Eaton 380 VCP-WR 16, 380 VCP-W 25, 380 VCP-WR 32, 380 VCP-W 21, 380 VCP-WR 21 Instructions For Installation, Operation And Maintenance

...
I.B. 3A74792H08
Instructions for Installation, Operation and Maintenance
of Type VCP-W and VCP-WR 38kV Vacuum Circuit Breakers
Effective September 2014
Type VCP-W (Fixed)
I.B. 3A74792H08 Page iii
WARNING
IMPROPERLY INSTALLING OR MAINTAINING THESE PRODUCTS CAN RESULT IN DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING ANY UNPACKING, ASSEMBLY, OPERATION OR MAINTENANCE OF THE CIRCUIT BREAKERS.
INSTALLATION OR MAINTENANCE SHOULD BE ATTEMPTED ONLY BY QUALIFIED PERSONNEL. THIS INSTRUCTION BOOK SHOULD NOT BE CONSIDERED ALL INCLUSIVE REGARDING INSTALLATION OR MAINTENANCE PROCEDURES. IF FURTHER INFORMATION IS REQUIRED, YOU SHOULD CONTACT EATON.
Eaton Corporation
Moon Township, PA. 15108
WARNING
THE CIRCUIT BREAKER ELEMENTS DESCRIBED IN THIS BOOK ARE DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL, RESULTING IN DEATH, BODILY INJURY AND PROPERTY DAMAGE.
ALL SAFETY CODES, SAFETY STANDARDS AND/OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO.
THE FIXED CIRCUIT BREAKER ELEMENTS ARE DESIGNED TO BE INSTALLED PURSUANT TO ALL APPLICABLE ANSI STANDARDS. SERIOUS INJURY, INCLUDING DEATH, CAN RESULT FROM FAILURE TO FOLLOW PROCEDURES OUTLINED IN THIS MANUAL, OR COMPLY WITH THE REQUIREMENTS OF APPLICABLE STANDARDS. THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PHASE TO PHASE INSULATION, PHASE TO GROUND INSULATION AND ALL BREAKER INTERLOCKS. THESE CIRCUIT BREAKER ELEMENTS ARE SOLD PURSUANT TO A NON-STANDARD PURCHASING AGREEMENT WHICH LIMITS THE LIABILITY OF THE MANUFACTURER.
Al l possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of particular equipment, contact a Eaton representative.
Effective 09/2014
Page iv I.B. 3A74792H08
TABLE OF CONTENTS
SECTION 1: INTRODUCTION Page
1-1 Preliminary Comments and Safety Precautions .......................................................................................... 1
1-1.1 Warranty and Liability Information ...................................................................................................... 1
1-1.2 Safety Precautions ............................................................................................................................. 1
1-2 General Information ..................................................................................................................................... 1
1-3 Type VCP-W and VCP-WC Vacuum Circuit Breaker Ratings .................................................................... 2
1-4 Outlines and Dimensions ............................................................................................................................. 6
SECTION 2: SAFE PRACTICES
2-1 Recommendations .................................................................................................................................... 8
SECTION 2: RECEIVING, HANDLING AND STORAGE
3-1 General ........................................................................................................................................................ 9
3-2 Receiving ..................................................................................................................................................... 9
3-3 Handling ....................................................................................................................................................... 9
3-4 Storage ...................................................................................................................................................... 10
3-5 Tools and Accessories .............................................................................................................................. 11
3-6 Type VCP-W and VCP-WR Vacuum Circuit Breaker Weights .................................................................. 11
SECTION 4: INITIAL IN SPE CT ION AND IN STA LLATI ON
4-1 Introduction ................................................................................................................................................ 17
4-2 Manual Operation Check ........................................................................................................................... 17
4-3 Vacuum Interrupter Integrity ...................................................................................................................... 17
4-4 Insulation ................................................................................................................................................... 17
4-5 Contact Erosion and Wipe ......................................................................................................................... 17
4-6 Primary Circuit Resistance ........................................................................................................................ 17
4-7 Nameplate ................................................................................................................................................. 17
4-8 Electrical Operation Check ........................................................................................................................ 17
4-8.1 Circuit Breaker Insertion and Removal .................................................................................... 18
4-8.2 Operation Check Performance ................................................................................................ 19
4-9 Breaker/Structure Interfacing ..................................................................................................................... 19
4-9.1 Interface Interlocks .................................................................................................................. 19
4-9.2 Drawout Breaker Interfacing Check (VCP-W) ......................................................................... 19
SECTION 5: DESCRIPTION AND OPERATION
5-1 Introduction ................................................................................................................................................ 21
5-2 Interrupter Assembly.................................................................................................................................. 21
5-2.1 Vacuum Interrupter .................................................................................................................. 22
5-2.2 Contact Erosion Indication ....................................................................................................... 22
5-2.3 Loading Spring Indication ........................................................................................................ 23
5-2.4 Contact Wipe and Stroke .................................................................................................
