Eastron SDM220-MT User guide

Page 1
Eastron SDM220-MT User Manual
- 1 -
Single-Phase Multi-Tariff Energy Meter
Measures 4 TARIFFS kWh/time.
And Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
User Manual V1.8
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
2016
Page 2
Eastron SDM220-MT User Manual
- 2 -
Application
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residential, utility and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) 5A
Max. Current (Imax) 100A
Mini Current (Imin) 0.25A
Starting current 0.4% of Ib
Power consumption <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
100/10/1 imp/kWh/kVarh (configurable)
Display LCD with blue backlit
Max. Reading 99999.99kWh
Specification
Tariff specifications
Tariff number 4
Time segments 10
Clock accuracy ≤0.5S (every 24 hours)
Battery Voltage 3.6V DC, ≥1.2Ah
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 3
Eastron SDM220-MT User Manual
- 3 -
Active energy Class 1 IEC62053-21
Class B EN50470-3
Reactive energy 1% of range maximum
Environment
Operating temperature -25 to +55
Storage and transportation temperature -40 to +70
Reference temperature 23℃±2
Relative humidity 0 to 95%, non-condensing
Altitude up to 2500m
Warm up time 10s
Installation category CAT II
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with total kwh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 36x90x62 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 4
Eastron SDM220-MT User Manual
- 4 -
Item
Descriptions
1
7 digits used to display measured values or RTC
2
Total value
3
Tariff information
4
Import information, Export information
5
Max. Demand for Power or Current
6
Pulse output 1 and Pulse output 2
7
Measurement units
8
PF = power factor Hz = frequency
9
Bar display of Power
10
Communication indicator
11
Time information
12
Low battery warning
13
Lock symbol
LCD display
PART 2
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
Full screen
Scroll display by Button
After initialization and self-checking program, the meter display the measured values. The default page is total
kWh. If the user wants to check other information, he needs to press the scroll button on the front panel.
Operation
software version Modbus ID Baud rate total kWh
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 5
Eastron SDM220-MT User Manual
- 5 -
Page
Display
Descriptions
1
Total active energy
Example:70.00kWh
2 Import(input) active energy
Example: 50.00kWh
3 Export(output)active energy
Example: 20.00kWh
4 T1 active energy
Example: 0.00kwh
5
T2 active energy
Example: 0.00kwh
The display order by scroll button :
Total kWh import kWhexport kWh T1 kwhT2 kwhT3 kwhT4 kwhtotal kvarh
import kVarh export kVarhT1 kvarhT2 kvarh T3 kvarhT4 kvarh Max. power demand
T1 Max. power demand T2 Max. power demand T3 Max. power demand
T4 Max. power demand voltage currentW Var VA power factor frequency
pulse constant Modbus ID baudratedatetimetime segment 1time segment 2
time segment 3time segment 4time segment 5time segment 6time segment 7
time segment 8time segment 9time segment 10
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 6
Eastron SDM220-MT User Manual
- 6 -
6 T3 active energy
Example: 0.00kwh
7 T4 active energy
Example: 0.00kwh
8 Total reactive energy
Example: 10.00kVarh
9 Import(input)reactive energy
Example: 5.00kVarh
10 Export(output)reactive energy
Example: 5.00kVarh
11 T1 reactive energy
Example: 0.00kVarh
12
T2 reactive energy
Example: 0.00kVarh
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 7
Eastron SDM220-MT User Manual
- 7 -
13 T3 reactive energy
Example: 0.00kVarh
14 T4 reactive energy
Example: 0.00kVarh
15
Max Power Demand
Example: 6930W
16 T1 Max. Power Demand
Example:0 W
17 T2 Max. Power Demand
Example:0 W
18 T3 Max. Power Demand
Example:0 W
19
T4 Max. Power Demand
Example:0 W
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 8
Eastron SDM220-MT User Manual
- 8 -
20 Voltage
Example: 229.8V
21 Current
Example: 30.156A
22 Active Power
Example: 4700W
23 Reactive Power
Example: 1030Var
24 Apparent power
Example: 4811VA
25 Power factor
Example: 1.000
26
Frequency
Example: 49.99Hz
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 9
Eastron SDM220-MT User Manual
- 9 -
27 Pulse Constant
Example: 1000
28 Modbus Address
Example: 001
29 Baud rate
Example: 9600
30 Date
FormatDay, Month,Year
Example1st,Jan,2014
