This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damages.
This UPS is intended for indoor use only.
Mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily
accessible.
UPS must be connected to an earthed mains socket outlet.
HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
CAUTION
Battery must be replaced when they reach end of service life.
Batteries must be replaced when the unit indicates battery replacement is necessary.
When replacing batteries, replace with the same number and type of batteries originally installed in the unit.
Failure to follow these instructions can result in minor or moderate injury and
equipment damage.
Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and required precautions.
When replacing battery the UPS must be OFF, and its AC inlet unplugged.
CAUTION Do not dispose of batteries in a re. The batteries may explode.
CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.
Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin
and eyes.
CAUTION A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries.
a. Remove watches, rings or other metal objects.
b.Use tools with insulated handles.
c. Wear rubber gloves and boots.
d.Do not lay tools or metal parts on top of batteries.
e. Disconnect the charging source prior to connecting or disconnecting battery terminals.
f.Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
For operation, please place the unit on the floor.
2. Connect the battery by pulling the battery handle up,
and then pushing it into the unit.
3. Connect equipment to the UPS. Avoid using extension cords.
4. Plug the Easy UPS power cord directly into a wall outlet, not into a surge protector or power strip.
5. Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Easy UPS is on and ready to provide protection.
The Eas y UPS sho uld cha rge f or at lea st 6 hour s to ensu re suff icient runtime. The unit i s
being c harged whe never i t is conn ected t o AC power, whether the unit is turned ON or OFF.
Features
A
ON/OFF button with indicator
B
Input power cord
*only for model with Schuko outlet
C
Battery backup and surge protected outlets
Battery connector
D
Circuit breaker
E
*only for model with Schuko outlet
AC power inlet with AC fuse
F
Model
Output Type
and Quantity
BV500I
BV650I
BV800I
BV1000I
BV500I-GR
BV650I-GR
BV800I-GR
BV1000I-GR
BV500I-MS
BV650I-MS
BV800I-MS
BV1000I-MS
NEMA jumper Cabl e for P C con nec tio n
*only for th e mod el wi th Un ive rsal outlet
2
Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA
x 6
x 4
x 4
A
F
IEC jumper C abl e for P C con nec tion
*only for th e mod el wi th IE C out let
C
B
E
D
Page 3
Specifications
Model
Input
Output
Protection
Battery
Physical
Voltage
Frequency
Brownout Transfer
Over-voltage Transfer
UPS Capacity (total)
Voltage On Battery
Frequency - On Battery
Transfer Time
AC Input
Circuit Breaker*
(*only for model with
Schuko outlet)
AC Input Fuse
Type
(maintenance-free)
Average Life
Typical Recharge Time
Net Weight
Dimensions (Hx Wx D)
BV500 IBV650 IBV 800IBV100 0I
230 VAC
50 Hz or 60 Hz
170 VAC, typical
280 VAC, typical
500VA / 300W
5A5A7A7A
5A5A10A10A
12V, 4.5AH
lead acid
The battery typically lasts for three to ve years.
Environmental factors impact battery life.
Elevated temperatures, high humidity, poor quality mains power,
and frequent, short duration discharges will shorten battery life.
The battery in the Easy UPS Series is not user-replaceable.
Contact SEIT Technical Support for a list of authorized service
centers near you.
650VA / 375W 800VA / 450W 1000VA / 600W
230VAC 10%±
50 Hz / 60 Hz ± 1Hz
6ms typical
12V, 7AH
lead acid
4.5 kg3.9 kg5.3 kg5.7 kg
9.25 cm x 16.05 cm x 30.5 cm
6-8 Hours
12V, 7AH
lead acid
12V, 9AH
lead acid
Wall Mount Installation
Horizontal installation, use 2 screws 11.1"(282 mm) apart.
Allow 5/16'’ (8 mm), of the screw to protrude from the wall.
11.1 in.
282 mm
Wall-mounting Template
Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA
3
Page 4
Status Indicators
LED
On
On
(Off during 4 beeps)
FlashingConstant beeping
Off
Audib le Alarm
Off
Constant Tone
Constant beeping
(every 1/2 second)
4 beeps repeated
every 30 seconds
(every 1/2 second)
Constant tone
Short beep every
4 seconds
Constant Tone
Condition
On-line - The EasyUPS is supplying AC power to the
connected equipment
On Line Overload - The power being used by the connected
equipment has exceeded the capacity of the unit.
