Eaton 150 VCP-WL, 50 VCP-WL, 75 VCP-WL Instructions For Installation, Operation And Maintenance

Instructions for Installation, Operation and Maintenance
IB131021EN
of Type VCP-WL Vacuum Circuit Breakers
Effective Mar 2018
THIS PAGE INTENTIONALLY LEFT BLANK
Effective Mar 2018
IB131021EN
IB13 1020EN Pag e ii
WARNING
IMPROPERLY INSTALLING OR MAINTAINING THESE PRODUCTS CAN RESULT IN DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING ANY UNPACKING, ASSEMBLY, OPERATION OR MAINTENANCE OF THE CIRCUIT BREAKERS.
INSTALLATION OR MAINTENANCE SHOULD BE ATTEMPTED ONLY BY QUALIFIED PERSONNEL. THIS INSTRUCTION BOOK SHOULD NOT BE CONSIDERED ALL INCLUSIVE REGARDING INSTALLATION OR MAINTENANCE PROCEDURES. IF FURTHER INFORMATION IS REQUIRED, YOU SHOULD CONTACT EATON.
WARNING
THE CIRCUIT BREAKER ELEMENTS DESCRIBED IN THIS BOOK ARE DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL, RESULTING IN DEATH, BODILY INJURY AND PROPERTY DAMAGE.
ALL SAFETY CODES, SAFETY STANDARDS AND/OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO.
THESE CIRCUIT BREAKER ELEMENTS ARE DESIGNED TO BE INSTALLED PURSUANT TO THE AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). SERIOUS INJURY, INCLUDING DEATH, CAN RESULT FROM FAILURE TO FOLLOW THE PROCEDURES OUTLINED IN THIS MANUAL. THESE CIRCUIT BREAKER ELEMENTS ARE SOLD PURSUANT TO A NON­STANDARD PURCHASING AGREEMENT WHICH LIMITS THE LIABILITY OF THE MANUFACTURER.
All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of particular equipment, contact an Eaton representative.
TABLE OF CONTENTS
SECTION 1: INTRODUCTION....................................................................................................................................................................................1
1-1 PRELIMINARY COMMENTS AND SAFETY PRE- CAUTIONS..................................................................................................................................1
1-2 GENERAL INFORMATION...................................................................................................................................................................................1
1-3 TYPE VCP-WL VACUUM CIRCUIT BREAKER ELEMENT RATINGS.........................................................................................................................2
1-4 OUTLINES AND DIMENSIONS.............................................................................................................................................................................3
SECTION 2: SAFE PRACTICES...................................................................................................................................................................................5
2-1 RECOMMENDATIONS.........................................................................................................................................................................................5
SECTION 3: RECEIVING, HANDLING AND STORAGE..................................................................................................................................................6
3-1 GENERAL............................................................................................................................................................................................................6
3-2 RECEIVING..........................................................................................................................................................................................................6
3-3 HANDLING..........................................................................................................................................................................................................6
3-4 STORAGE............................................................................................................................................................................................................6
3-5 TOOLS AND ACCESSORIES..................................................................................................................................................................................7
3-6 TYPE VCP-WL VACUUM CIRCUIT BREAKER ELEMENT WEIGHTS........................................................................................................................7
SECTION 4: INITIAL INSPECTION AND INSTALLATION............................................................................................................................................ 14
4-1 INTRODUCTION................................................................................................................................................................................................14
4-2 VACUUM INTERRUPTER INTEGRITY.................................................................................................................................................................14
4-3 INSULATION.....................................................................................................................................................................................................14
4-4 PRIMARY CIRCUIT RESISTANCE........................................................................................................................................................................14
4-5 NAMEPLATE.....................................................................................................................................................................................................14
4-6 ELECTRICAL OPERATION AND MECHANICAL OPEN CHECK..............................................................................................................................14
4-7 CIRCUIT BREAKER/STRUCTURE INTERFACING.................................................................................................................................................21