5-3 Stored Energy Mechanism ........................................................................................................................ 23
........ 23
Effective 09/2014
I.B. 3A74792H08 Page v
Page
5-3.1 Operation of Stored Energy Mechanism ..................................................................................... 23
5-3.2 Charging ....................................................................................................................................... 23
5-3.3 Closing Operation ................................................................................................................... 25
5-3.4 Tripping Operation .................................................................................................................. 25
5-4 Control Schemes ................................................................................................................................. 25
5-4.1 Timing ..................................................................................................................................... 25
5-4.2 Secondary Disconnects .......................................................................................................... 25
5-4.3 Secondary Terminal Blocks .................................................................................................... 29
5-4.4 Undervoltage Trip Device........................................................................................................ 29
5-5 Interlocks and Interfacing .................................................................................................................... 30
5-6 Levering Mechanism (VCP-W Only) .................................................................................................... 30
5-7 Operations Counter ............................................................................................................................. 30
5-8 Ground Contact ................................................................................................................................... 30
5-9 MOC and TOC Switch Operations ....................................................................................................... 30
SECTION 6: INSPECTION, MAINTENANCE AND TROUBLESHOOTING
6-1 Introduction ......................................................................................................................................... 32
6-2 Frequency of Inspection and Maintenance .......................................................................................... 32
6-2.1 Qualified Personnel ............................................................................................................... 32
6-2.2 Helpful Tools and Accessory Items ....................................................................................... 32
6-2.3 General Torque Guidelines ................................................................................................... 32
6-3 Inspection and Maintenance Procedures ............................................................................................. 35
6-4 Vacuum Interrupter Integrity Test ........................................................................................................ 36
6-5 Contact Erosion ................................................................................................................................... 36
6-6 Contact Wipe ....................................................................................................................................... 36
6-7 Insulation ............................................................................................................................................. 37
6-8 Insulation Integrity Check .................................................................................................................... 37
6-9 Primary Circuit Resistance Check ....................................................................................................... 37
6-10 Mechanism Check ............................................................................................................................... 39
6-10.1 CloSure
6-11 Lubrication ........................................................................................................................................... 43
6-12 Troubleshooting Chart ......................................................................................................................... 43
SECTION 7: RENEWAL PARTS
7-1 General .............................................................................................................................................. 46
7-1.1 Ordering Instructions ............................................................................................................. 46
Figure Title Page
1-1 Type VCP-W 38kV Drawout Circuit Breaker Outlines and Dimensions ................................................. 6
1-2 Type VCP-WR 38kV Fixed Circuit Breaker Outlines and Dimensions ................................................... 7
3-1 Circuit Breaker Shown Mounted with Ramp Still in Shipping Position (VCP-W Only) .......................... 10
3-2 Circuit Breaker Shown Being Moved Carefully Down Attached Ramp (VCP-W Only) ......................... 10
3-3 Optional Fifth Wheel Shown in Use (VCP-W Only) .............................................................................. 10
3-4 Front View VCP-W 38kV Drawout Vacuum Circuit Breaker ................................................................. 12
3-5 VCP-W or VCP-WR 38kV Vacuum Circuit Breaker with Front Cover Removed .................................. 13
3-6 Rear View VCP-W 38kV Drawout Vacuum Circuit Breaker ................................................................. 14
3-7 Rear View VCP-WR Fixed Vacuum Circuit Breaker ............................................................................ 15
Effective 09/2014
TM
Test ...................................................................................................................... 39
FIGURES
Page vi I.B. 3A74792H08
FIGURES
Figure Title Page
3-8 Typical VCP-W 38kV Escutcheon ............................................................................................................. 16
4-1 Type VCP-W Circuit Breaker Manual Charging Handle in Use ................................................................ 18
4-2 Drawout Circuit Breaker (Bottom View) ..................................................................................................... 20
5-1 Rear View Showing Pole Unit Enclosure (VCP-W Only) ........................................................................... 21
5-2 Plate Over Rear Truck Opening 2000A Breakers and Above (VCP-W Shown) ....................................... 21
