EAST COAST tr 0301, Temperature differential controller Operating Instructions And Installation Manual

SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE
Operating instructions
Temperature differential controller
3 inputs, 1 output
709.752 | Z02 | 07.50 | Subject to change due to technical improvements!
EN
These operating instructions are part of the product.
  
2
709.752 | 07.50
EN
Contents
1 About this manual ....................... 3
1.1 Applicability .....................................
3
1.2 Users .................................................
3
1.3 Description of symbols ....................
4
2 Safety ............................................ 5
2.1 Proper usage ....................................
5
2.2 Improper usage ................................
5
2.3 Dangers during installation and
commissioning .................................
6
2.4 Detecting faults ................................
7
2.5 Exclusion of liability ..........................
7
3 Description ................................... 9
3.1 Controller in the solar circuit ...........
9
3.2 Casing overview .............................
11
4 Installation ..................................12
4.1 Opening/closing the casing ...........
12
4.2 Mounting .......................................
13
4.3 Electrical connection .....................
14
5 Display overview ........................
18
6 Commissioning
.......................... 19
7 Description of controller
functions ..................................... 20
7.1 Automatic storage tank charging ..
20
7.2 Maximum storage tank
temperature ...................................
21
7.3 Maximum collector temperature ...
21
7.4 Tube collector function ..................
21
7.5 Holiday function ............................
22
7.6 Anti-freeze function .......................
23
8 Operation .................................... 24
8.1 Reading temperature values ..........
24
8.2 Setting the controller .....................
24
9 Maintenance ............................... 29
9.1 Fault causes ....................................
29
9.2 Testing the temperature sensors ....
33
10 Dismantling and disposal ..........
35
11 Legal guarantee ........................
36
12 Technical data .............................
37
3
EN
709.752 | 07.50
1 About this manual
1.1 Applicability
This manual describes the installation, commissioning, operation, maintenance and dismantling of the tem­perature differential controller for solar thermal energy systems. When installing the remaining components, e.g. solar collectors, pump assemblies, storage units, pumps and switching valves, be sure to observe the appropriate installation instructions provided by each manufacturer.
1.2 Users
Installation, commissioning, maintenance and dis­mantling of the controller may only be performed by trained professional personnel. Before commissioning, the controller must be professionally assembled and installed by professional personnel in accordance with the applicable regional and transregional regulations as well as the safety instructions and general instruc­tions within these installation and operating instruc­tions. The professional personnel must be familiar with these operating instructions.
The controller is maintenance-free. Use the controller only after first thoroughly reading
and understanding this instruction manual and the safety instructions. Adhere to all safety instructions. In the event of any ambiguities regarding the operation
4
EN
709.752 | 07.50
and alteration of parameters or functions, consult pro­fessional personnel.
1.3 Description of symbols
1.3.1 The structure of the warning notices
SIGNAL WORD
Type, source and consequences of the danger!
Measures for avoiding danger.
1.3.2 Danger levels in warning notices
Danger level Likelihoodof
occurrence
Consequences resulting from non­compliance
DANGER
Imminent threat of danger
Death, serious bodily injury
WARNING
Possible threat of danger
Death, serious bodily injury
CAUTION
Possible threat of danger
Minor bodily injury
CAUTION Possible threat of
danger
Property damage
1.3.3 Notes
NOTE
Note on easier and safer working habits.
Measures for easier and safer working habits.
5
EN
709.752 | 07.50
1.3.4 Other symbols and markings
Symbol Meaning
Precondition for action
Call to action
Result of action
List
Emphasis on is
-
sue at hand
Emphasis on issue at hand
2 Safety
2.1 Proper usage
The temperature differential controller (called control­ler in the following) may only be used for controlling solar thermal systems within the permissible ambient conditions (see chapter 12).
2.2 Improper usage
The controller must not be operated in the following environments:
outdoors in damp rooms in rooms where highly flammable gas mixtures can
occur in rooms in which the operation of electrical and
electronic components may cause dangers to arise
6
EN
709.752 | 07.50
2.3 Dangers during installation and commis­sioning
The following dangers exist during installation / com­missioning of the controller and during operation (in case of installation errors):
Risk of death by electrocution Risk of fire due to short-circuit Damage to any of the constructional fire safety
measures present in the building due to incorrectly installed cables
Damage to the controller and connected devices due to improper ambient conditions, inappropriate power supply and connecting prohibited devices or faulty devices and incorrect assembly or installation
Therefore, all safety regulations apply when working on the mains supply. Only electricians may perform work that requires opening the controller (such as electrical connection work).
When laying cables, ensure that no damage occurs to any of the constructional fire safety measures present in the building.
Make sure that the permissible ambient condi­tions at the installation site are not exceeded (see chapter 12).
Be sure to comply with the specified protection degree.
Factory labels and markings may not be altered, removed or rendered unreadable.
7
EN
709.752 | 07.50
Before connecting the device, make sure that the power supply matches the specifications on the type plate.
Make sure that all devices which are connected to the controller conform to the technical data of the controller.
Secure the device against unintentional start-up. All work on an open controller must be performed
with the mains supply disconnected. Protect the controller against overloading and
short-circuiting.
2.4 Detecting faults
Check the display regularly. In case of faults, isolate the cause (see chapter 9). As soon as it becomes evident that safe operation
is no longer possible (e.g. visible damage), remove the device from the mains supply immediately.
Have professional personnel remedy the fault.
2.5 Exclusion of liability
The manufacturer cannot monitor the compliance with this manual or the conditions and methods dur­ing the installation, operation, usage and maintenance of the controller. Improper installation of the system may result in damage to property and, as a result, to bodily injury.
Therefore, we assume no responsibility and liability
 
