Eagle Signal BRE SERIES Instruction Manual

MOUNTING DIMENSIONS
XXX = inches (XXX) = millimeters
ENCLOSURES
PART
NUMBER
1701-0893
DESCRIPTION
NEMA1 (General purpose)
ACCESSORIES
PAR T
NUMBER
HP50-103
HP50-105
DESCRIPTION
120 VAC 50/60 Hz Repeat Cycle Kit
240 VAC 50/60 Hz Repeat Cycle Kit
ORDERING INFORMATION
SYMBOL
Sym.
*** Not available in B6 v
SYMBOL
DESCRIPTION
Surface mounted with dial knob
E
and 9 point screw type terminal b
lock.
TIME RANGE
1
3
4
5
6
Sec. ***
5
15 Sec.
30 Sec.
60 Sec.
150 Sec.
ersion
AGE & FREQUENCY
VOLT
TAGE & FREQUENCY
VOL
A6 120V 50/60 Hz
240V 50/60 Hz
B6
Sym.Time Range
10
11
12
7
8
9
Time Range
5 Min.
10 Min.
30 Min.
60 Min.
5Hr.
10 Hr.
BR
BRE Dimensions Enclosed Construction
01
SYMBOL
Blank
01
erminal Block
FEATURES
DESCRIPTION
Standard Timer
Re
verse Start
w/9 Position T
E 5 A6
Printed U.S.A. 0793
BRE SERIES RESET TIMER
BRE enclosed construction with front facing dial and knob.
The BRE timer has a heavy duty terminal block, with 9 screw terminals that will readily accept 16 gauge wire commonly used in industrial circuit wiring.
The case of the BR series timer is injection molded Lexan®. This material is recognized by Underwriters Laboratories for use as the sole support of current carrying components. Lexan is self-extinguishing, has a high impact strength, and high dimensional stability.
OPERATION
The NEW BRE series reset timers are micro proces­sor driven. They provide an accurate adjustable time delay between the actuation of the control circuit and the operation of the load switches. New standard pilot light is on during timing period.
SPECIFICATIONS
Time Ranges
SYMBOL
Repeatability
Reset Time
1 ms
Voltage/Frequency
120V (+10, - 15%), 50/60 Hz 240V (+10, - 15%), 50/60 Hz
Power Consumption
1.5 Watts
Output Rating
10 Amp - 1/4HP 120/240 VAC 1/2 Amp - 125 VDC 1/4 Amp - 240 VDC
Activation Time
150 ms
Dial Setting Accuracy
3% of Full Scale
Minimum Setting
2% of Full Scale
Operating Temperatures
-10˚ to 140˚F (-23˚ to 60˚ C)
Laboratory Testing
U.L. Recognition E61735 F.M. Approved 21038
MAXIMUM
SETTING
1 3
15 sec.
4
30 sec.
5
60 sec.
6
150 sec. 7 8
10 min.
9
30 min.
10
60 min. 11 12
10 hr.
5 sec.
5 min.
5hr.
MINIMUM SETTING
.05 sec. .15 sec.
1.5 sec.
18 sec.
.3 sec. .6 sec.
3 sec. 6 sec.
.6 min.
3 min. 6 min.
DIAL MARK
DIVISIONS
1/4 sec.
1 sec. 2 sec. 2 sec.
5 sec. 15 sec. 30 sec.
2 min.
2 min. 15 min. 30 min.
BRE BULLETIN 116E REV. 2
OPERATION
Standard Start
Reverse Start
WIRING DIAGRAMS
BRE
Bold Lines are Internal Wiring
BRE
Instantaneous contact 8-9 and 8-3 operates directly with energization of 1 & 2, (CRI), offering different sequences of operation depending on the control circuit configuration.
Delayed contacts 6-5 close and 6-7 and 1-4 open when timer reaches a timed out condition. Contacts 6-7 and 1-4 close and 6-5 open when timer is reset.
Schematic Diagram
“STANDARD START”
Basic Sequence of Contact Operation for BR-E “Standard Start” Timer
X – Closed Contact O – Open Contact
Standard
Start
CRI
A
8-3
B
8-9
6-5
6-7
C
1-4
A. Timer Control Functions B. Instantaneous Contacts
E
Reset Timing
OFF
OFF
O
X
O
X
X
ON
ON
Timed
Out
ON
ON
X
O
O
X
X
X
O
X
O
O
C. Delayed Contacts
Instantaneous contact 8-9 operates directly with the energization of 1 & 2 (CRI).
Delayed contacts 6-5 close and 6-7 and 3-4 open when timer reaches a timed out position. Contacts 6-7 and 3-4 close and 6-5 open when timer is reset.
Schematic Diagram
“REVERSE START”
Basic Sequence of Contact Operation for BR-E “Reverse Start” Timer
X – Closed Contact O – Open Contact
Reverse
Start
CRI
A
B
8-9
6-5
6-7
C
3-4
A. Timer Control Functions B. Instantaneous Contacts
E
Reset Timing
ON
ON
O
O
X
X
OFF
ON
Timed
Out
OFF
ON
X
O
X
X
X
X
O
O
C. Delayed Contacts
Standard Start Sustained Control Switch - Close to start. Open to reset. Simple delayed closing and opening of load circuits.
Momentary Start, Automatic Reset - Switch 6-5-7 transfers to timed out condition indicated by X for 3/4% of maximum dial setting.
* Optional RESET switch - open to reset timer during
timing. If reset switch is not used, connect terminal 8 directly to line.
Reverse Start. Close switch to reset open to start
Timer remains in timed out condition until
timing. switch is closed to reset.
Standard Start - Sustained Control Switch - Close to start. Open to reset. Various control circuit operations obtained by connecting contacts in series.
Momentary Start Automatic Reset - With motor shut­off protection. Use this circuit when the start switch may not always be opened before end of timing. This insures that power is removed from motor at end of timing.
Reverse Start. Close switch to reset. Various control circuit operations obtained by connecting controls in series.