Eaton 5000, MX EXB RT, MX 5000 RT User Manual

Page 1
www.eaton.com
MX
5000 RT — UPS EXB RT — Extended Battery Transformer 5000
Installation and User Manual
Pulsar Series
Page 2
Page 3
www.eaton.com
MX Installation and User Manual, 86-87050-00
MX
5000 RT — UPS EXB RT — Extended Battery Transformer 5000
Installation and User Manual
Revision: A00 ECN#: 004747 04/2006
Revision: A01 ECN#: 004773 05/2006
Copyright © 2008 EATON All rights reserved.
For Technical Support, Customer Care Center, or Customer FAQ, please visit our website: www.eaton.com or call (800) 279-7776
Page 4
Page 5
Contents
Introduction ....................................................................................................................... 5
Important Safety Instructions ............................................................................................6
Symbol Usage ................................................................................................................... 7
1. Presentation
1.1 Standard Positions ............................................................................................................. 9
1.2 Rear Panels...................................................................................................................... 10
1.3 Display and Control Panel .............................................................................................. 11
1.4 Accessories for Rack Mount ...........................................................................................11
1.5 Extended Battery (EXB) ................................................................................................... 12
2. Installation
2.1 Unpacking and Contents Check ......................................................................................13
2.2 Internal Batteries Connection (Battery Start-Up) ............................................................. 14
2.3 Installation in Tower Position .........................................................................................14
2.4 Installation in Rack Position ............................................................................................. 15
2.5 Communication Ports ...................................................................................................... 17
2.6 Required Protective Devices and Cable Cross-Sections ................................................ 18
2.7 Hardwire Connection of Output Power Cable to UPS .................................................... 19
2.8 Connection to Output Receptacles .................................................................................20
2.9 Connection of Extended Battery Module, UPS, and Transformer ................................. 20
3. Operation
3.1 Initial Start-Up ................................................................................................................. 21
3.2 Final Start-Up Sequence .................................................................................................. 21
3.3 Operating Modes ........................................................................................................... 22
3.4 Operation on Battery Power ............................................................................................ 23
3.5 Return to Normal AC Source. .......................................................................................... 24
3.6 UPS Shutdown When AC Present .................................................................................. 24
3.7 UPS Shutdown When on Battery .................................................................................... 24
4. Access to Maintenance and Personalization Data
4.1 Display Organization ........................................................................................................ 25
4.2 Access to Measurements. ..............................................................................................25
4.3 Access to UPS Set-Up and Maintenance Using the Control Panel ................................. 25
4.4 UPS Set-Up ...................................................................................................................... 26
4.5 Maintenance ................................................................................................................... 27
4.6 Personalization Using External Software ......................................................................... 27
5. Troubleshooting
5.1 Troubleshooting LEDS (21) and (22) ................................................................................ 29
5.2 Troubleshooting Not Requiring EATON ......................................................................... 29
5.3 Troubleshooting Requiring EATON After-Sales Support ................................................. 30
86-87050-00 A02 - Page 3
Page 6
Contents
6. Life Cycle Monitoring (LCM)
6.1 Description ......................................................................................................................31
7. Maintenance
7.1 Hot Swapping the Power Sub-Module. ........................................................................... 33
7.2 Hot Swapping the Battery Sub-Module . ........................................................................ 33
8. Appendices
8.1 Technical Specifications ................................................................................................. .35
EATON Customer Care Center
Technical Support and Product Services
Who to Contact Scheduling Field Service Engineer Support Return Policy for Repair of Single Phase Products (RGA)
8.2 Glossary .......................................................................................................................... 39
86-87050-00 A02 - Page 4
Page 7
Thank you for selecting an EATON product to protect your electrical equipment.
01
PET
01
PET
The MX range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System).
Warning: This is a class A UPS product. In a domestic environment, this product may cause radio interference, in which
case, the user may be required to take additional measures. If the device must be installed in overvoltage category III or IV environments, additional upstream overvoltage protection must be provided for.
Before installing MX, please read the booklet on the required safety instructions. Then follow the indications in this manual.
To discover the entire range of EATON products and the options available for the MX range, we invite you to visit our web site at www.eaton.com or contact your EATON representative.
Environmental Protection
EATON has implemented an environmental-protection policy. Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
w The cardboard we use comprises over 50% of recycled cardboard. w Sacks and bags are made of polyethylene. w Packing materials are recyclable and bear the appropriate identification symbol.
Introduction
Material Abbreviation
Symbol number
Polyethylene terephthalate PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of collecting and eliminating our products at the end of their service life.
w Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
w Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed to comply with regulations and in view of correct disposal. The «Material Safety Data Sheets» (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, please visit our website: www.eaton.com.
