vac 180°
phase displacement; 120/208,
127/220 Vac 120°
phase displacement
50/60 Hz auto-sensing
32.2” H x 12” W x 32.5” D
Small-footprint tower, black
Up to 29 minutes typical, extendable up
to four hours (See battery backup charts)
9155 8-15 kVA
Reliability and efficiency have never looked so attractive.
The 9155 single-phase Uninterruptible Power System (UPS)
delivers a combination of advanced technology, userfriendly design and low price that's absolutely unmatched
by competing products. This innovative design offers high
efficiency (90 percent or better across all load ranges), low
input current distortion (less than 5 percent total harmonic
distortion, with an active IGBT rectifier that delivers 0.99
power factor correction) and high power factor output
(0.9 PF).
With advances being made in miniaturization and processing
power and more equipment being served by dual-cord
power supplies, the challenge of protecting that power, and
doing so in a limited space, grows ever greater.
Fortunately, advances in technology have also meant
that more power protection per square foot can now be
provided. The 9155 delivers premium levels of efficiency,
reliability and flexibility, all in a sleek tower half the size of
most other units on the market today.
Features of the Eaton 9155 UPS
• A true online, double-conversion topology protects
connected equipment from all nine of the most common
power problems
• Delivers maximum power density in a compact tower
design: 12” wide and 33” deep, including batteries
• Provides more real power in less space (5,500 watts per
square foot) with a 0.9 output power factor – protecting
more equipment for every utility dollar and leaving more
room for expansion of the data center
®
• Patented Powerware Hot Sync
modules delivers extra capacity or redundancy
• Customizable output distribution provides user-specied
power outlets along with terminals for connecting hardwired equipment
• Microprocessor-controlled ABM
increases battery life
• Provides a 0.99 input power factor and generator friendly
<5% total harmonic distortion using an active IGBT
rectifier to control the input power factor
paralleling of multiple
®
technology significantly
2 EATON CORPORATION 9155 UPS
• Ensures data and system integrity with complete
power management software for remote monitoring,
management and shutdown
• An Eaton factory limited warranty, technical support and
optional service plans provide investment protection and
peace of mind
Premium power protection is now easier
than ever.
Scalable architecture meets current and
future load requirements.
With raised-floor real estate at a premium, you’ll appreciate
that the 9155 requires only three to six square feet of floor
space, including internal batteries. Such a small footprint
gives you more location options and more space available
for future expansion.
Equipment installation is inexpensive and easy – essentially
plug-and-play. You can order 9155 models with your choice
of more than 19 types of output receptacles. To rearrange
or add data center equipment, you simply unplug from the
old receptacle and plug into a new one – no need for an
electrician to run new conduit and wiring.
Inside view of 9155 Parallel
Powerware Hot Sync Redundant/Capacity
Cabinet Maintenance Bypass
9155 UPS Parallel Cabinet
Load
Eaton 9155 UPSs are available in four models: 8, 10, 12
and 15 kVA, so you can choose the conguration that most
closely meets your own capacity requirements and price
point. And you can scale from there. Using our signature
Hot Sync paralleling technology, up to three 9155 modules
can be paralleled for extra capacity or redundancy. A 15
kVA UPS, for example, can grow to support loads of up to
45 kVA. There's no dependence on communications wiring
among these modules, enhancing reliability and simplifying
installation. This paralleling capability Is far more easily
achieved than is the case with competitors' products.
Battery innovations optimize battery performance and service life.
Standard internal batteries provide power until auxiliary power takes over or systems
are gracefully shut down. Battery runtime can be extended to hours by adding matching
Extended Battery Modules (EBM).
Eaton 9155 8-15 kVA UPS Backup Times (In Minutes)
UPS
VA Watt
15000 13500 4.6 23.0 43.0 65.1 88.6 13.3 43.0 76.7 113
14500 13050 4.9 24.1 45.2 68.3 93.0 14.1 45.2 80.5 119
14000 12600 5.2 25.2 47.3 71.5 97.4 14.9 47.3 84.2 125
13500 12150 5.5 26.4 49.4 74.7 102 15.8 49.4 88.1 130
13000 11700 5.8 27.6 51.6 78.1 106 16.7 51.6 92.0 136
12500 11250 6.1 28.8 54.0 81.6 111 17.6 54.0 96.2 142
12000 10800 6.5 30.2 56.5 85.5 116 18.6 56.5 101 149
11500 10350 6.9 31.6 59.3 89.7 122 19.2 59.3 106 156
11000 9900 7.3 33.3 62.4 94.4 129 20.2 62.4 111 164
10500 9450 7.8 35.1 65.9 99.6 136 21.4 65.9 117 174
10000 9000 8.4 37.2 69.8 106 144 22.6 69.8 124 184
9500 8550 9.1 39.6 74.2 112 153 24.1 74.2 132 196
9000 8100 9.9 42.3 79.4 120 163 25.7 79.4 141 209
8500 7650 10.8 45.5 85.2 129 175 27.6 85.2 152 225
8000 7200 11.9 49.1 91.9 139 189 29.8 91.9 164 242
+ Internal
32 Battery
(1)
EBM
64
(2)
EBM
64
(3)
EBM
64
(4)
EBM
64
UPS
+ Internal
64 Battery
(1)
EBM
96
(2)
EBM
96
Eaton 9155 8-15 kVA UPS Backup Times (In Minutes)
(3)
EBM
96
VA Watt
7500 6750 13.1 53.2 99.7 151 205 32.3 99.7 178 263
7000 6300 14.6 58.0 109 164 224 35.2 109 194 286
6500 5850 16.3 63.5 119 180 245 38.6 119 212 314
6000 5400 18.4 70.0 131 198 270 42.5 131 234 346
5500 4950 20.1 77.6 145 220 300 47.2 145 259 383
5000 4500 22.4 86.6 162 245 334 52.6 162 289 428
4500 4050 25.2 97.4 182 276 376 59.2 182 325 -
4000 3600 28.6 110 207 313 426 67.1 207 369 -
3500 3150 32.8 127 238 359 - 77.0 238 423 -
3000 2700 38.3 148 277 418 - 89.7 277 - -
2500 2250 45.6 176 329 - - 107 329 - -
Note: Backup times are approximate and may vary with equipment, configuration, battery age,
temperature, etc.
UPS
+ Internal
32 Battery
(1)
EBM
64
(2)
EBM
64
(3)
EBM
64
(4)
EBM
64
UPS
+ Internal
64 Battery
(1)
EBM
96
(2)
EBM
96
(3)
EBM
96
www.ea to n. co m/ 9155 1.800.356.5794 3