Earth Stove MP35/50 Installation And Operation Instruction Manual

Installation And Operation
Instructions
"linisappliance must be Installed by a qualified technician.
Read thoroughly before installaMon.
Save this manual for future reference.
TABLE OF CONTENTS
Introduction ........................................ 2
Operation ........................................- - 4
Maintenance ......................................- 8
Installation ......................................... 12
Troubleshooting ...................................- 18
Power Flow Diagram ............................... 20
Wiring Diagram .................................... 21
Glossary --'- ........ ................................. 22
Specifications ...................................... 23
Component Diagrams .............................. 24
Warranty .......................................... 25
Safety/Listing Label ................................ 26
Service/Maintenance Log ........................... 27
'4
p/n 16482
Rev. 10/97
.
.
IMPORTANT SAFETY NOTICE
PLEASE READ BEFORE ATTEMPTING TO BURN!
CAUTION: If this stove is not properly installed, a house fire may result For your safety,
follow the installation directions; contact local building officials about restrictions and
installation inspection requirements in your area.
Installation of this stove must comply with local codes. A building or installation permit may be required. Be sure to check with your local building official or fire department
before installing.
11.
If utilizing an existing chimney have your fireplace flue or chimney system inspected by
a qualified person prior to installation of the stove. Make any necessary repairs before
installing.
Terminate pellet vent pipe so that contact with humans or possible damage to pipe is
avoided.
12. Required fuel is: 1/4" diameter wood pellets, 1" ma_cimum length, 8500 BTU per pound,
10% maximum moisture content, 1 1/2% - 3% ash. Corn kernels, 10,000 BTU per
pound, 15% maximum moisture content. (Optional Cornpot and metering cup filler
plug required).
.
.
D
6.
.
So
.
Never connect stove flue to chimney being presently used by another appliance.
Never block any air intake or air outlet ports. Dangerous overheating can result.
Do not install this stove in a sleeping room.
Never connect the stove to an air duct system.
Never stack or pile combustible materials against the stove or around external vent
termination.
To avoid burns, children and adults should be alerted to the hazards of high surface temperatures.
To provide reasonable fire safety, install a smoke detector and a conveniently located
fire extinguisher.
13.
Do not attempt to burn cordwood or pressed
logs in this stove, severe damage or fire could result.
Testing/Listing The Earth Stove model MP35/50 pellet fired
appliance has been constructed, tested and listed for use in residential construction in accordance
with the applicable portions of the following standards - UL1482, UL127, UL103 or UL641,
UL507 and UL39i and for use in manufactured dwellings and park trailers according to OAR
918-520-010 through 918-520-110, by Pacific Inspection and Research Laboratory, Inc.,
(PIRL) Redmond, WA 98052. Listing file 89-174.
Based on a tested air to fuel ratio in excess of 35:1, this appliance is not an effeeted facility
under the EPA regulations for wood burning
stoves.
10. In the event of a chimney fire, notify the fire department, and unplug the stove.
Page I
INTRODUCTION Read Entire Manual Before Attempting to Burn
Three Pronged Plug (Grounded)
Ash Drawer
Your stove has a printed circuit board and other electrical components that require a grounded circuit
and proper polarity. Purchasing a surge protector provides additional insurance against unnecessary problems.
Control Panel/Fan Rheostat
The ash drawer located in the front of the pedestal is designed to make cleaning easier by containing the
ashes in a removable drawer. It is accessed by
turning the spring loaded screws located on the ash
drawer cover. Do not operate the stove with the ash drawer open or ajar. Replace gasket material as
necessary to insure a tight seal.
The primary control .board manages the performance of your stove. It allows you to regulate the fuel feed
rate, the draft fan voltage and main power to the
stove. The room air fan rheostat allows you to manually regulate the fan speed except when the
automatic high speed override is engaged.
Firepot
Decorative Logs
An important feature of your NaturalFire stove is the realistic fire created by the flame spread firepot and the refractory logs. Although the logs are quite durable, they should be handled carefully, as they
retain heat for a considerable period of time, and if
dropped can break.
The pellet firepot is where the fuel is burned.
Although ithas a self cleaning capability for much of the ash build up, variable fuel quality (ash
content) and extended periods of a low burn rate
will .necessitate some manual cleaning. An Earth
Stox_e firepot cleaning tool is highly recommended
,(part#1000).
Hopper
The hopper is where the fuel is stored before it feeds into the stove.
Placement of the logs is important in achieving a
realistic fire. One recommended pattern is pictured below which allows you to use a Firepot cleaner without having to remove the logs (except for full
maintenance).
Page 2
INTRODUCTION
How It Works
The fuel metering cup rotates in the throat of the hopper
providing a measured amount of fuel based on the set feed
rate. The fuel drops into the anger tube where it is moved
into the firepot. The draf_ f_n provides combustion air
through the _.ger tube and a series of holes in the inner
firepot, to allow for complete combustiom
The flame and hot gases provide heat to the heat exchange tubes lorm_ in the upper chamber of the stove. The
room air fan extracts the heat and delivers it to the room, along With the natural radiant heat from the glass and
metal surfaces.
Gold Door
Your Earth Stove's gold door frame should be cleaned thoroughly With a good window cleaning solution and a
soft cloth BEFORE the stove is burned. Do not use any
metal polishes or abrasives to clean the door. Any oils or
finge_v_ints leg on the gold could become Iw.u_ent blemishes if the stove is burned prior to _ removal.
Atkrr the first few fires the gold will cure.
Glass
The glass is a super heat resistant ceramic that withstmds continuoustemperatums upto 1390° F. This temperature
is well beyond the temperatures in which you operate your stove.
This appliance is designed to provide a flow of air over the inmde of the El_% which along with high heat helps
keep it clean. When operating the stove on low for extended periods of time, the gl___ may get dirty. A commercial _I_ cleaner designed for stoves is
recommended for cleuning.
The glass should be cleaned thoroughly with glass cleaner and a soft cloth BEFORE the stove is burned.
Marble Set
Marble is a natural product so each piece will have its
own unique chamc_. Marble may be cleaned With a damp cloth toremove oils or dust. Be sure to installthe
four cerawool strips (under the rfiarble) to protect it Do
notputro_ objects(suchas_vets,steamers,hopperlid,
etc.) on the _. Do not install the marble before curing the paint
Remote Wall Thermostat
One way to maxim_ the efficiency and convenience of
your stove is to install a re.mote wall thermostat. A Honeywell T87F 24 volt thennostat is recommended (see
page5).