5-3 Graphic Representation of Arc Interruption ............................................................................................... 22
5-4 Closing Cam and Trip Linkage .................................................................................................................. 24
5-5 Charging Schematic .................................................................................................................................. 26
5-6 Typical VCP-W “DC” and “AC” Control Schematics (Drawout) ................................................................. 27
5-7 Typical VCP-WR “DC” and “AC” Control Schematics (Fixed) ................................................................... 28
5-8 Secondary Plug Shown Mounted Lower Left Drawout Circuit Breaker ..................................................... 29
5-9 Secondary Terminal Blocks Shown Mounted Bottom Front Fixed Circuit Breaker ................................... 30
5-10 Undervoltage Trip Device Configuration .................................................................................................... 31
6-1 Lubrication Points (Drawout Circuit Breaker Shown) ................................................................................ 34
6-2 Rear Measurement for Contact Erosion Being Made (Circuit Breaker Closed) ........................................ 37
6-3 Graphical Representation of Contact Erosion Measurement .................................................................... 37
6-4 Side View of Loading Spring Indicator (Circuit Breaker Closed) ............................................................... 38
6-5 Graphical Representation of Contact Wipe Measurement of Loading Spring Indicator ............................ 38
6-6 Resistance Measurement Locations ......................................................................................................... 38
6-7 Status Indicators ........................................................................................................................................ 39
6-8 Starting Tape at Bottom ............................................................................................................................. 39
6-9 Wrapping Tape up around Cam ................................................................................................................ 39
6-10 Attaching Tape Around to Back of Cam .................................................................................................... 40
6-11 Attaching CloSure 6-12 Attaching CloSure
6-13 Manually Charging Closing Springs .......................................................................................................... 40
6-14 Manually Closing Circuit Breaker with Marker in Hole “C” ........................................................................ 41
6-15 Top View of Cam and Marker Interface ..................................................................................................... 41
6-16 Move Marker 15° to Right .......................................................................................................................... 41
6-17 Move Marker 15° to Left ............................................................................................................................ 41
6-18 Remove Marked Masking Tape from Cam ................................................................................................ 41
6-19 Place Tape on Right Side Panel of Breaker .............................................................................................. 41
6-20 Illustrative Testing Tape Sample ............................................................................................................... 42
6-21 Front View of CloSure 6-22 Typical Circuit Breaker Front View with CloSure
Table Title Page
1-1 Type VCP-W Ratings on Symmetrical Current Rating Basis ...................................................................... 2
1-2 Type VCP-WC Ratings on Symmetrical Current Rating Basis ................................................................... 4
3-1 Approximate Circuit Breaker Weights ........................................................................................................ 11
5-1 Circuit Breaker Timing ............................................................................................................................... 29
6-1 Torque Guidelines ..................................................................................................................................... 33
6-2 Test Voltage ............................................................................................................................................... 36
6-3 CloSure
TM
Tool Mounting /Testing Locations by Circuit Breaker Type ..................................................... 42
6-4 Approximate Resistance Measurements ................................................................................................... 43
7-1 Recommended Renewal Parts for ANSI Rated Breakers ......................................................................... 46
TM
Test Tool at Hole “A” ................................................................................................ 40
TM
Test Tool at H Pole “B” ............................................................................................. 40
TM
Tool Showing Mounting/Testing Hole Locations ................................................ 42
TM
Tool Attached ............................................................ 42
TABLES
Effective 09/2014
I.B. 3A74792H08 Page 1
SECTION 1: INTRODUCTION
1-1 PRELIMINARY COMMENTS AND SAFETY PRE­CAUTIONS
This technical document is intended to cover most aspects associated with the installation, application, operation and maintenance of the VCP-W and VCP-WR Vacuum Circuit Breakers. It is provided as a guide for authorized and qualified personnel only. Please refer to the specific WARNING and CAUTION in Section 1-1.2 before proceeding. If further information is required by the purchaser regarding a particular installation, application or maintenance activity, a Eaton representative should be contacted.
1-1.1 WARRANTY AND LIABILITY IN FORMATION
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information and descriptions contained herein.
1-1.2 SAFETY PRECAUTIONS
All safety codes, safety standards and/or regulations must be strictly observed in the installation, operation and maintenance of this device.
ING IS SHOWN ABOVE IN REVERSE TYPE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW.
CAUTION
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED PERSONS SHOULD BE PERMIT-TED TO PERFORM ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUIPMENT DAMAGE.