SECTION 5: DESCRIPTION AND OP E R ATIO N ........................................................................................................................................................23
5-1 INTRODUCTION................................................................................................................................................................................................23
5-2 INTERRUPTER ASSEMBLY.................................................................................................................................................................................23
5-3 ELECTROMAGNETIC MECHANISM...................................................................................................................................................................26
5-4 CONTROL SCHEMES.........................................................................................................................................................................................29
5-5 INTERLOCKS AND INTERFACING......................................................................................................................................................................29
5-6 LEVERING MECHANISM...................................................................................................................................................................................29
5-7 OPERATIONS COUNTER....................................................................................................................................................................................30
5-8 GROUND CONTACT..........................................................................................................................................................................................30
5-9 MOC AND TOC SWITCH OPERATIONS..............................................................................................................................................................30
SECTION 6: INSPECTION, MAINTENANCE A N D TR O U BLES H O OTI N G .................................................................................................................31
6-1 INTRODUCTION................................................................................................................................................................................................31
6-2 FREQUENCY OF INSPECTION AND MAINTENANCE..........................................................................................................................................31
6-3 INSPECTION AND MAINTENANCE PROCEDURES.............................................................................................................................................33
6-4 VACUUM INTERRUPTER INTEGRITY TEST.........................................................................................................................................................34
6-5 CONTACT EROSION AND WIPE.........................................................................................................................................................................35
6-6 INSULATION....................................................................................................................................................................................................35
6-7 INSULATION INTEGRITY CHECK........................................................................................................................................................................35
6-8 PRIMARY CIRCUIT RESISTANCE CHECK.............................................................................................................................................................36
6-9 MECHANISM CHECK.........................................................................................................................................................................................36
6-10 LUBRICATION...................................................................................................................................................................................................36
6-11 TROUBLESHOOTING CHART (CONTINUED NEXT PAGE).........................................................................................................................................37
6-11 TROUBLESHOOTING CHART (CONTINUED)..........................................................................................................................................................38
6-12 END OF LIFE PROCEDURES...............................................................................................................................................................................39
6-13 FAILURE REPORTING........................................................................................................................................................................................39
6-14 REPLACEMENT PARTS......................................................................................................................................................................................39
Pag e iv IB13 1021EN
FIGURES
FIGURE 1-1 TYPE VCP-WL CIRCUIT BREAKER OUTLINES AND DIMENSIONS..........................................................................................3
FIGURE 3-1 TYPICAL VCP-WL TOOLS AND ACCESSORIES......................................................................................................................8
FIGURE 3-2 TYPICAL FRONT VIEW VCP-WL VACUUM CIRCUIT BREAKER .....................9
FIGURE 3-3 TYPICAL VCP-WL VACUUM CIRCUIT BREAKER ELEMENT WITH FRONT COVER REMOVED.................................................10
FIGURE 3-4 VCP-WL MECHANISM DETAILS.......................................................................................................................................11
