Eaton 600 A 15 kV class BOL-T, 600 A 25 kV class BOL-T Assembly/installation Instructions

COOPER POWER
SERIES
Deadbreak Apparatus Connectors
MN650005EN
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other­wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recom­mendations and descriptions contained herein. The information contained in this manual is subject to change without notice.
ii
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015
Contents
SAFETY INFORMATION
Safety Information .............................................................................iv
PRODUCT INFORMATION
Introduction ...................................................................................1
Acceptance and Initial Inspection...................................................................1
Handling and Storage ............................................................................1
Standards .....................................................................................1
EQUIPMENT REQUIRED
Equipment Required.............................................................................2
TOOLS REQUIRED
Tools Required .................................................................................2
INSTALLATION OF CONNECTORS
Shear Bolt Installation Procedure. ..................................................................2
Compression Connector Procedure .................................................................7
COMPLETING T-BODY TERMINATION
Installation of BOL-T Connector Onto Apparatus Bushing ...............................................11
Separable Splice Assembly Instructions.............................................................14
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015
iii
!
SAFETY
FOR LIFE
Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our “Safety For Life” mission.
Safety for life
!
SAFETY
FOR LIFE
Safety information
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings.
Hazard Statement Definitions
This manual may contain four types of hazard statements:
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Safety instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.
DANGER
Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment.
G103.3
WARNING
Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage.
G101.0
WARNING
This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage.
G102.1
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only.
iv
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015
WARNING
Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage.
G122.3
DANGER
All associated apparatus must be de-energized during any hands-on installation or maintenance.
WARNING
The 600 A BOL-T Connector System is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. The elbow connector should be installed and serviced only by personnel familiar with good safety practices and the handling of high-voltage electrical equipment.
Additional information
These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative.
Acceptance and initial inspection
Each BOL-T connector is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the BOL-T connector and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately.
WARNING
Optional Capacitive Test Point Operating Instructions: Use only voltage indicating instruments specifically designed for test points. Use of conventional voltage sensing devices may provide false “No Voltage” indications.
The test point must be dry and free of contaminant’s when checking for voltage. After indication is taken: clean, dry, and lubricate the test point cap with silicone grease and assemble to the test point.
The capacitive test point is not sufficiently accurate, nor is it intended for, actual voltage measurements or phasing operations.
A reading of no voltage from the test point should not be the only indication of a de-energized circuit obtained before touching the connector. Other procedures can include direct conductor voltage testing or grounding using a live-line tool.
Product information
Introduction
Eaton terminates high-voltage underground cable to deadfront apparatus such as transformers, switches, and switchgear with its Cooper Power™ series 600 A 15/25 kV Class BOL-T™ deadbreak connectors. They are fully shielded, submersible, and meet the requirements of IEEE Std 386™-2006 standard – “Separable Insulated Connector Systems”. 600 A deadbreak connectors from Eaton are fully interchangeable with all other manufacturers that also certify compliance with IEEE Std 386™-2006 standard. The BOL-T connector is rated for 900 A when used with all copper current carrying components.
Handling and storage
Be careful during handling and storage of the BOL-T connector to minimize the possibility of damage. If the BOL-T connector is to be stored for any length of time prior to installation, provide a clean, dry storage area.
Standards
ISO 9001 Certified Quality Management System
Insulating Plug With Cap
Test Point
Neutral Wire
T-body
Unthreaded Com pres sion
Connector
Cable Adapter
Read this manual first
Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment.
Figure 1. Line illustration of 15/25 kV 600 A BOL-T connector.
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015
1
IMPORTANT
Installation Instructions to be used for 600 A, 15/25 kV Class BOL-T connector with shear bolt connector. Please see page 7 for installation instructions using a compression connector.
ote:N If concentric neutral cable is not being used,
follow cable preparation directions in shield adapter kit.
Equipment provided
BOL-T Connector Assembly Kit includes:
T-body
Cable Adapter
Insulating Plug with Cap
Shear Bolt Connector
Silicone Lubricant
Instruction Sheet
Threaded Stud
Installation of connectors
Shear bolt installation procedures
(For compression connector procedures, see page 7)
Prepare the cable
Step 1.
Train cable
Position cable vertically so that it is centered between apparatus bushing and parking pocket, parallel to, and 6" (152 mm) from apparatus frontplate.
Provide adequate cable slack for cable movement between standoff bushing and apparatus bushing.
Support cable as needed to maintain position.
Cut cable to length "A" from centerline of bushing. (Refer to Fig ure 3 and Table 2 for "A" length.
6"
(152 mm)
Tools required
Torque Wrench
5/16" Hex Wrench for Splice Application
Cable Stripping Tools
5 mm or 8 mm Allen Wrench
"A"
(See Table 2)
Bushing
Cable
Figure 3. Line illustration for cable training.
B
C
D A
Figure 2. Strip back dimensions.
2
600 A 15/25 kV class BOL-T connector assembly installation instructions for MN650005EN February 2015
Loading...
+ 14 hidden pages