East EA900Pro Series, EA902P, EA901P, EA903P Operation Manual

Page 1
Page 2
Table of Contents
1 Safety Information ........................................................................... 2
1.1 UPS
SAFETY INFORMATION ........................................................... 2
ATTERY SAFETY INFORMATION .................................................... 2
2 Product Overview ............................................................................ 4
2.2 F
2.3 R
PECIFICATIONS ........................................................................... 4
RONT PANEL FEATURES .............................................................. 6
EAR PANEL FEATURES ................................................................ 6
3 Installation ........................................................................................ 7
3.1 U
3.2 I
3.3 I
NPACKING INSPECTION ............................................................... 7
NSTALLATION INFORMATION ......................................................... 7
NSTALLATION AND OUTPUT CONNECTION ...................................... 8
XTERNAL BATTERIES CONNECTION (LONG BACKUP MODEL) .......... 8
4 Network Functions ......................................................................... 10
4.1 C
4.2 EPO
4.3 I
OMMUNICATION PORT ............................................................... 10
PORTOPTIONAL) ........................................................... 10
NTELLIGENT CARD (OPTIONAL).................................................... 11
5 Operation ........................................................................................ 12
5.2 D
5.3 UPS
5.4 UPS
5.6 O
UTTON OPERATION ................................................................... 12
ISPLAY INTERFACE .................................................................... 13
ON/OFF OPERATION ........................................................... 14
SETTINGS ........................................................................... 15
ARAMETERS INQUIRING OPERATION ........................................... 17
PERATION MODE....................................................................... 18
6 Fault Messages and Alarm ........................................................... 20
7 Troubleshooting ............................................................................. 25
1
Page 3
1 Safety Information
1.1 UPS safety information
Read all safety information an d operat ing instru ction s caref ully before atte mpting t o
install, service or maintain the UPS. Save this manual properly for reuse.
This UPS is intended for indoor use only. Do not operate this UPS in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space against
the wall for proper ventilation.
Do not open the UPS case as you will, there is a high risk of electric shocks inside.
All connection/wiring/s ervicing must be performed by a qualified electrician.
Do not connect to the equipment like hair dryer or electric heater. Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is
recommended.
CAUTION
UPS has high voltage inside, do not repair it by yourself. If any questions, please contact local service center or dealer.
1.2 Battery safety information
Environmental factors impact battery life. Elevated ambient temperatures, poor
quality utility power, and frequent short duration discharges will shorten battery life. Replacing battery periodically can help to keep UPS in normal state and assure backup time required.
Battery instal ling or replacing should be performed by a qualified electrician. If you
want to replace the battery cable, please purchase it from our local service center or distributors to avoid fever and lighter which can cause fire by inadequate power capacity.
Batteries may cause electric shocks and have a high short ci rcuit current, follow
below requirements before installing or replacing the batteries. A. Remove wristwatches, rings, jewelry and other conductive materials. B. Only use tools with insulated grips and handles C. Wear insulated shoes and gloves
2
Page 4
D. Do not put the metal tools or parts on the batteries
E. Before disconnecting the terminals from the batteries, cut off all the loads to the
battery first.
Do not dispose of the batteries with fire. The batt er ie s may explode. Do not open or mutilate batteries. Released electrolyte inside is harmful to the skin
and eyes, and maybe toxic.
Do not connect the positive pole and negative pole directly, otherwise it will cause
electric shocks or wil l be on fire.
The battery circuit is not isolated from the input voltage, high voltage may occur
between the battery terminals and ground, check if there is no voltage there before touching.
Symbols
Symbol Significations Symbol Significations
Caution
Danger! High Voltage!
