Eagle Signal B856 Series Technical Manual

Introduction
An excellent value in its class, the B856 features a compact 1/16 DIN package, the precision of digital setting, versatile functionality, and a straightforward button-per­digit interface.
It can be easily programmed to perform any standard timing operation: On-Delay, Off­Delay, Interval 1, Interval 2, or Repeat Cycle. A unique On-Delay /Interval Mode can in many cases perform the function of two separate timers. Output is via DPDT relay contacts.
An available model's output features separate timed and instantaneous SPDT contacts.
Simplicity of operation is maintained while still providing a high level of functionality. All programming is done through the front panel, with an intuitive button-per-digit keypad that makes entry of preset times quick and easy. A crisp dual line LCD display lets the operator readily view elapsed or remaining cycle time as well as the preset value. Prominent annunciators indicate information such as the time range and the status of the input and outputs.
Technical Manual 702070-0001
Reliability is a key feature of the B856. IEC Level 4 noise immunity ensures flawless operation in harsh electrical environments, while its IEC IP65 enclosure rating allows use in washdown conditions.
Wiring via an industry standard 11 pin socket and a power supply that can accept 24 - 240 VAC or 24 VDC vastly simplify setup.
Features
Field programmable choice of 6 operating modes
5 selectable time ranges with resolution down to 0.01 seconds
High Contrast LCD display indicates both process time and preset value
Simple button per digit interface
Programmable security levels prevent unauthorized setpoint or program changes
Universal Power Supply (24 - 240 VAC, 24 VDC)
External Start and Reset Inputs
UL and CUL recognized, CE marked
IEC IP65 rated front panel
Model with Instantaneous contacts also available
Index
Overview
Panel Mounting page 2 Wiring Connections page 2 Front Panel Operation page 2
Programming
Program Mode page 3-4
Operating Modes
Timing Diagrams page 5
General
Specifications page 8 Ordering Information page 8 Warranty page 8
Eagle Signal brand
Series B856 Multifunction LCD Timer
OVERVIEW
INSTALLATION & WIRING
48mm
8mm
66mm
81mm
For the -511 version,
Pins 1, 3, 4 are the
instantaneous contacts
Start
4
3
2
Socket
5
1
Power
6
11
To wire the unit, an 11 pin socket is required. The unit can then either be DIN rail mounted or panel mounted using the supplied mounting bracket. For panel mounting, place the unit in the cutout, then slide the bracket forward over the rear of the unit so that the tabs catch in the grooves on the housing and the bracket is as far forward as possible. Tighten the panel mount screws until there is a snug fit against the panel. Do not overtighten.
Reset
7
8
9
10
FRONT PANEL OPERATION
I/O Status Indicators
Illuminates to display when an input or output is active: "IN' for the start input, "OUT" for the timed output, and "RST" for the external reset signal.
Time Indicators
The word "Timing" flashes when a timing function is taking place. The applicable arrow also lights to indicate if the display is set to time up or time down.
Time Value
Indicates the elapsed/remaining time to preset.
Edit Key
Many of the parameters in Program Mode require selection of a specific choice as opposed to a numeric value. The Edit key is used to scroll through the available choices. In Operation mode, the Edit key can be pressed simultaneously with the Program key to reset the timer.
EAGLE SIGNAL
IN OUT
RST
1234
Timing
H M
1234
4 3 2 1
E
Program Key
Pressing the key continuously for 3 seconds moves the unit in and out of Program mode. Once in Program mode, pressing and releasing the key will scroll the display from one parameter to the next.
Time Range Indicator
Illuminates to show the time base: H for hours, M for minutes, S for seconds. Multiple indicators will be illuminated when the time base is Hours:Minutes or
H M S
P
Minutes:Seconds.
Set Value
Settable value used to trigger the timed output.
Numeric Keys
Each of the number keys is used to increment or decrement the value of the corresponding digit of the preset or a parameter value (increments if unit is set in time up mode and decrements if set in time down mode).
