Proper installation and servicing of the EarthLinked® Heat Pump is essential to its reliable
performance. All EarthLinked® systems must be installed and serviced by a technician authorized by
Earthlinked Technologies. Installation and service must be made in accordance with the instructions
set forth in this manual. Failure to provide installation and service by an ETI authorized installer in a
manner consistent with this manual will void and nullify the limited warranty coverage for the system.
Earthlinked Technologies shall not be liable for any defect, unsatisfactory performance, damage or
loss, whether direct or consequential, relative to the design, manufacture, construction, application or
installation of the field specified components.
phone: 863-701-0096 | toll-free: 866-211-6102
General Info: info-question@earthlinked.com
PSD-QS (02/16) Page 5
Earthlinked Technologies, Inc.
4151 S. Pipkin Road
Lakeland, Florida 33811 USA
www.earthlinked.com
CSI # 23 80 00
Page 6
Safety
IMPORTANT!
serious injury or death, or equipment or property damage.
if not avoided, may result in injury, or equipment or property damage.
IMPORTANT!
initiating the Start-Up procedure.
Warning, Caution and Important notices appear throughout the manual. Read these items carefully
before attempting installation, servicing or troubleshooting the equipment.
Notification of installation, operation or maintenance information which
is important, but which is not hazardous.
WARNING!
Indicates a hazardous situation, which if not avoided will result in
CAUTION!
Indicates a potentially hazardous situation or an unsafe practice, which
Equipment Manuals
The following is a listing of the equipment installation manuals that are provided with each component
specified for this EarthLinked® system.
Read and follow all installation instructions in these manuals,
appropriate for the EarthLinked® system being installed, BEFORE
Series AVS and AVV Air Handler
Series CCS Cased Coil
Series HCM Hybrid Cooling Module
Series GSTE Storage Water Heater
Earth Loop Specification and Installation Manual
Earth Loop Protection Kit Installation Manual
PSD-QS (02/16) Page 6
Page 7
Installation
Prime
Compress.
Unit1
Air Handler
Cased Coil
Hybrid Cooling
Module
Earth Loop2
ETI
Model
Arcoaire
Model
ETI
Model
Arcoaire
Model
-025
AVS-0025-C*
FEM4P3600AL
CCS-0025-C*
EAM4X36L21A
HCM-1836C
-024-C
-030
AVS-0030-C*
FEM4P4200AL
CCS-0030-C*
EAM4X42L24A
-030-C
-036
AVS-0036-C*
FEM4P4800AL
CCS-0036-C*
EAM4X48L24A
-036-C
-040
AVS-0040-C*
FEM4P4800AL
CCS-0040-C*
EAM4X48L24A
-042-C
-050
AVS-0050-C*
FEM4X6000BL
CCS-0050-C*
EAM4X60L24A
HCM-4272C
-048-C
-060
AVS-0060-C*
FEM4X6000BL
CCS-0060-C*
EAM4X60L24A
-060-C
1. Contained in each compressor package:
compressor unit
four L-shaped hold down brackets
product literature
2. All series Earth Loops
Warning!
AND/OR PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1) Component Matching
Upon receipt of the equipment, carefully check the component model numbers by referencing
Figure 1, to ensure that all components of the system match.
Figure 1. Matching Component Model Numbers
WEAR ADEQUATE PROTECTIVE CLOTHING AND PRACTICE ALL
APPLICABLE SAFETEY PRECAUTIONS WHILE INSTALLING THIS
EQUIPMENT. FAILURE TO DO SO MAY RESULT IN EQUIPMENT
Guidelines for the general layout of the system components are shown in Figure 2. Before placing the
compressor unit (outside or indoors), review the guidelines in Figure 2.
PSD-QS (02/16) Page 7
Page 8
Figure 2. General Layout of System Components
2) Compressor Unit Placement
EarthLinked® compressor units may be located inside or outside. If outside, place
compressor unit on a standard HVAC outdoor unit pad. If inside, place it on a level, hard
surface. If the compressor unit is to be fastened down, see Figure 3 for bracket
installation.
Avoid placing the compressor unit in or near the living area of the residence.
Attic installations must include a condensate pan with drain, and suspension from rafters
with suspension isolators.
Clearance around the unit for service is illustrated in Figure 4. However, local codes and
applicable regulations take precedence.
PSD Compressor Unit must be placed in an environment in which the surrounding air
temperature does not drop below 40°F.
If the compressor unit or other refrigerant-containing system components are located
indoors, they shall be in a location which (1) is an unoccupied space, or (2) is served by
the circulating air system, or (3) provides 280 cu. ft. of open space per nominal ton of rated
system capacity. The 2012 International Mechanical Code defines residential occupancy
as including permanent provisions for living, sleeping, eating, cooking, and sanitation.
Consult local code authorities to define unoccupied space for the specific installation.
PSD-QS (02/16) Page 8
Page 9
Figure 3. Compressor Unit Bracket Installation
IMPORTANT!
when required by the performance tables.
Figure 4. Compressor Unit Clearance
Placement instructions for other pieces of equipment that make up the EarthLinked® System are
included with those pieces of equipment and are listed in this manual under Equipment Manuals.
3) Refrigeration
After the EarthLinked® compressor unit and other system components are placed, the refrigeration
system tubing is run from the compressor unit to the other components, as appropriate. Figure 5
illustrates the refrigeration and electrical connection points for the compressor unit.
EarthLinked® compressor units that provide space cooling shall be
equipped with an EarthLinked® Hybrid Cooling Module (HCM) when:
(1) Required by the performance tables OR where BOTH of the
following circumstances occur:
(2) Ambient outdoor temperatures have exceeded the outdoor summer
design temperature conditions for a continuous system run time of
at least 7 hours, coupled with the conditions described in (3).
(3) Low thermal conductivity soils that do not effectively absorb and
dissipate heat. Examples of such soils are light dry soil or dry
sand, peat and organic soils dry clay soils and hardpan.