Turn on
Turn off
Standby or Shut down
AC
DC
Protective earth
Disable/mute audible
alarm
Overload
Battery inspection
Repeat
Display screen repeat key
Battery
3
Page 5
frequency
Total voltage harmonic
2 Product Overview
2.1 Specifications
Model 1kVAS 1kVAH 2kVAS 2kVAH
Rated Capacity 1 kVA / 900 W 2 kVA / 1800 W 3 kVA / 2700 W
Input
Rated input voltage 208 Vac / 220 Vac / 230 Vac / 240 Vac Rated input frequency 50 Hz / 60 Hz (auto-sense)
Input voltage range
Input frequency range 40 ~ 70 Hz PFC 0.99 THDI 6% Bypass voltage range -25% ~ + 15% (settable)
Output
Output voltage 208 Vac / 220 Vac / 230 Vac / 240 Vac (settable) Voltage accuracy ± 1% Output PF 0.9
Inverter overload capability
Load crest 3:1 From mains mode to BAT mode From mains mode to bypass
Line mode
Efficiency
Output
BAT mode 85% 86% 87% ECO mode 95% 96% 97% Line mode Same as input frequency BAT mode (50 / 60 ± 0.1) Hz
110 ~ 176 Va c (power derating linearly between 50% and 100% load);
176 ~ 280 Vac (no derating); 280 ~ 300Vac (power derating 50%)
105% ~ 125% load: transfer to bypass in 1 min;
125% ~ 150% load: transf er to bypass in 30 s;
> 150% load: transfer to bypass in 300 ms ;
0 ms (trans fe r time)
4 ms
90% 91% 92%
3kVAS 3kVAH
distortion
2% (linear load); 5% (non-linear load )
4
Page 6
12 V
12 V
12 V
12 V
12 V
12 V
2 3 3 4 6 6 6 8 8
± 0.4
± 0.6
± 0.6
± 0.8
± 1.2
± 1.2
± 1.2
± 1.6
± 1.6
Overload protection; Output sh ort
Batteries
Battery type Sealed lead acid maintenance free battery DC voltage
Inbuilt battery
Quantity
Charger output voltage
Recharging time Recover 90% capacit y i n 3 hours for standard models
24 V 36 V 36 V 48 V 72 V 72 V 72 V 96 V 96 V 9 AH
27.1
7 AH
40.7
/
40.7
9 AH
54.2
7 AH
81.3
/
81.3
9 AH
81.3
7 AH
108.4
/
108.4
Charging current (Max.)
Standard model: 1 A
Long time model: 6 A / 3 A
System Control and Communications
Protections
Over-temp protection; Fan testing protection;
circuit protection; Battery discharge protection Communication port Standard: RS232; Options: USB, SNMP card, dry contacts Display LCD
Environmental
Operating humidity 0 ~ 90 % RH @ 0 ~ 40°C (non-condensing) Storage temperature -25°C ~ 55°C(exclude batteries) Operating altitude 1000m, above 1000m, der ate 1% for each rising 100m Protection class IP 20 Noise level 50 dBA (at 1m)
Others
Dimensions (mm) W ×D×H Weight (kg)
144*336
144*414
144*336
191*418
191*418
191*418
191*418
191*464
*214
*214
*214
*335
*335
*335
*335
*335
9.5 13 6 18 25.8 10.5 27.2 32 11
191*418
*335
* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
Note:
Model Type Model Type
1kVAS 1kVA Standard model 1kVAH 1kVA Long backup model 2kVAS 2kVA Standard model 2kVAH 2kVA Long backup model 3kVAS 3kVA Standard model 3kVAH 3kVA Long backup model
5
Page 7
2.2 Front panel features
2.3 Rear panel features
a. 1kVAS & 1kVAH rear panel b. 2kVAS &2kVAH & 3kVAS & 3kVAH rear panel
① AC input socket ⑥ RS232 port ② Overcurrent protector ⑦ Intelligent slot ③ Fan ⑧ Surge protection for network / fax / modem ④ USB port Output sockets ⑤ EPO (Emergency Power Off) port Battery connector
Note: The figure is for reference only. Due to the technology upgrading and development, the real unit might be different from the figure.
6
Page 8
~ 4
3 Installation
3.1 Unpacking inspection
Open the UPS package and inspect the contents upon receipt. The accessories
attached to the UPS contain a power cord, a user manual , communication c able, CD-ROM. The long backup model also includes the cable for connection to battery bank.
