Read the instructions carefully and look at the equipment to become familiar with the device before
trying to install, operate, service or maintain it. The following special messages may appear throughout
this document or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of this symbol to either a “Danger” or “Warning” safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are not
followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
DANGER
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
NOTICE
NOT ICE is used to address practices not related to physical injury.
Product Handling Guidelines
< 18 kg
< 40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
> 55 kg
> 120 lb
Page 2
Safety and General Information
SAVE THESE INSTRUCTIONS –
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damages.
This UPS is intended for indoor use only.
Mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily
accessible.
UPS must be connected to an earthed mains socket outlet.
Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and required precautions. In this case, batteries is not user-replaceable.
When replacing battery the UPS must be OFF, and its AC inlet unplugged.
CAUTIO N Do not dispose of batteries in a fire. The batteries may explode.
CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.
Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin
and eyes.
Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
CAUTIO N A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries.
a. Remove watches, rings or other metal objects.
b.Use tools with insulated handles.
c. Wear rubber gloves and boots.
d.Do not lay tools or metal parts on top of batteries.
e. Disconnect the charging source prior to connecting or disconnecting battery terminals.
f.Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance.
The battery in the Easy UPS Series is not user-replaceable.
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Battery Replacement
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
Replace the battery at least every 5 years.
Replace the battery immediately when the UPS indicates battery replacement is
necessary.
Replace battery at the end of its service life.
Replace batteries with the same number and type of batteries as originally installed in
the equipment.
Replace the battery immediately when the UPS indicates a battery over-temperature
condition, or UPS internal over-temperature, or when there is evidence of electrolyte
leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries.
Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in injury.
The battery in the Easy UPS is not user-replaceable. Contact SEIT Technical Support for a list of
authorized service centers near you.
For the recycling battery information, please go to apc.com/us.
2
Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA
Page 3
Product Description
The APC by Schneider Electric Easy UPS offers power and surge protection for wireless networks,
computers, gaming consoles and other electronics in your home or business. This UPS supply battery
backup during outages and unstable voltage fluctuations, as well as provide protection from damaging
surges and spikes. They are the choice helps to protect your data and keep you connected.
For operation, please place the unit on the floor.
2. Connect the battery by pulling the battery handle up,
and then pushing it into the unit.
3. Connect equipment to the UPS. Avoid using extension cords.
4. Plug the Easy UPS power cord directly into a wall outlet, not into a surge protector or power strip.
5. Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Easy UPS is on and ready to provide protection.
The Easy UPS should charge for at least 24 hours to ensure sufficient runtime. The unit is being
charged whenever it is connected to AC power, whether the unit is turned ON or OFF.
Operational Features
Automatic Voltage Regulation (AVR)
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds levels.
This allows the equipment plugged into the unit to operate during low/high voltage conditions,
conserving the battery power in the event of a power cut.
The Easy UPS will switch to battery power if the input voltage level becomes too low/high for the
Automatic Voltage Regulation to compensate, or if the AC power is distorted.
USB Charging Port for Smartphones and Tablets (only for BVX700LUI models)
This USB charging port provides a maximum of 5V 1 A DC power. The port will charge the connected
equipment when the UPS is on line mode, battery mode and off charging mode.
Quick Mute
The Easy UPS is able to temporarily mute user correctable audible alarms such as On Battery. During
such audible alarms, a short press (less than 2 seconds) of the POWER button will temporarily mute
the audible alarm until the condition has been reset. A short double beep will confirm that Quick Mute
has been activated. Pressing the POWER button for more than 2 seconds will turn off the UPS.
Other events such as Battery replacement and Charger notification can not be temporarily muted. The
unit in these cases must be turned off.
Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA3
Page 4
Features
A
ON/OFF button with indicator
B
Input power cord
C
Battery backup and surge protected outlets
D
Battery connector
Circuit breaker
E
AC power inlet with AC fuse
F
*only for model with IEC/Universal outlet
G
USB charger port(only for BVX700LUI Models)
Model
Output
Type and
Quantity
Fuse
Circuit
Breaker
BVX700LUI
A
G
Model
Output Type
and Quantity
Fuse
Circuit Breaker
C
BVX700LI
BVX900LI
BVX700LI-GR
BVX700LUI-GR
BVX900LI-GR
x 4 x 2
C
D
BVX700LUI-AR
BVX900LI-AR
x 2
C
x 2
D
E
BVX700BVX900
BVX1200LI
BVX1600LI
BVX2200LI
x 6
F
BVX1200LI-GR
BVX1600LI-GR
BVX2200LI-GR
B
BVX1200LI-MS
x 4
C
BVX700LUI-MS
CC
x 4x 1
D
F
BVX900LI-MS
x 2x 1
D
E
B
D
F
BVX1200
IE C jump er Cabl e for PC c onnec tion (1 .2m)
*only f or th e model w ith IE C outl et
4
Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA
D
C
E
B
BVX1600LI
D
C
F
BVX2200LI
D
C
F
E
BVX1600
BVX2200
D
C
E
B
Page 5
Specifications
Model
Input
Output
Protection
Battery
Physical
Temperature
IP Rating
* The length of input power cord is 1.2m. For best operation, do not use output cable longer than 2m.
Voltage
Frequency
Brownout Transfer
Over-voltage Transfer
UPS Capacity (total)
Voltage On Battery
Frequency - On Battery
Transfer Time
USB Charger Port
AC Input
Circuit Breaker
(only for GR and AR
models)
The battery typically lasts for three to five years.
Environmental factors impact battery backup life.
Elevated temperatures, high humidity, poor quality mains power,
and frequent, short duration discharges will shorten battery life.
The battery in the Easy UPS Series is not user-replaceable.
Contact SEIT Technical Support for a list of authorized service
centers near you.