Corn Pot
NaturalFire pellet stoves will bum most types of corn with the _aa_fion of a corn pot kit. For dtcmils, see the section on burning com.
Several options are availal, le to enhance your NaturalF'ge pe[l_ stovz Please see your local d..-br for further inform_m_'_om
Page 3
OPERATION
Before Attempting To Start Your Stove, Read This Manual Thoroughly. Have Your Stove Pretested and Professionally Installed.
Start Up Procedure
1. Plug in the stove. Fill hopper with pellet fuel.
2. Turn the Main Power Switch to the "Feed System" position.
3. Provide starting fuel by pushing the "Start Button" and allow fuel to feed for approximately
five minutes (or put approximately two cups of fuel directly in the Firepot).
4. Turn the Main Power Switch to the "Off' position. (This will stop the fuel feed.)
5. Open fire door and apply Fire Starter gel to the fuel in the Firepot, then light. Allow the fuel to
burn for five minutes with the door slightly ajar.
Shut Down Procedure
1. Turn the Main Power Switch to the "Draft Fan" position. If using a remote
Thermostat, turn the Thermostat down.
2. When the fire in the Firepot goes out completely, shut the Main Power Switch to the
"Off" position.
WARNING: IF THE POWER SWITCH IS TURNED OFF PREMATURELY WHILE A FIRE
IS STILL ACTIVE IN THE FIREPOT, THIS MAY RESULT IN SMOKE BACK INTO THE
DWELLING (THIS WOULD DISSIPATE RAPIDLY).
Pellet Fuel Calibration *
6. Close the door.
7. Turn the Main Power Switch to the "Feed
System" position, then push the Start Button.
8. 'Set the Fuel Rate Switch to the "Full" position. If using a remote Thermostat, adjust it to'the
desired room temperature.
9. As the stove tem]?erature rises, the Room Air
Fan will automaucally engage. At that point, adjust the Fuel Rate Switch to the desired
setting. During the start up procedure or when running the stove on a "Low" Fuel Rate Setting,_
the Room Air Fan Rheostat must be in the off
position. Failure to do so could cool down the
stove and it will automatically shut off.
10. If the fire goes out, go back to step two again.
The MP35/50 is shipped from the factory, set to
50,000 BTU input. To adiust to 35,000 BTU input,
install the 1/8" filler plug into the fuel metering cup.
35,000 BTU - 1/8" filler plug 50,000 BTU - open
Filler Plug Installation
Place the filler plug into the bottom of the metering cup fuel cavity and secure with the screw provided
into the tapped hole.
Page 4
OPERATION
Control Board
A. Main Power Switch
The main power switch is a three way toggle with the following positions:
1. Off(stove off)
2. Draft Fan - aUows the draft tim to operate
alone during shut down.
3. Feed System - stove on
B. Fuel Rate Switch
The fuel rate switch controls the amount of time the burner feeds fueL It can be set to the
following threepositions:
o
2.
°
Full - will feed fuelcontinuously. Medium - will feed fuel approximately
two minutes on then two minutes oE
Low - will feed approximately one
minute on then _ minutes Off..
C. Draft Fan Switch *
The draft fan sSwitoh conlrols the amount of air used for combustion during piloting process. It
can be set to the following three posifiom:
1. High - runs at 75% of capacity when
stove is not feeding fuel.
2. Low- runs at 50% of capacity when
stove is not feeding fuel.
3. Off- runs at 0°,4 of capacity when stove
is not feedin_ fuel.
* The dmR fan will nm at 100% of capacity
during the feeding of fuel.
D. Start Button
Depress the start button to allow fuel to feed for approximately 12 minutes (used during start up of
thestove).
E. On/OffLight
The On/Off Light blinks to indicate electricity is flowing through the primary tonal boar&
F. Fuse
The Fuse protects the Primav/ Control Board fi_m power "surges or spikes".
Optional Remote Wall Thermostat
One way to maximize the efficiency and convenience of
your stove is to install a icmote wall thermostat. A Honeywell T87F 24 volt thermostat is recommended.
Follow the m_nuf_etu_s installation insm_ons using
18/2 stat wire. The leads from the stove are the yellow
wires found behind the Primary Control Board.
Once you have installed the Th_m_ostat, the Fuel Rate Switchshould be set to"Low". This will be the rate the
stove will run on pilot when the Thermostat is not cMllng for heal
Page 5
OPERATION
Room Air Fan Rheostat
The room air fan rheostat can be used to vary the speed of the room air fan by rotating it to the desired setting. When the stove is very hot
(running on high), the rheostat override (fan speed disc) will automatically run the fan on high to
prevent the stove from overheating.
Normal Operating Sounds
Heat Exchange Tubes - As the room air fans
increase in speed, you may hear air flowing through these tubes and out into the room.
Thermostatic Control Disc - There are four different heat activated temperature discs on the
insert. The discs can make a light clicking sound as
they cycle while the insert heats up or cools down.
Room Air Fan - The modern, high efficiency fan may have a hum or pulsating sound, particularly on the high setting. The sound may change as the fan
speed is varied.
Auger Feed System - When fuel is fed from the
hopper to the auger tube, a light clinking sound of the fuel being cut may be heard.
Auger/Cup Motor(s) - When feeding fuel, you
may hear the intermittent buT7 or hum of these motors.
Draft Fan - This motor runs at various speeds to provide combustion air to the firepot (and to aid in
the draft of the flue). The speed of this motor wiU
, increase with the feeding of fuel.
Page 6
OPERATION
Burning Corn (Optional)
Natural Fire pellet stoves will bum most types of
corn with the addition of a compot kit. R is not necessary to mix corn with wood pellets however,
wood pellets are required to start the fire.
NOTE: Burning treated seed corn is never
recommended
The compot kit consists of:
1 1/8" Filler Plug 1 3/8" Filler Plug
1 Compot
To install the cornpot, simply remove the screw(s) from the top of the auger housing and lift up and out on the firepot. Slide mounting flange of the cornpot
over the auger housing and replace screw(s).
Initially the air shutter on the draft: fan should be set at 1/2 open and the draft fan selector on "LOW". If
more or less combustion air is needed, adjust the air shutter accordingly to achieve a bright yellow flare e.
Because corn size and density varies, it will be necessary to calibrate the fuel metering cup in order
to maintain rated BTU input and prevent overfiring. This requires the installation of the filler plug in the fuel metering cup. Use the 3/8" filler plug provided
in the compot kit.