Check if the unit is damaged during transport. Do not power on and notify the
carrier and dealer if find damaged or parts missing.
Verify this unit is the model you want to buy. Check the model name showed both
on the front panel and rear panel.
Note:
Keep the packaging box and packaging materials for future transport use. The equipment is heavy. Always handle it with care.
3.2 Installation information
The UPS installation environment must be in good ventilation, away from water,
flammable gases and corrosive entities.
Do not lie down the UPS agai nst the w all so tha t front an d sid e pane l air int ake h ole,
rear panel air outtake hole will be unobs tructed.
The ambient temperature around the UPS should be within 0
non-condensing.
If dismantling the machine at low temperatures, there may be condensation
droplets, users can not install or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of electric shocks.
Place the UPS near the mains source so that can cut off utility power without any
delay in case of emergency.
Make sure the load connected to the UPS is off when users connect it to UPS, and
then turn on the load one by one later.
Connect the UPS with the power outlet which is over-current protected. Do not
connect the UPS with power outlets whose rated current is less than the maximum input current of this UPS.
All power outlets should be configured with earthing device for safety. UPS could be electrified or powered no matter the input power co rd is tied or not,
even when the UPS is off. The only way to cut off the output is switching off the UPS and disconnecting the mains power supply.
7
Page 9
Neutral
For all standard model UPS, it is advised to charge the batteries over 8 hours
before using. Once the AC mains power energizes the UPS, it will automatically charge the batteries. Without prior charging, UPS output remains as usual but with shorter back-up time than normal.
When connected to motor, display equipment, laser printer etc, UPS power
selection should be based on the startup power of the load which is usually twice as rated power.
Wiring by a qualified electrician is required. Ensure input cables and output cables
are connected correctly and firmly.
If install a leakage current protective switch, please install it on output cable. For 1-3K series long backup model units, you may need to prepare wires for
terminals based on the following table.
Wiring sp ec (AWG)
Model
Input Output Battery
1kVAS_DC24V 1mm² 1mm² 6mm² 1mm² 1mm² 1kVAS_DC36V 1mm² 1mm² 4mm² 1mm² 1mm² 1kVAH_DC36V 1mm² 1mm² 4mm² 1mm² 1mm² 2kVAS_DC48V 1.5mm² 1.5mm² 6mm² 1.5mm² 1.5mm² 2kVAS_DC72V 1.5mm² 1.5mm² 4mm² 1.5mm² 1.5mm² 2kVAH_DC72V 1.5mm² 1.5mm² 4mm² 1.5mm² 1.5mm² 3kVAS_DC72V 2.5mm² 2.5mm² 6mm² 2.5mm² 1.5mm² 3kVAS_DC96V 2.5mm² 2.5mm² 4mm² 2.5mm² 1.5mm² 3kVAH_DC96V 2.5mm² 2.5mm² 4mm² 2.5mm² 1.5mm²
Non-isolated
Ground
3.3 Installation and output connection
Normally, output connection of 1~3kVA series is configured with power outlets or terminal blocks, users can plug the load cable into the UPS power outlets to energize the load. Make sure the mains cable and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
3.4 External batteries connection (long backup model)
For different UPS model, users are instructed to configure different battery voltage
as below table. More or less units are forbidden, or else something abnormal or faulty will appear.
8
Page 10
Model 1kVAH 3 36 2kVAH 6 72 3kVAH 8 96
Battery Quantity (unit) Battery Voltage (volt)
One end of battery cable is for UPS terminals while the other end with triple cables
is for battery terminal s. Corre ct inst all ation pr ocedur e is hig hly v ital or el se pr obabl e electric shock will arise. Users are strictly required to follow the below procedure.
Connect batteries correctly and make sure the total battery voltage is available for
UPS.
Correctly connect the long battery cable to battery terminals first, red wire is to
positive plate while black is to negative. If users connect the UPS first, electric shock or other danger may not be avoided.
Before connecting loads, users s hould supply mains power and energize the UPS. Connect long battery cable to UPS terminals with correct poles link (re d is for ‘+ ’,
black is for ‘-‘), UPS will start charging automatically.