ALSO
EarthLinked® compressor units that provide space heating shall be
equipped with a Heating Performance Enhancement (HPE) control
PSD-QS (02/16) Page 9
Page 10
PORT
FUNCTION
TYPE OF
CONNECTION
SIZE, INCHES
-025
-030
-036
-040
-050
-060
A
Electrical, Power
1-1/4” Hole
1 1 1 1 1
1
B
Electrical, Control
7/8” Hole
3/4
3/4
3/4
3/4
3/4
3/4
1
AH/CC/HWM Liquid
Braze
1/2
1/2
1/2
1/2
1/2
1/2
3
EL Liquid*
Braze
3/8
3/8
1/2
1/2
1/2
1/2
4
Anode Socket
---
---
---
---
---
---
---
5
EL Vapor*
Braze
5/8
3/4
3/4
3/4
7/8
7/8
6
AH/CC/HWM Vapor
Braze
3/4
3/4
3/4
7/8
7/8
7/8
7
DWT Supply
Braze
1/2
1/2
1/2
1/2
1/2
1/2
8
DWT Return
Braze
1/2
1/2
1/2
1/2
1/2
1/2
9
Electrical, control
---
---
---
---
---
---
---
10
Electrical, control
---
---
---
---
---
---
---
N = Nameplate and other information
*Line set sizes with provided compressor unit adapters
LEGEND
AH – Air Handler
CC – Cased Coil
EL – Earth Loop
HWM – Hydronic Water Module
HWT – Hydronic Water Tank
DWT – Domestic Water Tank
PSD-QS (02/16) Page 10
Figure 5. PSD Connections
Page 11
Compressor units are shipped from the factory with a low pressure nitrogen holding charge. Carefully
adversely affect system performance and cause system failure.
Caution!
possible system failure.
relieve the holding charge when the compressor unit is being prepared to connect refrigerant system
piping.
This compressor unit is equipped with Copeland Ultra 32-3MAF Polyol
Ester Oil (POE). This is the only brand and type of oil that is
recommended for use with ETI compressor units.
POE oil absorbs significant amounts of moisture from the air very
rapidly. Exposure of the POE oil to air must be minimized. Even a few
minutes of exposure to air can be harmful to the system.
After the initial nitrogen holding charge has been released from the
compressor unit, it is critical that air not be allowed to enter the
compressor unit during the process of preparing compressor unit
To ensure air does not enter the compressor unit while preparing
refrigerant connections, “trickle” dry nitrogen through the compressor
unit, entering at the access port nearest the Active Charge Control
(ACC), to keep airborne moisture out of the compressor unit and the
POE oil.
Complete preparing and brazing all compressor unit refrigerant
connections at one setting to minimize exposure of open connections
to air. Failure to implement the above precautions will result in an
extended period of time to effectively evacuate the system, and may
REFRIGERANT PIPING CONNECTIONS
Refrigerant joints are to be brazed with 15% silver content brazing
alloy, utilizing the NITROGEN BRAZING PROCESS.
NITROGEN BRAZING PROCESS
PURPOSE:
Utilize the NITROGEN BRAZING PROCESS on all brazed refrigerant
piping connections. This process eliminates oxidation products from
inside joint surfaces.
TECHNIQUE:
“Trickle” nitrogen gas at 1-2 psi pressure through the joint area being
brazed, to displace the oxygen. When oxygen has been displaced,
turn off the nitrogen, and relieve the pressure at the joint to
atmospheric prior to brazing.
CONSEQUENCES:
Failure to displace oxygen with nitrogen at the brazed joint will result
in particulate matter being released into the system. The result is
discoloration of refrigerant oil, contamination of the system and
PSD-QS (02/16) Page 11
Page 12
The compressor unit has factory installed service valves on the earth loop vapor and liquid stubouts,
LINE SET ADAPTERS REQUIRED FOR THE AIR HANDLER, CASED COIL, HYDROINIC
WATER MODULE AND DOMESTIC WATER MODULE ARE FIELD SUPPLIED. CHECK ALL
APPROPRIATE COMPRESSOR UNIT STUB-OUT TUBING SIZES FOR REQUIRED FIELD
SUPPLIED ADAPTERS!
EARTHLOOP, AIR HANDLER, CASED COIL LINE SETS
HWM LINE SETS
COMPRESSOR
UNIT SIZE
LINE SET O.D., INCHES
HWM
MODEL
LINE SET O.D., INCHES
LIQUID*
VAPOR*
LIQUID*
VAPOR*
2.0 Tons (-025)
3/8
5/8
-1836
3/8
1/2
2.5 Tons (-030)
3/8
3/4
-1836
3/8
1/2
3.0 Tons (-036)
1/2
3/4
-1836
3/8
1/2
3.3 Tons (-040)
1/2
3/4
-4248
1/2
5/8
4.2 Tons (-050)
1/2
7/8
-5472
1/2
5/8
5.0 Tons (-060)
1/2
7/8
-5472
1/2
3/4
*Liquid and Vapor lines must BOTH be insulated with Armaflex® or equivalent with at least 1/2” wall thickness for the full
length of the line set.
outside the compressor unit.
For the installation of system components requiring refrigeration connections, refer to Figure 6 for line
set sizes and the appropriate installation manual(s) following Figure 6.
Figure 6. Line Set Sizes
Series AVS Air Handler
Series CCS Cased Coil
SD Series Heating Option Kit, SDHO-1872
Series HCM Hybrid Cooling Module
Earth Loop Specification and Installation Manual
After installing and nitrogen brazing the HVAC system components and compressor unit service
valves, turn the Service Valves to Full Open and pressurize the refrigeration system to 150 psig with
dry nitrogen and a trace of refrigerant. Valve off the nitrogen Tank from the HVAC system
components and check joints with a sensitive Electronic Leak Detector to ensure they are sealed.
