Eagle access control systems POWER II User Manual

INSTALLATION & OWNER'S
INSTALLATION & OWNER'S
MANUAL
MANUAL
THE EAGLE POWER II BATTERY BACK UP
Control Box
Battery Box
PHONE (818) 764-6690 / TOLL FREE (800) 708-8848
PRE INSTALLATION INSTRUCTIONS
!
BEFORE PROCEEDING WITH INSTALLATION READ THIS MANUAL THOROUGHLY AND CAREFULLY FOLLOW ALL THE OPERATION INSTRUCTIONS.
The Eagle-Power II Battery Back up is designed to provide back up power to a gate operator when the main AC supply voltage is interrupted or disconnected. There are two operations to the Eagle-Power II. First, (and recommended) when experiencing a power failure the back-up system not only supplies continuous power to run the gate operator, but will supply all of the the AC accessories (i.e. Loop Detectors, MAG lock, Photo Eyes and Edge Sensors) with all the power required to keep their full functions uninterrupted. Secondly, in the occurrence of power failure the gate can be opened by the Power I"hold open" relay and left open until power is restored. However, with the availability of continuous power available to the operator, this would not be necessary unless desired.
Using the Power II battery back up system with its 115V continuous power, enables the gate operator and all of its safety features to continue to be UL 325 / 991 compliant.
IMPORTANT: THE PHONE SYSTEM TRANSFORMER SHOULD BE INSTALLED DIRECTLY
TO THE OPERATOR OUTLETS AND NOT TO THE EAGLE POWER
IMPORTANT: MONTHLY TESTS MUST BE PERFORMED ON BATTERY.
!CAUTION
THE POWER II IS INTENDED FOR USE WITH ONE 1HP GATE OPERATOR. DO NOT INSTALL THE POWER II ON TWO OPERATORS.
!
CAUTION
I UNIT.
WARNING - HIGH VOLTAGE
ONLY A QUALIFIED TECHNICIAN SHOULD SERVICE THIS GATE OPERATOR
BATTERY TEST LOG
OPERATOR SERVICES DATESBATTERY TEST DATES
//
// // //
//
//
// //
//
//
// //
//
// // //////
//
//
//
//
// //
(1)
THE EAGLE POWER II INFORMATION & WARNINGS
The following items are included with the POWER II:
(A) Power II Control Box
(B) 1 - 75 AH Battery Box (in a second box)
(C) 1 - N/O Relay Output
(D) 2 - 3/4" Raintight Flexible Conduits
(E) 2 - 3/4" Raintight Conduit Connectors
(F) 1 - 12VDC Output (Optional)
(G) 1 - Instruction Manual
Power II
Approximate Dimensions: Control Box : 13 3/8" (h) x 18 5/8" (w) x 11" (d) Battery Box : 14 1/2" (h) x 12 1/2" (w) x 9" (d)
(SEE PAGE #6 FOR FURTHER MEASUREMENTS)
The Eagle-Power II is a indoor & outdoor unit
CAUTION!
!
THE POWER II IS DESIGNEDTO PROVIDE
POWER TO A GATE OPERATOR IN CASE OF A POWER FAILURE OR THE POWER IS SHUT OFF. THE OPERATOR CAN START UNEXPECTEDLY WHEN THE AC POWER IS NOT SUPPLIED. PRIOR TO THE SERVICING OF GATE OPERATOR, BE SURE TO DISCONNECT THE BATTERY PACK OR TURN THE POWER OFF
CAUTION!
!
THE POWER II PRODUCES LETHAL VOLTAGES. THE BATTERY CAN CARRY HAZARDOUS CURRENTS. THE ASPS SHOULD BE INSTALLED BY A QUALIFIED TECHNICIAN.
CAUTION!
!
DO NOT SHORT THE BATTERY TERMINALS!
(2)
INSTALLATION OF THE EAGLE POWER-II
EAGLE POWER- II
Eagle Operator Gate Size
Eagle-2000-1HP
Eagle-200- 1HP
E-POWER IIE-POWER II E-POWER II
Cycles Per 12 Hour Period
10' 80**
15'
20'
50**
30**
70**
Cycles Per 12 Hour Period With Extra Battery *
160
100
60
140
* An extra 70AH battery comes with separate mounting box and cables - Weight: 65 lbs ** All ratings are for operators (including The Diamond Control Board) and three of the following
accessories: Loop Detector, Receiver, MAG Lock, Phone System and Electric Eye. Additional accessories will reduce the amount of cycles. Testing was only performed on the above specified Eagle Operators. All cycle estimates are based on properly installed gates and operators.
(3)
INSTALLATION OF THE EAGLE POWER- II
CONNECTING THE AC LINE VOLTAGE:
Electrically, the Power II is wired in series with the incoming AC supply from the breaker box to the operator. The connector labeled "AC In" is connected to the main AC supply. The "AC Out" is connected to the operator.