Connect the battery pack to the battery connector.
9
Page 11
Note:
RS232 interface is set as bel
EPO is on off the output of UPS i mmedi ately by operati ng EPO port in case of
4 Network Functions
4.1 Communication port
Users could monitor the UPS system through the communication port such as standard RS232 port and USB port with computer. Connecting this UPS with computer by communication cable could achieve UPS management easily.
> RS232 port
Pins 1 2 3 4 5 6 7 8 9
Indication empty send receive empty ground empty empty empty empty
Bit rate: 2400bps Byte: 8bit Completion code: 1bit Bit pattern: None
ow:
> USB port:
Pins 1 2 3 4
Indication +5V date+ date- GND
4.2 EPO port(optional)
Normally, pin1 and pin2 are connected so that the machine c an be working normally. When some emergencies happen, and when users have to cut off the output, just need to disconnect the connection between pin1 and pin2, or just pulling it out.
the short for Emergency Power Off. EPO port is
the rear pane l of the UPS. It’s green. Users can cut
emergency.
10
Page 12
PIN1
ON:UPS is malfunctioning
PIN3
Ground
PIN5
Common
PIN7
ON:Battery low
PIN9
ON:No AC power in
4.3 Intelligent card (optional)
There is an intelligent slot on the rear panel of the UPS, it’s for SNMP card and dry contacts. Users can insert any type intelligent card from those three into it to monitor and manage the UPS. And users don’t have to turn off the UPS when install the intelligent card. Follow below process:
First of all, rem ove the intelligent slot cover; Then insert the intelligent card (SNMP card and dry contacts); Finally, screw the intelligent card back.
> SNMP card (optional)
SNMP card on UPS is compatible with the most software, hardware and network operating system, it is a network management of UPS, with this function, UPS can login on internet , which can supply information of UPS status and input power, and even possible to control UPS via net management system. SNMP interface is set as below:
Bit rate: 2400bps
> Dry contacts card (optional)
Insert the dry contacts card into the intelligent slot. It’s another type function of intelligent monitoring.
Position Definition
PIN2 ONAlarmsystem failure
PIN4 Remote shutdown
PIN6 ONBypass mode
PIN8
ONInverter mode OFFBypass mode
11
Page 13
( + )
5 Operation
5.1 Button operation
Button Function “ON” key
(
+ )
“OFF” key
Press the two keys for more than half a second to turn on the UPS.
Press the two keys for more than half a second to turn off the UPS.
TEST/MUTE key (
+ )
INQUIRING key
, )
(
FUNCTION SETTINGS key
(
)
Press the two keys for more than 1 second in Line mode or ECO mode or CUCF mode: UPS runs the self-test function. Press the two keys for more than 1 second in battery mode: UPS runs the mute function.
Not in setting mode:
Press or for more than half a second (less than 2
seconds): display the items or derly.
Press for more than 2 seconds: Circularly and orderly
display the items every 2 s econds, when press t he key for some time again, it will turn to output status.
In setting mode:
Press or for more than half a second (less than 2
seconds): Select t he setting option.
Not in setting mode:
Press the key for more than 2 seconds: Function settings
interface.
In setting mode:
Press the key for more than half a second (les s t han 2
seconds): go to the function setting options.
Press the key for more than 2 seconds: exit from this
function settings interface.
12
Page 14
illuminated. When UPS is over loaded, the load icon will flash.
hen the capacity of battery get low or battery
disconnected, the battery status icon will flash.
omic mode), SHUTDN
mode), CUCF (Constant Voltage and Constant Frequency
5.2 Display interface
Display Function
Icon display
Load icon: The approximate load cap acity percentage (0-25%, 26-50%, 51-75% and 76-100%) is indicate d by the number of load bar sec t ions
Mute icon: Indicates the audible alarm is disabled / mute. Press the mute key in the battery mode, the mute icon flash.
Fan icon: Indica te s fa n working status. When the fan normally runs, the icon displays rotation; if t he fan is not co nnected or faulty, the icon will flash.