13.8 x9.8 x 31
4.5 kg
22.2 x 14.2 x 34.6
BVX 90 0L I BVX 12 00 LI B VX1600 L I B VX2200 L I
220-240 Vac
50 Hz or 60 Hz (auto-sensing)
140 Vac
300 Vac
900VA/480W 1200VA/650W 1600VA/900W
230 Vac ±10%
50 Hz / 60 Hz ± 0.5Hz
6ms typical, 10ms max.
T 8A L 250Vac
12V, 9AH x 1
lead acid
16 x12 x 35.5
6.5 kg
25 x 19.7 x 43
T 10A L 250Vac T 12A L 250Vac T 15A L 250Vac
12V, 9AH x 1
lead acid
8 Hours
6.0 kg4.2 kg7.5 kg10.2 kg
8.5 kg
0 °C to 40 °C
12V, 7AH x 2
lead acid
19 x14 x 39
29.7 x 23.5 x 49.5
IP20
2200VA/1200W
12V, 9AH x 2
lead acid
12.2 kg
13.2 kg11.2 kg
Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA
5
Page 6
Status Indicators
LED
On
On
(Off during 4 beeps)
FlashingConstant beeping
Off
Audible Al arm
Off
Constant Tone
Constant beeping
(every 1/2 second)
4 beeps repeated
every 30 seconds
(every 1/2 second)
Constant tone
Short beep every
4 seconds
Constant Tone
Condition
On-line - The Easy UPS is supplying AC power to the
connected equipment
On Line Overload - The power being used by the connected
equipment has exceeded the capacity of the unit.
Disconnect some equipment.
Over-temperature Detected - The unit is overheating and will
operate in AVR mode for 1 minute. The Easy UPS will shut
down if the temperature is not lowered. Disconnect some of the
connected equipment.
On-Battery - The Easy UPS is supplying battery power.
Low Battery - The EasyUPS is supplying battery power
and the battery is near a total discharge state.
Replace Battery Detected - The battery needs to be charged,
or is at end of life.
Note:
- If the battery is disconnected, unplug the Easy UPS from AC
source and then turn it off. Refer to the section “Place and Power On” on page 3.
- If battery needs replacement, refer to the section “Battery Replacement” on page 2 for details.
Low Battery Shutdown - During On Battery operation
the battery power was almost completely exhausted, and the
Easy UPS is waiting for AC power to return to normal.
On Line Overload Fault - The connected equipment requires
more power than provided by the Easy UPS.
Unplug devices one at a time to remove overload.
If the detected problem is not corrected, contact SEIT Technical
Support
Charger Detected Fault - Easy UPS has an internal
problem detected, and is no longer powering the load.
Contact SEIT Technical Support
Long beep every
4 seconds
6
Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA
Over-temperature Detected Fault - The Easy U PS has
overheated and has shut down. Unplug connected devices
one at a time or wait for a few hours for system to cool down.
Page 7
Troubleshooting
Detected Problem and Possible Cause
The Easy UPS will not turn on
The Easy UPS has not been turned on.
The Easy UPS is not connected to AC
power, there is no AC power available at the
wall outlet, or the AC power is experiencing a
brownout or over voltage condition.
The battery is disconnected.
Connected equipment loses power
A Easy UPS overload condition has
occurred.
The Easy UPS battery is completely
discharged.
Connected equipment does not accept the
step-approximated sine waveform from the
Easy UPS.
The Easy UPS may require service.
The ON/OFF button is green and flashing every 30 seconds. 4 beeps repeated every 30 seconds.
The Easy UPS is operating on battery
power.
The ON/OFF button flashes green and constant beeps every 1/2 second.
The Easy UPS battery has
approximately. empty and will shutdown
The Easy UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful life and
should be replaced.
The UPS and outlets are but the UPS keeps beeping once every 4 seconds. The alarm offaudible
will mute after 32 seconds.
The UPS have shut down due to low battery,
but control power exists.
Press the ON/OFF button.
Make sure the power cord is securely connected to the
wall outlet, and that there is AC power available at the
wall outlet. Where applicable, check that the wall
outlet is switched on.
Refer to the “Place and Power On” on page 3.
Remove all nonessential equipment connected to the
outlets. One at a time reconnect equipment to the
Easy UPS.
Charge the battery for 24 hours to make sure it is fully
charged. If the overload condition still occurs, replace
the battery.
Connect the Easy UPS to AC power and allow
the battery to recharge for ten hours.
The output waveform is intended for computers and
peripheral devices. It is not intended for use with motor
driven equipment.
Contact Schneider Electric Technical Support for
more in depth troubleshooting
The Easy UPS is operating normally on battery
power. At this point the user should save all open files,
and shutdown the computer. When AC power is
restored the battery will recharge.
The Easy UPS battery is near a total discharge
state. At this point the user should save all open files,
and shutdown the computer. When AC power is
restored the battery will recharge.
Leave the Easy UPS connected to AC power for
ten hours while the battery charges to full capacity.
As a battery ages, the runtime capability decreases.
The UPS will return to normal operation once the
AC input voltage has returned to a normal range.
Solution
7Easy UPS BVX Series 700VA, 900VA, 1200VA, 1600VA, 2200VA
Page 8
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by
Schneider Electric website, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit.
b.Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If
this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d.Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
website for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam
beads for packaging. Damage sustained in transit is not covered under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department
of Transportation (DOT), and the International Air Transport Association (IATA) regulations
require that UPS batteries be disconnected before shipping. The internal batteries may remain in
the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace
the original unit with a factory reconditioned unit. Customers who must have the original unit back due
to the assignment of asset tags and set depreciation schedules must declare such a need at first contact
with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective
unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card
number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs
to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric website, www.apc.com.