The moisture content of the corn should be 15% or less, and care should be taken to ensure that there are no foreign objects in the corn (i.e. sticks, stalks,
cob parts, etc.). When burning corn, the primary combustion takes place on a bed at the bottom of the
compot.
The compot has a solid bottom and sides with air
holes because burning corn forms a fluid-like residue which becomes solid when cool. The
cornpot cleaning will depend upon the quality and quantity of corn being used. The compot should be cleaned when the build up starts to reach the bottom
air holes inside of the compot. You will need to
remove the ash, and in some instances a white calcium like deposit. The stove must be shut down and cooled before cleaning.
CORN BURNING SHOULD BE DONE IN TOP
VENT INSTALLATIONS ONLY. .If the installation must elbow into a wall thimble, the
horizontal mu sl_ould not be more than 24". The use of a wall mounted thermostat, part #CTR140 is
suggested.
Start Up Procedure
We recommend starting a corn fire with wood
pellets because corn has a dense shell that can be
difficult to start. Manually fill the cornpot, to the bottom of the auger tube, with wood pellets. Use of the start button feature is not recommended when
initially starting the unit for corn burning. (See
"Start Up Procedure" in the Operation section for additional start up information).
Page 7
MAINTENANCE
Ash Removal and Disposal CAUTION: BE SURE THE FIRE IS OUT AND
STOVE IS COLD BEFORE REMOVING
ASHES! NEVER BURN YOUR STOVE WITH
THE ASH DRAWER OPEN.
Ashes can hold live embers for several days, and must be disposed of with care. Be certain the fire is
out before you remove the ash drawer. Brush ashes
into the ash drawer. After emptying, clean and
replace the ash drawer and tighten the spring loaded
screws. NEVER Elace ashes in a cardboard box or
any other combusUble receptacle. Place the ashes in a metal container with a tight fitting metal lid. The
closed container should be stored on a noncombustible surface, away from combustible
materials. Keep the ashes in the closed container
until you are certain all the cinders have completely
cooled. Replace ash drawer gasket if it becomes damaged.
Paint
Your stove finish is a high temperature paint that
requires time and temperature for the silicon resin in the paint to completely cure. Depending on your
use, this may take a few hours or a few days. The paint manufacturer recommends you ventilate the
house during the initial bums. Although the emis'sion is primarily Carbon Dioxide, there are
other components emitted which make it smell bad and may irritate some people. Do not place
anything on the stove surface until the paint is completely cured, as it will become soft durin_ this
process. Do not attempt to repaint the stove unul the _aint is completely cured. If the surface later
ecomes stained Or marred, it may be lightly sanded
and touched up with spray paint trom the same paint
manufacturer, paint is available at your local
dealer.
KEEP YOUR HOUSE WELL VENTILATED DURING THE CURING PROCESS. THE
CHEMICAL SMELL AND BLUISH HAZE EMITTED BY THE CURING PAINT CAN BE
QUITE NOTICEABLE AND MAY SET OFF A SMOKE DETECTOR.
Fan(s)
At least once each year, check the room air fan and draR fan inlets for deposits from carpeting, pet hair,
furniture coverings, etc. Use a brush and/or light vacuuming for cleaning.
Door Gasket
A spun fiberglass gasket (3/4" in diameter) provides
the seal around the fuel door. Should this become
frayed or ,damaged it should be replaced. Spun fiberglass rope" gasketing can be purchased from your dealer or some hardware stores. It must be the
same diameter as the original. Use high temperature (RTV) silicone sealer as an adhesive.
WARNING: MAINTAIN THE DOOR SEAL IN
GOOD CONDITION. DO NOT LEAVE THE
STOVE BURNING WITH THE DOOR OPEN OR AJAR. DO NOT USE ANY TYPE OFARRASIVE
CLEANER OR POLISH ON GOLD PLATING.
Creosote Formation and Need for
Removal
If your stove is properly adjusted, very little creosote will develop in your flue system. If creosote begins to develop, it is likely that poor
adjustment or needed maintenance is causing incomplete combustion of the fuel. Be sure your draft fan switch, and draft fan shutter are set
properly. What causes creosote is the moisture content of fuel
verses the rate at which it is burned. Piloting a stove
on low feed rate for long periods of time, causes incomplete combustion, cre.atin_ vapors which may
condense in a relatively cool chimney, thus forming creosote. These deposits tend to form in long runs
of venting where gases cool prior to exhausting.
Soft fly ash is a normal by product of bumingpellet
fuel, and Can accumulate in your flue system. Using
lower grade fuel will increase the frequency of cleaning that wiU be needed. Check your flue regularly (at least once a month) until a schedule can
be established for your installation and fuel quality. Remember, during high use periods to increase your
inspection cycle.
Note: Single wall pi]_e cools rapidly, therefore
installations using this type of flue are more susceptible to creosote deposits.
Page 8
MAINTENANCE
Refractory_ Logs
The following steps will insure the longevity of your logs:
1. Never attempt to handle the logs while they are hot.
.
Carefully remove logs from firepot when the stove is cold. Remove ashes from the firepot.
Then carefully place the logs into their proper position (see page 2).
Firepot
Keep the firepot inner holes free of obstructions (buildup). Remove the flrepot and empty it when this occurs.. The quality and quantity of pellets
used will dictate the necessary cleaning. Remove clinkers or carbon build up.
Clinkers are a byproduct of the fuel. Silica (or dirt) in the fuel, along with other impurities can fuse
under heat and cause clinkering. Clinkering is a function of the fuel, not the stove. A clinker should
be removed using a clean out tool.
Cleaning the MP35/50
. Turn the unit off two to three hours before
cleaning to allow the unit to cool (see Shut Down Procedure).
2. Place protective floor covering around the
front of the stove.
o
,
.
.
o
Remove ash drawer and empty ashes into your noncombustible container. Dispose of ashes as previously described (see Ash Removal and
Disposal). Clean any remaining ash from the firebox and ash drawer area.
After the stove chimney has been swept, the top/rear chimney seal off plate needs to be
pulled off of the stove to vacuum the unit out. There is a baffle plate beneath the heat exchange tubes. Fly ash will acel_mulate on
this plate and must be removed to ensure flail efficiency. To clean, remove the baffle plate and pull the cleaner plate all the way forward
and then return to the rear of the firebox.