Repair any leaks and re-test as appropriate.
PSD-QS (02/16) Page 12
Page 13
4) System Applications and Electrical
The PSD compressor unit electrical box major components and electric data for all compressor sizes
are shown in Figure 7.
The SureStart Module is a factory installed component that (1) reduces compressor starting current
and (2) reduces compressor starting torque, thus reducing stress on the compressor at start-up.
The Earth Loop Protection Control System, comprised of the EPS Power Supply, EPS Module and
EPS Fuse is in the contained within the electric box. This system is factory wired and ready to be
connected to the anode wire through an external electrical connection on the backside of the
compressor cabinet. The anode wire connection is detailed in a later section of this manual.
PSD Heating and Cooling System electrical and application illustrations are as follows.
Figure 8. PSD Compressor Unit Electrical Schematic, 230-1-60
Figure 9. PSD Compressor Unit Electrical Schematic, 230-3-60
Figure 10. PSD Air Heating/Cooling/Water Heating System Application
Figure 11. PSD Air Heating/Cooling/Water Heating System Field Wiring Diagram
MFS = Maximum Fuse or HACR Circuit Breaker Size
(External)
AWS = Consult NEC and Local Codes
Figure 7. PSD Electric Box Components & Electrical Data
PSD-QS (02/16) Page 14
Page 15
Figure 8. PSD Compressor Unit Electrical Schematic, 230-1-60
PSD-QS (02/16) Page 15
Page 16
Figure 9. PSD Compressor Unit Electrical Schematic, 230-3-60
PSD-QS (02/16) Page 16
Page 17
Figure 10. PSD Air Heating/Cooling/Water Heating Application
PSD-QS (02/16) Page 17
Page 18
Figure 11. PSD Air Heating/CoolingWater Heating Field Wiring Diagram
PSD-QS (02/16) Page 18
Page 19
5) SureStart
Features
SureStart is a factory installed soft starter that reduces light flicker caused at start-up by scroll
compressor motors. This control has the following features:
60 to 70% reduction in direct in-rush current
Under voltage protection
Motor reversal protection
Self-adjusts for optimal start performance
50/60 Hz compatible
ETL, CE, EMC and RoHs compliant
Tolerant to “dirty power” conditions
Fault LED
Internal current limiting
SureStart is factory wired for the appropriate power supply.
Operation
When the system control calls for compression operation, the compressor contactor will energize. If
the supply voltage is less than “minimum start-up voltage”, a 50 second delay is initiated. At the end
of the delay, another attempt will be made to start the compressor unless the supply voltage remains
unchanged. See Figure 11a for the SureStart Mode of Operation.
SureStart uses an optimated starting process that learns the starting characteristics of the
compressor to further refine the starting cycle on each recurring start.
If the compressor fails to start, the module will terminate the start attempt after 1 second and initiate a
3 minute lockout before attempting a restart.
While the compressor is running,, if supply voltage falls below the “shutdown on low voltage” limit for
2 seconds, SureStart will stop the compressor and initiate a 3 minute lockout. A restart will be initiated
after 3 minutes if the supply voltage is equal to or greater than the “minimum startup voltage”. This is
done to protect the compressor against a sudden drop in supply voltage.
SureStart is able to detect an interruption in power, when the interruption is 0.1 seconds or longer.
When a power interruption is detected, it will shut down the compressor for 3 minutes. A power
interruption that is shorter than 0.1 seconds may result in the compressor running backwards.
SureStart is able to determine if the compressor is running backwards. If this condition is detected,
the control will stop the compressor for 3 minutes before restart is initiated.
If the run capacitor if faulty or has failed, SureStart will shut down the compressor for 3 minutes before
initiating a restart.
PSD-QS (02/16) Page 19
Page 20
Figure 11a. SureStart Mode of Operation
PSD-QS (02/16) Page 20
Page 21
Flash Codes – Single Phase
LED Flash Codes
A Red LED indicator will flash under the following conditions. [NOTE: LED fault indicator is turned
off in normal running mode.]
a) Rapid Flash (10 / sec) : Low Voltage
b) Triple Flash Every Three Seconds (3 / 3 secs): Lockout on Three Failed Starts
c) Slow Flash (1 / 3 secs): Lockout on Over Current
d) Slow Steady Flash (1 / sec): Cycle Delay / Fault Mode
Flash Code (Rapid Flash (10 / sec) : Low Voltage)
- Displayed for “Low supply voltage” before or after a softstart.
- If Low voltage is detected before a start, a re-start is attempted after 50 seconds.
- If Low voltage is detected after a start, a re-start is attempted after 3 minutes.
Flash Code (Triple Flash every three seconds (3 / 3 secs): Lockout on Three Failed Starts)
- Displayed after failure to start on “Three consecutive start attempts”.
- Re-start is attempted after 50 minutes.
- Standard lockout period is revised to 3 minutes after a successful start.
In circumstances where the compressor may have seized or is unable to startup due to failure of
other components in the HVAC system, the software will check for three consecutive failed starts.
On the third sequential failed start, the program goes into Lockout for 50 mins. On failing to get a
good start even after 50 mins, it will re-attempt start again after duration of 50 mins. Once a good
start is eventually achieved, it will reset the hardstart counter and will require 3 failed starts again
to force it back into Lockout mode. Lockout can be cleared anytime through a power reset of the
SureStart device.
- Displayed for “Overcurrent” in running mode of the compressor motor.
- Overcurrent limit is “25A for 08-16A version” and “50A for 16-32A rated version”.
- Also displayed, if internal Klixon of the compressor trips out on overheat.
- Re-start is attempted after 10 minutes.
To limit the current in compressors from extending abnormally beyond its stated capacities,
SureStart is also equipped with Overcurrent limit protection. For models rated from 16-32A,
SureStart is designed to trip out in overload conditions exceeding 50A. In smaller models, it is
designed to cutoff power to the compressor if the current drawn exceeds 25A. On overcurrent
lockout, SureStart attempts a re-start automatically after 10 minutes.