86-87050-00 A02 - Page 5
Page 8
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
The MX models that are covered in this manual are intended for installation in an environment within 0° to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Certification Standards
w IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability w FCC rules and regulations of Part 15, Subpart J, Class A w UL listed under 1778, Standards for Uninterruptible Power Supply Equipment w IEC 61000-4-2 (ESD): level 4 w IEC 61000-4-3 (Radiated field): level 3 w IEC 61000-4-4 (EFT): level 4 w IEC 61000-4-5 (Fast transients): level 4 w IEEE-C6241 Category B (ring wave) w IEC 61000-4-6 (electromagnetic field) w IEC 61000-4-8 (conducted magnetic field)
Safety of Persons
w
The system has its own power source (the battery). Consequently, the power outlets may be energized even if the systems is discon-
nected from the AC power source.
w
Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service personnel.
w
The system must be properly grounded.
w
The battery supplied with the system contains small amounts of toxic materials. To avoid accidents, the directives listed below must be
observed:
- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
- Do not lay tools or metal parts on top of batteries.
Product Safety
w
The UPS connection instructions and operation described in the manual must be followed in the indicated order.
w
A protection circuit breaker must be installed upstream and be easily accessible. The system can be disconnected from the AC power
source by opening this circuit breaker.
w
Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the
equipment to be connected to the system.
w
The socket-outlet shall be installed near the equipment and shall be easily accessible.
w
Never install the system near liquids or in an excessively damp environment.
w
Never let a foreign body penetrate inside the system.
w
Never block the ventilation grates of the system.
w
Never expose the system to direct sunlight or source of heat.
w
If the system must be stored prior to installation, storage must be in a dry place.
w
The admissible storage temperature range is -20ºC to +40ºC
Special Precautions
w
All handling operations will require at least two people (unpacking, installation in rack system).
w
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at
least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
w
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module
provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
Environment
w
This product has been designed to respect the environment: It does not contain any Chlorofluorocarbon (CFC) or Hydrochlorofluorocarbon (HCFC).
w
UPS recycling at the end of service life:
EATON undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products
recovered at the end of their service life (contact your EATON branch office).
w
Packing: UPS packing materials must be recycled in compliance with all applicable regulations. WARNING: This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by specialized companies.
86-87050-00 - Page 6
.
Page 9
Symbol Usage
Important instructions that must always be followed.
Visual indication.
Action.
Audible signal.
LED off.
Information, advice, help.
LED on.
86-87050-00 - Page 7
Page 10
(This page left blank intentionally)
86-87050-00 A02 - Page 8
Page 11
1.1 Standard Positions
Tower Position
1. Presentation
Dimensions (H x W x D) in inches/mm
MX 5000 RT
MX EXB RT
Transformer 5000
Weights in lbs/kg
MX 5000 RT 125/57
MX EXB RT 154/70
Transformer 5000 84/38
17.5 x 5.16 x 29.2/
444.5 x 131 x 741.4
17.5 x 5.16 x 25.6/
444.5 x 131 x 650
17.5 x 3.5 x 25.6/
444.5 x 88.9 x 650
Rack Position
Dimensions (H x W x D) in inches/mm
MX 5000 RT
MX EXB RT
Transformer 5000
5.16 x 17.5 x 29.2/ 131 x 444.5 x 741.4
5.16 x 17.5 x 25.6/ 131 x 444.5 x 650
3.5 x 17.5 x 25.6/
88.9 x 444.5 x 650
Weights in lbs/kg
MX 5000 RT 125/57
MX EXB RT 154/70
Transformer 5000 84/38
86-87050-00 A02 - Page 9
Page 12
BATT. NO.