Remove the clean out access cover and vacuum out the fly ash (see page 10).
Reinstall your firepot being sure that the auger tube protrudes about 1/8" into the firepot,
Replace baffle and clean out access. Reseal and secure stove chimney.
The cleaning frequency will be dictated by the
quality and q, antity of the fuel burned. The
following is the suggested schedule to
establish a minimum: A_Rer every 1/2 ton of
pellets, when the metal surfaces of the exchange tubes are no longer visible, or after
every 2-3 weeks of use.
3. CAREFULLY remove the decorative logs
from the firebox and set them aside.
4. Remove the firepot by removing screw(s) from the auger housing and pulling up and out.
Page 9
MAINTENANCE
Top Chimney Outlet
Upper Baffle Plate
Heat Exchanger Tubes
Lower Baffle Plate
Clean-Out Access
- Firepot
Page I0
MAINTENANCE
Maintenance Requirements
As with all appliances, periodic maintenance is required to keep them operating at optimum efficiency.
We recommend an annual maintenance service by a qualified technician.
Maintenance Related Problems
Problem: Decrease in heat output or incomplete
combustion.
Solution: See maintenance points A, B, C, D & E.
Problem: Decrease in Room Air Fan velocity. Solution: See maintenance point D.
Problem:
Solution:
Noticeable change in Room Air Fan
noise.
See maintenance point D.
Problem: Solution:
Stove smokes or odor in home. See maintenance points A, B, C,E, G &
H.
Problem: Flames appear to bum lazily.
Solution: See maintenance points A, B, C & E.
Problem:
Solution:
Pellets stick to inside surface of hopper
(additives in fuel bonding to paint).
See maintenance point I.
Recommended Maintenance Points
A. Once for every 1/2 ton of'fuel burned,
remove all dust and flue ash from Heat Exchange Tubes and Baffle areas using the
cleaner plate.
no
Remove and clean the Firepot. Keep inner air
holes free from buildup. Remove ashes from the
Ash Drawer weekly or as fuel dictates.
C. Clean chimney, cap and exhaust passageway
annually or as needed. Inspect monthly.
D. Vacuum air intake and squirrel cage on Room
Air Fan annually.
E. Clean squirrel cage on Draft Fan annually.
F. If Remote Thermostat is used, remove cover and
clean contacts annually.
G. Replace Door Gasket as needed.
H. Replace Ash Drawer Door Gasket as needed.
Ig
Clean inside surface of hopper with a good
window cleaning solution, then apply a non-stick spray (i.e. Teflon Spray). Do not use vegetable or oil based sprays.
If solutions fail to cure problem, See Trouble Shooting Section.
Page 11
INSTALLATION
Recommended Pre-Installation Procedure
NOTE TO INSTALLER: Before the unit is 5.
installed it is recommended that the unit be pre-buraed to verify the operation, to bum off oils
that are sometimes found in the heat exchange tubes, and to cure the paint. The "Pre-lnstaIiation 6. Procedure" should be done in a well ventilated area
as follows.
i.
,
3.
.
Remove the baffle plate from the pallet and place it on the brackets inside the stove. The
brackets are located below the heat exchange tubes at the rear and above the door at the from.
Make certain the baffle plate is placed all the way to the rear and left hand side of the unit and
not centered. The heat exchanger cleaner plate han_es should fit into the two notches in the
baffle plate
Plug the stove into a grounded oulet (using a circuit tester, verify the electrical outlet for
proper ground and polarity where the unit will be installed. Failure to do so could result in
damage to the electrical components and void
thewarranty).
Check the shutter on the dra_ fan and make sure it js set at 1/2 open (once installed the actual
setting will depend upon the dra_ of the flue).
On the primary control board, A) set the main
power switch from "Off" to the "Draft Fan" position and B) put the fuel feed rate on "Full". The draft fan should now start. Open the door,
place your hand over the firepot and see if the draft Fan is forcing air into the firepot. Turn the main power switch to the "Off" position.
Turn the rheostat "On" to see if the room air fan ram_..After checking the fan, turn the rheostat
"Off".
Look down into the hopper, and make sure
nothing is obstructing the fuel metering cup. Pour 1/4 bag of pellets in the hopper.
With the main power switch in the "Feed
System" position, push the start button. Allow fuel to feed for approximately five mirLutes or
add two cups of pellets by hand to the center of the firepot (see page 4, item 3). Put the main power switch in the "Off" position. Apply non-volatile lighting material to the pellets and
light it with a match. Let the fuel bum for five minutes leaving the door slightly ajar.
.
Close the door and set the main power switch to
the "Feed System" position, and the fuel rate Switch to the "Full" position. Push the start
button. The draft fan will run at high and .the flame will increase (a full flame will need to be
established in the firep0t before normal operation can be maintained.
,
Once running, observe the stove operating for
15-30 minutes.
9. As the stove temperature rises, the room air fan
will automatically be engaged. Set the rheostat to the desired speed.
10. If necessary, adjust the _ fan shutter to bring the fire to a bright yellow flame (the average
installation will be 1/2 way open).
1I. Once the stove is operating properly, complete
filling the hopper and run the unit for 30
minutes.
Page 12
INSTALLATION
Vent Termination Requirements
The termination of the outside chimney of the _oellet stove shall be located in accordance with the
llowing:
1. Higher than 3 ft. above any forced air inlet (air conditioner, etc.) located within 10 ft.
2. Not less than 4 ft. below, 4 ft. horizontally from or 1 ft. above any gravity air inlet
(door, window, etc.).
3. Not less than 2 ft. from an adjacent building and not less than 7 ft. above grade when located adjacent to the public sidewalks
(access).
4. Not less than 3 ft. below an eave or any
construction that projects more than 2" from the plane of the wall.
Corner
I
Rear Wall or Alcove
Note: Do not use class B venting intended for gas
appliances as a chimney or connector pipe on a
pellet fired unit.
Minimum Clearances to Combustibles
Side: 12"
Back: 1" Front: 48" horizontal from door
Single Wall pipe: 9" Maximum horizontal run: 36"
Offsets allowed: 2
I,
*- 12" Min.
.......... i
48" Min.
12" Min..=.)
Rove Face
---C
6" Max.
Alcove Clearances *
The MP35/50 pellet stove may be installed in an alcove with the following minimum clearances:
Alcove height: 72"
Side Wall Clearance: 12"
Back Wall Clearance: 1"
The stove cannot be recessed into the alcove more than 6" from the face of the stove to the plane of
the opening of the alcove.
