Loadbreak Connector
Catalog Data
CA650005EN
Effective February 2015
Supersedes 500-40C June 2008
200 A 25 and 28 kV class insulated
standoff bushing-Canadian Edition
General
Eaton's Cooper Power™ series 200 A, 25 and
28 kV insulated standoff bushing meets the full
requirements of IEEE Std 386
– Separable Insulated Connector Systems and
provides a single loadbreak interface made of high
quality peroxide-cured EPDM rubber. It is used to
isolate and sectionalize energized cable in padmounted cabinets, underground vaults, and other
apparatus. Temporary or permanent parking of
energized 200 A, 25 kV and 28 kV loadbreak elbow
connectors that conform to IEEE Std 386
standard is simplified with use of the insulated
standoff bushing.
The insulated standoff bushing is designed to
be installed in the parking stand mounted on a
transformer or other apparatus. A grounding lug
is provided on the standoff bushing bracket for
attachment of a drain wire to ensure deadfront
construction. When mated with a comparably rated
product, the insulated standoff bushing provides a
fully-shielded, submersible, separable connector for
energized operation.
™
-2006
standard
™
-2006
The standard insulated standoff bushing has a
stainless steel eyebolt with a brass pressure foot.
The molded peroxide-cured EPDM rubber body
is bolted to a stainless steel base bracket using
a galvanized steel holddown ring. A completely
stainless steel bracket assembly is available for
extremely corrosive environments.
Installation
No special tools are required. A clampstick tool is
used to place the standoff bushing in the parking
stand on the front plate of the apparatus. Refer to
Service Information S500-22-1, 200 A 15, 25, and
35 kV Class Insulated Standoff Bushing Installation
Instructions for details.
Catalog Data CA650005EN
Effective February 2015
200 A 25 and 28 kV class insulated standoff bushing-Canadian Edition
Production tests
Tests conducted in accordance with IEEE Std 386™-2006 standard:
•
AC 60 Hz 1 Minute Withstand
• 25 kV - 40 kV
• 28 kV - 45 kV
•
Minimum Corona Voltage Level
• 25 kV - 19 kV
• 28 kV - 21.5 kV
•
Test Point Voltage Test
Tests conducted in accordance with Eaton requirements:
•
Physical Inspection
•
Periodic Dissection
•
Periodic X-ray Analysis
Table 1. Voltage Ratings and Characteristics
Description 25 kV 28 kV
Standard Voltage Class 25 25
Maximum Rating Phase-to-Ground 15.2 16.2
AC 60 Hz 1 Minute Withstand 40 45
DC 15 Minute Withstand 78 100
BIL and Full Wave Crest 125 125
Minimum Corona Voltage Level 19
Voltage ratings and characteristics are in accordance with IEEE Std 386
™
-2006 standard.
21.5
Ordering information
To order the 25 and 28 kV Insulated Standoff Bushing Kit, refer to
Table 2.
Each kit contains:
•
Insulated Standoff Bushing with Bracket
•
Shipping Cap (not for energized operation)
•
Installation Instruction Sheet
Table 2. Standoff Bushing Kit
Catalog Number
Description
Standoff Bushing with Standard Bracket ISB225 ISB228
Standoff Bushing with Stainless Steel Bracket ISB225S ISB228S
25 kV 28 kV
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Cooperpower.com
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. CA650005EN
Eaton and Cooper Power are valuable
trademarks of Eaton in the U.S. and other
countries. You are not permitted to use these
trademarks without the prior written consent
of Eaton.
IEEE Std 386™-2006 standard is a trademark
of the Institute of Electrical and Electronics
Engineers, Inc., (IEEE). This publication is not
endorsed or approved by the IEEE.
For Eaton’s Cooper Power
series insulated standoff
bushing product information
call 1-877-277-4636 or visit:
www.cooperpower.com.