200-250V~,24A
RPO
RS-232
CAUTION:
DO NOT DISCONNECT
BATTERY CABLE
UNDER LOAD
BATTERY
CONNECTOR
180VDdc
1
5
8
9
10
4
6
7
2
3
13
11
12
12
LOAD 4 / 120V~,16A
LOAD 1
120V~,16A
LOAD 2
120V~,16A
SET THIS
SWITCH WHEN
UNPOWERED
BY ALL SOURCES
INPUT VOLTAGE
SELECTION
240~
208~
INPUT
BREAKER
TRANSFORMER
PROTECTION
LOAD 3 / 120V~,16A
LOAD 3
BREAKER
LOAD 1
BREAKER
LOAD 2
BREAKER
LOAD 4
BREAKER
19
17
63
18
64
14
16
15
1. Presentation
1.2 Rear Panels
MX 5000 RT MX EXB RT Transformer 5000
86-87050-00 A02 - Page 10
(1) One group of 4 L6-30R outlets for connection of equipment
(2) Output terminal block
(3) Normal AC source input cable with L6-30P
(4) Connector for additional battery module
(5) Slot for optional communication card
(6) USB communication port
(7) RS232 communication port
(8) Communication port by relay
(9) Connector for Remote Power Off control
(10) Connector for automatic detection of battery module(s)
(11) Connectors for automatic detection of battery module(s)
(12) Connectors for battery modules (to the UPS or to the other battery modules)
(13) DC Battery circuit breaker
(14) Resetable 20Amp circuit breakers for NEMA 5-15/20 receptacle
(15) 6 NEMA 15/20 receptacle
(16) Resetable 20Amp circuit breakers to protect each L5-20R receptacle
(17) Input cable with L6-30P plug
(18) Input resetable CB
(19) 2 NEMA L5-20R receptacle
(63) Input voltage selecting (240V/208)
(64) Transformer protection CB
Page 13
1.3 Display and Control Panel



1. Presentation
(20) Load protected LED
(21) Downgraded operation LED
(22) Load not protected LED
(23) Alphanumeric display
(24) Escape (cancel) button
(25) Function buttons (scroll down)
(26) Function buttons (scroll up)
(27) Enter (confirm) button
(28) UPS OFF button
(29) UPS ON button
(30) Rectifier LED
(31) Battery LED
(32) Inverter LED
(33) Bypass LED
(34) Load supplied LED
1.4 Accessories for Rack Mount
Rack Mounting Kit
Telescopic rails for MX RT mounting in 19’’ enclosure with mounting hardware
(35) Front mounting bracket
(36) Rear support bracket
(37) Telescopic rails, 639 mm to 1005 mm
length (27.36’’ to 39.96’’)
86-87050-00 A02 - Page 11
Page 14
1. Presentation
MX 5000 RT
MX 5000 RT:5 min 22 min 41 min 62 min
MX EXB RT
MX EXB RT
MX EXB RT
1.5 Extended Battery (EXB)
MX RT offers a standard backup time of 5 minutes at full load. To increase backup time, it is possible to connect MX EXB RT modules to the UPSs for backup times up to 62 minutes (at full load).
Battery extensions for MX RT
Battery Integration System Kit with Casters (86005)
Optional battery extension cable (6 ft/1.8 m)
This extended battery cable will be used instead of the standard battery cable when battery modules are distant from each other (located in two different enclosures, for instance).
The Battery Integration System is intended for extended backup time configurations to conveniently stack and secure up to 5 modules on the same cart (swivel wheels with brakes, leveling feet, seismic side panels, plates to lock modules, and screws included).
86-87050-00 A02 - Page 12
Page 15
2.1 Unpacking and Contents Check
46
47
option
(66102)
45
43
54
49
51
i
50
53
51
52 54
53
43
UPS Module Contents (87050)
Optional Transformer Module Contents (87102)
2. Installation
Step down transformer is designed to provide isolated 120 volts AC outlets.
Optional Battery Module Contents (87103)
(40) MX 5000 UPS
(41) Two sets of tower stands
(42) RS232 communications cable
(43) Product documentation
(45) Telescopic rails for rack enclosure with
mounting hardware
(46) Screw driver
(47) Solution-Pac power management suite CD-ROM
Please see the appropriate manual for packing contents of the optional battery module and transformer module.
Packaging must be destroyed according to waste management standards. Recycling icons are displayed for easy selection.
(48) Network Management card (optional)
(49) Transformer 5000
(50) MX EXB RT battery module
(51) Tower stand expanders
(52) Battery cable
(53) Battery communication cable
(54) Stabilizer bracket (4 screws included)
A dangerous voltage is present inside the power module and the battery module. Any operations to be
carried out on these modules must be done so by qualified personnel.
86-87050-00 A02 - Page 13
Page 16
2. Installation
BATT. N
O
.
200-25
0V~,
2
4A
RP
O
R
S-232
C
AUTION:
D
O N
O
T
D
IS
C
ONN
E
C
T
B
ATTE
R
Y
CAB
L
E
U
N
DE
R
L
OA
D
B
A
T
TE
R
Y
CO
NN
E
C
TO
R
1
80
V
D
d
c
59
60
Input Cable L6-30P
6 inches
17.7 inches
2.2 Internal Battery Connection (Battery Start-up)
1. Remove the two mounting screws (59) to free the battery disconnect switch (60).
2. Push the battery disconnect switch so that you can read “Connected”.
3. Secure the two mounting screws (59).
2.3 Installation in Tower Position
Follow steps 1 to 3 in the illustration below to adjust the tower stands for the upright position.
Always keep 6 inches free space behind the UPS rear panel. The distance between the tower stands should
be 17.7 inches.