FIGURE 3-5 TYPICAL REAR VIEW VCP-WL VACUUM CIRCUIT BREAKER ELEMENT................................................................................12
FIGURE 3-6 TYPICAL VCP-WL VACUUM CIRCUIT BREAKER FRONT COVER ARRANGEMENT................................................................. 13
FIGURE 4-1A INSERTION OF THE DRAWOUT EXTENSION RAILS.........................................................................................................15
FIGURE 4-1B LIFTING AND SETTING THE BREAKER IN THE HOUSING..................................................................................................15
FIGURE 4-1C BPI PAN ASSEMBLY......................................................................................................................................................17
FIGURE 4-2 ENGAGING EXTENSION RAILS IN A LOWER CIRCUIT BREAKER COMPARTMENT................................................................19
FIGURE 4-3 TYPICAL VCP-WL CIRCUIT BREAKER BOTTOM VIEW........................................................................................................20
FIGURE 4-4 ENGAGING LEVERING-IN CRANK....................................................................................................................................21
FIGURE 5-1 VCP-WL POLE UNIT AND VACUUM INTERRUPTER...........................................................................................................23
FIGURE 5-2 GRAPHIC REPRESENTATION OF ARC INTERRUPTION.......................................................................................................24
FIGURE 5-3 MEASUREMENT OF CONTACT STROKE...........................................................................................................................25
FIGURE 5-4 LOOSENING THE DRIVE ROD HOUSING JAM NUT............................................................................................................25
FIGURE 5-5 MEASUREMENT OF CONTACT OPEN GAP.......................................................................................................................25
FIGURE 5-5 TYPICAL VCP-WL CONTROL SCHEME..............................................................................................................................29
IB13 1021EN P ag e v
TABLES
TABLE 1-1 (ANSI STANDARDS) TYPE VCP-WL VACUUM CIRCUIT BREAKER...........................................................................................2
TABLE 3-1 VCP-WL ANSI RATED BREAKER WEIGHTS............................................................................................................................7
TABLE 6.1 TORQUE GUIDELINES.......................................................................................................................................................32
TABLE 6.2 (INSULATION & VACUUM INTEGRITY) TEST VOLTAGE.......................................................................................................34
TABLE 6.3 TYPICAL RESISTANCE MEASUREMENTS.............................................................................................................................36
INTRODUCTIONSECTION 1:
PRELIMINARY COMMENTS AND SAFETY PRE- 1-1
CAUTIONS
This technical document is intended to cover most aspects associated with the installation, operation and maintenance of Type VCP-WL Vacuum Circuit Breakers. It is provided as a guide for authorized and qualified personnel only. Please refer to the specific WARNING and CAUTION in Paragraph 1-1.2 before proceeding past Section 1. If further information is required by the purchaser regarding a particular installation, application or maintenance activity, an Eaton representative should be contacted.
WARRANTY AND LIABILITY FORMATION1-1.1
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information and descriptions contained herein.
WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PROCEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE IN REVERSE TYPE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW.
CAUTION
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED PERSONS SHOULD BE PERMIT-TED TO PERFORM ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUIPMENT DAMAGE.
1-2 GENERAL INFORMATION
1-1.2 SAFETY PRECAUTIONS
All safety codes, safety standards and/or regulations must be strictly observed in the installation, operation and maintenance of this device.
Effective Mar 2018
The purpose of this book is to provide instructions for unpacking, storage, use, operation and maintenance of Type VCP-WL Vacuum Circuit Breakers. These circuit breakers are horizontal drawout type removable interrupting elements designed for use in VacClad-W Metal­Clad Switchgear and appropriate VCP-WL modules. The Type VCP-WL Vacuum Circuit Breakers are designed to operate as a roll-in replacement for Type VCP-W Vacuum Circuit Breakers. They provide reliable control and protection for medium voltage electrical equipment and
Pag e ii IB13 1021EN
circuits. All VCP-WL circuit breaker elements are designed to ANSI Standards for reliable performance, ease of handling and simplified maintenance.
WARNING
SATISFACTORY PERFORMANCE OF THESE BREAKERS AND OR MINIMOD IS CONTINGENT UPON PROPER APPLICATION, CORRECT INSTALLATION AND ADEQUATE MAINTENANCE. THIS INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL LIFE OF THE MINIMOD. EQUIPMENT TO FAIL, RESULTING IN DEATH, BODILY INJURY AND PROPERTY DAMAGE.
ALL SAFETY CODES, SAFETY STANDARDS AND/OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO.
TYPE VCP-WL VACUUM CIRCUIT BREAKER ELEMENT RATINGS1-3
Rated Values
Circuit Breaker Type
Nominal Voltage Class
Insulation Level Current
Interrupting Time
Permissible Tripping Delay
Y
Current Values
Withstand Test Voltage
Continuous Current at 60 Hz
Short Circuit Current (at Rated Max. kV)
I
Closing and Latching Capability
2.7 K Times Rated Short Circuit Current
Closing and Latching Capability Momentary
1.6 K Times Rated Short Circuit Current
Power Frequency (1 Min.)