1-2 GENERAL INFORMATION
The purpose of this book is to provide instructions for unpacking, storage, use, operation and maintenance of Type VCP-W Drawout and Type VCP-WR Fixed 38kV Vacuum Circuit Breakers. They are similar in many ways with the main differences centering around the secondary/primary connection methods and the mounting methods used. The differences are specifically addressed in this book. The Type VCP-W is a horizontal drawout, roll on the floor type removable interrupter element. The Type VCP-WR is a fixed interrupter element with the customer responsible for all required operational and safety interfaces. Designed to ANSI Standards for reliable performance, ease of handling, and simplified maintenance, VCP-W and VCP-WR circuit breakers provide reliable control and protection for electrical equipment and circuits. In addition, these technologically advanced circuit breakers provide higher insulation levels in less space, thus reducing the overall switchgear size.
WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PROCEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEAD-
Effective 09/2014
WARNING
SATISFACTORY PERFORMANCE OF THESE BREAKERS IS CONTINGENT UPON PROPER APPLICATION, CORRECT INSTALLATION AND ADEQUATE MAINTENANCE. THIS INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL LIFE OF THE CIRCUIT BREAKERS.
Page 2 I.B . 3A74792H08
A
A
WARNING
THE CIRCUIT BREAKERS DESCRIBED IN THIS BOOK ARE DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS. OPERATION
EQUIPMENT TO FAIL, RESULTING IN DEATH, BODILY INJURY AND PROPERTY DAMAGE. ALL SAFETY CODES, SAFETY STANDARDS AND/OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO.
OUTSIDE OF THESE RATINGS MAY CAUSE THE
1-3 TYPE VCP-W AND VCP-WC VACUUM CIRCUIT BREAKER RATINGS (TABLES 1.1 AND 1.2)
Table 1.1 Type VCP-W Ratings on Symmetrical Current Rating Basis
Identification Rated Values
Circuit
Breaker
Type
380 VCP-W 16
and
380 VCP-WR 16
380 VCP-W 25
and
380 VCP-WR 25
380 VCP-W 32
and
380 VCP-WR 32
380 VCP-W 21
and
380 VCP-WR 21
380 VCP-W 40
and
380 VCP-WR 40
Nominal Voltage
Class
kV rms kV rms kV rms kV rms kV Peak Amperes rms kA rms %
34.5 38 1 38 80 170
34.5 38 1 38 80 170
34.5 38 1 38 80 170
34.5 38
34.5 38 1 38 80 170
Voltage Insulation Level Current
Voltage
Maximum
Voltage
V
Range Factor
K
1.65
V/K
23
Power Frequency (1 Minute)
Withstand Test
Lightning
Impulse
1 .2x50 µs
80 170
Continuous
Current
at 60 Hz
600 1200 1600 2000
600 1200 1600 2000
600 1200 1600 2000
3000FC
2500 1200
2000
3000FC
2500
1200 2000
3000FC
2500
Sym. Inter-
rupting
ponent
at V
(Isc)
16 47 1.2 19.2 16 19.3 43 26 16 3
25 47 1.2 30.0 25 30.0 68 40 25 3
31.5 47 1.2 37.8 31.5 37.8 85 50 31.5 3
21 47 1.2 39.5
40 47 1.2 48.0 40 48.0 107 63 40 3
% dc Com-
(Idc)
sym.
Factor
S
(ref.)

Short Circuit Current
sym.
Max. Sym.
Inter-
Inter-
rupting
rupting
(It)
at V/K
(KxIsc)
kA rms
Total kA rms
35
Max. Asym.
(SxKxIsc)
Closing
Inter-
rupting
at V/K
and
Latching
Capability
Momentary
Withstand Capability
Current
Short Time
Current
kA rms
Total kA Peak
42.0 95 56 35 3
kA rms
Total kA rms s
KEMA tested to applicable standards ANSI C37.04 - 1979, C3 7.09 - 1979, C37.06 - 1997 (ope rating Duty Seque nce CO - 15s - CO). Typical operating time values: opening 45 ms, closing 75 ms, and reclosing 300 ms
(18 cycles).
K=1 .0, therefore E=E/K and I=KI, refer to the Consulting Application Catalog for further information. Rated and Tested also for Rapid Re-closing Capability O - 0.3s - CO. Not rated for Rapid Re-closing.
At 23kV rms (Rated Max Voltage/K), Rated maximum symmetrical interrupting capability = 35kA rms (K x I). For Force Air Cooled Fixed Breaker Applications, consult Eaton. The ANSI C37.06 Standard requires 150kV BIL. If higher BIL levels are required, please refer to the “C” breakers.
