IMPROPERLY INSTALLING OR MAINTAINING
THESE PRODUCTS CAN RESULT IN DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE.
READ AND UNDERSTAND THESE INSTRUCTIONS
BEFORE ATTEMPTING ANY UNPACKING, ASSEMBLY, OPERATION OR MAINTENANCE OF THE CIRCUIT BREAKERS.
INSTALLATION OR MAINTENANCE SHOULD BE
ATTEMPTED ONLY BY QUALIFIED PERSONNEL.
THIS INSTRUCTION BOOK SHOULD NOT BE CONSIDERED ALL INCLUSIVE REGARDING INSTALLATION OR MAINTENANCE PROCEDURES. IF FURTHER INFORMATION IS REQUIRED, YOU SHOULD
CONTACT EATON.
Eaton Corporation
Power Components Division
Instruction Book
Page3
THE CIRCUIT BREAKER ELEMENTS DESCRIBED IN
THIS BOOK ARE DESIGNED AND TESTED TO
OPERATE WITHIN THEIR NAMEPLATE RATINGS.
OPERATION OUTSIDE OF THESE RATINGS MAY
CAUSE THE EQUIPMENT TO FAIL, RESULTING IN
DEATH, BODILY INJURY AND PROPERTY DAMAGE.
ALL SAFETY CODES, SAFETY STANDARDS
AND/OR REGULATIONS AS THEY MAY BE
APPLIED TO THIS TYPE OF EQUIPMENT MUST BE
STRICTLY ADHERED TO.
THESE CIRCUIT BREAKER ELEMENTS ARE
DESIGNED TO BE INSTALLED PURSUANT TO THE
AMERICAN NATIONAL STANDARDS INSTITUTE
(ANSI). SERIOUS INJURY, INCLUDING DEATH, CAN
RESULT FROM FAILURE TO FOLLOW THE PROCEDURES OUTLINED IN THIS MANUAL. THESE CIRCUIT BREAKER ELEMENTS ARE SOLD PURSUANT
TO A NON-STANDARD PURCHASING AGREEMENT
WHICH LIMITS THE LIABILITY OF THE MANUFACTURER.
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding his particular installation, operation or maintenance of particular equipment,
contact an Eaton representative.
IB131009EN
InstructionBook
Page 4
TABLE OF CONTENTS
SECTION 1 INTRODUCTION
1-1
Type W-VAC, W-VACR and W-VACW Breaker Ratings ....................................................................................... 1
SECTION 2 SAFE PRACTICES
SECTION 3 RECEIVING, HANDLING AND STORAGE
5-1.4 “T” Cutout Loading Spring Indicator ...................................................................................................................... 28
5-1.5 Contact Wipe and Stroke ...................................................................................................................................... 28
5-1.6 Pole Unit Support Molding .................................................................................................................................... 28
5-2 Stored Energy Mechanism .................................................................................................................................... 29
5-2.1 Operation of Stored Energy Mechanism .................................................................................... .......................... 29
6-2 Frequency of Inspection ........................................................................................................................................ 37
6-3 Inspection and Maintenance Procedures .............................................................................................................. 38
6-4 Vacuum Interrupter Integrity Test .......................................................................................................................... 37
6-5 Contact Erosi on (Except 3150A) ........................................................................................................................... 40
6-9.1 CloSure Test .......................................................................................................................................................... 42
7-1 General .................................................................................................................................................................. 50
7-2 Ordering In structions ............................................................................................................................................. 50
FIGURES
Figure Title Page
1-1 Type W-VACR 630A Breaker Element Only Outline Dimensions (millimeters) & Weights (Kilograms) .... 3
1-2 Type W-VACR 630A Breaker Element Only Outline Dimensions (millimeters) & Weights (Kilograms) .... 4
1-3 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 5
1-4 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 6
1-5 Type W-VACR 800/1250A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) ....... 7
1-6 Type W-VACR 2000A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) .............. 8
1-7 Type W-VACR 2500A Breaker Element Only Outline Dimensions (millimeters) & Weights (kg) .............. 9
1-8 Type W-VAC Breaker Element Only Outline Dimensions (millimeters) and Weights (Kilograms) .......... 10