Impulse
kV kV rms Amperes kA rms Cycles Seconds kA Peak kA rms
150 VCP-WL 15 36 95 1200 25 3 or 5 2 65 39 75 VCP-WL 8.25 36 95 1200 25 3 or 5 2 65 39
50 VCP-WL 4.76 36 95 1200 25 3 or 5 2 65 39
Table 1-1 (ANSI Standards) Type VCP-WL Vacuum Circuit Breaker Through 15 kV Rated Symmetrical Current Basis
Identification
Pag e iv IB13 1021EN
OUTLINES AND DIMENSIONS1-4
Figure 1-1 Type VCP-WL Circuit Breaker Outlines and Dimensions
Front View
IB13 1021EN P ag e v
SECTION 2: SAFE PRACTICES
Effective Mar 2018
Side View
2-1 RECOMMENDATIONS
Type VCP-WL Vacuum Circuit Breaker Elements are equipped with high speed, high energy operating mechanisms, and are designed with several built-in inter-
Pag e vi IB13 1021EN
locks and safety features to provide safe and proper operating sequences.
WARNING
TO PROTECT THE PERSONNEL ASSOCIATED WITH INSTALLATION, OPERATION, AND MAINTENANCE OF THESE CIRCUIT BREAKER ELEMENTS, THE FOLLOWING PRACTICES MUST BE FOLLOWED:
Only qualified personnel, as defined in the local electrical code, who are familiar with the installation and maintenance of medium voltage circuits and equipment, should be permitted to work on these circuit breaker elements.
Read these instructions carefully before attempting any installation, operation or maintenance of these breakers.
Always remove the breakers from the enclosure before performing any maintenance. Failure to do so could result in electrical shock leading to death, severe personal injury or property damage.
tripping. Carelessness could cause the circuit breaker to fall from the rails resulting in personal injury to those in the area.
Do not work on a closed breaker or a breaker with capacitor bank charged. The capacitor bank should be discharged and the main contacts open before working on the breaker. The capacitor bank will discharge after control power is removed. Failure to do so could result in severe injury or death.
Do not use a circuit breaker by itself as the sole means of isolating a high voltage circuit. Remove the breaker to the DISCONNECT position and follow good lockout and tagging rules, as well as all applicable codes, regulations and work rules.
Do not leave the breaker in an intermediate position in the cell. Always have the breaker either in the TEST or CONNECTED position. Failure to do so could result in a flash over and possible death, personal injury or property damage.
Breakers are equipped with safety interlocks. Do not defeat them. This may result in death, bodily injury or equipment damage.
BE EXTREMELY CAREFUL while the circuit breaker is on the extension rails. Use provided rail clamps to firmly hold the circuit breaker on the extension rails while performing such activities as charging, closing and
SECTION 3: RECEIVING, HANDLING AND STORAGE
IB13 1021EN P ag e vii
3-1 GENERAL
Type VCP-WL Vacuum Circuit Breaker Elements are subjected to complete factory production tests and inspection before being packed. They are shipped in packages designed to provide maximum protection to the equipment during shipment and storage and at the same time to provide convenient handling.
3-2 RECEIVING
If the circuit breaker element is not to be used immediately but is to be placed in storage; maximum protection can be obtained by keeping it packed as shipped.
Upon receipt of the equipment, inspect the containers for any signs of damage or rough handling. Open the containers carefully to avoid any damage to the con-tents. Use a nail puller rather than a crow bar when required. When opening the containers, be careful to save any loose items or hardware that may be otherwise discarded with the packing material. Check the contents of each package against the packing list.