86-87050-00 A02 - Page 14
Page 17
2.4 Installation in Rack Position
2
3
1
Adjustment of the orientation of the logo and control panel
2. Installation
UPS module rack mounting
MX RT is very heavy. To ease its rack integration, we strongly recommend to remove the battery tray as shown below.
See Section 7.2 for complete instructions on battery removal.
86-87050-00 A02 - Page 15
Page 18
2. Installation
Do not install the UPS or battery module in hermetic closed environments without any exchange of air.
Follow steps 1 to 4 for rack mounting the UPS onto the rails.
The rails and the necessary mounting hardware are supplied by EATON.
Note for step 1: It is possible to adjust the position of both front mounting brackets.
Rear bracket system (included with rail kits)
To be used if you need to move the rack enclosure with UPS already rack-mounted inside.
86-87050-00 A02 - Page 16
Page 19
2.5 Communication Ports
8
MX RT provides 4 communication methods.
1. The RS232 port provides communications using EATON Serial HID UPS transfer (SHUT) protocol. The SHUT protocol is compatible with the power management applications available on the enclosed Solution-Pac 2 CD-Rom.
2. The Output contacts port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.
3. The USB port is compatible with the power management applications available on the enclosed Solution-Pac 2 CD-Rom.
4. The slot is compatible with the optional 66102 — Network Management Card (NMC) 2006 Edition and the 66103-Status Card.
Note All communications options can be used simultaneously except for the SHUT RS232 and USB port. If both the USB and SHUT ports are connected then the USB takes control.
Connection to the RS232 or USB communication port (42)
2. Installation
1 Connect the RS232 (42) or USB (44) communication cable to the serial or USB port on the computer equipment.
2. Connect the other end of the RS232 cable (42) to the RS232 (7) communication port or the USB cable (not included) to the USB port (6) on the UPS.
The UPS can now communicate with various EATON power management application software.
Please note that Personal Solution-Pac can be used to configure (personalize) the UPS parameters such as voltage, frequency, battery test, etc. See section 4.6 for more details.
Connection to the communication port by relays (8)
w Pin 1, 2: not used, w Pin 3: Remote Power Off signal (5 to 27 V DC,
10 m A max),
w Pin 4: Operation on mains (not on battery), w Pin 5: User common, w Pin 6: Operation on automatic by-pass, w Pin 7: Low battery, w Pin 8: Load protected, w Pin 9: Operation on battery.
n.o: contact normally open. n.c: contact normally closed.
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.
Output relays specifications:
w Voltage: 48 V DC max, w Current: 2 A max, w Power: 62.5 VA, 30 W.
Example: for 48 V DC, Imax=625 mA
86-87050-00 A02 - Page 17
Page 20
2 poles circuit breaker
To UPS Normal AC source
L1G L2 (N)
L1
L2 (N)
2. Installation
RJ12
5 V DC to 27 V DC
+
_
RJ12
5 VDC to 27 VDC
+
_
Remote Power Off communication port (9)
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize MX RT with the RPO port, it is necessary to use a two-position switch (Normally Open or Closed contact). Once switch is energized/de-energized, the UPS shuts off the display and the output of the UPS.
w The output devices can be powered again through auto bypass when the two-position switch is released (open or closed).
w The output devices will remain powered < 1 sec. after RPO activation.
Push the start button to return to normal operation.
Note: The internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Installation of optional communication card (66102)
Remote power off contact normally open (9)
Remote power off contact normally closed (9)
w Signal: activation voltage: 5 V DC to 27 V DC, current: 10 mA max.
2.6 Required Protective Devices and Cable Cross-Sections
Recommended upstream protection
UPS Power Rating
86-87050-00 A02 - Page 18
Required cable cross-sections
w Terminal-block cable capacity: 6 mm2, solid or stranded wire (maximum AWG 10). w Capacity for earthing conductor: 6 mm2 , solid or stranded wire (maximum AWG 10).
5000 RT D curve - 35A
Upstream Circuit
Breaker
Page 21
2.7 Hardwire Connection of Output Power Cable to UPS
BATT. N
O.
200-250V~,
2
4A
RP
O
R
S-
232
CAUTION:
D
O
N
O
T
D
ISC
ON
N
E
C
T
B
AT
T
E
R
Y
CAB
L
E
U
N
DE
R
LOA
D
B
A
T
TE
R
Y
CO
N
N
E
C
TO
R
1
80
V
D
d
c
1
2
3
BATT. NO.
200-250V~,
2
4A
RP
O
R
S-
232
CAUTION:
D
O
N
O
T
D
ISC
ON
N
E
C
T
B
AT
TE
R
Y
C
AB
L
E
U
N
DE
R
L
OA
D
B
A
T
TE
R
Y
CO
NN
E
C
TO
R
1
80
V
D
d
c
2 & 3
2
3
Output Terminal
L2(N)GND L1
BATT. N
O.