  
8
EN
709.752 | 07.50
for loss, damage or costs which result from or are in any way related to incorrect installation, incorrect execution of installation work, improper operation and incorrect usage and maintenance.
Similarly, we assume no responsibility for patent right or other right infringements of third parties caused by usage of this controller.
The manufacturer reserves the right to make changes to the product, technical data or installation and oper­ating instructions without prior notice.
9
EN
709.752 | 07.50
3 Description
3.1 Controller in the solar circuit
3.1.1 The purpose of the controller
The controller controls the solar thermal system
3.1.2 The structure of the solar circuit
Temperature differential controller
Storage tank
Pump
Temperature sensor 1 (collector sensor)
Temperature sensor 2 (lower area of storage tank)
Collector
T1
T2
Solar circuit
T3
Temperature sensor 3 (upper area of storage tank)
10
EN
709.752 | 07.50
3.1.3 The function of the solar circuit
The controller constantly compares the temperatures between the collector (T1) and the lower area of the storage tank (T2). Once the sun heats the collector and there is a temperature difference of 8 K between the collector and the storage tank, the pump is switched on.
The pump extracts the heat transfer fluid from the lower cooler area of the storage tank and pumps it to the collector. The heat transfer fluid in the collector is heated by the sun and flows back to the storage tank.
The heat transfer fluid heats the domestic water via a heat exchanger located in the storage tank.
11
709.752 | 07.50
EN
3.2 Casing overview
Automatic
On
Off
Operating buttons Arrow up SET button Arrow down
Display
graphic display, animated, for controller operation and system settings
Operating switch
The following modes of operation can be selected:- On for commissioning and testing for function- Automatic for automatic operation
- Off to switch-off the pumps
Connections
Pump, mains grid, temperature sensor
Latches
Operating buttons
Upper casing
Screw
Lower casing
12
EN
709.752 | 07.50
4 Installation
4.1 Opening/closing the casing
DANGER
Risk of death by electrocution!
Remove the controller from the power supply before opening the casing.
Make sure that the power supply cannot be unin­tentionally switched on.
Do not damage the casing. Only switch the power supply back on after the cas-
ing has been closed.
The upper casing is connected to the lower casing by two latches, and fastened with a screw.
4.1.1 Opening the casing
Loosen the screw and remove the upper casing in an upwards direction.
4.1.2 Closing the casing
Place the upper casing over the lower casing at an angle. Insert the latches into the recesses of the lower casing.
Pivot the upper casing down and feed the operat­ing buttons through the matching holes.
Fasten the casing tightly with the screw.
Loading...
+ 26 hidden pages