Icon display
UPS status information
Operation mode
Fault icon: Indicates UPS is in fault mode.
Battery status icon: Indicates the battery capacity of 0-25%, 26-50%, 51-75%, and 76-100%. W
UPS status information
In non-setting mode, it displays UPS output information when UPS
normally runs; Fault code will be told in fault mode.
In setting mode, users co uld adjust different output vol t age, activ ate ECO
mode, act iv at e CUC F mod e, s el ect an I D numb e r and s o on by o per at i ng function setting keys and inquiring key.
Operation mode
Indicates the power capacity of UPS within 20 seconds after starting up. Indicates UPS operation mode i n 20 seconds, such as STDBY (standby mode), BYPASS (Bypass mode), LINE (AC mode), BAT (Battery mode), BATT (Battery Self Test mode), ECO (Econ (Shutdown mode).
13
Page 15
LED indicator light functions
continuously: it
The fault light (red LED indicator light) illuminates continuously: it indicates
panel and alarm list.
mains power. After the self-test finishes, UPS will work in battery mode.
After UPS shutdown, there is no output. If output is needed, you can set BPS
panel.
more second, it will restart to beep again.
They are respectively inverter light and fault light from left to right. The inverter light (green LED indicator light) illuminates indicates that UPS is in mains mode or ECO mo de or power supply status in battery mode.
that UPS is in fault status. Note: For LED indication in differen t m odes, please refer to LED/dis play
5.3 UPS On/Off operation
Operation Description
> Turn on the UPS with mains power
With mains power conne cted, UPS works in bypass mode, its output is same
as the input voltage within the input range. If there is no need of output voltage when mains power connected, you can set up bPS to ‘OFF’. Default bPS is ON, it means t here is bypass output when power on.
Press the ON key for more than half a second to start the UPS, then it will
start the inverter.
Turn on the UPS
Once started, the UPS will perform a self-test fu nction. W hen the self-test
finishes, it wi ll t urn to online mode.
> Turn on the UPS by battery without mains power
When main power is disconnected, press the ON key for more than half a
second to start UPS.
The operati on of U PS start up p roc ess is almo st sam e as ab ove pr oces s wit h
> Turn off the UPS in Line mode
Press the OFF key for more than half a second t o t u rn off the UPS.
‘ON’ on LCD setting menu.
Turn off the UPS
> Turn off the UPS in battery mode without mains power
Press the OFF key for more than half a second to turn off the UPS.
When UPS shut down, it will do self-test first, unti l there i s no disp lay on t he
When UPS is in LINE Mode, press the self-test/mute key for more than 1
UPS
self-test/mute test
operation
second. UPS gets to self-test mode and tests its status. It will exit automatically after finishi ng test.
When UPS is in BAT Mode, press the self-test/mute key for more than 1
second, the buzzer stops beeping. If you press the self-test/mute key for one
14
Page 16
UPS Setting
setting will be configured normally.
Enter Setup interface. Press and hold the function setting key for more
than 2 seconds, then come to Setup interface, press and hold t he inquiring key ( the function setting, choose the setup interface, at the moment, the letters flash.
Enter the setup interf ace. Pres s and hol d the func tion set ting ke y for
more than half a second (less than 2 seconds), then come to the setup interface, at this time, the letters doesn’t flash any more, the numeri ca l v al ue flash. Press and hold the inquiring key ( second (les s th an 2 sec ond s), s el ect the nume ric al v al ue in acc ord anc e wit h the function.
Confirm the setup interface. After selecting numerical value, press and hold
the function setting Now, the setting function is completed and the numerical value illuminates without flashing.
Exit from the setup interface. Press and hold function setting key for
more than half a second (less than 2 seconds), exit from t he setup interface and return to the main i nterface.
Note:
UPS could not be set until it is connected to the battery and it is turned off and
switched to Stdby mode (standby mode).
Disconnect mains power after setting. The LCD display screen will automatically extinguish in about 1 min, and the
, ) for mor e t ha n h al f a s ec ond (less th a n 2 s ec on ds ) , s elect
, ) for more than half a
for more than half a second (less than 2 seconds).