200-250V~,
2
4A
RP
O
R
S-
232
CAUTION:
D
O
N
O
T
D
ISC
ON
N
E
C
T
B
AT
TE
R
Y
CAB
L
E
U
N
DE
R
L
OA
D
B
A
T
TE
R
Y
CO
N
N
E
C
TO
R
1
80
V
D
d
c
4
2
3
w This type of connection must be carried out by qualified electrical personnel. w Before carrying out any connection, check that the battery circuit breaker and the upstream protection device
(Normal AC source) is open «0» (off).
1. Remove the top of the terminal box cover (2 screws) with the included screwdriver.
2. Insert the output cable/conduit (provided by others) through the cable knockout (2).
3. Connect the outlet cable to the output terminal
block.
4. Tighten the cable/conduit flange and refit the terminal box cover by means of the 2 screws.
Always connect the ground wire first.
2. Installation
Note: 10’ Input cable with L6-30P (3) comes
attached by EATON. Output cable/conduit (2) is not included (provided by others).
86-87050-00 A02 - Page 19
Page 22
2. Installation
BATT. N
O
.
200-250V~,
2
4A
RP
O
R
S-232
C
AUTION:
D
O
N
O
T
D
ISC
ON
N
E
C
T
B
AT
TE
R
Y
CAB
L
E
U
N
DE
R
LOA
D
B
A
T
TE
R
Y
CO
N
N
E
C
TO
R
1
80
V
D
d
c
TRANSFORMER INPUT CABLE
BATTERY
MODULE
BATTERY
MODULE
UPS MODULEMXTRANSFORMER
MODULE
12
13
10
11
4
53
53
53
52
2.8 Connection to Output Receptacles
1. Connect the equipment to the UPS 4 NEMA L6-30R.
If more than one load is connected to the UPS, the total capacity of the loads should not exceed 30 Amps.
2.9 Connection of Extended Battery Module, UPS, and Transformer
1. Check that the battery circuit breaker(s) (13) is OFF («0» position).
2. Connect the battery power cable (52) to the connector (4) of the power module and to the connector (12) of the battery module.
3. Connect the battery detection cable (53) to the connector (10) of the power module and to the connector (11) of the battery module.
4. Switch on the battery circuit-breaker(s) (13).
86-87050-00 A02 - Page 20
Page 23
3. Operation
i
20
30 32 34
29
21 22
33 34
22
3.1 Initial Start-Up
To ensure that your system is configured in complete accordance with safety regulations and to benefit from the manufacturer’s warranty, please contact Technical Support at www.eaton.com or call (800) 279-7776.
1. Check that the battery disconnect switch (60) on top cover is connected (see section 2.2 Internal Battery Connection).
2. Set the upstream circuit breaker (not included) to the on position.
The equipment is powered via the Normal AC source, but not protected by the UPS.
Batteries are recharging, an 8 hour recharge period is necessary to get full backup time.
LED (22) is ON, LEDs (33) and (34) are green.
UPS Set-Up
If UPS personalization is desired, it is advised to enter the personalization mode at this time (see the 4.4 «Personalization» section).
3.2 Final Start-Up Sequence
3. Press and hold the «I» (on) button (29) for 3 seconds.
The buzzer beeps once, and after UPS internal test sequence, the LED (20) is ON.
LEDs (30), (32), (34) are green.
The equipment is protected by the UPS.
If LED (21) or (22) is ON, an alarm has occurred (see the «troubleshooting» section).
86-87050-00 A02 - Page 21
Page 24
3. Operation
3.3 Operating Modes
Normal mode
ECO mode
This is the standard operating mode, set by default in the factory.
Under normal condition (Normal AC source available):
LED (20) is ON. LEDs (30), (32), (34) are green.
The equipment is protected by the UPS.
AC out of tolerance
The main advantage of the Eco mode (see glossary) is that it reduces the consumption of electrical power.
Under normal condition (Normal AC source available):
LED (20) is ON. LEDs (33), (34) are green.
The equipment is supplied in ECO mode.
If normal AC source is out of tolerance:
LEDs (20), (21) are ON. LEDs (30), (32), (34) are green.
The equipment is protected by the UPS.
86-87050-00 A02 - Page 22
Page 25
3.4 Operation on Battery Power
When the Normal AC source is not available, the load continues to be protected by the UPS. Power is supplied by the battery.
Transfer to battery power
Low battery warning
3. Operation
LEDs (20), (21) are ON. LEDs (31), (32), (34) are green.
The audible alarm beeps every 10 seconds.
The equipment is protected by the UPS and supplied by the battery.
The display indicates the battery remaining backup time.
End of backup time
LEDs (20), (21) are ON. LEDs (31), (32), (34) are green.
