Eagle Signal CX300 Catalog Page

EAGLE SIGNAL brand
Electronic Timers
CX300 Microprocessor Timer/Counter
Microprocessor based timer/counter housed in the industrial standard CYCL-FLEX case
®
5
E L
T
The CX300 is a microprocessor based timer/counter housed in a
E
I
C
standard 15 terminal CYCL-FLEX® plug-in case which allows easy
M
T
removal for programming changes and replacement. Time or count
E
R
operation, time range, and the type of start input switch operation are
R
O
programmed with 7 miniature rocker switches located inside the unit
S
T
N
housing.
I
I
M
C
The front panel of the CX300 is a sealed membrane keypad which
E
provides excellent protection for most industrial environments. The time
R
or count setpoint is entered using the increment and decrement keys for
S
each digit position. The SET and ENT keys provide access to the setpoint, as well as to the front panel programmable software functions. These programmable functions control the pulse output length, setpoint to zero or zero to setpoint cycle progress indication, and count input scale factor. The software programming functions are indicated by prompts to help the user program these functions without the need for written instructions.
Keypad lock function allows viewing of setpoint, but does not allow
unauthorized changes
4 1/2 digit (19999) liquid crystal display - .5 inch high digits
Annunciators (right of the display) flash to indicate timing or counting
Two form C instantaneous contacts and two form C programmed
contacts
Five time ranges from 19.999 sec. to 199 hr.: 59 min.
Three count rate input rate speeds are programmable with a max.
count display of 19999 - can be extended via count input scale factor
24, 120, or 240 VAC operations
Count input available for 120 volt AC or low voltage AC/DC
operations
When programmed as timer, count input circuit serves as time inhibit
(without resetting the unit)
Non-volatile memory data retention
®
RECOGNIZED
®
CERTIFIED
SPECIFICATIONS
Time/Count Ranges:
Sym.
1 2 3 4 5 6 7 8
Operating Voltage/Frequency: A6 - 120 VAC, 50/60 Hz
B6 - 240 VAC, 50/60 Hz Z6 - 24 VAC, 50/60 Hz
Time Inhibit/Count Line Terminals B & C:
CX311/CX341 - 12-50 VDC or 20-28 VAC, 50/60 Hz CX312/CX342 - 120 VAC, 50/60 Hz or 120 VDC
Setting Accuracy: Time: ±0.1% or 50 ms, whichever is larger (0˚ to 60˚C)
Count: 100%
Repeat Accuracy:
Time: ±0.1% or 35 ms, whichever is larger (0˚ to 60˚C) Count: 100%
Reset Time: 30 ms following voltage removal from simulated clutch input
(CR1)
Power on Response: 300 ms max. after voltage applied to terminal 11 Operating Temperature: +32˚ to +140˚F (0˚ to +60˚C) Output Rating: Relay: 10 amp (resistive), 120 VAC
Mechanical Life: 20 million operations Electrical Life: contingent upon controlled load Solid State: 1 amp, 0-264 VAC, VDC
Vibration: Unit function is unaffected by 2.5G sinusoidal vibration magni-
tude in both directions of the perpendicular mounting axes imposed from 10 to 100 Hz
Static Discharge: Unit function is unaffected by a constant 3600 volt peak,
60 Hz discharge applied to the grounded front plate at a relative humidity of less than 25%
Approvals: UL Recognition E96337
CSA Certification LR26861
Maximum
Range
19999 Cts. 19999 Cts. 19999 Cts.
199.99 Sec.
1999.9 Sec.
19.999 Sec.
199 Min.: 59 Sec.
199 Hr.: 59 Min.
Minimum
Setting
1 Ct. 1 Ct. 1 Ct.
.01 Sec.
.1 Sec.
.001 Sec.
1 Sec. 1 Min.
4000/Sec. 12-50 VDC Count Input
Count
Rate
500/Min. AC or DC
5000/Min. AC or DC
DANAHER SENSORS & CONTROLS
OUTPUT OPERATING MODES
ON-Delay Operation
The contacts are energized at the end of the timing/counting cycle and remain energized until the unit is reset.
Interval Operation
The contacts are energized during the timing/counting cycle and then shut off at the end of the cycle.
START INPUT
PROGRAMMED
CONTACTS
TIMING OR COUNTING
RESET
RESET
Pulse Output Operation
The contacts are energized at the end of the timing/counting cycle for a pulse which is user programmable. See Front Panel Feature Programming instructions for details on how to program the pulse length..
START INPUT
PROGRAMMED
CONTACTS
TIMING OR COUNTING
PULSE
RESET
MOUNTING
DRILL AND TAP FOUR HOLES FOR 8-32 SCREWS (INCLUDED W/UNIT)
+
1.406
(35.71)
1.406
(35.71)
3.187 .062 +
(80.95 1.57)
DIA. CUTOUT
START INPUT
PROGRAMMED
CONTACTS
TIMING OR COUNTING
RESET
Pulse and Repeat Operation
The contacts are energized at the end of the timing/counting cycle for a pulse which is user programmable. At the same time that the cycle is completed and the pulse output begins, the timing/counting cycle resets and begins again. This repeat operation continues as long as the start circuit is energized.
START INPUT
PROGRAMMED
CONTACTS
4.250
(107.95)
TIMING OR COUNTING
3.062
(77.77)
PULSE
TIMING OR COUNTING
RESET
PULSE
5
T
E L
O
T
E
T
I
C
A
M
T
L
E
R
R
I
O
S
N
Z
I
I
C
N G
1.406
(35.71)
1.406
(35.71)
MTG. HOLE USED FOR GROUNDING CASE
ENCLOSURES
Model No. NEMA Class Description HN308 1 Surface Mtg. with terminal block
HN364 1 Surface Mtg. without terminal block HN370 1A Dual unit cabinet less unit cases and
toggle switch, with 9 terminal block
ORDERING INFORMATION
CX3 1 2 A6
OUTPUT TYPE
Sym. Description
10A DPDT Instantaneous
1
10 DPDT Delayed Relay Output 1A Solid State Output
4
COUNT / INHIBIT INPUT VOLTAGE
Sym. Description
1 2
3.812
(96.82)
ACCESSORIES
Model No. Description
H-5331 Mounting Brackets 2 req'd per timer HP50-31 One Hole Mounting Ring HP50-131 CYCL-FLEX Water-Sealed Housing HP50-133 PDM-534 1/4 DIN Adapter Plate
12-50 VDC, 20-28 VAC, 50/60 Hz 120 VDC, 120 VAC, 50/60 Hz
4.125
(104.78)
5.750
(146.05)
1.625
(41.27)
Surface Mounting Adapter to use in place of brackets
VOLTAGE & FREQUENCY
Sym.
A6 B6 Z6
Description
120 VAC, 50/60 Hz 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz
DANAHER SENSORS & CONTROLS