1-9 Outline and Dimensions (mm) Type W-VAC B reaker Element with Carri age
Assembly and Cradle Assembly ........................................................................................................................ 11
1-10 Outline and Dimensions (mm) Type W-VAC 3150 Breaker with Carriage Assembly .............................. 12
3-1 Typical VCP-W Tools and Accessories .......................................................................................................14
3-2 Typical Front View VCP-W Vacuum Circuit Breaker Element ................................................................... 16
3-3 Typical VCP-W Vacuum Circuit Breaker Element with Front Cover Removed ....................................... 17
3-7 Front and Rear External View W-VAC 3150A Breaker with Carriage Assembly for
Single Tier Switchgear .................................................................................................................................21
5-2 Behind the Door Configuration ................................................................................................................... 27
5-3 Closeup of Type W-VAC Breaker Vacuum Interrupters and Current Carrying System ........................... 27
5-4 a Type W-VAC 95 kV BIL Breaker Shown With Left Hand Cover Removed for Clarity Purposes ............. 28
5-4 b Type W-VAC 3150 Ampere Breaker Closeup of Completely Enclosed Pole Units ................................. 28
5-5 Closing Cam and Trip Linkage ................................................................................................................... 30
1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings .................................................................... 1
1.2 Type W-VACR Vacuum Circuit Breaker Ratings ......................................................................................... 2
5.1 Typical Opening and Closing Times Value ................................................................................................ 32
6.1 Test Voltage. ............................................................................................................................................... 39
7.1 Recommended W-VAC and W-VACW Spare Parts .................................................................................. 50
Page
IB131009EN
r
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for
unpacking, storage, installation, operation and maintenance of Types W-VAC, W-VACR, and W-VACW
Vacuum Circuit Breakers. They are a horizontal drawout
type removable interrupting element design, unless
there is an “R” in the designation.The “R” as in W-VACR
indicates a fixed breaker configuration. They were
designed specifically to IEC 56 Standards for reliable
performance. All types can be applied in single tier or
double tier switchgear applications, with the basic
breaker element applicable to retrofitting. Reliable control and protection are achieved though the use of the
W-VAC family of breakers.
1-1 W-VAC, W-VACR AND W-VACW RATINGSTable 1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings
Rated Short Circuit
Breaking Current
& Short Circuit
Duration
kA
Sec
SATISFACTORY PERFORMANCE OF THESE
BREAKERS IS CONTINGENT UP-ON PROPER
APPLICATION, CORRECT INSTALLATION AND
ADEQUATE MAINTENANCE. THIS INSTRUCTION
BOOK MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKERS.
TYPES W-VAC, W-VACR AND W-VACW BREAKERS
ARE PROTECTIVE DEVICES, AS SUCH, THEY ARE
MAXIMUM RATED DEVICES. THEREFORE, THEY
SHOULD NOT UNDER ANY CIRCUMSTANCES BE
APPLIED OUTSIDE THEIR NAMEPLATE RATINGS.
Rated Insulation Level
Lighting
Pulse
Withstand
Voltage
Figure 1-1 Type W-VACR 630A. breaker element only outline dimensions (millimeters) and weights (kilograms).
630A = 105kg
IB131009EN
InstructionBook
Page 4
630A Element
Figure 1-2 Type W-VACR 630A. breaker element only outline dimensions (millimeters) and weights (kilograms).
630A = 105kg
IB131009EN
Instruction Book
Page5
800/1250A Element
800A/1250A = 110kg
Figure 1-3 Type W-VACR 800/1250A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
InstructionBook
Page 6
800/1250A Element
800A/1250A = 110kg
Figure 1-4 Type W-VACR 800/1250A. breaker element only outline dimensions (millimeters) and weights (kilograms).
IB131009EN
Instruction Book
2000A Element
Figure 1-5 Type W-VACR 2000A. breaker element only outline dimensions (millimeters) and weights (kilograms).