The audible alarm beeps every 3 seconds.
The remaining battery power is low.
Shut down all applications on the connected equipment because automatic UPS shutdown is imminent.
LED (22) is ON. LED (34) is red.
The audible alarm beeps continuously.
The equipment is not powered.
The UPS displays «End of backup time Battery low».
86-87050-00 A02 - Page 23
Page 26
25 2827
NO YES
33 34 28
22
ON AUTO BYPASS
3. Operation
3.5 Return to Normal AC Source
After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalization) and the load is supplied again.
3.6 UPS Shutdown When AC Present
Before shutdown, please read ALL instructions below:
1. Press and hold the «0” (off) button (28) for 3 seconds. The buzzer beeps once.
The load is no longer protected by the UPS. It is powered via the Normal AC source (bypass). If
the UPS is set in frequency converter mode, the equipment will not be powered. If the Normal AC
source is out of tolerance, the UPS will generate a 10ms output calibrated break.
LEDs (22) is ON, LEDs (33) and (34) are green.
For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the off position or remove the Normal AC source.
3.7 UPS Shutdown When on Battery
Before shutdown, please read ALL instructions below:
1. Press and hold the «0” (off) button (28) for 3 seconds. The buzzer beeps once.
2. The display asks for confirmation.
3. Press the scroll button (25) to select yes.
4. Press confirm button (27).
The UPS is now fully shut down.
86-87050-00 A02 - Page 24
Page 27
4. Access to Maintenance and Personalization Data
Local settings
Output settings
ON/OFF settings
Battery settings
Model
UPS Set-up Maintenance
Measurements
Alarm History
Manual battery test
Led and Buzzer test
LCM
Statistics
Operation limits
UPS input measurements
Status and Alarms
UPS output measurements
Battery measurements
4.1 Display Organization
4.2 Access to Measurements
Press the scroll button (25)to access measurements for voltage, current, frequency, power output and battery capacity.
4.3 Access to UPS Set-Up and Maintenance Using the Control Panel (23)
w Press the scroll button (25) a number of times to point to the UPS set-up or Maintenance menu. w Press the “Enter” button (27) to get access.
86-87050-00 A02 - Page 25
Page 28
4. Access to Maintenance and Personalization Data
4.4 UPS Set-Up
Local Settings
Function Factory Setting Options
Language English French, German, Italian, Portuguese, Spanish
Date/Time Format
Date/Time Change
Audible Alarm Yes No
Output Settings
Function Factory Setting Options Comments
Output Voltage 208V
Freq Converter Disabled Enabled
International format (DD-MM-YYYY/HH :MM)
GMT+ 1(Continental Europe)
US (MM-DD-YYYY/HH:MM AM/PM)
MM-DD-YYYY/HH :MM adjustable
200V / 230V / 220V /240V / 250V
Output Frequency 60 Hz 50 Hz
Eco Mode Disabled Enabled
Slew rate 1 Hz/sec. 0.5 Hz/sec.
Bypass Transfer Yes No
Interrupt Time 10 ms 20 ms, ...... , 200 ms
Overload Prealarm 105% 40%, 50%, 70% Alarm if threshold is overrun
User selectable under frequency­converter mode
Transfer to bypass if Normal AC source is out of tolerance
Break time calibration during load transfer on Normal AC source out of tolerance
ON/OFF Settings
Function Factory Setting Options Comments
Cold Start Disabled Enabled
Forced Reboot Enabled Enabled
Auto Restart Enabled Disabled
Energy Saving Disabled Enabled
Start on battery
Enables automatic restart of the system even if Normal AC source is restored before the end of the shutdown sequence
UPS restarts automatically when Normal AC source is restored
Automatic shutdown on battery if output load level < 10%
Sleep Mode Enabled Disabled
Remote Command Enabled Disabled
86-87050-00 A02 - Page 26
Enables consideration of shutdown or restart orders from software to be authorized
Page 29
4. Access to Maintenance and Personalization Data
Battery Personalization
Function Factory Setting Options Comments
Battery test Every week No test / daily test / monthly
Low Batt warning 20% 0 to 100% 1% increment
User Battery Settings
Deep DischargeProtect Yes No
4.5 Maintenance
Function Sub-Function Options/Display Comments
Model Power Module
Alarm History
Manual Batt Test Manual Battery Test No / Yes
Led Buzzer Test Led & Buzzer Test No / Yes
Life Cycle Monitoring LCM Enable / Disable Life cycling monitoring alarms
Statistics
Operation Limits Operation Limits
UPS reads number of battery modules connected
Read
Erase No / Yes
Auto Statistics Statistics
Custom Statistics
From 0 to 40 Ah 5 Ah increment
SN: xxxxxxxxx SOFT: xxx NT: xxx
Description Date Hour Alarm xxx
Reset Date: No, Yes Statistics
Protection against deep discharge. If disable, EATON warranty will be void
Serial number Soft version Technical level
10 alarms can be stored automatically
Automatic alarms displayed when UPS is operating near the limits
4.6 UPS Set-Up Using External Software
w Insert the Solution-Pac CD-ROM in the drive.
w On the first navigation screen, select «Point to Point solution» and follow the instructions on how to install the Personal Solution-Pac software.
w Then select «Settings», «Advanced settings» and «UPS settings».