If you require 50 ms (3 cycle) interrupting time, please refer to the “C” breakers. The Standard Breaker is not rated for capacitor switching. If you require capacitor switching, please refer to the “C” breakers.
Duration
of Short Time
Current
T
A B L E C O N T
I N U E D
F R O M
N E X T
P A G
E
Effective 09/2014
I.B. 3A74792H08 Page 3
Table 1.1 Type VCP-W Ratings (continued from previous page)
Rate
T
A B L E C
O
N T
I N U E D
F R
O M
P R E V
I
O
U S
P A
G
E
Values
Operating Duty
(Duty Cycle)
CO - 15s - CO 100 83 5 2 0.6 2000
CO - 15s - CO 100 83 5 2 0.6 2000
CO - 15s - CO 100
CO - 15s - CO
CO - 15s - CO
CO - 15s - CO
Rated
Reclosing
Factor R
Interrupting
Time
% ms Cycles Seconds kV/µs
83
83
100
Maximum
Transient
Permissible
Recovery
Tripping
Delay
5
2
5
2
Mechanical
Voltage
Endurance
(RRRV)
No-Load
Operations
0.6 2000
0.6 2000
CO - 15s - CO
83 5 2 0.6 2000
Effective 09/2014
Page 4 I.B. 3A74792H08
A
A
A
A
Table 1.2 Type VCP-WC Ratings on Symmetrical Current Rating Basis
Identification Rated Values
Circuit
Breaker
Type
380 VCP-W 16C
and
380 VCP-WR 1 6C
380 VCP-W 25C
and
380 VCP-WR 25C
380 VCP-W 32C
and
380 VCP-WR 32C
380 VCP-W 21 C
and
380 VCP-WR 21C
380 VCP-W 40C
and
380 VCP-WR 40C
KEMA tested to applicable standards ANSI C37.04 - 1979, C37.09 - 1979, C37.06 - 1997 (operat ing Duty Seque nce CO - 1 5s - CO). Typical operating time values: opening 45 ms, closing 75 ms, and reclosing
300 ms (18 cycles).
K=1 .0, therefore E=E/K and I=KI, refer to the Consulting Application Catalog for further information. Rated and Tested also for Rapid Re-closing Capability O - 0.3s - CO. Not rated for Rapid Re-closing.
At 23kV rms (Rated Max Voltage/K), Rated maximum symmetrical interrupting capability = 35kA rms (K x I). For Force Air Cooled Fixed Breaker Applications, consult Eaton.
Voltage
Nominal
Maximum
Voltage
V
Voltage Factor
Voltage
Class
kV rms kV rms kV rms kV rms kV Peak Amperes rms kA rms %
34.5 38 1 38 80 170
34.5 38 1 38 80 170
34.5 38 1 38 80 170
34.5 38
34.5 38 1 38 80 170
Range
K
1.65
Insulation Level Current
Withstand Test
V/K
23
Power Frequency (1 Minute)
Impulse 1 .2x50 µs
80 170
Lightning
Continuous
Current
at 60 Hz
600 1200 1600
2000
600 1200 1600
2000
600 1200 1600 2000
3000FC
2500 1200
2000
3000FC
2500
1200 2000
3000FC
2500
Sym.
% dc
Com-
ponent
(Idc)
sym.
Factor
S
(ref.)
rupting
kA rms
Inter-
Total kA rms
Inter-
rupting
at V (Isc)
16 75 1.46 23.3 16 23.3 50 30 16 3.09
25 65 1.36 34.0 25 34.0 75 44 25 3.09
33.1 57 1.28 42.5 33.1 42.5 91 54 31.5 3.09
21 52 1.24 26.1
40 63 1.34 53.5 40 53.5 107 65 40 3.04
sym.
(It)
Short Circuit Current
Max. Sym.
Max. Asym.
