Eaton 9135 User Manual

Page 1
Powerware series
Eaton 9135 UPS
Features
• Provides clean, continuous power to protect critical equip­ment and applications from power-related downtime, data loss and corruption, and process interruption
• Saves valuable rack space by delivering 6000 VA/4200W in only 3U
• Offers deployment versatility through rack and tower installation options with rail kits and pedestals provided
• Increases availability with hot-swappable batteries and power module
• Offers extended battery runtime options to power essential systems for more than an hour during an outage
Product snapshot
Power rating: 6 kVA/4.2 kW
Voltage: 230V nominal,
200–250 Vac range
Frequency: 50/60 Hz (auto-sensing)
Configuration: Rackmount (3U) or tower
Advanced power protection for:
• Medium-density data centers
• Banking and security systems
• Manufacturing process control
• Retail point-of-sale systems
• Telecommunications/VoIP equipment
The Eaton® 9135 UPS, Power-
®
series, resolves utility
ware power problems and sup­plies continuous, conditioned power. You get clean power for valuable IT and network­ing equipment, battery back­up to gracefully handle utility outages, and on-demand visi­bility into UPS status from anywhere.
Get more usable power for less cost
The 9135 provides exactly the level of power protection needed under the conditions of the moment—optimizing for both efficiency and perfor­mance. The more efficient the UPS, the lower your utility and cooling bills.
Under normal power condi­tions, the UPS can operate in high-efficiency mode at up to 97 percent efficiency. In double conversion mode, the UPS operates at up to 91 percent efficiency.
Double-conversion design for superior reliability and protection
In double conversion mode, the 9135 is constantly moni­toring power conditions— regulating both voltage and frequency. Even when pre­sented with the most severe power problems, this UPS’s output remains within two percent of nominal voltage.
Page 2
With a wide range of acceptable input voltages, this UPS does not depend on batteries to smooth out power fluctuations. Batteries are conserved for those times when utility power is highly unstable or completely out. If an outage occurs, the 9135 transfers to battery with no break in power, making this an ideal UPS for equipment sensitive to voltage fluctuations.
More power in less space
High power density. The 9135 increases power density, deliv­ering 6000 VA/4200W in only 3U of rack space, freeing more rack space for IT and telecom equipments. Rail kits and tower pedestals are included with every 9135 for flexible installation.
Rack model and EBM installation
Hot swappable batteries
This UPS is even more user-friendly than its predecessors offering greater distribution capabilities, with eight IEC 10A & two IEC 16A outlets to power multiple pieces of equipment without a PDU.
You can combine the 9135 with an Eaton enclosure PDU (ePDU™) to power an entire rack of equipment from a single power cord input. ePDU outlets can be monitored, switched, sequenced and managed individually, providing maximum flexibility in distributing power from the 9135.
Maximum availability for critical systems
Battery runtime for minutes or hours. During a power outage, internal batteries in the 9135 keep loads running long enough to gracefully shut down systems. Add up to four external bat­tery modules (EBMs) to deliver more than an hour of extended runtime at full load—or hours under lighter loads. Each EBM occupies only 3U of rack space. These battery modules are hot-swappable and can be replaced at any time without inter­rupting UPS operation and load protection.
Maximum battery runtime for critical equipments. LanSafe power management software enables independent control of load segments. With this feature, you can manage scheduled shutdowns and sequential startups of protected loads. During a power outage, you could shut down power to less essential loads to extend battery backup time for more critical devices.
Load segments
ConnectUPS-MS Network Management Card web interface
When the load segments feature is used with optional Connect UPS-MS connectivity cards, users can remotely re-boot lock­ed-up network equipment. Simply access the ConnectUPS-MS card over the network, and toggle the password-protected load segment controller to get your network back online.
Service without downtime.
The 9135 features hot-swappable
components and an automatic internal bypass. The UPS auto­matically switches to an alternate power path within the unit if it senses a trouble condition with an internal component. Users can even remove and replace the battery and power modules without powering down the UPS or interrupting po­wer to loads.
2 EATON CORPORATION Eaton 9135 UPS
Page 3
Visibility, control and management from anywhere
Local UPS status at a glance. An intuitive LCD interface pro­vides detailed information and menu-driven functions for UPS management. The entire display rotates for the best orienta­tion, whether the UPS is used vertically as a tower unit or horizontally in a rack. The blue, backlit LCD screen displays four lines of alphanumeric information. LEDs clearly display UPS status:
Load Protected
Downgraded Operation Load Not Protected UPS ON/OFF button
Choice of connectivity options. Connectivity options are avail­able for almost any networking environment. The standard unit comes with USB and RS-232 serial communication ports and a DB-9 dry contact port. You can customize your UPS by adding MS-slot interface options for other types of communi­cations.
1.