Both failed start lockout and overcurrent limit protection have been designed to prevent the
compressor from drawing abnormal currents in conditions not feasible for the compressor
operation.
- Displayed for “Cycle delay” between two consecutive softstarts or other faults mentioned
below.
- Re-start is attempted after a default period of 3 minutes.
- Other possible reasons for this Fault mode indicator can be due to
- a failed Softstart attempt,
- intermittent power loss (duration longer than 100ms),
- frequency out of range
Flash Code (Low Voltage / Over Voltage: (2 / 2 secs))
- Displayed for “Low supply voltage” or “High supply voltage” before or after a softstart.
- If voltage is out of range before a start, a re-start is attempted after 50 seconds.
- If voltage is out of range after a start, a re-start is attempted after 3 minutes.
PSD-QS (02/16) Page 22
Page 23
6) Internal Heat Recovery System
The PSD compressor unit has a built-in heat recovery system which provides supplemental domestic
water heating at a significant operating cost savings. The heat recovery system operates throughout
the year to provide free hot water when operating in cooling mode and reduced cost hot water when
operating in the heating mode. The heat recovery system supplements hot water production, but
does not replace the standard storage water heater sized for the application.
The heat recovery system may be plumbed into an existing standard water heater as illustrated in
Figure 12.
Figure 12. Standard Storage Water Heater – Service Connections
Alternatively, the heat recovery system may be plumbed to the ETI Series GSTE storage water
heater as shown in Figures 13a and 13b. The Series GSTE storage water heaters are preferred
because the heat recovery system ports are designed to provide more efficient heat exchange within
the storage water heater.
PSD-QS (02/16) Page 23
Page 24
Figure 13a. GSTE Storage Water Heater - Service Connections
Figure 13b. GSTE Storage Water Heater – Tank Top View
PSD-QS (02/16) Page 24
Page 25
The PSD compressor unit internal heat recovery system contains a water high temperature control. It
ΔT
30
40
50
60
70
80
90
GPH
62
46
37
31
26
23
21
*ΔT in ºF; GPH in U.S. Gallons per hour.
WARNING!
is factory set to 140°F. The heat recovery system also contains a refrigerant low temperature which is
factory set to 130°F. Also, a freeze protection control is designed to operate the circulating pump
when water temperature drops to 40°F, in order to provide water circulation independent of
compressor operation.
The GSTE storage water heaters are available in 60, 80 and 119 US gallon capacities, all of which
have a 4.5 kW electric heating element, which provides the following recovery rates for increases in
water temperature.
The PSD compressor unit and associated water piping must be in an
environment maintained at a temperature of at least 40°F to avoid the
potential freeze-up problems which can cause equipment failure and
damage to the occupied structure.
PSD-QS (02/16) Page 25
Page 26
Earth Loop Protection System
WARNING!
All power of the EarthLinked® System is to be shut OFF at the disconnect while
1) Anode Wire Installation
Prior to this, the below grade installation of the DIRECT AXXESS® Earth Loop System, including the
Earth Loop Protection System anode and anode wire has been completed per the Earth Loop Protection Kit Manual, and at this point the anode wire is ready to be connected to the compressor
unit.
The earth loop protection system connection to the anode wire is on the back side of the compressor
cabinet as illustrated in Figure 14, showing the electrical socket with the sealing cap.
Figure 14. Compressor Cabinet Socket/Cap
The EPS-KIT contains the plug connector, which will be field assembled and connected to the
anode wire.
The steps to install the anode wire to the plug connector assembly are as follows.
Remove the sealing cap assembly tool from the compressor unit cabinet shown in Figures 14 and
15. Using the sealing cap assembly tool, as shown in Figure 15, unscrew the locking ring from the
plug connector assembly to access the plug insert. Then, remove the gland nut, gland cage,
and gland from the other end of the plug body as shown in Figure 15.
field wiring the Earth Loop Protection System. Failure to do so may result in
serious injury or death, or equipment or property damage.
PSD-QS (02/16) Page 26
Page 27
Figure 15. Disassembled Plug Connector
PSD-QS (02/16) Page 27
Page 28
Strip the insulation from the multi-strand anode wire back approximately ¾ inch from the end and,
while keeping the strands together, push the anode wire through the gland nut, gland cage, gland
and plug body as shown in Figure 16. Loosen one of the two screw terminals on the plug insert to
receive all of the strands of anode wire on one terminal.
Figure 16. Anode Wire Insertion
After inserting all strands of the anode wire into one of the terminals on the plug insert, tighten the
wire in place by tightening the screw on that terminal. Once tightened, push the plug insert back into
the plug body as shown in Figure 17 until it is firmly seated. Engage the locking ring with threads in
the plug body and turn clockwise with the sealing cap assembly tool until the lock ring is firmly
seated and tight against the plug insert.
PSD-QS (02/16) Page 28
Page 29
Figure 17. Install the Plug Insert
Slide the gland forward on the anode wire until it is firmly seated in the plug body as shown in Figure
18. Next, slide the gland cage over the gland, and slide the gland nut firmly against the gland cage, with the gland nut against the plug body. Engage the threads of the gland nut with those
inside the plug body and manually thread the gland nut clockwise by hand.
PSD-QS (02/16) Page 29
Figure 18. Engage the Gland Nut
Page 30
Once the gland nut has been hand tightened into the plug body, use two adjustable wrenches to
further tighten the gland nut until it is snug in the plug body as shown in Figure 19 and the anode
wire is held firmly in the plug body and will not slip out. Do not over-tighten the gland nut!
Figure 19. Secure the Anode Wire.
