Read all safety information an d operat ing instru ction s caref ully before atte mpting t o
install, service or maintain the UPS. Save this manual properly for reuse.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space against
the wall for proper ventilation.
Do not open the UPS case as you will, there is a high risk of electric shocks inside.
All connection/wiring/s ervicing must be performed by a qualified electrician.
Do not connect to the equipment like hair dryer or electric heater.
Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is
recommended.
CAUTION
UPS has high voltage inside, do not repair it by yourself. If any questions, please
contact local service center or dealer.
1.2 Battery safety information
Environmental factors impact battery life. Elevated ambient temperatures, poor
quality utility power, and frequent short duration discharges will shorten battery life.
Replacing battery periodically can help to keep UPS in normal state and assure
backup time required.
Battery instal ling or replacing should be performed by a qualified electrician. If you
want to replace the battery cable, please purchase it from our local service center
or distributors to avoid fever and lighter which can cause fire by inadequate power
capacity.
Batteries may cause electric shocks and have a high short ci rcuit current, follow
below requirements before installing or replacing the batteries.
A. Remove wristwatches, rings, jewelry and other conductive materials.
B. Only use tools with insulated grips and handles
C. Wear insulated shoes and gloves
2
D. Do not put the metal tools or parts on the batteries
E. Before disconnecting the terminals from the batteries, cut off all the loads to the
battery first.
Do not dispose of the batteries with fire. The batt er ie s may explode.
Do not open or mutilate batteries. Released electrolyte inside is harmful to the skin
and eyes, and maybe toxic.
Do not connect the positive pole and negative pole directly, otherwise it will cause
electric shocks or wil l be on fire.
The battery circuit is not isolated from the input voltage, high voltage may occur
between the battery terminals and ground, check if there is no voltage there before
touching.
Symbols
Symbol Significations Symbol Significations
Caution
Danger! High Voltage!
Turn on
Turn off
Standby or Shut down
AC
DC
Protective earth
Disable/mute audible
alarm
Overload
Battery inspection
Repeat
Display screen repeat key
Battery
3
frequency
Total voltage harmonic
2 Product Overview
2.1 Specifications
Model 1kVAS 1kVAH 2kVAS 2kVAH
Rated Capacity 1 kVA / 900 W 2 kVA / 1800 W 3 kVA / 2700 W
Battery type Sealed lead acid maintenance free battery
DC voltage
Inbuilt battery
Quantity
Charger output voltage
Recharging time Recover 90% capacit y i n 3 hours for standard models
24 V 36 V 36 V 48 V 72 V 72 V 72 V 96 V 96 V
9 AH
27.1
7 AH
40.7
/
40.7
9 AH
54.2
7 AH
81.3
/
81.3
9 AH
81.3
7 AH
108.4
/
108.4
Charging current
(Max.)
Standard model: 1 A
Long time model: 6 A / 3 A
System Control and Communications
Protections
Over-temp protection; Fan testing protection;
circuit protection; Battery discharge protection
Communication port Standard: RS232; Options: USB, SNMP card, dry contacts
Display LCD
Environmental
Operating humidity 0 ~ 90 % RH @ 0 ~ 40°C (non-condensing)
Storage temperature -25°C ~ 55°C(exclude batteries)
Operating altitude ≤ 1000m, above 1000m, der ate 1% for each rising 100m
Protection class IP 20
Noise level ≤ 50 dBA (at 1m)
Others
Dimensions (mm)
W ×D×H
Weight (kg)
144*336
144*414
144*336
191*418
191*418
191*418
191*418
191*464
*214
*214
*214
*335
*335
*335
*335
*335
9.5 13 6 18 25.8 10.5 27.2 32 11
191*418
*335
* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
Note:
Model Type Model Type
1kVAS 1kVA Standard model 1kVAH 1kVA Long backup model
2kVAS 2kVA Standard model 2kVAH 2kVA Long backup model
3kVAS 3kVA Standard model 3kVAH 3kVA Long backup model
5
2.2 Front panel features
2.3 Rear panel features
a. 1kVAS & 1kVAH rear panel b. 2kVAS &2kVAH & 3kVAS & 3kVAH rear panel
① AC input socket ⑥ RS232 port
② Overcurrent protector ⑦ Intelligent slot
③ Fan ⑧ Surge protection for network / fax / modem
④ USB port ⑨ Output sockets
⑤ EPO (Emergency Power Off) port ⑩ Battery connector
Note:
The figure is for reference only. Due to the technology upgrading and development,
the real unit might be different from the figure.
6
~ 4
3 Installation
3.1 Unpacking inspection
Open the UPS package and inspect the contents upon receipt. The accessories
attached to the UPS contain a power cord, a user manual , communication c able,
CD-ROM. The long backup model also includes the cable for connection to battery
bank.
Check if the unit is damaged during transport. Do not power on and notify the
carrier and dealer if find damaged or parts missing.
Verify this unit is the model you want to buy. Check the model name showed both
on the front panel and rear panel.
Note:
Keep the packaging box and packaging materials for future transport use. The
equipment is heavy. Always handle it with care.
3.2 Installation information
The UPS installation environment must be in good ventilation, away from water,
flammable gases and corrosive entities.
Do not lie down the UPS agai nst the w all so tha t front an d sid e pane l air int ake h ole,
rear panel air outtake hole will be unobs tructed.
The ambient temperature around the UPS should be within 0 ℃
(non-condensing).
If dismantling the machine at low temperatures, there may be condensation
droplets, users can not install or operate it before UPS completely got dry both
inside and outside, otherwise there will be danger of electric shocks.
Place the UPS near the mains source so that can cut off utility power without any
delay in case of emergency.
Make sure the load connected to the UPS is off when users connect it to UPS, and
then turn on the load one by one later.
Connect the UPS with the power outlet which is over-current protected. Do not
connect the UPS with power outlets whose rated current is less than the maximum
input current of this UPS.
All power outlets should be configured with earthing device for safety.
UPS could be electrified or powered no matter the input power co rd is tied or not,
even when the UPS is off. The only way to cut off the output is switching off the
UPS and disconnecting the mains power supply.
7
Neutral
For all standard model UPS, it is advised to charge the batteries over 8 hours
before using. Once the AC mains power energizes the UPS, it will automatically
charge the batteries. Without prior charging, UPS output remains as usual but with
shorter back-up time than normal.
When connected to motor, display equipment, laser printer etc, UPS power
selection should be based on the startup power of the load which is usually twice
as rated power.
Wiring by a qualified electrician is required. Ensure input cables and output cables
are connected correctly and firmly.
If install a leakage current protective switch, please install it on output cable.
For 1-3K series long backup model units, you may need to prepare wires for
Normally, output connection of 1~3kVA series is configured with power outlets or
terminal blocks, users can plug the load cable into the UPS power outlets to energize
the load. Make sure the mains cable and breakers in the building are enough for the
rated capacity of UPS to avoid the hazards of electric shock or fire.