MOUNTING DIMENSIONS
XXX = inches
(XXX) = millimeters
ENCLOSURES
PART
NUMBER
1701-0893
DESCRIPTION
NEMA1 (General purpose)
ACCESSORIES
PAR T
NUMBER
HP50-103
HP50-105
DESCRIPTION
120 VAC 50/60 Hz
Repeat Cycle Kit
240 VAC 50/60 Hz
Repeat Cycle Kit
ORDERING INFORMATION
SYMBOL
Sym.
*** Not available in B6 v
SYMBOL
DESCRIPTION
Surface mounted with dial knob
E
and 9 point screw type terminal
b
lock.
TIME RANGE
1
3
4
5
6
Sec. ***
5
15 Sec.
30 Sec.
60 Sec.
150 Sec.
ersion
AGE & FREQUENCY
VOLT
TAGE & FREQUENCY
VOL
A6 120V 50/60 Hz
240V 50/60 Hz
B6
Sym.Time Range
10
11
12
7
8
9
Time Range
5 Min.
10 Min.
30 Min.
60 Min.
5Hr.
10 Hr.
BR
BRE Dimensions Enclosed Construction
01
SYMBOL
Blank
01
erminal Block
FEATURES
DESCRIPTION
Standard Timer
Re
verse Start
w/9 Position T
E 5 A6
Printed U.S.A. 0793
BRE SERIES
RESET TIMER
BRE enclosed construction with front facing dial
and knob.
The BRE timer has a heavy duty terminal block, with
9 screw terminals that will readily accept 16 gauge
wire commonly used in industrial circuit wiring.
The case of the BR series timer is injection molded
Lexan®. This material is recognized by Underwriters
Laboratories for use as the sole support of current
carrying components. Lexan is self-extinguishing,
has a high impact strength, and high dimensional
stability.
OPERATION
The NEW BRE series reset timers are micro processor driven. They provide an accurate adjustable time
delay between the actuation of the control circuit and
the operation of the load switches. New standard pilot
light is on during timing period.
SPECIFICATIONS
Time Ranges
SYMBOL
Repeatability
Typical ± 1/4% of full scale
Reset Time
1 ms
Voltage/Frequency
120V (+10, - 15%), 50/60 Hz
240V (+10, - 15%), 50/60 Hz
Power Consumption
1.5 Watts
Output Rating
10 Amp - 1/4HP 120/240 VAC
1/2 Amp - 125 VDC
1/4 Amp - 240 VDC
Activation Time
150 ms
Dial Setting Accuracy
3% of Full Scale
Minimum Setting
2% of Full Scale
Operating Temperatures
-10˚ to 140˚F (-23˚ to 60˚ C)
Laboratory Testing
U.L. Recognition E61735
F.M. Approved 21038
MAXIMUM
SETTING
1
3
15 sec.
4
30 sec.
5
60 sec.
6
150 sec.
7
8
10 min.
9
30 min.
10
60 min.
11
12
10 hr.
5 sec.
5 min.
5hr.
MINIMUM
SETTING
.05 sec.
.15 sec.
1.5 sec.
18 sec.
.3 sec.
.6 sec.
3 sec.
6 sec.
.6 min.
3 min.
6 min.
DIAL MARK
DIVISIONS
1/4 sec.
1 sec.
2 sec.
2 sec.
5 sec.
15 sec.
30 sec.
2 min.
2 min.
15 min.
30 min.
BRE BULLETIN 116E REV. 2
OPERATION
Standard Start
Reverse Start
WIRING DIAGRAMS
BRE
Bold Lines are Internal Wiring
BRE
Instantaneous contact 8-9 and 8-3 operates directly
with energization of 1 & 2, (CRI), offering different
sequences of operation depending on the control circuit
configuration.
Delayed contacts 6-5 close and 6-7 and 1-4 open
when timer reaches a timed out condition. Contacts
6-7 and 1-4 close and 6-5 open when timer is reset.
Schematic Diagram
“STANDARD START”
Basic Sequence of Contact Operation for BR-E
“Standard Start” Timer
X – Closed Contact
O – Open Contact
Standard
Start
CRI
A
8-3
B
8-9
6-5
6-7
C
1-4
A. Timer Control Functions
B. Instantaneous Contacts
E
Reset Timing
OFF
OFF
O
X
O
X
X
ON
ON
Timed
Out
ON
ON
X
O
O
X
X
X
O
X
O
O
C. Delayed Contacts
Instantaneous contact 8-9 operates directly with the
energization of 1 & 2 (CRI).
Delayed contacts 6-5 close and 6-7 and 3-4 open
when timer reaches a timed out position. Contacts
6-7 and 3-4 close and 6-5 open when timer is reset.
Schematic Diagram
“REVERSE START”
Basic Sequence of Contact Operation for BR-E
“Reverse Start” Timer
X – Closed Contact
O – Open Contact
Reverse
Start
CRI
A
B
8-9
6-5
6-7
C
3-4
A. Timer Control Functions
B. Instantaneous Contacts
E
Reset Timing
ON
ON
O
O
X
X
OFF
ON
Timed
Out
OFF
ON
X
O
X
X
X
X
O
O
C. Delayed Contacts
Standard Start Sustained Control Switch - Close to
start. Open to reset. Simple delayed closing and
opening of load circuits.
Momentary Start, Automatic Reset - Switch 6-5-7
transfers to timed out condition indicated by X for
3/4% of maximum dial setting.
* Optional RESET switch - open to reset timer during
timing. If reset switch is not used, connect terminal
8 directly to line.
Reverse Start. Close switch to reset open to start
Timer remains in timed out condition until
timing.
switch is closed to reset.
Standard Start - Sustained Control Switch - Close to
start. Open to reset. Various control circuit operations
obtained by connecting contacts in series.
Momentary Start Automatic Reset - With motor shutoff protection. Use this circuit when the start switch
may not always be opened before end of timing. This
insures that power is removed from motor at end of
timing.
Reverse Start. Close switch to reset. Various control
circuit operations obtained by connecting controls in
series.