Rear Wall orAlcove
Floor Protection
If placing units on a combustible surface, the following requirements must be met:
Residential Installation: No floor protection
required when installed on a solid level surface (no
carpe0.
Mobile Home Installations: The floor protection must cover the area beneath the stove and extend
one inch beyond the base on all sides.
* IF INSTALLED TO THE. MINIMUM SIDE
AND REAR CLEARANCES IN AN ALCOVE, REMOVAL OF THE APPLIANCE MAY BE
NECESSARY FOR SERVICING.
Page 13
T
Alcove
36" Max.
1
INSTALLATION
yentin_ Requirements There are several options for the installation and
venting of your pellet stove. Refer to clearances before ins_ing your stove.
Connect onlyone flue per appliance. When oassing _arough walls or .ce_!in_sl The manufacturer.
recommends that ctearances are maintained in
accordance with NFPA 21.1. Do not dowusize your connecting pipe or chimney.
Your NaturalFire pellet stove must be connected to a 4" oioe The preferred type of pipe is a listed
cbimn'e_ which co"nforms to- UL standard 641 or a single wall pipe, 26 gauge minimum. Single wall
connector pipe is limited to use within the room.of
installation; wall or ceiling penetrati.'on must be ..vg.m a listed vent pipe and a wall thimble or ceiling
penetration plate• Follow the pipe manutacturers mstallatinn instructions and clearances. ALl p!pe
joints must be sealed wi_ the compound supphe-d
with the pipe or a RTV silicone with a rating of at least 570°F.
You may connect the single wall or pellet vent to the top of the stove using three screws to secure it to
the collar. Use a RTV silicone with a rating of at
least'570°F, or interam to provide a complete seal.
Note: Single wall pipe can be used as a liner in a
class A, or masonry chimney.
Connection To A Masonry Chimney.
Be sure to verify the construction of a masonry chimney, as many have combustible framing.
Follow the pipe manutacturer clearances. An oversized chimney or high altitude may re.suit in
less than optimum performance. Inst911.atiom " mto a large, masonry cl_lmney may regutre a }mer to
improve performance. The use of single w_,. n.ex or rigtd (26 gauge galvanized or stainless steeu pipe as
a liner is approved.
Standard (Recommended)
The most desirable installation is Pellet Vent pipe connected to the top of the stove and run up throu_,h
the ceiling, then terminating above the roof line. pe
sure to follow all clearances listed by the pipe manufacturer.
Connection To An Existing Class A
Chimney
An adaptor can be used to make_e connection from 4" Pellet Vent pipe to existing UL cmmuey system. Verify with th_ pipe manufacturer that. your pipe brands will interconnect. Installauons rote a large
* . e
UL chimney system may reqmre a liner to unprov
-- -- _ r •d
performance. The use of single wall flex.or ngl
_26 gauge galvanized or stainless steel) pipe as a liner through a UL class "A" chimney is approved.
Page 14
INSTALLATION .-
Direct Vent
Although a direct vent flue is an approved
installation, the manufacturer recommends the outside flue should be installed with a cleanout "T",
and Pellet Vent chimney pipe run up through the cave. This will eliminate the possibility of siding
discoloration and/or to enhance performance in bad draw situations. Terminate the pipe using the
standard clearance. Exception: If using a UL listed
Pellet Vent pipe you may use the Pellet Vent
manufacturer's cleara/lces.
IF BURNING CORN, DIRECT VENT IS NOT AN APPROVED INSTALLATION.
IMPORTANT!! Never turn the Draft Fan Selector to the "OFF" position on any direct vent
installations. Keep the Combustion Fan Switch on
the Primary Control Board in the "Low" or High" position. In the event of a toss of power in a rear
vent direct termination application, natural draft is not present and you may receive smoke back in to the dwelling that will dissipate rapidly.
To Install
The MP35/50 can be converted to a direct vent by transferring the top flue outlet to the rear vent position. Replace the top flue outlet by using the
rear cover plate, removed from the back of the stove. Follow the directions listed below:
1. Lift off the top louvered trim (A) to access the
top flue outlet. Remove mounting nuts and
starting collar.
2. Remove right side heat shield by removing screws on rear flange to expose access opening.
3. Remove the rear flue cover plate located on the back of the stove.
4. Install the gasket (B) and starting collar (C) making sure the gasket is intact for a tight .seal. Replace nuts and tighten.
5. Place the rear flue cover plate over the top opening. Make sure the gasket is in place and
there is a complete seal. Replace nuts and
tighten.
6. Attach section of pellet vent pipe (D). Seal this connection with high temperature silicone
sealant. Secure the section of pipe with two sheet metal screws into the starting collar. One
up from the bottom at 6:00 position and one from the side through the access opening at the
9:00 position. The horizontal run may not exceed 36 inches..
When rear breaching, a trim kit is available through your dealer, part number TRK35. It consists of the
1) New louvered top trim, and 2) Two flue seal
gaskets (the additional gasket is provided in case of accidental damage during installation).
A) Top Louvered Trim Panel B) Gasket Material
C) 4" Starting Collar D) 4" pellet pipe, 24" section E) 4" Wall Thimble F) 4" Rain Cap
Page 15 '
INSTALLATION
Mobile Home Installation Requirements
Installation of the MP35/50 into manufactured housing must follow the instructions for residential
installation, with the following supplemental requirements per OAR 814-23-900 through
814-23-909:
.
No single wall pipe may be used as a connector or chimney. Pellet Vent pipe must be used from stove top to termination.
2. Maximum two offsets permitted.
,
The chimney must provide for a section joint so that any parts extending above 13' 6" from ground level can be removed for transportation
of the mobile structure.
o
The stove must be grounded to the mobile home
wailer frame with a No. 8 (minimum) solid
conductor.
5. The combustion air must communicate to the
outside air.
6. Floor protection must cover the area beneath the
stove and extend one inch beyond the base on all sides.
7. Structural members such as roof trusses or floor
joists cannot be cut or modified while making
the installation.
Outside Air Provision
Although this section applies to a mobile home
installation, it may also be required by local codes in
standard residential installations. Use the manufacturers optional outside air kit (part #85-35)
or equivalent.
1,
Set the stove in its irmtalled position and select
the floor or outside wail location for the outside
air penetration. The air ducting must connect
with the bottom of the motor cabinet of your stove, using rigid or flexible 3" duct.