After the plug and anode wire have been assembled, re-connect the sealing cap assembly tool to
the socket on the compressor unit cabinet. After aligning the electrical contact pins, manually
engage the threads on the plug locking cap with the threads on the socket and turn clockwise until
the plug is firmly hand-tightened to the socket as shown in Figure 20. If the anode wire rises away from the compressor cabinet, be sure to shape a drip loop into the contour of the anode wire near
the plug and socket.
After the plug and socket joint is secured, the power may be turned ON at the disconnect.
PSD-QS (02/16) Page 30
Figure 20. The Plug and Socket Joint
Page 31
2) EPS Operation and Service
IMPORTANT!
Reference Figure 21 for the EPS components in the compressor unit electric box.
Figure 21. Electric Box with EPS Components
With power ON, and viewing the EPS Module in the compressor unit electric box, the EPS green
light should be illuminated, indicating there is power to the EPS system.
If the yellow light is illuminated, there is an opening in the earth loop electrical circuit. The audible
signal will also be heard. After shutting power OFF, all electrical connections from the EPS module to
the earth loop system should be checked and adjusted as appropriate to ensure good electrical
contact.
If the red light is illuminated, there is a short in the earth loop electrical circuit. The audible signal
will be heard. Check and correct all wiring and connection as appropriate from the EPS module to the
earth loop to ensure they are not shorting.
If none of the lights are illuminated, check and replace, as appropriate, the fuse for the EPS Power
Supply as shown in Figure 21. For service purposes, a spare fuse has been factory supplied and is
located in the electrical box. The replacement fuse is Littlefuse 213 Series Slo-Blo® rated at 250
Volts, 2 Amperes, P/N 0213002MXP. This is also Allied Electronics Stock Number R1090710.
If it is necessary to operate the heating and cooling system while the EPS is down for service, the
EPS power may be temporarily disengaged to eliminate the audible alarm, by removing the EPS Fuse
shown in Figure 21. Upon completion of servicing the EPS, replace the fuse to energize the EPS
system and maintain warranty coverage.
DO NOT troubleshoot the EPS power supply or EPS module! If the above
steps do not resolve the problem, call ETI for technical service assistance at 1863-701-0096.
PSD-QS (02/16) Page 31
Page 32
3) Current Verification
Nominal System Capacity, Tons
Current Rating
1.5 thru 2.5
80 mA +/- 10%
3.0 thru 3.5
120 mA +/- 10%
4.0 thru 6.0
240 mA +/- 10%
WARNING!
measurement has been taken and before attempting to disengage the Ammeter
If it is necessary to verify the current flow through the EPS system, it can be checked with a digital DC
ammeter set on the Milliampere scale. The correct electrical currents for nominal system capacities
are listed in Figure 22.
Figure 22. EPS Current Ratings
Use extreme caution when checking current through the EPS system. Turn
OFF the main disconnect to the compressor unit when setting up the Ammeter
for the current measurement. Turn the power supply on only after the
Ammeter is in place for the measurement and hands and body are clear of all
electrical circuit conductors. Turn OFF the main disconnect after the current
and re-connect the EPS wiring. Failure to do this, could cause personal injury
or death.
To check the current, disconnect the “Loop” wire from the EPS module as shown in Figure 23 and
connect the DC ammeter as shown to measure and verify the current flow.
PSD-QS (02/16) Page 32
Figure 23. Test for DC Current
Page 33
Start-Up Process
CAUTION!
components. Failure to do so will cause lockout on start-up.
1) System Leak Check
During the Evacuation and Initial Charging processes, be sure that ALL
power to the EarthLinked® System is OFF. This includes the
compressor unit, air handler and all other electrically powered system
After all indoor and outdoor refrigerant bearing components of the system have been installed and
joints have been nitrogen brazed, pressurize the system prior to evacuation to leak test the system.
Do not exceed 150 psig when pressure testing the compressor unit and indoor system components.
Test for leaks with a sensitive electronic leak detector and bubble solution.
Repair leaks as appropriate prior to evacuation.
Evacuation and charging of the system is done through the compressor unit. All of the refrigerant
containing components in the compressor unit are illustrated in Figures 24 and 25.
The Start-up Process is illustrated in Figure 32.
PSD-QS (02/16) Page 33
Page 34
Figure 24. PSD Internal Flow Schematic
PSD-QS (02/16) Page 34
Page 35
PSD-QS (02/16) Page 35
Figure 25. PSD Piping
Page 36
2) Evacuation
IMPORTANT!
IMPORTANT!
Refer to Figure 26 and the following procedure:
1. Carefully vent any pressurized nitrogen charge from the compressor unit and system..
2. After venting the pressurized system, use a good quality gage manifold and a non-permeable
hose set as shown in Figure 26. If possible, use two Schrader core removal tools. Install one
on the discharge line access port and the other on the initial charging port. Removal of the
Schrader cores will reduce the time to achieve the desired vacuum.
3. Attach a good quality digital vacuum gage with an isolation valve to the liquid line service valve
access port as shown in Figure 26.
4. Use a well maintained, high quality vacuum pump with an isolation valve, rated at 7 cfm or
greater connected to the gage manifold. Ensure that the vacuum pump oil has been changed
prior to initiating the evacuation process to avoid contamination.
5. Fully open the LP and HP valves and both service valves. Reference Figure 26.
DO NOT ENERGIZE THE COMPRESSOR WHILE THE SYSTEM IS UNDER
VACUUM. THIS WILL CAUSE DAMAGE TO THE COMPRESSOR.
6. Open the vacuum pump isolation valve and start the pump. Evacuate the system down to
400 MICRONS or less as read on the digital vacuum gage. After 400 microns or less has
been achieved, isolate the vacuum pump. Wait 5 minutes and read the digital vacuum gage.
The system pressure must not exceed 500 MICRONS WITHIN 15 MINUTES. If it does,
continue the evacuation to remove any remaining non-condensibles in the system. A dry
system will hold 500 microns for 15 minutes.