Inter-
rupting
at V/K
(KxIsc)
35
Closing
Inter-
rupting
at V/K
(SxKxIsc)
kA rms
Total kA Peak
43.4 102 60 35 3.21
and
Latching
Capability
Momentary
Withstand Capability
Short
Current
Time
Current
kA rms
Total kA rms
Duration
of
Short
T
B L E
C O N T I N U E D
F R O M
N E X T
P
G E
Effective 09/2014
I.B. 3A74792H08 Page 5
Table 1.2 Type VCP-WC Ratings (continued from previous page)
Rated Values
T
A
Operating Duty
B
(Duty Cycle)
L E C O N
T
I
N
CO - 15s - CO
U E D
F
CO - 15s - CO 100 50 3 2
R O M
N
CO - 15s - CO
E X
T
CO - 15s - CO
P
CO - 15s - CO 100
A G
CO - 15s - CO
E
CO - 15s - CO
Capacitor Switching Rating
Maximum
Tripping
Delay
2
2
Transient Recovery
Voltage (RRRV)
0.7
1.3
0.7
1.3
0.7
0.7
0.7
1.3
1.3
0.7
0.7
1.3
1.3
0.7
Rated
Reclosing
Factor R
Interrupting
Time
% ms Cycles Seconds kV/µs
100 50 3 2
100 50
53
50
50 3 2 0.7 15000 — — 53 — —
3
3
Permissible
Mechanical Endurance
Operations kA rms A rms A rms A rms A rms kA Peak kHz
No-Load
15000
15000
15000
15000
Out-of-
Phase
Overhead
Switching
Line
Current
8.4
8.4
8.4
8.3
8.4
8.4
8.4
8.3
8.4
8.4
8.4
8.3
8.3
8.4
8.3
8.3 — — 53 — —
Charging
Current
5 56
5 56
5 53
5 53
Cable
Current
Isolated
Shunt
Capacitor
Bank
Current
250 250 250
250 & 1000
250 250 250
250 & 1000
250 250
250 250 & 1000 250 & 1000
250 250 & 1000 250 & 1000
Definite Purpose
Back to Back Capacitor Switching
Bank
Inrush
Current
20 20 20
20 & 20
20 20 20
20 & 20
20 20
20 20 & 20 20 & 20
20 20 & 20 20 & 20
Capacitor
Current
250 250 250
250 & 1000
250 250 250
250 & 1000
250 250
250 250 & 1000 250 & 1000
250 250 & 1000 250 & 1000
Inrush
Frequency
4.4
4.4
4.4
5 & 5
4.4
4.4
4.4
5 & 5
4.4
4.4
4.4 5 & 5 5 & 5
4.4 5 & 5 5 & 5
Effective 09/2014
Page 6
1-4 OUTLINES AND DIMENSIONS
I.B. 3A74792H08
Figure 1-1 Type VCP- W 38kV Drawout Circuit Breaker Outlines and Dimensions (inches and [mm])
Effective 09/2014
I.B. 3A74792H08 Page 7
Effective 09/2014
Page 8 I. B. 3A74792H08
Figure 1-2 Type VCP- WR 38kV Fixed Circuit Breaker Outlines and Dimensions (inches and [mm])
SECTION 2: SAFE PRACTICES
2-1 RECOMMENDATIONS
Type VCP-W and VCP-WR Vacuum Circuit Breakers are equipped with high speed, high energy operating mechanisms. They are designed with several built-in interlocks and safety features to provide safe and proper operating sequences. Cell interlocks used with drawout circuit breakers are meant to interact with the appropriate cell interface and levering mechanism.
WARNING
TO PROTECT THE PERSONNEL ASSOCIATED WITH INSTALLATION, OPERATION, AND MAINTENANCE OF THESE CIRCUIT BREAKERS, THE FOLLOWING PRACTICES MUST BE FOLLOWED:
Only qualified persons, as defined in the National
Electrical Safety Code, who are familiar with the installation and maintenance of medium voltage circuits and equipment, should be permitted to work on these circuit breakers.
Read these instructions carefully before attempting any
installation, operation or maintenance of these circuit breakers.
If the final breaker design is drawout, always remove
the breaker from the enclosure before performing any maintenance. If the breaker is applied in a fixed con­figuration, always make sure that primary and secondary power are disconnected from the breaker. Failure to do so could result in electrical shock leading to death, severe personal injury or property damage.
Do not work on a drawout circuit breaker with a
secondary test coupler engaged. Failure to disconnect the test coupler could result in an electrical shock leading to death, personal injury or property damage.
Do not work on a closed circuit breaker or a
breaker with closing springs charged. The closing springs should be discharged and the main circuit contacts open before working on the circuit breaker. Failure to do so could result in cutting or crushing injuries.
Do not use an open circuit breaker by itself as the
sole means of isolating a high voltage circuit. Remove the circuit breaker to the Disconnect position and follow all lock-out and tagging rules of the National Electrical Code and any other applicable codes, regulations and work rules.
