Eaton 105U-2-5W Installation Manual

Instruction Leaflet IL032004EN
Effective December 2015 Version 2.0
105U-2-5W wireless extension I/O installation guide
Figure 1. Antenna Installation
CAUTION
For continued protection against risk of fire, replace the module fuse only with the same type and rating.
Statutory requirements
Antenna installation
Use Figure 1 as a guide for installing an antenna and attaching it to the module.
Wavelengths: 360 MHz = 32.7" (83 cm)
512 MHz = 22.8" (58 cm)
Surge Arrestor (optional)
105U-2
ELPRO
105U-2 Multi I/O
at least 11 AWG (4 mm
Coaxial Cable
GND
GND
Stress Relief Loop
2
)
Antenna*
1 Wavelength
(minimum)
Weatherproof Connections (recommended:
3M
23 self-
bonding tape)
Mast
Earth Conductor at least 5 AWG
2
)
(16 mm
For maximum
*
range, install above local obstructions.
Provide good ground connection to mast, module, and surge arrestor.
If ground conditions are poor, use more than one stake.
Earth Stake
Instruction Leaflet IL032004EN
Effective December 2015
Version 2.0
105U-2-5W wireless extension I/O installation guide
EATON_105U-2-5W Install Guide
Installation
Choose a power supply option:
12–24Vac, 1.5A CSA certified Class 2 *
15–30Vdc, 1.5A CSA certified Class 2 *
11–15Vdc, 2.0A
Solar panel with battery
After choosing a power supply option, wire the module as shown in Figure 2.
ote:N All I/O must be SELV.
*Backup battery must be used if radio power is set to 2W or higher.
When the wiring is completed, connect the module to a computer (PC) and configure it using the configuration software. For details, refer to the user manual.
Before operating the module, read the sections on operation and configuration in the user manual to take advantage of all product features.
Figure 2. Wiring Diagram
11–15 Vdc Supply or 12V Backup Battery 12 Ah for AC/DC 100 Ah for Solar
-
+
2A
AI 3 +
BAT+
COM
GND
AI 4 +
OUTPUTS
AI 5 +
AI 6 +
Digital Output Max. 30 Vdc, 500 mA DC Relay Supply
DC Load
COM
+24V
DOT
ELPRO
105U-2 Multi I/O
WARNING
EXPLOSION HAZARD
Do not disconnect while circuit is live unless area is known to be non-hazardous.
AC Supply 12–24 Vac Min. 15 Vac for Battery Charging
Do not earth SUP1 or SUP2
connection.
SUP1
SUP2
GND
SOL
12V Solar Panel Supply; Max. 20 Vdc Max. 30 W Panel
SUP1
+
DC Supply 15–30 Vdc Min. 17 Vdc for Battery Charging
To Earth Stake
SUP2
-
1
GND
SOL
Digital Input Voltage-Free Contact or Transistor Device
INPUTS
DI 1
DI 2
DI 3
3
DI 4
COM
4
+AI 1
+24V
+
-
Loop­Powered Analog Transducer
-
+AI 2
-
-
+
External Powered Analog Transducer
Eaton
1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
Eaton’s wireless business
www.eaton.com/wireless
© 2014 Eaton All Rights Reserved Printed in USA Publication No. IL032004EN December 2015
Eaton is a registered trademark.
All other trademarks are property of their respective owners.