2000A = 149kg
Page7
IB131009EN
InstructionBook
Page 8
2000A Element
Figure 1-6 Type W-VACR 2000A. breaker element only outline dimensions (millimeters) and weights (kilograms).
2000A = 149kg
IB131009EN
Instruction Book
Page9
2500A Element
2500A = 154kg
Figure 1-7 Type W-VACR up to 2500A, 50kA. breaker element only outline dimensions (millimeters) and weights (kg.).
IB131009EN
InstructionBook
Page 10
Up to 1250A Element
(Front View) (Side View)
800A/1250A = 121kg
(Front View)
1600A & 2000A Elements
1600A/2000A = 160kg
Figure 1-8 Type W-VAC breaker element only outline dimensions (millim eters) and wei ghts (kilog ram s).
(Side View)
630A = 115kg
IB131009EN
Instruction Book
197
325
570
350
373
202
33.3
A
G
F
F
B
“A” POLE
“B” POLE
“C” POLE
C
1160
795.7
520
480
Rating
Up to 15 kV/Up to 1250A to 40kA
Up to 15 kV/1600A and2000A/Up to 40 kA
33.3
197
Earthing Contacts
A
B
C
D
E
F
570 300 1226 1202 1340 165470 29
719 350 1299 1275 1340 200620 33
570
373
202
C
E
720
B
80
Earthing Contacts
440
Rating
Up to 15 kV/Up to 1250A to 40kA
701
490 300 786 762 738 165470 23
Up to 15 kV/1600A and2000A/Up to 40 kA
A
640 350 856 835 736 200620 25
355.7
B
C
D E
F
19.34
269
“A” POLE
44.6
G
9.5
G
F
A
G
“C” POLE
“B” POLE
84.4
456.6
538
Weight Carriage
Weight Carriage
F
228.3
48.3
E
D
D
Figure 1-9 Outline and Dimensions (mm) Type W-VAC breaker element with carriage assembly and cradl e assem bly
Page11
IB131009EN
InstructionBook
Page 12
Figure 1-10 Outline and Dimensions (mm) Type W-VAC 3150 breaker with carriage a ssembl y
IB131009EN
Instruction Book
Page13
SECTION 2: SAFE PRACTICES
W-VAC, W-VACR, and W-VACW breakers are
equipped with high speed, high energy operating mechanisms. They are designed with several built-in interlocks and safety features to provide safe and proper
operating sequences.
closing springs charged. The closing spring should be
WARNING
TO PROTECT THE PERSONNEL ASSOCIATED WITH
INSTALLATION, OPERATION, AND MAINTENANCE
OF THESE BREAKERS, THE FOLLOWING PRACTICES MUST BE FOLLOWED:
• Only qualified persons, as defined in the local electrical code who are familiar with the installation and maintenance of medium voltage circuits and equipment,
should be permitted to work on these breakers.
• Read these instructions carefully before attempting
any installation, operation or maintenance of these
breakers.
• Always remove the removable breakers from their
enclosures or disconnect the fixed primary connections
associated with fixed breakers before performing any
maintenance. Failure to do so could result in electrical
shock leading to death, severe personal injury or property damage.
• Do not work on a breaker with the secondary test coupler engaged or fixed secondary connections made.
Failure to disconnect the test coupler could result in an
electrical shock leading to death, personal injury or
property damage.
• Do not work on a closed breaker or a breaker with
discharged and the main contacts open before working
on the breaker. Failure to do so could result in cutting or
crushing injuries.
• Do not use a drawout circuit breaker by itself as the
sole means of isolating a high voltage circuit, Remove
the breaker to the Disconnect position and follow good
lock-out and tagging rules, as well as all applicable
codes, regulations and work rules.
• Do not leave a drawout breaker in an intermediate
position in the cell. Always have the breaker either in the
Test or Connected position. Failure to do so could result
in a flash over and possible death, personal injury or
property damage.
• Always remove the maintenance tool from the breaker
after charging the closing springs.
• Circuit breaker elements are equipped with safety
interlocks. Do Not remove, interfere with or in any
manner defeat them. This may result in death, bodily
injury or equipment damage.
IB131009EN
Loading...
+ 43 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.