Eaton 10000HXL31, 20000HXL31, 15000HXL31 User Manual

Table of Contents
www.eaton.com/dxups
USER MANUAL
ON LINE UPS
10000HXL31/15000HXL31/20000HXL31
Uninterruptible Power Supply
Table of Contents
1. Brief introduction
1.1 System and model description---------------------------------------------------------------------1
1.2 Description of commonly used symbols---------------------------------------------------------2
1.3 Appearance---------------------------------------------------------------------------------------------3
1.4 Product specification and performance----------------------------------------------------------4
General specification
Electric performance
Operating environment
2. Installation
2.1 Unpacking & Inspection-------------------------------------------------------------------------- ---5
2.2 Input and output power cords and protective earth installation----------------------------5
2.3 Operating procedure for connecting the long backup time model UPS with the
external battery ---------------------------------------------------------------------------------------8
2.4 Parallel operation--------------------------------------------------------------------------------------9
3. Operation and operating mode
3.1 Operation------------------------------------------------------------------------------------------------12
3.2 Operating mode--------------------------------------------------------------------------------------- 13
4. Battery maintenance----------------------------------------------------------------------------------17
5. Notes for battery disposal and battery replacement ------------------------------------- 18
6. Trouble shooting --------------------------------------------------------------------------------------19
Appendix 1 Display panel --------------------------------------------------------------------------------21 Appendix 2 The corresponding form of the LED display--------------------------------------22
1. Brief introduction
--1--
1.1 System and model description
This Online Series is an uninterruptible power supply incorporating double-conversion technology. It provides perfect protection specifically for computer equipment, communication systems to computerized instruments.
Its true online double-conversion design eliminates all mains power disturbances. A rectifier converts the alternating current from the utility power to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a pure sinusoidal AC voltage, which is constantly powering the loads.
Computers and Peripherals are thus powered entirely by the UPS. In the event of power failure, the maintenance-free batteries power the inverter.
This manual is designed for the product that the model designation rules as followed:
The description followed in this text is make example with Eaton DX 10000HXL, DX 15000HXL and DX 20000HXL.
This manual is applicable to the following models:
1) The 10000HXL31 is a three-phase input and single-phase output long backup time model, which is able to connect with the external battery bank.
2) The 15000HXL31 is a three-phase input and single-phase output long backup time model, which is able to connect with the external battery bank.
3) The 20000HXL31 is a three-phase input and single-phase output long backup time model, which is able to connect with the external battery bank.
Eaton E Series DX 1000H (X) (XL)
Brand name
UPS series
Output capacity(VA)
Code Batteries internal or external
Nil Standard model with batteries internal
XL
Long backup time model with batteries external
Code
Receptacle and plut type
B
Brazilian type
I
Indian type
... ..
Code
Voltage level
H220/230/240V
L
110 /11 5/1 20V
1. Brief introduction
--2--
1.2 Description of commonly used symbols
The following symbols will be used in this manual and may appear during the course of your practical applications. Therefore, all users should be familiar with them and understand their meanings.
Recyclable
Do not dispose with ordinary trash
1. Brief introduction
--3--
1.3 Appearance
The method, type and appearance of the input socket and output socket are vary with different areas
and different client, the appearance of the products is based on what it is.
BACK VIEW of 10000HXL31
Fan
Cable tying
Intelligent slot
Parallel port
Maintenance switch
RS232
Input breaker
Terminal blocks
Input breaker
Fan
RS232
Cable tying
Terminal blocks
TB cover
Intelligent slot
Parallel port
External battery
socket
Maintenance
switch
BACK VIEW of 15000HXL31/20000HXL31
1. Brief introduction
--4--
1.4 Product specification and performance
General specification
Model 10000HXL31 15000HXL31 20000HXL31
Power Rating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Frequency (Hz) 50/60Hz 50/60Hz 50/60Hz
Voltage (304-478)VAC (304-478)VAC (304-478)VAC
Input
Current 50A max. 75A max. 100A max.
Voltage 240VDC 240VDC 240VDC
Battery
Current 40A max 60A max 80A max
Voltage 220VAC 220VAC 220VAC
Output
Current 45A 68A 91A
Dimension (WxDxH) mm 260x570x717 260x570x717 260x570x717
Weight (kg) 39 55 55
Electrical performance
Input
model Voltage Frequency Power Factor
10000/15000/20000 Three-phase(380VAC/220VAC) 46-54Hz/56-64Hz
>0.95(Full
load)
Output
Voltage Regulation
Power Factor
Frequency
tolerance.
Distortion Overload capacity
Current
crest ratio
±1%
0.7 lag
Synchronized
50/60HZ(±4Hz) in
Line mode (AC
mode)
±0.1% of normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)
105%-130% load transfers to
bypass mode after 10
minutes
>130% load transfers to
bypass mode after 1 second
and shutdown the output after
1 minute
3:1
maximum
Operating environment
Temperature Humidity Altitude Storage temperature
0°C-40°C
<95% <1000m
0°C--40°
Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following :
Altitude(M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating power 100% 95% 91% 86% 82% 78% 74% 70% 67%
2. Installation
--5--
2.1 Unpacking and inspection
1) Unpack the packaging and check the package contents. The shipping package
contains:
A UPS
An user manual
A communication cable
A battery cable (for 10000HXL31 only)
2) Inspect the appearance of the UPS to see if there is any damage during transportation.
Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts.
2.2 Input and output power cords and protective earth ground installation
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a very low temperature environment. In this case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use. Otherwise there are hazards of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. The battery breaker also needs to be cut off if it is a long backup time model (“XL” model).
1) Open the terminal block cover located on the rear panel of the UPS, please refer to the appearance diagram)
2) For 10000HXL31, it is recommended to select the UL1015 8AWG(10mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.
3) For 15000HXL31/20000HXL31, it is recommended to select the UL1015 6AWG(25mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.
2. Installation
--6--
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise, the receptacle may be burned and destroyed.
4) Connect the input and output wires to the corresponding input and output terminals according to the following diagram.
Note: you must make sure that the input and output wires and the input and output terminals are connected tightly
5) The protective earth ground wire refers to the wire connection between the equipment which consumes electric equipment and the ground wire. The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used.
6) After having completed the installation, make sure the wiring is correct.
7) Please install the leak current protective breaker at the output power distribution panel of the UPS if necessary.
8) To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one.
9) No matter the UPS is connected to the utility power or not, the output of the UPS may have electricity. The parts inside the unit may still have hazardous voltage after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility power supply.
10) Suggest charging the batteries for 8 hours before use. After connection, turn the bypass breaker in the “ON” position, the UPS will charge the batteries automatically. You can also use the UPS immediately without charging the batteries first, but the backup time may be less than the standard value.
11) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up power consumption is too big when it is started.