2
PROGRAMMING
PROGRAM MODE
• Enter the Program Mode by holding down the "P" key for 3 seconds
• Press the "P" key to move the top display from one parameter to the next
• Press the "E" key to scroll the bottom display through the available choices for that parameter
• While in Program Mode the unit will stop timing, and the output will retain its last state. The new settings will only become effective after returning to Operation Mode by holding down the "P" key for 3 seconds
P
For 3 Seconds
Operating Function: Determines how outputs will operate in relation to the set value. Choices are:
Func
OndL
P
See Appendix A for timing charts.
On-Delay (OndL)
Off Delay (OFdL)
Interval 1 (int1)
Interval 2 (int2)
Delay/Interval (dint)
Repeat Cycle (CYCL)
1St
On
P
int
1.0
S
P
trnG
S
P
dEcP
0
S
First Operation: Determines whether the Repeat Cycle will start with an On or an Off Operation
Note: This parameter will only appear if Repeat Cycle is chosen as the Operating Function
Interval Time: Sets the amount of time the output will be active after the On-Delay function has timed
out. Use the 1 through 4 keys to set the value in a range from 0.1 to 999.9 seconds.
Note: This parameter will only appear if Delay/Interval is chosen as the Operating Function
Time Range: Sets the unit of measure for the time values that will be shown on the display in
Operation Mode. Choices are:
Seconds
Minutes
Hours
Minutes:Seconds
Hours:Minutes
Decimal Position: Sets the decimal position for the time display. Choices are: no decimal point (0), 1/10ths position (0.0), or Hundredths position (0.00). The time range selected in the previous parameter will remain illuminated for reference.
Note: This parameter will not appear if Minutes:Seconds or Hours:Minutes is selected as the time range
3
PROGRAMMING
P
Timing Direction: Determines whether the time value will increment from zero and change the state
tdir
uP
P
PrSt
On
P
FrSt
On
of the output at the set value (uP) or decrement from the set value and change the state of the output at zero (dn).
Power Reset Enable: After a loss of power, the unit can be programmed to either reset upon reapplication of power (On) or continue from the point of power interruption (Off).
Front Panel Reset Enable: When active (On), the timing operation can be reset in Operation Mode by simultaneously pressing the "E" and "P" keys. If inactive (Off), the timing operation can only be reset through the remote input.
P
SLuL
0
Security Level: 4 different levels of security are available:
0 = Full Access
1 = SP Locked Out
2 = Access to Program Mode only by holding the "P" key for 8 seconds
3 = SP Locked Out and access to Program Mode only by holding the "P" key for 8 seconds
4
OPERATING MODES
TIMING DIAGRAMS
On-Delay
Power
Start
Output
Reset
Instant. Output
T
Timing begins on the leading edge of the start input. The output will activate at the completion of the preset time (T) and will remain active until the reset signal is applied or power is interrupted.* The instantaneous output will activate upon the start signal and will remain active until the reset signal is applied or power is interrupted.*
Power
Start
Output
The output is activated at the leading edge of the start signal. Timing begins on the trailing edge. The output will remain active until the preset time (T) has elapsed or power is interrupted.* Reapplying the start signal before T has elapsed will reset the time value. The reset input is not used.
Interval 1
Power
Start
Output
T
T
Power
Start
Output
T
Off-Delay
T
Interval 2
T
T
On the leading of the start input, the output is activated and timing begins. The output will remain active until the preset time (T) has elapsed or power is interrupted.* Removal of the start signal will also cause the output to be
On the leading of the start input, the output is activated and timing begins. The output will remain active until the preset time (T) has elapsed or power is interrupted.* The reset input is not used.
deactivated and the time value to be reset. The reset input is not used.
Repeat Cycle
Power
Start
Output
T
T
T
Timing begins on the leading edge of the start signal. A cycle is initiated where the output will be OFF for the preset time (T), then ON for the preset time. This cycle will continue until a reset signal is applied, start signal is removed or power is interrupted.* The unit can also be programmed for the timing sequence to begin with an ON cycle.