31 Time
FormatHour, Minute, Second
Example: 00:02:39
32 Time segment 1
FormatHour, Minute, Tariff Example00:00, Tariff 1
33
Time segment 2
FormatHour, Minute, Tariff
Example02:00 Tariff 2
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 10
Eastron SDM220-MT User Manual
- 10 -
34 Time segment 3
FormatHour, Minute, Tariff
Example04:00 Tariff 3
35 Time segment 4
FormatHour, Minute, Tariff
Example05:00 Tariff 4
36 Time segment 5
FormatHour, Minute, Tariff
Example07:25 Tariff 1
37 Time segment 6
FormatHour, Minute, Tariff
Example08:11 Tariff 2
38 Time segment 7
FormatHour, Minute ,Tariff
Example15:40 Tariff 3
39 Time segment 8
FormatHour, Minute, Tariff Example17:00 Tariff 4
40
Time segment 9
FormatHour, Minute, Tariff
Example10:00 Tariff 1
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 11
Eastron SDM220-MT User Manual
- 11 -
41 Time segment 10
FormatHour, Minute Tariff
Example23:00 Tariff 2
Page
Display
Descriptions
The setting is done correctly
The entering information is wrong. The
operation fails.
1 Password
To get into Set-up mode, it asks a password
confirmation.
Default password: 1000
2 Address ID
Default ID is 001
Range: 001~247
2-1
Press the Enter button, the first digit
flash. Press the Scroll button to change
the value.
After choose the new address value, the
user need pressing the Enter button to
confirm the setting.
Set-up Mode
To get into Set-up Mode, the user need press the “Enter” button for 3 second.
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 12
Eastron SDM220-MT User Manual
- 12 -
3 Baud rate
Default value: 9600bps
Range: 1200, 2400, 4800, 9600bps.
3-1 Press the Enter button, the red digit flash.
Press the Scroll button to change the
value.
After choose the new baud rate, the user
need pressing the Enter button to
confirm the setting.
4 Parity
Default: None
OptionNone, Even, Odd
4-1 Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new Parity, the user need
pressing the Enter button to confirm the
setting.
5 Pulse Output
Default: kWh
Option kWh / KVarh / Imp. Kwh /
Exp.kWh / Imp.kVarh / Exp.kVarh
5-1 Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new Pulse output option,
the user need pressing the Enter button
to confirm the setting.
6
Pulse Constant
Default: 1000
Option: 1000 / 100 / 10 / 1
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 13
Eastron SDM220-MT User Manual
- 13 -
6-1 Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new Pulse constant
option, the user need pressing the Enter
button to confirm the setting.
7 Pulse duration
Default: 100mS
Option: 200 / 100 / 60ms
7-1 Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new Pulse duration
option, the user need pressing the Enter
button to confirm the setting.
8 Demand Integration Time
Default: 15 minutes
Option: 0 / 5 / 10 / 15 / 30 / 60
8-1 Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new DIT option, the user
need pressing the Enter button to
confirm the setting.
9 Automatic Scroll Time Interval
Default: 0 S
Option: 0 ~ 30S
9-1
Press the Enter button, the red part flash.
Press the Scroll button to change the
option.
After choose the new “Scrl” option, the
user need pressing the Enter button to
confirm the setting.
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 14
Eastron SDM220-MT User Manual
- 14 -
10 Password set-up
Default: 1000
10-1
Press the Enter button, the red part flash.
Press the Scroll button to change the
value.
After choose the new password, the user
need pressing the Enter button to
confirm the setting.
11 Date set-up
Press the Enter button to enter the date
set-up page
11-1
Press the Scroll button to change the
value. After choose the new value, the user
need pressing the Enter button to
confirm the setting.
Date format: Day ,Month, Year
12 Time set-up
Press the Enter button to enter the time
set-up page
12-1
Press the Scroll button to change the
value. After choose the new value, the user
need pressing the Enter button to
confirm the setting.
Time format: Hour, Minute, Second
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 15
Eastron SDM220-MT User Manual
- 15 -
Wiring diagram
Dimensions
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 16
Eastron SDM220-MT User Manual
- 16 -
Installation
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883 Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Loading...