Note This feature is only supported through Windows and the RS232 communication.
Page 30
(This page left blank intentionally)
86-87050-00 A02 - Page 28
Page 31
5. Troubleshooting
27
ENVIRONMENT FAULT
5.1 Troubleshooting LEDS (21) and (22)
If LED (21) is ON:
The equipment is protected by the UPS but the
operation is downgraded.
If LED (22) is ON:
The equipment is no longer protected by the UPS.
5.2 Troubleshooting Not Requiring EATON After-Sales Support
Press the “Enter” button (27) to display the details below:
Displayed details Signification Correction
NO BATTERY
I/O BAD CONNECTION
NO POWER MODULE
NO BATTERY MODULE
INV THERM OVERLOAD
INVERT LIMITATION
The battery is incorrectly connected
AC source is not connected to the correct terminals
The power sub-module is not inserted
The battery sub-module is incorrectly connected
The UPS shuts down automatically because of a major overload
Short circuit conditions on output devices
Check battery connections (see section 2.9)
Check AC wiring
Check power sub-module connections (see section 7.1)
Check battery connections (see section 7.2)
Check the power drawn by the connected devices and disconnect any non-priority devices
Check the installation at the UPS output (wiring, fault equipment)
86-87050-00 A02 - Page 29
Page 32
27
ENVIRONMENT FAULT
5. Troubleshooting
5.3 Troubleshooting Requiring EATON After-Sales Support
Displayed Signification Correction
The battery is incorrectly
POWER MODULE FAULT
BATT MODULE FAULT
FRAME FAULT
connected. Internal power sub-module fault detected. Use “Enter” button (27) to display details.
Battery fault detected during the battery test. Use “Enter” button (27) to display details.
Internal chassis fault detected. Use”Enter” button (27) to display details.
See after-sales support at www.eaton.com. Follow the power sub-module replacement procedure (see sections 7.1 and 7.2)
See after-sales support at www.eaton. com. Follow the battery sub-module and battery module replacement procedure (see section 7.2)
See after-sales support at www.eaton.com. Follow the frame replacement procedure (see sections 7.1 and 7.2)
Note: In case of multiple fault, press the “Enter” button (27) and the scroll button (25) to get access to further details.
86-87050-00 A02 - Page 30
Page 33
6. Life Cycle Monitoring (LCM)
i
6.1 Description
This function, embedded in the UPS, displays messages on screen, and communication channels, at every important stage of the UPS’s life, allowing you to:
Press the “Enter” button (27) to display LCM warning details.
Secure your installation power continuity
Anticipate needed maintenance actions thanks to automatically displayed warnings:
LCM warning details Signification
BATTERYCHECK RECOMMENDED CONTACT www.eaton.com
Battery is approaching its reliability end of life. Risk of dramatically reduced backup time
Reset or disable LCM
In case of any LCM messages displayed:
w For temporary reset: Press ESC for more than 3 seconds in the Status and Alarm screen, to temporarily cancel the alarm status. The alert will be repeated twice in 30 days. w For permanent reset: Press ENT for more than 3 seconds in the LCM warning screen, to permanently cancel this LCM event.
At any time: To Disable all LCM messages select “disable all”, in LCM menu with LCD navigation.
You will not be aware of any LCM events that can happen on the UPS if you disable all LCM messages.
86-87050-00 A02 - Page 31
Page 34
(This page left blank intentionally)
86-87050-00 A02 - Page 32
Page 35
7.1 Hot Swapping the Power Sub-Module
i
i
This operation must be carried out by qualified electrical personnel only. This operation can be performed without interrupting the equipment.
Disconnecting the power sub-module (87100):
1. Remove the 6 mounting screws to free the main front panel bezel.
2. Place the front panel above the UPS.
3. Remove the 2 mounting screws on each side of the power sub-module.
4. Withdraw the power sub-module.
Reconnecting the power sub-module:
w Carry out the above instructions in reverse order. w Replace the faulty power sub-module by another one with same power rating (MX 5000).
7. Maintenance
Note: There is a safety pin at the rear of the
module. Lift the sub-module slightly and the sub-module will slide out (follow the arrow in the diagram).