Examine the circuit breaker element for any signs of shipping damage such as broken, missing or loose hardware, damaged or deformed insulation and other components. File claims immediately with the carrier if damage or loss is detected and notify the nearest Eaton Office.
breaker element side openings with the lifting hole toward the interrupters. Once the lifting yoke is securely seated in the holes, the breaker element can be carefully lifted and moved.
3-4 STORAGE
If the circuit breaker element is to be placed in storage, maximum protection can be obtained by keeping it packed as shipped. Before placing it in storage, checks should be made to make sure that the breaker element is free from shipping damage and is in satisfactory operating condition.
The circuit breaker element is shipped with its contacts open and capacitor bank discharged. The indicators on the front panel should confirm this.
Outdoor storage of the breaker element is NOT recommended. If unavoidable, the outdoor location must be well drained and a temporary shelter from sun, rain, snow, corrosive fumes, dirt, falling objects and excessive moisture must be provided. Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation. Moisture can cause rusting of metal parts and deterioration of high voltage insulation. A heat level of approximately 400 watts for each 100 cubic feet of volume is recommended with the heaters distributed uniformly throughout the structure near the floor.
Indoor storage should be in a building with sufficient heat and air circulation to prevent condensation. If the building is not heated, the same general rule for heat as for outdoor storage should be applied.
3-3 HANDLING
CAUTION
DO NOT USE ANY LIFTING DEVICE AS A PLATFORM FOR PERFORMING MAINTENANCE, REPAIR OR ADJUSTMENT OF THE BREAKER OR FOR OPENING, CLOSING THE CONTACTS OR CHARGING THE SPRINGS. THE CIRCUIT BREAKER ELEMENT MAY SLIP OR FALL CAUSING SEVERE PERSONAL INJURY. ALWAYS PERFORM MAINTENANCE, REPAIR AND ADJUSTMENTS ON A SOLID WORK SURFACE CAPABLE OF SUPPORTING THE BREAKER ELEMENT.
When a breaker element is ready for installation, a lifting yoke in conjunction with an overhead lifter or portable floor lifter can be used to move a breaker element. When a breaker element is to be lifted, position the lifting yoke over the breaker element and insert the lifter tabs into the
Effective Mar 2018
3-5 TOOLS AND ACCESSORIES
Tools and accessories, both standard and optional are available for use with the circuit breaker element (Figure 3-1).
Pag e viii IB13 1021EN
Amperes Lbs. (kg)
50VCP-WL25 1200 350
75VCP-WL25 1200 350
150VCP-WL25 1200 350
Spin-Free Levering-In Crank: Used to crank breaker between TEST and CONNECTED positions (Style 701B601G11).
Extension Rails: Permits breaker to be withdrawn from its compartment (Style 7813C41G03 for VCP-WL).
Rail Clamps: Used to secure breaker to extension rails (Style 6511C83G11 for VCP-WL).
Lifting Yoke: Used to lift breaker (Style 691C607G11 for VCP-WL).
Drawout Ramp: Used to insert or withdraw breaker from lower compartment without portable lifter (Style 1C14163G02 for VCP-WL).
Table 3-1 VCP-WL ANSI Rated Breaker Weights
Rating
Does not include shipping carton
Portable Lifter: Used to lift breaker to or from extended rails (Style 1C14504H01).
Docking Transport Dolly: Used to insert or withdraw breaker from lower compartment without portable lifter or move breaker from one location to another (Style 6510C71G11 for VCP-WL).
Electrical Levering-In Device: Used to electrically move breaker between TEST and CONNECTED positions (Style 1A30257G01).
Test Jumper: Used to operate breaker electrically while breaker is on extension rails or transport dolly (Style 6526C23G11 for VCP-WL).
Test Cabinet: Used to provide power to operate breaker outside its compartment (Styles 8346A28G21 – G23 for VCP-WL depending on voltage requirements).
3-6 TYPE VCP-WL VACUUM CIRCUIT BREAKER ELEMENT WEIGHTS (TABLE 3.1)
Loading...
+ 32 hidden pages