2. Cut an opening for the outside air kit (Part
#85-35).
3. Install the outside air kit.
Outside Combustion -_-_"
Air Inlet
Page 16
INSTALLATION
Optional Installation Applications
Direct Vent Termination
<
m
Direct Vent Using a Cleanout "T"
Page 17
SIX STEP TROUBLESHOOTING GUIDE (Qualified Technicians Only)
Tools Essential For Troubleshooting
I. Stove Installation and Operation Manual.
2. Circuit Tester (Micronta # 22-101 or equivalent).
3. Molex Pin Extractor, I/8" (p/n # 15068).
4. Volt Meter.
ATTENTION: Before attempting any troubleshooting; I) Check your outlet to see that you do have
power and the outlet is wired properly (use circuit tester); 2) Check the flue for blockage; 3) Take the time to clean the stove; 4) Note the model number of the primary control board (ira model number is
not printed on the face of the primary control board, it is a model: Emerson.)
Step #1
Room Air Fan System Check
Turn the rheostat knob till it "clicks", it is now
"ON". In this position the'room air fan will operate
at full speed (115v). Place your hand in front of the air outlet to con.firm that air is coming out. Further
rotation of the knob will slow the speed of the room
air fan. On the lowest setting the fan receives approximately 65 volts. If the room air fan comes on and operates properly (as described), the source
of the problem will not be the rheostat, room air fan, fan speed disc, wiring connections or circuitry.
Should the room air fan fail to come on, the first step in finding the problem is to check the power source (using a circuit tester or simply plug a lamp or other small appliance into the outlet). Once it has
been determined that there is power to the outlet, the room air fan motor can be checked by removing the leads from the molex connector and connecting
them to a l15v power source. If the room air fan runs, the problem is a loose connection. If the
room air fan fails to run, replacement of the fan will
be necessary.
Step #2 Confirm Power to primary Control
Board
Turn main power switch from the "OFF" position to the "DRAFT FAN" position. If the red indicator
light comes on, there is power to the primary control board. If the light does not come on, check
the following:
A. Power source (see Step #1) B. Fuse
C. High limit manual reset discs
D. High limit auto reset disc
If the fuse is not blown and the high limit manual reset disc has not "popped out", inspect the molex connectors and be certain the pins are making
proper contact. Then, using a volt meter, check for power at the power switch. If the volt meter
indicates 115v and the red indicator light is not on, it will b e necessary to replace the primary control
board.
Page 18
SIX STEP TROUBLESHOOTING GUIDE- (Qualified Technicians On!y)
Step #3
Confirm Draft Fan Operation
Set the main power switch to the "DRAFT FAN" position
then set the fuel rate switch to the "FULL" position. The
drai_ fan should now operate at full power (aprox.ll5v).
During the piloting process, the draft fan will operate at
thefollowingspeeds:
Switch Position Voltage High 70-75v
Low 60-65v
Off 0v
To check the daft fan when the stove is cold, check for movement of air by placing your hand in or near the firepot If the movement of air is not obvious, inspect the
draft fan to be certain the air shutter is opera If the air
shutter is open and the draft fan is not running, check it by
usingtherroacedureinStep#Lr_-,agaph2.
Step #4
Inspect Fuel Metering Cup for Blockage
To inspect the fuel metering cup, FIRST:
UNPLUG THR, POWER CORD.
NEVER PUT YOUR FINGERS IN THE FUEL
CAVITY OF THE METERING CUP.
Remove all the fuel from the hopper. Reach down inside the hopper and rock the fuel metering cup back and forth
(beingewefulnottoputfingersin fuel cavity of metering
cup). The cup should move approximately 1/4" in either direction. If it does not move, something is jamming it (usually a foreign object) and will have to be removed by using one of the following methods:
A. Using a tool, such as a slotted s_tcv_ driver, clear the
obsm_on (between the fuel cavity of the metering cup and the blade).
, vity
Blade-/ " Obstruction
B. Locate the metering cup motor cooling propellor on
the back of the appliance and turn it by hand in the reverse direction until the metering cup rotates
back far eno,_h to clear the obsmx_don.
C. If procedures A or B fails to clear the obstruction,
then remove the metering cup motor and metering cup to find and clear the obstruction_
Step #5
Confirm Cup and Auger Motor Operation Set the main power switch to the "FEJ_r3 SYSTEM"
position. Press the "START' button. Both the cup and auger motor should start. If the motors run but the fuel
metering cup and/or auger does not turn, check the cast iron coupler on the ends of each motor shaft to make certainthe set serew is fight on the flat part ofthe shatL If
the motors are not Droning, use a volt meter to check for
line voltage (115v) at the molex connector or check them
by asing the procedure described in Step #1, paragraph 2. Note: Anytime you are checking the motors, you should
verify the speed at which the motors are turning. This can be accomplished by timing the revolu_on of the coupler. Using the set screw as a reference point, the bottom motor (auger) will make approximately one revolution in 10 seconds. The top motor (cup) will make approximately one revolution every 48 seconds.
step. j
Re-light The Stove Follow the nonnal start up procedure. If the unit fiil_ to
check to be certain th_ leads to the safety disc are
attached.
Page19
POWER FLOW DIAGRAM
_D
Fan Speed Rheostat
o) Blue ' _, '
a) . > Black
¢ Yellow
/ ), Black
/
>
Room Air Fan (s)
/-_ Blower
e_ _ Manual
_ / Reset
Control
BumerManualResetc_.c.) _ !_]fl_k-_p_ple (Insegs have auto reset) ._ __ _ ]
'l N '
-_ o/1_)) Auger 1.3 Draft Fan_. M_.,or ,
(Combustion Fan)
Thermostat
Wires
Fan. Speed Disc
60T13 L140-20F P/N 15057
Blower Manual Reset 60T14 L200-40F P/N 15011
Burner Manual Reset 60T14 L200-40F P/N 15011
Safety Disc 60T12 F110-20F P/N 11565
Page 20
WIRING DIAGRAM -,Model MP35/50
Control Board
(P)
T87F Tha'mostat I
Wall Plate
white (c)
Fan Spe_xi Conh'ol Rheostat
_Brown (P).
ak
Comnlon = C
Power = P
* Gray wires to control board arc for factory testing only.
_;=_) (P)(c) 115 Volt A.C. Power Supply
_ must have proper polarity.
