• Provides clean, continuous power to protect critical equipment and applications from power-related downtime, data
loss and corruption, and process interruption
• Saves valuable rack space by delivering 6000 VA/4200W in
only 3U
• Offers deployment versatility through rack and tower
installation options with rail kits and pedestals provided
• Increases availability with hot-swappable batteries and
power module
• Offers extended battery runtime options to power essential
systems for more than an hour during an outage
Product snapshot
Power rating: 6 kVA/4.2 kW
Voltage: 230V nominal,
200–250 Vac range
Frequency: 50/60 Hz (auto-sensing)
Configuration: Rackmount (3U) or tower
Advanced power protection for:
• Medium-density data centers
• Banking and security systems
• Manufacturing process control
• Retail point-of-sale systems
• Telecommunications/VoIP equipment
The Eaton® 9135 UPS, Power-
®
series, resolves utility
ware
power problems and supplies continuous, conditioned
power. You get clean power
for valuable IT and networking equipment, battery backup to gracefully handle utility
outages, and on-demand visibility into UPS status from
anywhere.
Get more usable power for
less cost
The 9135 provides exactly
the level of power protection
needed under the conditions
of the moment—optimizing
for both efficiency and performance. The more efficient the
UPS, the lower your utility
and cooling bills.
Under normal power conditions, the UPS can operate
in high-efficiency mode at
up to 97 percent efficiency.
In double conversion mode,
the UPS operates at up to 91
percent efficiency.
Double-conversion design
for superior reliability and
protection
In double conversion mode,
the 9135 is constantly monitoring power conditions—
regulating both voltage and
frequency. Even when presented with the most severe
power problems, this UPS’s
output remains within two
percent of nominal voltage.
Page 2
With a wide range of acceptable input voltages, this UPS does
not depend on batteries to smooth out power fluctuations.
Batteries are conserved for those times when utility power
is highly unstable or completely out. If an outage occurs, the
9135 transfers to battery with no break in power, making this
an ideal UPS for equipment sensitive to voltage fluctuations.
More power in less space
High power density. The 9135 increases power density, delivering 6000 VA/4200W in only 3U of rack space, freeing more
rack space for IT and telecom equipments. Rail kits and tower
pedestals are included with every 9135 for flexible installation.
Rack model and EBM installation
Hot swappable batteries
This UPS is even more user-friendly than its predecessors
offering greater distribution capabilities, with eight IEC 10A
& two IEC 16A outlets to power multiple pieces of equipment
without a PDU.
You can combine the 9135 with an Eaton enclosure PDU (ePDU™)
to power an entire rack of equipment from a single power cord
input. ePDU outlets can be monitored, switched, sequenced
and managed individually, providing maximum flexibility in
distributing power from the 9135.
Maximum availability for critical systems
Battery runtime for minutes or hours. During a power outage,
internal batteries in the 9135 keep loads running long enough
to gracefully shut down systems. Add up to four external battery modules (EBMs) to deliver more than an hour of extended
runtime at full load—or hours under lighter loads. Each EBM
occupies only 3U of rack space. These battery modules are
hot-swappable and can be replaced at any time without interrupting UPS operation and load protection.
Maximum battery runtime for critical equipments. LanSafe
power management software enables independent control of
load segments. With this feature, you can manage scheduled
shutdowns and sequential startups of protected loads. During
a power outage, you could shut down power to less essential
loads to extend battery backup time for more critical devices.
Load segments
ConnectUPS-MS Network Management Card web interface
When the load segments feature is used with optional Connect
UPS-MS connectivity cards, users can remotely re-boot locked-up network equipment. Simply access the ConnectUPS-MS
card over the network, and toggle the password-protected
load segment controller to get your network back online.
Service without downtime.
The 9135 features hot-swappable
components and an automatic internal bypass. The UPS automatically switches to an alternate power path within the unit
if it senses a trouble condition with an internal component.
Users can even remove and replace the battery and power
modules without powering down the UPS or interrupting power to loads.