Do not leave a drawout circuit breaker in an
intermediate position in the cell. Always have the circuit breaker either in the Disconnect/Test or Connected position. Failure to do so could result in a flash over and possible death, personal injury or property damage.
• Always remove the maintenance tool from the circuit breaker after charging the closing springs.
• Circuit breakers are equipped with safety
interlocks. Do Not remove, interfere with or in any
manner defeat them. This may result in death, bodily injury or equipment damage.
Do not work on a circuit breaker suspended from a
lifting yoke or chains. Maintenance work should be per-formed on a solid work surface, such as the floor.
Effective 09/2014
I.B. 3A74792H08 Page 9
SECTION 3: RECEIVING, HANDLING AND STORAGE
3-1 GENERAL
Type VCP-W and VCP-WR Vacuum Circuit Breakers are subjected to complete factory production tests in accordance with ANSI C37.09 and inspection before being packed. They are shipped in packages designed to provide maximum protection to the equipment during shipment and storage and at the same time to provide convenient handling. Tools and accessories, such as the maintenance tool, are shipped separately.
3-2 RECEIVING
If the circuit breaker is not to be used immediately but is to be placed in storage, maximum protection can be obtained by keeping it packed as shipped.
Upon receipt of the equipment, inspect the containers for any signs of damage or rough handling. Open the containers carefully to avoid any damage to the con­tents. Use a nail puller rather than a crow bar when required. When opening the containers, be careful to save any loose items or hardware that may be other­wise discarded with the packing material. Check the contents of each package against the packing list.
Examine the circuit breaker for any signs of shipping damage such as broken, missing or loose hardware, damaged or deformed insulation and other components. File claims immediately with the carrier if damage or loss is detected and notify the nearest Eaton Office.
NOTICE
The VCP-W and VCP-WR 38kV shipping container and pallet were specifically designed to facilitate removal of the circuit breaker from its pallet and container. Before proceeding, installation personnel should be familiar with the procedures outlined in Paragraph 3-3 entitled “Handling.”
3-3 HANDLING
FOR OPENING, CLOSING THE CONTACTS OR CHARGING THE SPRINGS. THE CIRCUIT BREAKER MAY SLIP OR FALL CAUSING SEVERE PERSONAL INJURY. ALWAYS PERFORM MAINTENANCE, REPAIR AND ADJUSTMENTS ON A SOLID WORK SURFACE CAPABLE OF SUPPORTING THE CIRCUIT BREAKER.
VCP-W and VCP-WR 38kV Vacuum Circuit Breakers are shipped mounted to a skid specially designed to
facilitate removal of the breaker. Refer to Figures 3-1 and 3-2 and proceed with the following steps:
WARNING
AFTER REMOVING THE BRACKETS USED TO HOLD THE CIRCUIT BREAKER SECURELY TO THE SHIPPING SKID AND ALL DURING THE PROCESS OF MOVING THE CIRCUIT BREAKER OFF OF THE SHIPPING SKID AND DOWN THE RAMP TO THE FLOOR, TAKE SPECIAL PRECAUTIONS TO INSURE THAT THE CIRCUIT BREAKER IS MOVED SLOWLY AND UNDER CONTROL TO AVOID ANY ACCIDENTS. THE CIRCUIT BREAKER IS A LARGE DEVICE WHICH COULD CAUSE SERIOUS BODILY INJURY IF IT IS TIPPED OVER OR PERMITTED TO ROLL IN AN UNCONTROLLED MANNER.
CAUTION
DO NOT PULL ON OR USE THE MAIN (PRIMARY) CONDUCTORS AND OR THE PRIMARY DISCONNECTS TO MANEUVER THE CIRCUIT BREAKER IN ANY FASHION. FAILURE TO COMPLY WITH THIS CAUTION COULD RESULT IN SIGNIFICANT EQUIPMENT DAMAGE.
WARNING
DO NOT USE ANY LIFTING DEVICE AS A PLAT­FORM FOR PERFORMING MAINTENANCE, REPAIR OR ADJUSTMENT OF THE CIRCUIT BREAKER OR
Effective 09/2014
Page 10 I.B. 3A74792H08
Figure 3-1 Circuit Breaker Shown Mounted with Ramp Still in Shipping Position (VCP-W Only)
Step 1: VCP-WR breakers must be lifted from the
shipping pallet. Refer to paragraph 3-5 for the optional lifting yoke used with an overhead lifting device after all shipping hardware used to hold the breaker to the skid is removed.