5.4 UPS Settings
Output voltage setting
LCD display Settings
For 208/220/230/240 VAC models, you may choose the following output voltage:
208: output voltage is 208Vac 220: output voltage is 220Vac 230 (default): output voltage is 230Vac 240: output voltage is 240Vac
15
Page 17
Low voltage of battery setting
(Default): UPS won’t start up automatically when
LCD display Settings
The battery voltage selecting interface. You may choo se the following output voltage:
9.8: Low voltage of battery is 9.8Vdc
9.9: Low voltage of battery is 9.9Vdc 10: Low voltage of battery is 10Vdc
10.2: Low voltage of battery is 10.2Vdc
10.5: Low voltage of battery is 10.5Vdc dEF (default): EOD voltage automatically varies with loads,
including 21.5 hours discharge protection
Bypass mode setting
LCD display Settings
Enable or disable Bypass f unction. You may choose the following two options:
ON: Bypass enable OFF (default): Bypass disable
AUO setting LCD display Setting
AUO setting only can be set in Stdby mode or Bypass mode. You may choose the following two options: ON: UPS will start up automatically and works in Line mode when connect mains.
OFF
connect mains except EOD, it will work in standby or bypass mode.
16
Page 18
as the following graphics shows, the WATT of the load is
display the highest temperature of UPS
following graphics shows, the input voltage is 220V, input
raphics shows, the battery voltage is 24V, the
capacity of battery is 100% (the capacity of battery is
5.5 Parameters inquiring operation
Press the inquiring key or for more than half a second (less than 2 seconds) to inquire about items. The inquired items include Input, Battery, Output, Load and
Temperature. The displayed items on LCD screen are show n as follow ing:
LCD display Description
Output
the UPS. As the following graphic shows, the output voltage is 220V, the output frequenc y is 50Hz.
Load: Display the numerical value of the active power (WATT) and apparent power (VA) of the load. For example,
800W, VA is 1.0kVA (when disconnect loads, it is a normal phenomenon to show a small numerical value of WATT and VA).
Display the output voltage and output frequen cy of
Version and Temperature: Indicate firmware version of UPS and components; As the following graphics shows, the firmware version is v1.7, the maximum temperature is 40 ℃.
Input: Display the voltage and frequency of the input. As the
frequency is 50Hz.
Battery: Disp lay t he vol tage a nd capa cit y of th e batt ery. As the following g
approximately reckoned according to the battery v o ltage).
17
Page 19
Being in line mode are as following: When input mains UPS is powered off and no output supply power, but still can
Warning: Display the warning code.
5.6 Operation mode
Operation mode and LCD display Description
Bypass mode
Line mode
Stdby mode
Turn to bypass mode under the foll owing three conditions:
Connect mains power and t he bypass setup is ON. Turn off the UPS in l ine mode and the bypas s setup is
ON. Overload in line mod e. Note: When UPS is working in bypass mode, it has no bac k up function.
corresponding to the working conditions, UPS will work in line mode, LCD displays ‘Line’.
charge batt eries.
18
Page 20
Battery mode
make the buzzer stop beeping temporarily to wait for
ECO mode
CUCF mode
Being in battery mode are as following: the buzzer beeps once ever y 4 s econds. When the mains power is low or unstable, UPS will turn to battery mode at once, and LCD displays ‘batt’.
Being in E C O m ode are as fol lowing: When the input mains meet the input range of the ECO mode and the ECO function is on, the UPS works in ECO mode . If input mains exceed the range of ECO several times within one minute but stays in inverter input range, UPS will work in inverting mode automatically. LCD displays ‘ECO’.
Frequency conversion mode is mainly to provide a stable voltage and frequency (mainly in terms of frequency). After starting this mode, its output will not be affected by utility to meet input needs of some precision equipment and make users’ load more stable and secure. After opening CUCF mode setup, LCD displays ‘CUCF’. Under the CUCF mode, when the output frequency is set to 50HZ, the load capacity decreased to 80% of the original volume; when t he output frequency is set to 60HZ, the load capacity decreased to 70% of the original capacity. The output frequency is fixed with the setting values, it doesn’t vary with utility change. And the UPS cannot be set to going bypass under this mode.
