EAGLE SIGNAL brand
Electronic Timers
HP5E CYCL-FLEX
®
Reset Timer
Modern, high quality timer
housed in industry standard
patented plug-in housing
5
E
The Eagle Signal brand Series HP5E CYCL- FLEX timer is a modern,
L
microprocessor based reset timer housed in the standard CYCL- FLEX
T
E
plug-in enclosure. Timing progress is indicated by a LED array that
I
C
displays remaining time interval. Its 5.20 inches circumference
M
T
E
calibrated dial is easy-to-read with well defined resolution increments on
R
R
all ranges. The 15 terminal ABS (U. L. rated 94V- 0) molded housing
O
S
T
N
has high impact resistance and will not support combustion.
I
I
M
C
■ 16 standard time ranges from 5 seconds to 60 hours
E
R
■ Knob adjustable time ranges and LED progress indicator
S
■ Pilot light indicates when timer is active
■ Optional reverse action mode will not reset on power failure
■ 15 terminal ABS (UL rated 94V-0) molded housing has high impact
resistance and will not support combustion
SPECIFICATIONS
Time Ranges
Sym.
Dial
Minimum
Setting
17
15
14
0
1
2
3
4
18
5
6
7
8
9
10
11
Reset Time: 500 mS at maximum setting
Voltage/ Frequency:
120 V (+10 -15%) 50/60 Hz
240 V (+10 -15%) 50/60 Hz
Power Consumption: 1.5 watts
Contact Rating:
10 Amps Resistive / Inductive @ 120vAC 1/6 HP @ 120VAC
5 Amps Resistive / Inductive @ 240VAC 1/2 HP @ 240VAC
Electrical Contact Lifetime: Average, contingent on load characteris-
tics. Inrush current should not exceed 10 amps.
At full load: 250,000 cycles
At 1 amp load: 5 million cycles
5 Sec.
10 Sec.
15 Sec.
30 Sec.
60 Sec.
150 Sec.
5 Min.
10 Min.
15 Min.
30 Min.
60 Min.
150 Min.
5 Hr.
10 Hr.
30 Hr.
60 Hr.
1/5 Sec.
1/5 Sec.
1/2 Sec.
1 Sec.
1 Sec.
5 Sec.
12 Sec.
12 Sec
1 Min.
1 Min.
1 Min.
5 Min.
12 Min.
12 Min.
1 Hr.
1 Hr.
Dial
Divisions
1/5 Sec.
1/5 Sec.
1/2 Sec.
1 Sec.
1 Sec.
5 Sec.
12 Sec.
12 Sec.
1 Min.
1 Min.
1 Min.
5 Min.
12 Min.
12 Min.
1Hr.
1 Hr.
Repeat
Accuracy
±.05 Sec.
±.05 Sec.
±.08 Sec.
±1.5 Sec.
±3 Sec.
±7.5 Sec.
±15 Sec.
±2 Sec.
±4.5 Sec.
±9 Sec.
±18 Sec.
±45 Sec.
±1.5 Min.
±3 Min.
±9 Min.
±18 Min.
File No. E61735
C
Power On Response:
28 ms average pull-in
17 ms average drop-out
Operationg Temerature: -10 to +140 F (-23 to +60 C)
Approximate weight: 1.7 lbs.
Agency Approvals: FM; UL/CUL Recognition
®
US
E61735
FM
APPROVED
OPERATION (reference Schmatic Diagram)
Standard: Instantaneous contacts 9-10-C and 6-7-8 operates directly
with power applied to 1, 11(E) and 2. Different operating sequences are
possible depending on the control circuit configuration.
Delayed contacts 4- 3 and 11- A close and contacts 4- 5 and 11- 12
open when timer reaches a timed out condition. Contacts 4- 5 and 1112 close and contacts 4- 3 and 11- A open when timer is reset.
Reverse Start: Instantaneous contacts 9-10-C and 6-7-8 operates
directly with power applied to 1, 11(E) and 2. Different operating
sequences are possible depending on the control circuit configuration.
Delayed contacts 4- 3 and 11- A close and contacts 4- 5 and 11- 12
open when timer reaches a timed out position. Contacts 4- 5 and 11- 12
close and contacts 4- 3 and 11- A open when timer is reset.
CRI
12
10
9
C
8
6
7
STANDARD
Factory Wiring
E
A
11
12
3
4
5
Schematic Diagram
CRI
12
10
9
C
8
6
7
REVERSE
Factory Wiring
E
A
11
12
3
4
5
5.06
DANAHER SENSORS & CONTROLS
MOUNTING
3 1/16
(77.77)
3 13/16
(96.83)
4 1/4
(107.95)
4 1/8
(104.78)
DRILL AND TAP FOUR
HOLES FOR 8-32 SCREWS
(INCLUDED WITH UNIT)
1 13/32
(35.71)
1 13/32
(35.71)
3 3/16 ± 1/16
(80.95 ± 1.57)
DIA CUTOUT
1 13/32
(35.71)
5 3/4
(146.05)
1 13/32
(35.71)
TERMINALS AND
WIRING DIAGRAM
ON REAR OF
TIMER CASE
1 5/8
(41.27)
4.250
(107.95)
MTG HOLE
USED FOR
GROUNDING
CASE
C
9
10
MINIMUM SPACING
4.00
(101.60)
6
7
8
11
12
4.875
(123.83)
ENCLOSURES
Model No. NEMA Class Description
HN308 1 Surface Mtg. with terminal block
HN364 1 Surface Mtg. without terminal block
5
B
4
E
A
3
2
1
ACCESSORIES
Model No. Description
H-5331 Mounting Brackets (2 required per timer)
HP50-31 One Hole Mounting Ring
HP50-133 Surface Mounting Adapter to use in place of brackets
HP50-295E Dial Lock
ORDERING INFORMATION
TIME RANGE
Symbol Description
17
15
14
0
1
2
3
4
0-5 Sec.
0-10 Sec.
0-15 Sec.
0-30 Sec.
0-60 Sec.
0-150 Sec.
0-5 Min.
0-10 Min.
DANAHER INDUSTRIAL CONTROLS
2100 West Broad Street
Elizabethtown, NC 28837
Symbol Description
18
5
6
7
8
9
10
11
HP5E 15 A6 01
0-15 Min.
0-30 Min.
0-60 Min.
0-150 Min.
0-5 Hr.
0-10 Hr.
0-30 Hr.
0-60 Hr.
CUSTOMER CARE
Toll-Free: +1.800.390.6405
Fax: +1.910.879.5486
Email: etn-customerservice@dancon.com
VOLTAGE &
FREQUENCY
Symbol Description
120V, 50/60 Hz
A6
240V, 50/60 Hz
B6
FEATURES
Symbol
Reverse
01
Dial Lock
07*
Water Resistant Window & Housing
22
*Dial Lock not available with water resistant housing
Description
TECHNICAL SUPPORT
Toll-Free: +1.800.234.8731
Fax: +1.847.782.5277
Email: eagle-signal.techsupport@dancon.com