A procedure often used to evacuate a system, known as the triple evacuation method, is
detailed in the section of this manual entitled Triple Evacuation.
Local codes may require other evacuation criteria, in which case the local codes take
precedence over the evacuation requirements described above.
DO NOT CHARGE THE SYSTEM UNTIL THE CONDITIONS OF STEP #6
ARE COMPLETED!
7. When the system has been successfully evacuated, close the LP and HP valves on the
manifold gage set. Do not remove the manifold gage set or hoses, as air will be drawn into the system and defeat the evacuation process.
PSD-QS (02/16) Page 36
Page 37
PSD-QS (02/16) Page 37
Figure 26. Evacuation of PSD System
Page 38
WARNING!
Inhalation of high concentrations of refrigerant gas vapor is harmful and
may cause heart irregularities or death. Vapor reduces oxygen available
the refrigerant container. Do not overheat.
3) Initial Charge
1. Disconnect the vacuum pump and isolate the digital vacuum gage. Connect the refrigerant
container to the charging hose of the manifold gage set as shown in Figure 27.
for breathing and is heavier than air. Decomposition products are
hazardous. Liquid contact can cause frostbite. Avoid contact of liquid
with eyes and prolonged skin exposure. Liquid and gas are under
pressure. Deliberate inhalation of refrigerant gas is extremely
dangerous. Asphyxiation can occur without warning due to lack of
oxygen. Before using, read the material safety data sheet. Use proper
safety measures when charging the system, especially when warming
2. Place the refrigerant container upside down, with the refrigerant valve at the bottom, on the
scale, as shown in Figure 27. Purge the charging hose by loosending it at the manifold end,
until refrigerant is released. Tighten the charging hose and zero out the refrigerant scale.
3. Open the LP valve on the manifold gage set. Opening the refrigerant container valve sends
liquid refrigerant through the initial charging port into the system. Continue to add refrigerant until 3 pounds per ton of system capacity has been added. In cold weather, it may be
necessary to warm the refrigerant container to charge to 3 pounds per ton.
4. After completing the initial refrigerant charge to the system, turn the LP valve off, re-install the
Schrader valve core into the initial charging port, remove the tool, and install the Schrader
valve cap firmly on the Schrader valve.
PSD-QS (02/16) Page 38
Page 39
Figure 27. Initial Charge of PSD System
PSD-QS (02/16) Page 39
Page 40
4) Final Charge
1. Remove the Schrader core tool from the hose just taken off of the initial charging port.
2. Crack open the LP valve on the manifold gage set so that a small amount of refrigerant gas
flows to purge the hose. Connect the hose to the final charging port, shown in Figure 28.
Tighten the hose to the final charging port and turn off the LP valve when the hose connection
is secure.
3. Start the system in heat mode.Disconnect the control wire from the “O” terminal to ensure
the system remains in the heat mode during the final charging process. In an air system, the
design (and minimum) air flow is 400 cfm per nominal ton. In a hydronic system, the design
(and minimum) circulating water flow to 3 pgm per nominal ton. As installed, higher than
design air and circulating water flows are acceptable, recognizing that this will cause greater
power consumption by the air handler and circulating pump motors.
4. Slowly open the LP valve on the manifold gage set and add refrigerant just fast enough to
maintain the suction pressure.
5. Slowly add refrigerant until liquid refrigerant is clearly seen in the middle sight glass of the
ACC, as shown in Figure 29.
6. Shut the LP valve on the manifold gage set and run the system for 20 minutes to ensure that
the refrigerant liquid level remains at the middle slightly glass. If the liquid refrigerant level
drops below the middle sight glass during this time, slowly add refrigerant until the liquid level
stabilizes at the middle sight glass.
7. With the liquid refrigerant level at the middle sight glass, attach and insulate a temperature
clamp or probe securely to the earth loop vapor line at the compressor unit service valve
shown in Figure 28. Read the measured temperature. Also read the LP gage pressure on the
manifold gage set. Use a pressure/temperature chart (Figure 31) to verify that the system is
operating at saturation, meaning that no superheat is measured on the earth loop vapor line.
To verify this, the measured vapor line temperature should be within ± 3°F of the saturation
temperature read from the chart for the measured LP gage pressure. If the measured
temperature is out of this range, contact ETI technical support at 1/863-701-0096.
8. After verifying that the system is operating at saturation in heating mode, and with the system still operating in heating mode, slowly open the LP valve on the manifold gage set,
and slowly add refrigerant to the system until the refrigerant liquid level is at, but not above, the top ACC sight glass, as shown in Figure 30. At no time should the refrigerant
liquid level be above the top ACC sight glass.
9. The system is now fully charged. Document the weight of the refrigerant charge in the system. Write it down on the Warranty Registration Card and inside the compressor unit on
the electrical diagram, for future reference.
10. Re-connect the control wire to the”O” terminal. The system is now operational in heating and
cooling modes.
PSD-QS (02/16) Page 40
Page 41
Figure 28. Final Charge of PSD System
PSD-QS (02/16) Page 41
Page 42
Figure 29. Charging to the Middle Sight Glass
Figure 30. Charging to the Top Sight Glass
PSD-QS (02/16) Page 42
Page 43
TEMPERATURE
(°F)
PRESSURE
(psig)
TEMPERATURE
(°F)
PRESSURE
(psig)
-20
26.1 70
199.2
-15
30.8 75
216.1
-10
35.9 80
234.0
-5
41.5 85
253.0
0
47.5 90
273.0
5
54.1 95
294.1
10
61.2 100
316.4
15
68.8 105
339.9
20
77.1 110
364.6
25
86.0 115
390.5
30
95.5 120
417.7
35
105.7
125
446.3
40
116.6
130
476.3
45
128.3
135
507.6
50
140.8
140
540.5
55
154.1
145
574.8
60
168.2
150
610.6
65
183.2
Figure 31. Pressure-Temperature for R-410A
PSD-QS (02/16) Page 43
Page 44
PSD-QS (02/16) Page 44
Figure 32. Start-Up Process
Page 45
Troubleshooting
CAUTION!
