Eagle Signal HP5 Catalog Page

EAGLE SIGNAL brand
Electric Timers
Also see Series HP5E in Section 5 for Solid­State Model
HP5 CYCL-FLEX® Reset Timer
The high quality timer that has become an industry standard... knob setpoint, cycle progress pointer, pilot light, and patented plug-in housing
®
RECOGNIZED
®
CERTIFIED
FM
APPROVED
The HP5 CYCL-FLEX® series timer is a high quality, synchronous motor driven reset timer housed in the standard CYCL-FLEX® plug-in housing.
6
16 standard time ranges from 5 seconds to 60 hours
Knob adjustable time ranges - progress pointer for each
E L
T
Highly visible, calibrated dials (7.85 inch circumference)
E
I
Easily read and well-spaced calibrations
C
M
T
E
Red progress pointer displays remaining time interval
R
R
I
Pilot light indicates when timer motor is energized
S
C
Standard timers supplied with "power on" clutch operation
Optional reverse action clutch will not reset on power failure
15 terminal ABS (UL rated 94V-0) molded housing has high impact
resistance and will not support combustion
OPERATION
Application of power to terminals 1, 2, and 11 energizes the clutch coil, closes contacts 9-10 and 6-8, and starts the timing period. At time out, contacts 4-3 close, 11-12 open, and the motor stops. The timer will remain in this condition until power is removed from the clutch coil.
Contacts 6-7-8 and 9-10-C are instantaneous contacts and operate with the application of power to the clutch coil. Contacts 3-4-5 and 11-12-A operate at time out with contacts 3-4-5 operating prior to contacts 11-12-A.
SPECIFICATIONS
Time Ranges:
Sym.
17 15 14
0 1 2 3 4
Dial Minimum
Setting
5 Sec. 10 Sec. 15 Sec. 30 Sec. 60 Sec.
150 Sec.
5 Min. 10 Min.
1/6 Sec. 1/3 Sec. 1/2 Sec.
1 Sec. 2 Sec.
4.5 Sec. 9 Sec.
20 Sec.
Dial
Divisions
.05 Sec. 1/6 Sec. 1/4 Sec. 1/2 Sec.
1 Sec. 2 Sec. 3 Sec.
10 Sec.
Accuracy
Repeat
±.05 Sec. ±.05 Sec. ±.08 Sec. ±.15 Sec.
±.3 Sec. ±.75 Sec. ±1.5 Sec.
±3 Sec.
Time Ranges Cont.:
Sym.
Dial
Minimum
Setting
18
5 6 7 8
9 10 11
Reset Time: 1/2 second at max. setting Voltage/Frequency: 120V (+10, -15%), 60 Hz
240V (+10, -15%), 60 Hz
Burden: Motor: 2.45 VA, 120 VAC
Clutch: 10.5 VA
Output Rating: 10 amps, resistive, 120 VAC
5 amps, resistive, 240 VAC
Electrical Lifetime: Contingent on load characteristics. Average contact
life at full load is 250,000 operations. At 1 amp load, switch life increases to 5 million cycles. Inrush current should not exceed 10 amps.
Power On Response: 28 ms average pull-in
17 ms average drop-out
Temperature Range: 0˚ to 140˚F (-18˚ to +60˚C) Vibration: Unaffected by 2.5G sinusoidal vibration magnitudes in both
directions of three perpendicular mounting axes imposed from 10 to 900 Hz
Approximate Weight: 2 lb. 14 oz. Agency Approvals: UL Recognition E61735
UL Recognition 71726 (Feature 92 only) CSA Certification LR26861 CSA Certification (Feature 92 only) FM Approval 15030 RoHS
15 Min. 30 Min. 60 Min.
150 Min.
5 Hr. 10 Hr. 30 Hr. 60 Hr.
30 Sec.
1 Min. 2 Min.
4.5 Min. 9 Min.
20 Min.
1 Hr. 2 Hr.
Dial
Divisions
15 Sec. 1/2 Min.
1 Min. 2 Min. 3 Min.
10 Min.
1/2 Hr.
1 Hr.
Repeat
Accuracy
±4.5 Sec.
±9 Sec. ±18 Sec. ±45 Sec.
±1.5 Min.
±3 Min.
±9 Min. ±18 Min.
6.08
OPERATION
Standard and Reverse Start
Instantaneous contacts 9-10-C and 6-7-8 operate directly with the clutch offering different sequences of operation depending on the control circuit configuration.
Delayed contacts 4-3 and 11-A close and contacts 4-5 and 11-12 open when timer reaches a timed out condition. Contacts 4-5 and 11-12 close and contacts 4-3 and 11-A open when timer is reset.
Schematic Diagram
1
10
9
C 8
6
7
2
M
A
11
12
3
4
5
MOUNTING
DRILL AND TAP FOUR HOLES FOR 8-32 SCREWS (INCLUDED W/UNIT)
+
1.406
(35.71)
1.406
(35.71)
3.187 .062 +
(80.95 1.57)
DIA. CUTOUT
ENCLOSURES
Model No. NEMA Class Description HN308 1 Surface Mtg. with terminal block
HN364 1 Surface Mtg. without terminal block
HN368 !A Dual unit cabinet with 9 position
terminal block, timer housings, and DPST toggle switch
HN370 1A Dual unit cabinet less unit cases and
toggle switch, with 9 terminal block
ACCESSORIES
Model No. Description
H-5331 Mounting Brackets 2 req'd per timer HP50-31 One Hole Mounting Ring HP50-103 120 VAC, 50/60 Hz Repeat Cycle Kit
Not applicable with Feature 19
HP50-131 CYCL-FLEX® Water-Sealed Housing HP50-133 Surface Mounting Adapter to use in place of brackets HP50-295 Dial Lock
4.250
(107.95)
3.062
(77.77)
6
T O
E
T
L
T
E
A
I
C
L
M
T
E
I
R
R
Z
I
S
I
C
N G
1.406
(35.71)
1.406
(35.71)
ORDERING INFORMATION
TIME RANGE
Sym. Description
17 15 14
0 1 2 3 4
0-5 Sec. 0-10 Sec. 0-15 Sec. 0-30 Sec. 0-60 Sec.
0-150 Sec.
0-5 Min. 0-10 Min.
Sym. Description
18
5 6 7 8
9 10 11
MTG. HOLE USED FOR GROUNDING CASE
3.812
(96.82)
HP5 15 A6 01
0-15 Min. 0-30 Min. 0-60 Min.
0-150 Min.
0-5 Hr. 0-10 Hr. 0-30 Hr. 0-60 Hr.
VOLTAGE & FREQUENCY
Sym. Description
A6 B6
120V, 60 Hz 240V, 60 Hz
4.125
(104.78)
5.750
(146.05)
1.625
(41.27)
FEATURES
Sym.
Reverse Clutch Arrangement
01
Dial Lock
07
Revision for Mtg. to HN383 Explosion Proof
19
Cabinet. Add when purchased without cabinet. DOES NOT have pilot light. Water Resistant Window & Housing
22
Enclosed in HN383 Explosion Proof Cabinet
92*
Description
*Laboratory Testing: UL Recognition E61735
CSA Certification LR45132-1
6.09
Loading...