When reconnecting the sub-module, carry out the aboveinstructions in reverse order. A red button will be depressed behind plate 3, reestablishing connection.
7.2 Hot Swapping the Battery Sub-Module
This operation must be carried out by qualified electrical personnel only.
The battery can cause electrocution and high short-circuit currents. The following safety cautions are required before servicing the battery components:
w Remove watches, rings, bracelets and all other metal objects from the hands and arms, w Use tools with an insulated handle.
This operation can be performed without interrupting the equipments.
This operation must be carried out by qualified electrical personnel only.
Disconnecting the battery sub-module (87101):
1. Remove the 6 mounting screws to free the main front panel bezel.
2. Place the front panel above the UPS.
3. Remove the 4 mounting screws on the sides of the battery sub-module.
4. Withdraw the battery sub-module.
Reconnecting the battery sub-module:
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
Caution! The battery is heavy
(approx. 60 lbs.).
86-87050-00 A02 - Page 33
Page 36
86-87050-00 A02 - Page 34
Page 37
8.1 Technical specifications
Output power
Electrical supply network
w Rated input voltage w Input voltage range w Frequency w Power factor w Leakage current
Load output
w Voltage w Frequency w Harmonic distortion w Overload capacity
Battery
Environment
w Operating temperature range w Relative humidity w Storage temperature range w Altitude
MX 5000 MX EXB
(1)
5000 VA
4500 W
Single phase 208 V
120/156 V to 280 V
/
(2)
(3)
50/60 Hz (autoselect)
> 0.99
7 mA
Single phase 208 V ±3%
50/60 Hz ±0,5%
(4)
(5)
< 3%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
15 x 12V - 5 Ah, sealed lead acid, maintenance free
0°C to 40°C
20% to 90% (non-condensing)
-25°C to 40°C 1000 m
8. Appendices
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
Noise level < 45 dBA
(1) If the output voltage is 200V — 250V, the output power is 5000VA / 4500W.
(2) With one EXB module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the Personal Solution-Pac software.
(5) Frequency-converter mode is programmable using the Personal Solution-Pac software.
(6) Step-down transformer is available for 120V output.
86-87050-00 A02 - Page 35
Page 38
86-87050-00 A02 - Page 36
Page 39
8. Appendices
EATON
Customer Care Center
Technical Support and Product Services
Technical questions? If you encounter a problem while following the instructions in this manual, or have questions
about the operation, repair, or servicing of your equipment, please visit our web site www.eaton.com for complete
service information.
To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial number of the unit and include them in any discussions or correspondence.
Part Number: ________________________________________________________________________________________
Assembly Number: __________________________________________________________________________________
Serial number: ______________________________________________________________________________________
Who To Contact
For Te chnical Support, Customer Care Center , Customer FAQ please visit our website: www.eaton.com
Scheduling Field Service Engineer Support
Scheduling of the EATON Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please contact EATON to insure a safe installation and start-up that will maintain the EATON warranty and insure smooth performance.
Return Policy for Single Phase Products (RMA)
Should you require factory service for your equipment, contact EATON Customer Care Center and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to EATON without first obtaining an RMA number.
.
For further details please visit our website: www.eaton.com
Date: ______________________________________________________________________________________________
RMA Number: ______________________________________________________________________________________
Contact Name: ______________________________________________________________________________________
86-87050-00 A02 - Page 37
Page 40
86-87050-00 A02 - Page 38
Page 41
8.2 Glossary
Backup time Time that the connected equipment can operate on battery power.
Bypass AC source Source supplying the bypass line. The equipment can be transferred to the bypass
ECO mode Operating mode by which the equipment is supplied directly by the AC source if it
Equipment Devices or systems connected to the UPS output.
Normal (double The normal UPS operating mode in which the AC source supplies the UPS which in turn
conversion) mode supplies the connected equipment (after electronic double conversion).
Frequency converter Operating mode used to convert the AC-power frequency between the UPS input and
Normal AC source Normal source of power for the UPS.
Low-battery warning This is a battery-voltage level indicating that battery power is low and that the user must
Relay contacts Contacts supplying information to the user in form of signals.
8. Appendices
line if an overload occurs on the UPS output, for maintenance or in the event of a malfunction.
is within the tolerances defined by the user. This mode reduces the consumption of electrical power.
output (50 Hz -> 60 Hz or 60 Hz -> 50 Hz).
take action to prevent the imminent break in the supply of power to the load.
Personalization It is possible to modify certain UPS parameters set at the factory. Certain UPS functions
canalso be modified by the EATON power management products to better suit user needs.
UPS Uninterruptible Power System.
86-87050-00 A02 - Page 39
Page 42
Notes
86-87050-00 A02 - Page 40
Page 43
86-87050-00 A02