SERVICE MAY BE PERFORMED ONLY BY AN EARTHLINKED
TECHNOLOGIES AUTHORIZED PROFESSIONAL HVAC OR
REFRIGERATION SERVICE PERSON. USE ONLY SAFE AND
APPROVED SERVICE TECHNIQUES.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
MAINTENANCE OR SERVICE CAN CAUSE 1) THE
EARTHLINKED® SYSTEM OR COMPONENTS TO MALFUNCTION
AND OR FAIL, 2) PROPERTY DAMAGE, INJURY OR DEATH.
IMPORTANT!
cut-out temperature is 240°F. This is a manual reset switch.
EarthLinked® Refrigerant System Safety Switches
EarthLinked® compressor units are equipped with the following three
safety switches that will turn the compressor off if the following limits
are exceeded.
High Pressure Switch: Located between the compressor discharge port and
the reversing valve, the cut-out pressure is 600 psig. This is a manual reset
switch.
Low Pressure Switch: Located between the ACC and the compressor
suction port, the cut-out pressure is 25 psig. This is an automatic reset
switch.
Discharge Temperature Switch: Located at the compressor discharge, the
If you experience difficulties with the EarthLinked® system, please review the appropriate section of
the manual. It may be helpful to have another professional HVAC or refrigeration service person
review and check it with you.
Time and expense can be saved by taking a thoughtful and orderly approach to troubleshooting.
Start with a visual check: Are there loose wires, crimped tubing, missing parts, etc?
1) Compressor
After setting the remote (wall) thermostat system switch to the “OFF” position and the thermostat fan
switch to the “AUTO” position, proceed to check the supply voltage at (1) the line terminals to the
breaker/disconnect; 2) the system side of the breaker/disconnect, and 3) the line-side of the
transformer. Verify the proper voltage rating for the system. Reference Figure 33.
PSD-QS (02/16) Page 45
Page 46
Figure 33. Compressor Unit Voltage Information
The following compressor checklist is provided to analyze the compressor and determine if it is
operating properly or if it is faulty:
1. Electrical Service Panel – turn power off.
a. Check circuit connections for tightness
b. Circuit breaker sized right?
c. Wire size correct? (check NEC or local codes)
2. Check capacitor or other start components for bulges, overheating or loose
connections.
3. Test capacitor and start components and replace if necessary. Capacitors can be
checked by substitution or with capacitance meter. OK if reads ±10% of the
manufacturer’s specification.
4. Check incoming power supply voltage to determine whether it is within acceptable
voltage range. (See Figure 33)
5. Check voltage at compressor unit terminals to determine whether it is within
acceptable voltage range. (See Figure 33)
6. Running Amperage. Connect a clip-on type ammeter to the (common) lead to the
compressor. Turn on the supply voltage and energize the unit. The compressor will
initially draw high amperage; it should soon drop to the RLA value (See Figure 7) or less.
If the amperage stays high, check the motor winding resistance and/or run capacitor.
PSD-QS (02/16) Page 46
Page 47
Note: Feel the top of the compressor to see if it has overheated. If it is hot, the internal
overload may be open. You may have to wait several hours for it to reset before
proceeding.
If the compressor draws a high amperage and does not start (amperage is approximately
locked rotor amperage – LRA (See Figure 7)), the compressor is locked mechanically
and should be removed from the system and replaced. Verify before removing!
7. Motor Circuit Testing
Using a digital volt-ohmmeter (VOM), measure the resistance across the compressor
windings as shown in Figure 34. The power leads to the compressor must be
disconnected before taking an electrical measurement. A good rule of thumb for single
phase compressors is that start winding resistance (R2) is 3 to 5 times greater than run
winding resistance (R1).
Figure 34. Compressor Motor Circuit Testing
8. Grounded Windings
PSD-QS (02/16) Page 47
Page 48
Test the compressor motor for a grounded winding. The check should be made using an
ohmmeter capable of measuring very high resistance on a VOM. The resistance
between windings and the housing is one million to three million ohms for an
ungrounded winding.
Attach one lead to the compressor case on a bare metal tube or ground terminal, and to
each compressor terminal as shown in Figure 35. A short circuit at a high voltage
terminal indicates a motor defect (grounded).
Figure 35. Compressor Motor Grounded Winding Test
9. Compressor not pumping.
Connect gage block hoses to the suction and discharge pressure ports in the
compressor unit. Read pressure gages to affirm that system is pressurized with
refrigerant. Turn on power to compressor unit and run unit. Observe pressure gages. If
pressures on both gages remain the same, compressor is not pumping and there is a
possible internal failure. See System Troubleshooting Chart.
PSD-QS (02/16) Page 48
Page 49
2) System
Problem /
Symptom
Likely Cause(s)
Correction
A. System does not
run.
Note: Some digital
thermostats have
a built-in fiveminute time
delay.
2. Check resistance element(s) for
continuity.(Heating mode only)
3. Defective heater relay.
(Heating mode).
3. Check relay for proper operation.
Replace if defective. (Heating mode
only)
4. Thermal limit is open. (heat kit)
4. Check continuity across thermal limit
switch. (Heating mode only)
5. Compressor fault.
5. To reset switch, turn primary power off
then back on; turn thermostat system
switch to OFF, then back on.
6. Outdoor thermostat not connected
or failed (heating mode).
6. Check outdoor thermostat and electric
supplemental heat operation. Confirm
proper wiring. (Heating mode only)
PSD-QS (02/16) Page 50
Figure 36. System Troubleshooting Chart (con’t)
Page 51
G. Uncomfortable
temperature.