2 EATON CORPORATION Eaton 9135 UPS
Page 3
Visibility, control and management from anywhere
Local UPS status at a glance. An intuitive LCD interface provides detailed information and menu-driven functions for UPS
management. The entire display rotates for the best orientation, whether the UPS is used vertically as a tower unit or
horizontally in a rack. The blue, backlit LCD screen displays
four lines of alphanumeric information. LEDs clearly display
UPS status:
•
Load Protected
•
Downgraded Operation
Load Not Protected •
UPS ON/OFF button•
Choice of connectivity options. Connectivity options are available for almost any networking environment. The standard
unit comes with USB and RS-232 serial communication ports
and a DB-9 dry contact port. You can customize your UPS by
adding MS-slot interface options for other types of communications.
1.
5
1
4
3
2
Optional communication card
slot for Web/SNMP interface
USB port
2.
DB 9 serial port3.
DB 9 with five dry output 4.
contacts
5.
Remote power off
LCD rotatable display
Web/SNMP card
Unified management for power protection. The 9135 comes
complete with the Eaton Software Suite CD, including SNMPcompatible power management software providing control
and visibility over all your UPS systems. From a central vantage point anywhere within the reach of a network connection,
you can:
•
Establish prioritized shutdown of network devices and client/ server applications
Test all network-connected UPSs from one node
•
Intelligent Power Manager (IPM)
Stay informed of power problems via email broadcasts •
MODELS
DescriptionStyle number
Rating
(VA/
Watts)
Input
plug
Output receptacles
Dimensions
H x W x D, mm
Weight,
kg
Rack Tower Models
9135G-6000 R/T 3U 103006722-6591 6000/4200 Hardwired Hardwired + (2) C19, (8) C13 130 x 444 x 74157
Extended Battery Modules
9135G-6000 EBM R/T 3U 103006723-6591 NANANA130 x 444 x 65077.5
* Runtimes available for the 6 kVA model only. Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
www.eaton.com/9135 3
Page 4
Eaton 9135 UPS Product Focus
TECHNICAL SPECIFICATIONS
General
User interfaceGraphical LCD with blue backlight and text in
LEDsFour status-indicating LEDs
TopologyDouble-conversion
DiagnosticsFull system self-test
UPS bypassAutomatic bypass
DimensionsSee models selection guide
Rail kitIncluded with all units
Electrical Input
Nominal voltage230V
Voltage range156–280 Vac (output PF 0.7)
Power draw of UPS
(full load)
Recommended input-
breaker rating
Frequency50/60 Hz autoselect
Frequency range40–70 Hz
Electrical Output
Power factor0.7
On utility voltage±2% of nominal regulation
On battery voltage±2% of nominal regulation
Efficiency>97% in high-efficiency mode; 91% in normal mode
Frequency regulation ±3% Hz online
Load crest factor3 to 1
Battery replacementHot-swappable internal and external batteries
Start-on-batteryAllows start of UPS without utility input
In the interests of continual product improvement all specifications are subject to change without notice.
English, French, German, Portuguese, Italian and
Spanish
220V-240V
user selectable
6000VA: 26A @230V
35A
Up to four per 9135, rail kits included for rack
mounting
(0.7 PF)
For additional details, see battery runtime chart
Six (6) hours to recover 90 percent of nominal backup
time after 100 percent RCD load discharge
Communications
Serial portRS-232 standard, RS-232 cable provided
USB portHID standard, for communicating with Windows XP/
Vista
Relay outputDB-9 Dry Contact-common alarm standard
SoftwareIntelligent Power Manager (IPM) and IPP
Optional
communication
cards
ConnectUPS-MS Network Management Card for direct
control and monitoring in SNMP-based ne works
ConnectUPS-MS Card with ModBus RTU interface
Serial Management Card-MS for integration to indus-
trial environment and building management systems,
remote shutdown for IBM AS/400 systems
Environmental
Safety markingsCE, GS
EMCIEC/EN 62 040-2 class A
Audible noiseMax 46 dB
Ambient operating0˚C to +40˚C
Storage temperature -20˚C to +40˚C with batteries and
-25˚C to +55˚C without batteries
Relative humidity5–90% non-condensing
Heat Dissipation (BTUs/hr)
Operating modeEfficiency5 kVA6 kVA
Normal91%11501350
Battery86%16501960
High efficiency97%370450