_-" Green (Ground)
(C_ [_ _., Whit_(C)
a_ _ _ -- Black(P)
r--_ Cr," ) "
i ii el i i k _ |
o_.g_ IV'X"& I
T . _
Manual
Reset
Yellow
_X______Isck(C) ,,, ,.....
I (c) \ -_k___
tt.---._(p)
_., (P)
Blue
(('" (P) ") g
S_'ety Di_
Page 21
GLOSSARY OF TERMS
AUGER The auger transfers the fuel down the
burner tube into the firepot.
AUGER MOTOR The auger motor drives the
auger to deliver fuel to the firepot.
BLOWER HIGH LIMIT MANUAL RESET If
the temperature of the stove reaches 200°F, the high limit manual reset will "POP" and stop the
flow of electricity to the fuel feed system. This disc will require resetting by pressing the red button until it locks in (see page 24 showing location).
BURNER HIGH LIMIT MANUAL RESET If
the temperature of the burner area reaches 200c' F, the flow of electricity will be stopped to the feed
system. This disc will require resetting by pressing the red button until it locks in (see page 24 showing
location):
BURNER TUBE The burner tube contains two passageways; one for the auger and the other for
combustion air. This tube supplies both the fuel and;combustion air to the firepot.
cuP MOTOR' The cup motor drives the fuel
metering cup to deliver fuel to the auger.
DRAFT FAN pushes air into the firepot for
combustion and into the flue for draft.
FAN SPEED DISC At stove temperatures above
1400 F, the fan speed disc activates, by passing the
rheostat causing the room air fan to run at full speed.
FIREPOT The firepot is where combustion
OCC_.
FUEL METERING CUP The fuel metering cup meters the amount of fuel and delivers it down to
the auger. The cup will deliver a set amount of fuel.
HOPPER . The hopper is where the pellets are stored and funneled down to feed the fuel metering
cup.
MAIN POWER SWITCH The main power switch allows electricity to flow through the
primary control board to the cup motor, auger motor and dra_ fan.
RHEOSTAT The Rheostat controls the speed of the morn air fan. To vary the speed of the room air
fan, rotate the rheostat dial to the desired setting. When the insert is hot (stove temperatures above
140° F.), the rheostat override (fan speed disc) will
automatically run the fan on high speed to prevent the insert from overheating.
SAFETY DISC At stove temperatures above 110 °, the Safety Disc engages to allow electricity to
flow to the Fuel Feed System.
Page 22
SPECIFICATIONS - Model MP35/50
Approx Sq Ft Heat Capacity Up to 1800 Sq. Ft.
Flue Size 4" Top/Rear
Width 24"
Depth Overall 33"
Height Overall 33.5"
Height 31.75"
Floor to Rear Flue Center 17.5"
*L.H.Side of stove
to cntr/flue 4.25"
Outside Air Provision Yes
Floor Protection Requirements
Mobile Home
Residentia
Fuse
Hopper Capacity
Heat Input (Max.)
Ship Weight
Room Blower
Cup Motor
Auger Motor
Draft Fan
Yes
** No
3 amp
55 Ibs
35,000-50,000 BTU/hr
350 Lbs.
210 CFM 1.2 amps
Approx. 1 RPM .34 amps
Approx. 6 RPM 1.12 amps
Approx. 60 CFM .65 amps
Viewed from behind unit, facing forward.
If instaUed on a solid level surface (no carpet).
-ll ¸
17 1/4"
_-'--- 21" ,I
25 3/4"
127/
¢----
_---"_ 21'"-'------_
24'
30"
12 3/4"
31 3/4"
Page 23
COMPONENT DIAGRAMS
Top Vent
Outlet
Gold
Ash I
f ""-D_
____ o I I o
l l
Hopper --_ _..__.
,Rear Vent Outlet- _ _ _.
Burner Manual Reset (15011)_
(Shown with motor cabinet removed)
l_ Safety Disc (11565)
-]_ Blower Manual Reset (15011) _-" Fan Speed Disc (15057)
" Cup Motor (15060)
_ Auger Motor (15070) +
Room Air Fan (16492)
Control Board C
Rheostat (528)
Motor Cabinet
Power Cord (02071)
Page 24
The Earth Stov
Pellet Appliance
Limited Warranty
WHO IS COVERED:
The original purchaser.
WHAT IS COVERED:
WHAT YOU MUST DO TO OBTAIN WARRANTY
SERVICE:
Contact your selling dealer. Provide the following information to the dealer;, Model number, Serial number,
Date of Purchase, and Place of Purchase (if different).
100% of all parts to be free of defects in materials and OR
workmanship (except marble, and glass).
FOR HOW LONG:
One year from date of purchase. Marble is covered for 90 days.
Glass is covered for 30 days.
ADDITIONAL COVERAGE:
Electrical par_ are covered 100% for two years from
date of purchase.
The stove body, door flame, and heat exchange tubes are covered year two through five at the current retail price at
time of repair or replacement, according to the schedule below:
Year 2 - 80% coverage Year 3 - 60% coverage
Year 4 - 40% coverage Year 5 - 20% coverage
Year two through five coverage excludes:
Gaskets/Rope
Baffles
Paint
Logs Firepot
WHAT IS NOT COVERED:
* The cost of inspection
* Adjusmaents to the stove
ALL THE ABOVE MUST
PURCHASER.
Prior to repair or replacement, send the defective part (Freight Prepaid) with the above information to:
The Earth Stove, Inc.
10595 SW Manhasset St.
Tualatin, OR 97062
IMPORTANT: THIS WARRANTY IS NOT VALID UNLESS:
The warranty registration card has been properly completed and returned within 30 days of
purchase.
The defective stove or part(s) are promptly
delivered, with ALL FREIGHT AND HANDLING CHARGES PREPAID, to The Earth
Stove, Inc. or oar authorized dealer from which the stove was purchased.
When returning parts for warranty, do not cut
wires, alter or disassemble part(s).
The appliance must be installed by a Qualified
Technician.
We shall not be liable for incidental or consequential damages or commercial loss, nor for any loss or damage except as set
forth in this warranty. This warranty gives you specific legal rights and you may
have other rights which vary from state to state. Some states may not allow the limitations or exclusions set forth so the limitations or exclusions may not apply to you. N ° person is
authorized to extend or enlarge any liability or obligation which we may have in connection with the sale of the stove.
RETAIN THIS FOR YOUR RECORDS
Model
Removal and reinstallation costs, shipping costs to and * Serial Number. from factory and or authorized service center. Dealer
Date of Purchase.