Fault mode
When UPS has a failure, the buzzer beeps and the UPS turns to fault mode. UPS cut s o ff t he output and LC D displ ays fault codes. At the moment, users can press the mute key to
maintenance. Users can also press the OFF key to shut down the UPS when confirm that there is no serious fault.
19
Page 21
LED flashes
er
1
Inverter mode (mains power)
voltage
Line
always
protection, switch
sec
sec
sec
6 Fault Messages and Alarm
Table 1: Fault code messages
Fault code Fault type Bypass output Note
01234 Bus high yes
56789 Bus low yes 1011121314 Bus unbalance yes 1516171819 Bus soft start fail yes 2021222324 Inverter soft start fail yes 2526272829 Inverter high yes 3031323334 Inverter low yes 3536373839 Bus discharge fail yes 4041424344 Over heat yes 4546474849 OP(inverter) short no 5051525354 Overload yes 5556575859 Line NTC break yes 6061626364 Shutdown fault yes 6566676869 AC input fuse open yes unused 7071727374 Communication fault yes unused 7576777879 Communication fault yes 8081828384 Relay fault yes 8586878889 AC input SCR fault yes unused 9091929394 CAN fault yes
Table 2: Working status messages
S/
Working status LCD displa y messages
N
Mains power
Mains power high/low voltage
Working mode displays
Working mode displays bAT
20
Alarm
beep
No beep No flash
One
beep / 4
LCD
flashes
One flash / 4
Invert
Flash
One flash /
Fault
/
/
Page 22
sec
/ 4 sec
sec
of battery
sec
/ sec
sec / 3
Bypass mode
Bypass
/2 sec / 4
Warning for battery disconnec ted
0, and flash all the time
sec
/ 4 sec
/2 sec
and flash all the time
sec
/ 4 sec
all the time
5
Output overload protection
/ sec
overload
corresponding codes
/ sec
sec
overload
corresponding codes
flash all the time
sec
/ 2 sec
2 sec
depending on current
sec
to battery mode
2 Battery mode
Battery voltage - normal
Warning for abnormal voltage
Working mode displays bAT
Working mode displays bAT, Bat flash
One
beep / 4
One
beep /
One flash
One flash
One flash /
One flash /
/
Mains power – normalunder
Bypass mode
Inverter mode
Power on / Switch on
Warning for mains power overload
Protect operation for mains power mode
Warning for battery overload
Working mode displays byPASS
Working mode displays byPASS, bat display is
Working mode displays Line, bat display is 0,
LCD illuminates when power on, and display the capacity of the UP S , later working mode displays Line or byPASS, bat icon flash
Working mode displays Line, load icon flash
Working mode displays FAULT and the
Working mode displays bAT, load icon flash
One beep
/ 2 min
One
beep / 4
One
beep / 4
6 beeps
2 beeps /
sec
Long beep
2 beeps /
sec
No flash
One flash
One flash
Flash always
2 flashes
Flash always
2 flashes
One flash
One flash
Flash always
Flash always
/ /
Flash always
/
One flash /
/
/
Flash always
/
Flash always
/
Protect operation for battery mode
Warning for bypass
6
mode overload
7 Fans fault(fan icon
Working mode displays FAULT and the
Working mode displays byPASS, load icon
Fan icon flash, working mode displays
21
Long beep
One
beep / 2
One
beep / 2
Flash always
One flash
No flash / /
/
One flash /
Flash always
/
Page 23
code
2 ● 3 ● ●
8 ●
mode
Working mode displays
8 Faults mode
FAULT, numerical value area displays the corresponding error
Long beep
Flash always
/
Flash always
Note:
End user need to provide below information when require to maintain the UPS. UPS Model No. & Serial No. Date of fault occurrence. Fault details (LCD status, noise, AC power situation, l oad ca p aci t y, battery capacity
configuration ect.)