(Not enough
heat/cold air)
(cont’d)
7. Refrigerant undercharged.
7. Check for refrigerant level in
ACC.(Heating mode only)
Repair leak, evacuate and recharge the
system. Check In-line sight glass in
cooling mode.
8. Restriction in refrigerant circuit.
8. Check for blockage or restriction,
especially in Liquid Flow Control.
Assure that modification of non-ETI air
handler is performed. Check valves,
filter/dryer and anti-migration valve.
9. System is locked out on high or
low pressure.
9. Check low pressure and high pressure:
Check limit cut-off pressures. Control
is set to actuate at 5 (R-22 &
407C)/25psig (R-410A) (low pressure)
and 400 (R-22 & 407C)/600 psig (R410A) (high pressure) +10%. Check for
continuity on both switches under
normal pressure conditions. Refer to
Unit performance table.
10. Defective pressure control.
10. Check limit cut-off pressures. Control
is set to actuate at 5 (R-22 &
407C)/25psig (R-410A) (low pressure)
and 400 (R-22 & 407C)/600 psig (R410A) (high pressure) +10%. Check for
continuity on both switches under
normal pressure conditions.
11. Reduced air flow.
11. Check air ducts for leaks and repair.
Check blower operation. Check air
filter(s). Remove air flow restrictions
(min.400 CFM/ton).
12. Unit undersized/ oversized.
12. Contact ETI Technical Support at 863-
701-0096.
H. Poor Compressor
Performance
(Runs, but Not
pumping
Refrigerant)
1. Reversing Valve stuck and
Compressor will not create a
pressure difference between high
and low side of the system.
1a. Pinch closed the Discharge Line to
verify the Compressor builds High
Pressure, if so, replace Reversing
Valve.
1b. If High pressure does not build after
pinching the Discharge Line closed, the
Compressor has failed, replace
Compressor.
2. Bad Compressor
2. Replace after verification of Amp Draw
below RLA and pinch closed the
Discharge Line between the
Compressor and the reversing Valve to
verify pressure does not build on the
high side.
PSD-QS (02/16) Page 51
Figure 36. System Troubleshooting Chart (con’t)
Page 52
Commissioning Document
The document that follows (LIT-170) enables verification and documentation of system component
model numbers, location of underground system components and system performance for air and
hydronic heating and cooling.
PSD-QS (02/16) Page 52
Page 53
PSD-QS (02/16) Page 53
Page 54
PSD-QS (02/16) Page 54
Page 55
PSD-QS (02/16) Page 55
Page 56
PSD-QS (02/16) Page 56
Page 57
PSD-QS (02/16) Page 57
Page 58
PSD-QS (02/16) Page 58
Page 59
Tools and Equipment
The purpose of the following list is to highlight key pieces of equipment, tools and materials necessary
for the installation, maintenance and servicing of EarthLinked® Heating and Cooling System HVAC
(above ground) equipment.
The professional HVAC technician is expected to have a compliment of standard tools for the general
servicing of refrigeration equipment.
Equipment, Tools and Materials
ITEM DESCRIPTION
Vacuum Pump (7 CFM or greater capacity with isolation valve)
Evacuation Manifold (for vacuum pump)
Digital Vacuum (micron) Gauge and Isolation Valve
Schrader Valve Core Removal Tool (quantity of 2)
Charging/Evacuating Manifold for R-410A
Charging/Hi-Vacuum Hoses (black, quantity of 6)
Digital Refrigerant Scale
Digital Thermometer
Digital Sling Psychrometer
Air Flow Meter (for air handlers)
Nitrogen Tank with 0 – 600 psig Regulator and Handtruck
Oxy-acetylene Welding Torch Set
15% Silver Brazing Alloy
Refrigerant Recovery Unit (1/2 #/minute minimum vapor capacity)
Recovery Cylinder (50# capacity)
Halogen Leak Detector
Digital VOM
Digital Clamp-on Ammeter
Digital Water Flowmeter (3 to 30 gpm)
Tubing Cutters
Tubing Benders
Nut Driver
Cordless Drill (3/8”)
Swaging Kit
Deburring Tool
Drill Bit Set
Inspection Mirror
PSD-QS (02/16) Page 59
Page 60
Triple Evacuation
Triple evacuation is implemented to evacuate a system to a deep vacuum. It is accomplished by
evacuating a system to a vacuum of 1500 microns, and then bleeding a small amount of dry nitrogen
into the system. The nitrogen is then blown out to the atmosphere. The system is then evacuated
until the vacuum is again reduced to 1500 microns. This procedure is repeated three times, with the
last vacuum level reaching a deep vacuum of 400 microns, which is held for 10 to 15 minutes. The
following is a detailed description of the triple evacuation.
1. Attach an electronic micron gage to the system. The best place is as far from the vacuum port
as possible, which would be the access port on a service valve on the EarthLinked®
compressor unit.
2. Let the vacuum pump run until the digital vacuum gage reaches 1500 microns. After reaching
1500 microns, isolate the digital vacuum gage.
3. Allow a small amount of dry nitrogen to enter the system until the LP gage shows about 5 psig.
This small amount of dry nitrogen will fill the system and mix with the other vapors.
4. Release system pressure to 0 psig and close the valve. Then open the isolation valve on the
digital vacuum gage.
5. Open the vacuum pump valve and start the vapor removal process from the system again.
Let the vacuum pump run until the vacuum is again reduced to 1500 microns. Repeat Step 3.
6. After nitrogen has been added to the system a second time, open the vacuum pump valve
and again remove the vapor. Operate the vacuum pump until the vacuum on the electronic
micron gage reads 400 microns.
7. Once the micron gage reads 400 microns for 10 to 15 minutes, isolate the micron gage. The
system must not exceed 500 microns in 15 minutes. If it does, repeat step 6.
8. Then charge the system in accordance with the initial refrigerant charging procedure.
PSD-QS (02/16) Page 60
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.