Shipping damage, improper handling, improper operation, misuse, abuse, neglect, accident, damage from * Serial Number Locations
improper installation, alteration, or unauthorized service.
Freestanding - on the back, above motor cabinet
BE BORNE BY THE Insert- inside hopper loading lid.
Page 25
SAFETY/LISTING LABEL
5_ALLAT1Cfl MUST m=MACEtNACCORDANCEWITHLDOM.COO_SA_ THEMAflUFACTURE.q'sg(STALLA'DONINS_UCTI_ OgTAiNAPERMIT.
L'iNSTALLkl'ION(X31TETREFAIr EHCOMFORMANTAL0[CODESLOCALESET LJESINSTIKICTIONSD(JFABAICANT,ONDOlTOBTEN_ UN PE_MIS.
Idan,_ac_,d by/Pmdultpar
TFEEAR]14STOVE,U_C, 10_16SW_ Cr.
Thoy_r_rantt_ it_ a dupSc_ colthe modelbm.'cL gsSwz_n_ quec'mit u_ d_* du_dd* ¢Lu*mitmo_ze.
Tistb_ andlts_ngrecmj_lon is _dd If5_slal:dIs nun_ ot the unit IsnotImMled acco_l_ to direr.
Lesepreu_H_ r_c_lfte #e con_ sort nU_ dce ma_m esterrk,ve ou sl_elomne_ n'_
paslr_u,e se_n lesirs_u_on_
PelletFiredStc_e F_meau: Bru_ DesOoulettes
MINIMUMCLE.AP,ANCETOCOMBUSTIBLES
aodeJ Numbu'_ 35-.ZO be Modelet_urnemMP35-50
Cornnuy be usedzs a_ when fire p_LpertnumberCP-1Isinstalled.
On FeutemFIoye_lehied'lndl co.me ¢¢_nbus_ablequandle potdefeu l le 1_ _m_o CP-1 _
Ir_e.
APPROVEDFUEL: Pdletbedblcmlas_1/4"_ _ BTUAb,,10% moisturecontent,I% ash, firingi 40,0_)BTU/nr.
LE COMBUSTIBLEAPPR_VE: be 8iomzssdesboulet/em(1/4"de dta.,10%vdumed'numide,ILSC0
8TUdb.1%deIrene, tau_defeude40,000S1_h_.)
DOn_ o_st_ct thespaceunderheater, I _'obst_z _ I'es_aceso_s Inf_Jn*d
16" 1" |
22"
WARffiNG
* iX) NOTINSTALLINA S_F.._rNGRDOU.
DONOTOPERATEWITHFIREBOXIX)OR OPEN.
b_SPECT,CLEANHEATEFI,AN9 VENTSYSTEMREGULARLY.
DONOTOPRRATET_4SUNITUi'_JES_YOUAREFAM[UARwm.i THEPROCEDURE.
* NEVERADOPELLETSBYHANDTOASMOLDERINGFIRE.
SUITA_UEFORRES_DENTIALORMOB_.EHOMEI_STALLA_,OFIS
SU_z_ formobilehomeFnstflladon; muslusamJldO_rair Idtp_rtnumber_.35. Ahea_ extensionis reqdredtos.a'_d_h_lw-,Jre.e_Jl_o_u.S_ J_ lnslructloe_
D(_ UNITEDSTATES:Conn_-t to =lnimum 4"dbLrecognizedclassL _inu_y with4" ell _l_m_*d st_l p_, Z4_. mln. _ meal _P SS.50.
AUCAK4DA:Em_oye_seuk_ kes_mpoeumud'eventerde "£ARTHSTOV£': Ave_Ledh_da4"_ La#_e d_t eb'etrader ga_lse.
Replace_a_moelywflhceran_:g_au I_rtnumbe_(_000-7. RempLzcezle v_meseulemeMawc In vibescenm_klz_s,ke_r t numem629Q0.1.
POWER'AE_JmEUENTS:$Amp_ vol_, _ H*.
AV_'nSSEMENT
* N'IN_TALL.ERpAr_AUNECHAMSREACOUCH_R.
NEMPt.OYEZPASQUANOLAPORT_DUPOTDE_U ESTOLIVEKFE. * VE_IF1EZETNETTOy_ZLIEFOURHEAUETLESYSTEME17EVENTERAVECASStD_jETF_
WOPRREZPASCE FOURNEAUSALg:OUEVOUS COflNAISSEZDEL.APROCEDURE. , W.I_)OUTF.RJAMAB PARLEMAD(AUNFEUDE COMBuffrIONI.ENTE.
CAUTICH:HOT_ IN 0_c_A_OK 00 NOTTOUCH.KEEPCHILDREN,CL01_ING
F_RNII_J_EAWAY.CONTACTMAYCAUSESIQNBUI_i$. SE_ NAMF.P_..ATEANDINSTTtucnoNs.
kVERTISSEMENT:LE FOURNEAUESTCHAUDENOPERANT.NELE TOUCHEZPAS.HEPERMETTI
PASDE[2 TO_: L£SENFANTS,tIESHABITS(3ULES MAUBLES.SI ONLETOUCHEAVECL2 PEAU,ONPEUTETREBRULE.VOYEZLESb_ISI_JC11CNSETLEPt._T NOM.
Listed by
OR. USA TUALATIN, OR 97062
MODEL: MP 35-50 PELLET FIRED STOVE
Beaverton, MFG: THE EARTH STOVE, INC.
1MNI
sE.,...o.8,i I
THIS PELLET FIRED HEATING APPLIANCE HAS BEEN CONSTRUCTED, TESTED AND LISTED FOR USE IN STANDARD
RESIDENTIAL CONSTRUCTION IN ACCORDANCE WITH THE APPLICABLE UL STANDARDS AND FOR USE IN MANUFACTURED
DWELLINGS ACCORDING TO OREGON ADMINISTRATIVE RULES 918-520-010 THROUGH 918-520-110.
SEE MAIN LABEL AND INSTRUCTION BOOK FOR INSTALLATION AND VENTING REQUIREMENTS• THE MANUFACTURER WARRANTS
IT IS A DUPLICATE OF THE MODEL TESTED.
Page 26
SERVICE AND MAINTENANCE LOG
Service Service Service Date Technician Description
Page27
LENNOX HEARTH PRODUCTS 1110 West Taft Ave.
It Orange, CA 92865-4150
Phone: (714) 921-6100
Loading...