Page 1

Eastron SDM220-MT User Manual
SDM220-MT
Single-Phase Multi-Tariff Energy Meter
Measures 4 TARIFFS’ kWh/time.
And Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
User Manual V1.8
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
2016
Page 2

Eastron SDM220-MT User Manual
Application
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residential, utility and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) 5A
Max. Current (Imax) 100A
Mini Current (Imin) 0.25A
Starting current 0.4% of Ib
Power consumption <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
100/10/1 imp/kWh/kVarh (configurable)
Display LCD with blue backlit
Max. Reading 99999.99kWh
Specification
Tariff specifications
Tariff number 4
Time segments 10
Clock accuracy ≤0.5S (every 24 hours)
Battery Voltage 3.6V DC, ≥1.2Ah
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 3

Eastron SDM220-MT User Manual
Active energy Class 1 IEC62053-21
Class B EN50470-3
Reactive energy 1% of range maximum
Environment
Operating temperature -25℃ to +55℃
Storage and transportation temperature -40℃ to +70℃
Reference temperature 23℃±2℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 2500m
Warm up time 10s
Installation category CAT II
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with total kwh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 36x90x62 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 4

Eastron SDM220-MT User Manual
7 digits used to display measured values or RTC
Import information, Export information
Max. Demand for Power or Current
Pulse output 1 and Pulse output 2
PF = power factor Hz = frequency
LCD display
PART 2
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
Full screen
Scroll display by Button
After initialization and self-checking program, the meter display the measured values. The default page is total
kWh. If the user wants to check other information, he needs to press the scroll button on the front panel.
Operation
software version Modbus ID Baud rate total kWh
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 5

Eastron SDM220-MT User Manual
2 Import(input) active energy
3 Export(output)active energy
The display order by scroll button :
Total kWh import kWhexport kWh T1 kwhT2 kwhT3 kwhT4 kwhtotal kvarh
import kVarh export kVarhT1 kvarhT2 kvarh T3 kvarhT4 kvarh Max. power demand
T1 Max. power demand T2 Max. power demand T3 Max. power demand
T4 Max. power demand voltage currentW Var VA power factor frequency
pulse constant Modbus ID baudratedatetimetime segment 1time segment 2
time segment 3time segment 4time segment 5time segment 6time segment 7
time segment 8time segment 9time segment 10
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 6

Eastron SDM220-MT User Manual
9 Import(input)reactive energy
10 Export(output)reactive energy
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 7

Eastron SDM220-MT User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 8

Eastron SDM220-MT User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 9

Eastron SDM220-MT User Manual
Format:Day, Month,Year
Example:1st,Jan,2014
Format:Hour, Minute, Second
Example: 00:02:39
Format:Hour, Minute, Tariff
Example:00:00, Tariff 1
Format:Hour, Minute, Tariff
Example:02:00 Tariff 2
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 10

Eastron SDM220-MT User Manual
Format:Hour, Minute, Tariff
Example:04:00 Tariff 3
Format:Hour, Minute, Tariff
Example:05:00 Tariff 4
Format:Hour, Minute, Tariff
Example:07:25 Tariff 1
Format:Hour, Minute, Tariff
Example:08:11 Tariff 2
Format:Hour, Minute ,Tariff
Example:15:40 Tariff 3
Format:Hour, Minute, Tariff
Example:17:00 Tariff 4
Format:Hour, Minute, Tariff
Example:10:00 Tariff 1
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 11

Eastron SDM220-MT User Manual
Format:Hour, Minute Tariff
Example:23:00 Tariff 2
The setting is done correctly
The entering information is wrong. The
To get into Set-up mode, it asks a password
confirmation.
Default password: 1000
Default ID is 001
Range: 001~247
Press the “Enter” button, the first digit
flash. Press the “Scroll” button to change
the value.
After choose the new address value, the
user need pressing the “Enter” button to
confirm the setting.
Set-up Mode
To get into Set-up Mode, the user need press the “Enter” button for 3 second.
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 12

Eastron SDM220-MT User Manual
Default value: 9600bps
Range: 1200, 2400, 4800, 9600bps.
3-1 Press the “Enter” button, the red digit flash.
Press the “Scroll” button to change the
value.
After choose the new baud rate, the user
need pressing the “Enter” button to
confirm the setting.
Default: None
Option:None, Even, Odd
4-1 Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new Parity, the user need
pressing the “Enter” button to confirm the
setting.
Default: kWh
Option : kWh / KVarh / Imp. Kwh /
Exp.kWh / Imp.kVarh / Exp.kVarh
5-1 Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new Pulse output option,
the user need pressing the “Enter” button
to confirm the setting.
Default: 1000
Option: 1000 / 100 / 10 / 1
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 13

Eastron SDM220-MT User Manual
6-1 Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new Pulse constant
option, the user need pressing the “Enter”
button to confirm the setting.
Default: 100mS
Option: 200 / 100 / 60ms
7-1 Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new Pulse duration
option, the user need pressing the “Enter”
button to confirm the setting.
8 Demand Integration Time
Default: 15 minutes
Option: 0 / 5 / 10 / 15 / 30 / 60
8-1 Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new DIT option, the user
need pressing the “Enter” button to
confirm the setting.
9 Automatic Scroll Time Interval
Default: 0 S
Option: 0 ~ 30S
Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
option.
After choose the new “Scrl” option, the
user need pressing the “Enter” button to
confirm the setting.
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 14

Eastron SDM220-MT User Manual
Press the “Enter” button, the red part flash.
Press the “Scroll” button to change the
value.
After choose the new password, the user
need pressing the “Enter” button to
confirm the setting.
Press the “Enter” button to enter the date
set-up page
Press the “Scroll” button to change the
value. After choose the new value, the user
need pressing the “Enter” button to
confirm the setting.
Date format: Day ,Month, Year
Press the “Enter” button to enter the time
set-up page
Press the “Scroll” button to change the
value. After choose the new value, the user
need pressing the “Enter” button to
confirm the setting.
Time format: Hour, Minute, Second
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 15

Eastron SDM220-MT User Manual
Wiring diagram
Dimensions
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn
Page 16

Eastron SDM220-MT User Manual
Installation
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573-83698881 83698882 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web:
www.eastron.com.cn Email: sales@eastron.com.cn