Step 2: For VCP-W breakers, remove the vertically
mounted ramp from the shipping skid and place it on the floor next to the skid. It should be positioned with the highest part of the ramp next to the side of the skid with the front of the circuit breaker.
Step 3: Remove the shipping brackets used to hold
the circuit breaker to the skid. Use the same shipping brackets and hardware to attach the ramp to the shipping skid.
Step 4: Slowly move the circuit breaker forward and
down the ramp. Make certain that the circuit breaker moves down the ramp slowly and straight in line with the ramp. Once the circuit breaker is on the floor, it can be easily maneuvered via its integral wheels. VCP-W breakers can also be lifted using the
Figure 3-2 Circuit Breaker Shown Being Moved
Figure 3-3 Optional Fifth Wheel Shown in Use (VCP-W Only)
3.4 STORAGE
If the circuit breaker is to be placed in storage, maxi-
Effective 09/2014
I.B. 3A74792H08 Page 11
optional lifting yoke described in Step 1
mum protection can be obtained by keeping it packed as shipped. Before placing it in storage, checks should be made to make sure that the circuit breaker is free from shipping damage and is in satisfactory operating condition.
3-6 TYPE VCP-W AND VCP-WR VACUUM CIRCUIT BREAKER WEIGHTS (TABLE 3.1)
Table 3. 1 Approximate Circuit Breaker Weights
Rating Pounds
The circuit breaker is shipped with its contacts open and closing springs discharged. The indicators on the front panel should confirm this. Insert the maintenance tool in
the manual charge socket opening (Figure 3-8).
Charge the closing springs by pumping the handle up and down approximately 38 times until a crisp metallic “click” is heard. This indicates that the closing springs are charged and is shown by the closing spring “charged” (yellow) indicator. Remove the maintenance tool. Push the “manual close” button. The circuit breaker will close as shown by the circuit breaker contacts “closed” (red) indicator. Push the “manual trip” button. The circuit breaker will trip as shown by the circuit breaker contacts “open” (green) indicator. After completing this initial check, leave the closing springs “discharged” and circuit breaker contacts “open”.
Outdoor storage is NOT recommended. If unavoidable, the outdoor location must be well drained and a temporary shelter from sun, rain, snow, corrosive fumes, dirt, falling objects and excessive moisture must be provided. Containers should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation. Moisture can cause rusting of metal parts and deterioration of high voltage insulation. A heat level of approximately 400 watts for each 100 cubic feet of volume is recommended with the heaters distributed uniformly throughout the structure near the floor.
Indoor storage should be in a building with sufficient heat and air circulation to prevent condensation. If the building is not heated, the same general rule for heat as for outdoor storage should be applied.
380 VCP-W 16
&
380 VCP-W 16C
380 VCP-WR 16
&
380 VCP-WR 1 6C
380 VCP-W 25
&
380 VCP-W 25C
380 VCP-WR 25
&
380 VCP-WR 25C
380 VCP-W 32
&
380 VCP-W 32C
380 VCP-WR 32
&
380 VCP-WR 32C
380 VCP-W 21
&
380 VCP-W 21C
600 1200 1600 2000
600 1200 1600 2000
600 1200 1600 2000
600 1200 1600 2000
600 1200 1600 2000 2500 3000
600 1200 1600 2000 2500
1200 2000 2500 3000
1070 1080 1090 1140
937 948 958
1025
1070 1080 1090 1140
937 948 958
1025
1070 1080 1090 1140 1182 1182
937 948
958 1025 1064
1080 1140 1182 1182
3-5 TOOLS AND ACCESSORIES
Several tools and accessories, both standard and optional are available for use with the circuit breaker.
Maintenance Tool (Standard): Used to charge closing
springs.
Lifting Yoke (Optional): Used to lift circuit breaker with
overhead lifting device.
Effective 09/2014
380 VCP-WR 21
&
380 VCP-WR 21 C
380 VCP-W 40
&
380 VCP-W 40C
380 VCP-WR 40
&
380 VCP-WR 40C
1200 2000 2500
1200 2000 2500 3000
1200 2000 2500
948 1025 1064
1182 1182 1182 1182
1064 1064 1064
Page 12 I.B. 3A74792H08
Does not include shipping carto n.
Fifth Wheel (Optional): Used to maneuver a circuit breaker on a flat, hard surface (Figure 3-3).
Effective 09/2014
I.B. 3A74792H08 Page 13
Figure 3-4 Front View VCP-W 38kV Drawout Vacuum Circuit Breaker
Effective 09/2014
Loading...
+ 43 hidden pages