* The Power Reset parameter in Program Mode can be set so that a timing sequence will not be reset upon power interruption but instead continue on when power is restored.
Power
Start
Output
Reset
The delay cycle begins upon application of the start signal. The output will activate at the completion of the preset time (T1). Upon activation of the output, the Interval cycle will begin. The output will be deactivated at the end of the Interval time (T2). T1 is the primary preset value and is set in Operation Mode. T2 is set in Program Mode in a range from 0.1 to 999.9 seconds. The timing sequence and output can also be reset through the reset input or interruption of power.*
Delay/Interval
T1
T2
5
NOTES
6
Veeder-Root Dynapar Eagle Signal
NOTES
Veeder-Root Dynapar Eagle Signal
7
GENERAL
ORDERING INFORMATION
SPECIFICATIONS
Inputs
Start: NPN or Dry Contact Reset: NPN or Dry Contact
Outputs
Timed (B856-500): DPDT - 5 amp Timed (B856-511): SPDT - 5 amp Instantaneous (B856 -511): SPDT - 5 amp Activation Time: 15 msec. max.
Physical
Dimensions: 48mm x 48mm, 81mm deep Mounting Panel Mounting 45 x 45 cutout, or
DIN rail
Wiring Connection Via 11 pin plug in socket
Operation
Supply Voltage: 24 - 240 VAC 50/60Hz, or 24 VDC Power Consumption: 50 VA @ 240 VAC Time Ranges: Hours, Minutes, Seconds, Hours:Minutes,
Resolution: Settable for XXXX or XX.XX for Hours,
Operating Modes: On Delay, Off Delay, Interval 1, Interval 2,
Repeat Accuracy: + 0.03% Electrical Service Life: 100,000 cycles at full load Mechanical Service Life: 10 million cycles at min. load Weight: 100 grams (3.5 ounces)
Environmental
Front Panel Rating: IEC IP65 Operating Temperature: B856-500: 0° to 60° C (32° to 140° F)
Storage Temperature: -40° to 90° C (-40° to 194° F) Humidity: 5% to 95% RH non-condensing Approvals: UL, CUL recognized; CE certified
ORDERING INFORMATION
Minutes:Seconds
Minutes and Seconds ranges
Repeat, Delay/Interval
B856-511: 0° to 50° C (32° to 122° F)
Description Model #
Multifunction Timer, 24 - 240 VAC, 24 VDC B856-500
Timer w/Instant Cont, 24 - 240 VAC, 24 VDC B856-511
Description Model #
11 Pin Socket 60SR3P06
11 Pin Socket - Outward Facing Terminals PBT-03172
WARRANTY
Standard B856 products manufactured by the Company are warranted to be free from defects in workmanship and material for a period of two years from the date of shipment, and products which are defective in workmanship or material will be repaired or replaced, at the option of the Company, at no charge to the Buyer. Final determination as to whether a product is actually defective rests with the Company. The obligation of the Company hereunder shall be limited solely to repair and replacement of products that fall within the foregoing limitations, and shall be conditioned upon receipt by the Company of written notice of any alleged defects or deciency promptly after discovery within the warranty period, and in the case of components or units purchased by the Company, the obligation of the Company shall not exceed the settlement that the Company is able to obtain from the supplier thereof. No products shall be returned to the Company without its prior consent.
Products which the Company consents to have returned shall be shipped F.O.B. the Company's factory. The Company cannot assume responsibility or accept invoices for unauthorized repairs to its components, even though defective. The life of the products of the Company depends, to a large extent, upon the type of usage thereof, and THE COMPANY MAKES NO WARRANTY AS TO FITNESS OF ITS PRODUCTS FOR SPECIFIC APPLICATIONS BY THE BUYER NOR AS TO PERIOD OF SERVICE UNLESS THE COMPANY SPECIFICALLY AGREES OTHERWISE IN WRITING AFTER THE PROPOSED USAGE HAS BEEN MADE KNOWN TO IT.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE.
8