Disconnect some equipment.
Over-temperature - The unit is overheating and will operate
in AVR mode for 5 minutes. The Easy UPS will shut down if
the temperature is not lowered. Disconnect some of
the connected equipment.
On-Battery - The Easy UPS is supplying battery power.
Low Battery - The EasyUPS is supplying battery power and
the battery is near a total discharge state.
Bad Battery Detected - The battery needs to be charged,
or is at end of life.
Low Battery Shutdown - During On Battery operation
the battery power was almost completely exhausted, and the
Easy UPS is waiting for AC power to return to normal.
On Battery Overload - The connected equipment requires
more power than provided by the Easy UPS battery.
Unplug devices one at a time to remove overload.
If the problem is not corrected, contact SEIT Technical
Support
Charger Detected Fault - Easy UPS has an internal problem,
and is no longer powering the load.
Contact SEIT Technical Support
Long beep every
4 seconds
Over-temperature Protected - The Easy UPS has
overheated and has shut down. Unplug connected devices
one at a time or wait for a few hours for system to cool down.
Operational Features
Automatic Voltage Regulation (AVR)
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds levels.
This allows the equipment plugged into the unit to operate during low/high voltage conditions,
conserving the battery power in the event of a power cut.
The Easy UPS will switch to battery power if the input voltage level becomes too low/high for the
Automatic Voltage Regulation to compensate, or if the AC power is distorted.
4
Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA
Page 5
Troubleshooting
Problem and Possible Cause
The Easy UPS will not turn on
The Easy UPS has not been turned on.
The Easy UPS is not connected to AC power,
there is no AC power available at the wall
outlet, or the AC power is experiencing a
brownout or over voltage condition.
The battery is disconnected.
Connected equipment loses power
A Easy UPS overload condition has occurred.
The Easy UPS battery is completely
discharged.
Connected equipment does not accept the
step-approximated sine waveform from the
Easy UPS.
The Easy UPS may require service.
The ON/OFF button is green and ashing every 30 seconds. 4 beeps repeated every 30 seconds.
The Easy UPS is operating on battery power.
The ON/OFF button ashes green and constant beeps every 1/2 second.
The Easy UPS battery has approximately
empty and will shutdown
The Easy UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful life and
should be replaced.
The UPS and outlets are off but the UPS keeps beeping once every 4 seconds. The alarm will
mute after 32 seconds.
The UPS have shut down due to low battery,
but control power exists.
Press the ON/OFF button.
Make sure the power cord is securely connected to the
wall outlet, and that there is AC power available at the
wall outlet.Where applicable, check that the wall
outlet is switched on.
Refer to the Place and Power On on page 2.
Remove all nonessential equipment connected to the
outlets. One at a time reconnect equipment to the
Easy UPS.
Charge the battery for 24 hours to make sure it is fully
charged. If the overload condition still occurs, replace
the battery.
Connect the Easy UPS to AC power and allow the
battery to recharge for ten hours.
The output waveform is intended for computers and
peripheral devices. It is not intended for use with motor
driven equipment.
Contact Schneider Electric Technical Support for
more in depth troubleshooting
The Easy UPS is operating normally on battery
power. At this point the user should save all open les,
and shutdown the computer. When AC power is
restored the battery will recharge.
The Easy UPS battery is near a total discharge state.
At this point the user should save all open les, and
shutdown the computer. When AC power is restored
the battery will recharge.
Leave the Easy UPS connected to AC power for ten
hours while the battery charges to full capacity.
As a battery ages, the runtime capability decreases.
The UPS will return to normal operation once the
AC input voltage has returned to a normal range.
Solution
5Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA
Page 6
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by
Schneider Electric website, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit.
b.Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If
this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d.Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
website for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam
beads for packaging. Damage sustained in transit is not covered under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department
of Transportation (DOT), and the International Air Transport Association (IATA) regulations
require that UPS batteries be disconnected before shipping. The internal batteries may remain in
the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace
the original unit with a factory reconditioned unit. Customers who must have the original unit back due
to the assignment of asset tags and set depreciation schedules must declare such a need at first contact
with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective
unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card
number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs
to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric website, www.apc.com.