Eaton 600 A 35 kV class, Cooper Power Series Installation Instructions Manual

Deadbreak Connectors
COOPER POWER
SERIES
Catalog Data
CA650058EN
Effective May 2015 Supersedes 600-63 June 200 0
600 A 35 kV class insulated protective cap
Description
Eaton meets the full requirements of IEEE Std 386™-2006 standard - Separable Insulated Connector Systems, with its Cooper Power™ series 600 A, 35 kV Class insulated protective pap, providing an insulated, fully shielded submersible protection for energized 35 kV Class deadbreak interfaces. The cap is required for temporary or permanent installation on 35 kV deadbreak bushings, junctions and other accessories having interfaces that conform to IEEE Std 386™-2006 standard.
The cap design includes a semi conducting EPDM insert for stress relief and high quality peroxide cured EPDM insulation. The molded EPDM semi­conducting shield maintains ground potential on the cap’s surface when the drain wire is connected to a common ground.
(Top image on left shows standard insulated protective cap and bottom image shows U-OP™/ T-OP™ II connector insulated protective cap.)
Installation
No special tools are required. A hotstick tool is used to place the protective cap on a de-energized bushing. Refer to Service Information S600-63-1
600 A 15/25 and 35 kV Class Deadbreak Protective Cap Installation Instructions for details.
Production tests
Tests are conducted in accordance with IEEE Std 386™-2006 standard.
ac 60 Hz 1 Minute Withstand
50 kV
Minimum Corona Voltage Level
26 kV
Tests conducted in accordance with Eaton requirements:
Physical Inspection
Periodic Dissection
Periodic Fluoroscopic Analysis
Catalog Data CA650058EN
Effective May 2015
PULLING EYE Stainless Steel Reinforced Pulling Eye ensures high strength for hotstick opera­tion.
6.8"
(173 mm)
600 A 35 kV class insulated protective cap
SEMICONDUCTIVE SHIELD Molded Semiconductive EPDM Shield meets requirements of IEEE Std 592™­2007 standard.
3.5"
(88 mm)
EPDM INSULATION DRAIN WIRE AND EYE 30-inch, #14 AWG Stranded Tin Plated Copper drain wire prevents low energy discharge from the molded semi conducting shield.
5
/8" – 11 UNC 2A BRASS THREAD
High Quality Peroxide Cured EPDM Insulation is mixed and formulated in-house for complete control of raw rubber characteristics.
Figure 1. Insulated protective cap cutaway shows design characteristics and dimensions.
ote:N Dimensions given are for reference only.
Table 1. Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 35
Maximum Rating Phase-to-Ground 21.1
ac 60 Hz 1 Minute Withstand 50
dc 15 Minute Withstand 103
BIL and Full Wave Crest 150
Minimum Corona Voltage Level 26
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
2
www.eaton.com/cooperpowerseries