Table 3: Alarm code display
The alarm code will be displayed in four digital tubes on the right of the numerical part of the LCD screen (red mark) , as show n below :
Alarm icon Alarm code
The alarm truth table during operations is shown as below
‘●’ signifies the alarm occurs, blank signifies no alarm appears
The first digital tube from right to left
Display
0 1
4 5 6 7
9
A
Bypass lost
Remote
22
overload
Battery
Page 24
The second
2 ●
7 ● ● ●
Low battery
Median abnormal
0
5 ● ● 6 ● ●
digital tube from right to left
B C D E F
Display
0 1
3 4 5 6
8 9 A B C D E F
Display
Overcharging
EEPROM
Mains
Fan
Start-up
Charger fault
The third digital tube from right to left
1 2 3 4
7 8 9 A B C D
23
Page 25
Over load fault
Mains lost
5 ● ●
E F
The fourth digital tube from right to left
Display
0 1 2 3 4
6 7
Bypass
Example: If the alar m c ode "2000" appears on the LCD screen, it indicates loss of mains power.
24
Page 26
fault code is 00-14
fault code is15-24
supplier directly.
fault code is 25-39
persists, contact the supplier.
problem persists, contact the supplier.
Fault icon display, audible
Input NTC fault
Contact the supplier.
7 Troubleshooting
When the system works in fault mode, the LCD displays as below:
Fault code
Problem Possible Cause Solution
Fault icon display, audible buzzer alarm continually, the
Bus bar voltage fault
Test the bus bar voltage or contact the supplier.
Fault icon display, audible buzzer alarm continually, the
Fault icon display, audible buzzer alarm continually, the
Fault icon display, audible buzzer alarm continually, the fault code is 40-44
Fault icon display, audible buzzer alarm continually, the fault code is 45-49
Fault icon display, audible buzzer alarm continually, the fault code is 50-54
Check the soft start circuit, e sp ecially
Soft start fault
Inverter voltage fault Contact the supplier .
Over temperature inside
Output short-circuit
Overload
the soft start resistance or contact the
Be sure that the UPS are not overloaded, and the fan vent is not obstructed, as well as the indoor temperature is not high. Leave alone the UPS 10 minutes for cooling, and restar t it. If the problem
Turn off the UPS and disconnect all the loads. Be sure there is no any fault or internal short circuit of the loads. And then restart the UPS. If the
Check the load level and disc onnect the non-critical equipments, recount the total capacity of your load and reduce t he load to the UPS. Check whether the load equipments has fault or not.
25
Page 27
buzzer alarm continually, the
fault code is 55-59
fault code is 60-64
supplier if it is abnormal.
the supplier.
supplier.
short
seconds to start the UPS.
disconnect
fault
than 3 hours
the non-critical equipments,
spare parts.
power on
Fault icon display, audible buzzer alarm continually, the
Fault icon display, audible buzzer alarm continually, the fault code is 65-69
Fault icon display, audible buzzer alarm continually, fan icon in the LCD flickers
UPS fail to start when operate ‘On’ key
Back up time become short
Power fault
Input fuse fault
Fan fault
Pressing time too
The input connection is not ready or UPS internal battery
UPS inter nal system
Battery undercharge
UPS overload
Battery maturing, capacity descend
Check whether the input & output power are normal or not, contact the
Check if the input fuse is burnt. Replace the old fuse and restart the UPS. If the problem persists, contact
Check whether the fans are connected and fixed well or not, and if fans are not broken. If all seems fine, contact the
Press the power key more than 2
Connect the input well, if the battery voltage is too low, disconnect the input and start the UPS with no-load.
Contact the supplier. Keep the UPS battery recharging more
Check the load level and disconnect
Replace with new batteries, contact the supplier to get the new batteries and
UPS doesn ’t have any power going through even mains
UPS input breaker disconnected
Reset the circuit breaker by manual.
Note:
When the output is short-circuited, the action of UPS protection will show up. Before turning off the UPS, make sure to disconnect the entire loads and cut off the mains power supply, otherwise it will make the AC input shor t circuit.
26
Loading...