5
1
4
3
2
Optional communication card slot for Web/SNMP interface
USB port
2.
DB 9 serial port3.
DB 9 with five dry output 4. contacts
5.
Remote power off
LCD rotatable display
Web/SNMP card
Unified management for power protection. The 9135 comes complete with the Eaton Software Suite CD, including SNMP­compatible power management software providing control and visibility over all your UPS systems. From a central van­tage point anywhere within the reach of a network connection, you can:
Establish prioritized shutdown of network devices and cli­ent/ server applications
Test all network-connected UPSs from one node
Intelligent Power Manager (IPM)
Stay informed of power problems via email broadcasts
MODELS
Description Style number
Rating (VA/ Watts)
Input plug
Output receptacles
Dimensions H x W x D, mm
Weight, kg
Rack Tower Models
9135G-6000 R/T 3U 103006722-6591 6000/4200 Hardwired Hardwired + (2) C19, (8) C13 130 x 444 x 741 57
Extended Battery Modules
9135G-6000 EBM R/T 3U 103006723-6591 NA NA NA 130 x 444 x 650 77.5
BATTERY BACKUP TIMES (IN MINUTES)*
Loads (VA/Watts) Standards Internal Batteries +1 EBM 2 EBMs +3 EBMs +4 EBMs
1000/700 36 132 232 332 433
2000/1400 13 52 95 140 184
3000/2100 10 40 74 110 146
4000/2800 7 29 53 80 107
5000/3500 5 22 41 62 83
6000/4200* 4 18 33 50 68
* Runtimes available for the 6 kVA model only. Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
www.eaton.com/9135 3
Page 4
Eaton 9135 UPS Product Focus
TECHNICAL SPECIFICATIONS
General
User interface Graphical LCD with blue backlight and text in
LEDs Four status-indicating LEDs Topology Double-conversion Diagnostics Full system self-test UPS bypass Automatic bypass Dimensions See models selection guide Rail kit Included with all units
Electrical Input
Nominal voltage 230V
Voltage range 156–280 Vac (output PF 0.7) Power draw of UPS
(full load) Recommended input-
breaker rating Frequency 50/60 Hz autoselect Frequency range 40–70 Hz
Electrical Output
Power factor 0.7 On utility voltage ±2% of nominal regulation On battery voltage ±2% of nominal regulation Efficiency >97% in high-efficiency mode; 91% in normal mode Frequency regulation ±3% Hz online Load crest factor 3 to 1
Battery
Internal battery type 5.5Ah, sealed, lead-acid; maintenance free Externa battery
modules EBM battery type 5.5 Ah, sealed, lead-acid; maintenance free Battery runtime Four (4) minutes with internal batteries @100% load
Battery recharge time
Battery replacement Hot-swappable internal and external batteries Start-on-battery Allows start of UPS without utility input
In the interests of continual product improvement all specifications are subject to change without notice.
English, French, German, Portuguese, Italian and Spanish
220V-240V user selectable
6000VA: 26A @230V
35A
Up to four per 9135, rail kits included for rack mounting
(0.7 PF) For additional details, see battery runtime chart
Six (6) hours to recover 90 percent of nominal backup time after 100 percent RCD load discharge
Communications
Serial port RS-232 standard, RS-232 cable provided USB port HID standard, for communicating with Windows XP/
Vista Relay output DB-9 Dry Contact-common alarm standard Software Intelligent Power Manager (IPM) and IPP Optional
communication cards
ConnectUPS-MS Network Management Card for direct
control and monitoring in SNMP-based ne works
ConnectUPS-MS Card with ModBus RTU interface
Serial Management Card-MS for integration to indus-
trial environment and building management systems,
remote shutdown for IBM AS/400 systems
Environmental
Safety markings CE, GS EMC IEC/EN 62 040-2 class A Audible noise Max 46 dB Ambient operating 0˚C to +40˚C Storage temperature -20˚C to +40˚C with batteries and
-25˚C to +55˚C without batteries
Relative humidity 5–90% non-condensing
Heat Dissipation (BTUs/hr)
Operating mode Efficiency 5 kVA 6 kVA Normal 91% 1150 1350 Battery 86% 1650 1960 High efficiency 97% 370 450
SINGAPORE Tel : +65 6825 1684 Fax : +65 6825 1689 EatonSEA@eaton.com
INDONESIA Tel : +62 21 522 6181 Fax : +62 21 522 6182
MALAYSIA Tel : +603 7804 3618 Fax : +603 7803 6193
THAILAND Tel : +662 946 6843 Fax : +662 519 0574
VIETNAM Tel : +84 4 3936 5303 Fax : +84 4 3936 5307
Eaton is the trade name, trademark, and/ or service mark of Eaton Corporation or its
subsidiaries and affi liates.
® 2008 Eaton Corporation All Rights Reserved Printed in Singapore July 2010
Loading...