Connect the incoming AC line to the AC In as follows:
L - AC Line In (Live): Black N - AC neutral (Common): White G - AC Ground (Earth): Green
Connect the outgoing AC line to the AC Out as follows:
L - AC Line Out: Black N - AC neutral: White G - AC Ground: Green
Refer to the installation manual provided with operator for the proper connections to the operator
APPLYING THE POWER AND CONNECTING THE SYSTEM RELAY
With the power to the operator and breaker box turned off and all of the AC line connections are complete, install the provided relay. After 5 to 10 seconds the green inverter light will turn on. Then run the operator with the main breaker off to test the Power I. When testing is completed, turn on the breaker and the green inverter light will go off, then the charger green or yellow light will go on.
FOR HOLD OPEN APPLICATION
Connect the two orange wires from the sub panel to the "exit open" on the operator. Using this connection will immediatly open the gate upon power failure. The operator will resume normal operation when power is resumed.
REMINDER:
failure and the initial functioning of the Power II .
There is a time delay of approximately 1-3 seconds between a power
IMPORTANT!
Eagle recommends surge protection be installed on the incoming 110 AC Line to the battery back-up unit.
(4)
INSIDE OF THE EAGLE POWER II
Control Box
Control Sub Panel
AC OUT
2000 Watt Inverter
Hold Open
AC IN
Battery Charger
+
-
Battery Terminals
Battery Box
-
+
70 Ah Battery
(5)
INSTALLATION OF THE E-I PSMOUNTING THE EAGLE POWER I
21"
Mounting Bracket Holes 3/8" Diameter
13 3/8"
Rear View of Control Box
18 1/2"
20" OC
16"
Mounting Bracket Holes 3/8" Diameter
10" OC
1"
Drawings Not To Scale
2 1/2"
12 1/2"
Rear View of Battery Box
14 1/2" OC
13 3/4"
7 1/2" OC
2 1/2"
(6)
THE EAGLE POWER II
Recommended Installation with flex conduit
Control Box
Battery Box
3/4" Water-tight flexible conduit with fittings
(7)
S PE C IFICATIO N S & W AR R A NTY
INPU T VO LTAGE : 105 - 125 VAC BATTE RY: 12VDC / 70AH RECHARGE TIME: 8 HOURS OUT P UT VO LTAGE : 115 VAC OUTP UT F R E QUE NC Y: 60 Hz OUTPUT CUR R E NT: 15 AMPS SURGE CURRENT: 30AMPS AC OU T P UT PO W E R : 2000 WAT T S S U R G E P OW E R : 4000 WATT S RELAY OUTPUTS: 10AMPS
TECHNICAL SPECIFICATIONS
CAUTION!
!
DO NOT EX C E E D T H E
OUTPUT CAPACITY
OF THE POWE R II.
CONNECTING A MO TOR LO A D LAR GE R T HA N R E C O MME N D E D
MAY DAMAG E T HE POWER II AND VOID
THE WARRANTY.
MA NU F A CTUR E R ' S L IMIT E D WAR R A NTY
E agle Acces s C ontrol S ystems, Inc. warrants its Power II to be free from defect in material and workmanship for a period of one ( 1) yea r from the date of purchas e for s ingle family home or multi-fa mily and c ommercia l us e. To obtain se rvice c onta ct your de a ler.
To obtain s e rvic e under this warranty the buyer must obtain authorization ins tructions for the return of a ny goods from E agle before returning the goods. T he goods mus t be re turned with complete identification, with copy of proof-of-purchase , freight prepaid a nd in ac cordance with E agle's instructions or they will not be a cce pted. In no event will E agle be res ponsible for goods returned without proper authorization or ide ntifica tion.
G oods returned to E agle for warranty repair within the warra nty period , which upon receipt by E a gle are confirmed to be defective and covered by this limited wa rranty, will be repa ired or replaced a t E agle's s ole option, at no cos t a nd re turne d pre pa id. De fective pa rts will be repa ired or repla ced with new or factory re built parts E agle's sole option.
T his limited warra nty doe s not cove r non-de fect da ma ge , damage caus e d by unreasona ble us e, dama ge c a us ed by improper ins tallation or care, vandalis m, or lightning, fire or exces s ive heat or other acts of G od (including, but not limited to misus e , abus e or altera tions , fa ilure to provide reasonable and nec ess ary ma intenance ), la bor charges for dismantling or reinstalling a repaired or replaced unit, or replacement batteries.
T he s e warra nties are in lieu of a ll other wa rranties , either e xpres s e d or implied. All implied warra nties of merchantability a nd/or a particular purpos e are hereby discla imed a nd excluded. Under no circums tanc es s ha ll E agle be liable for consequential , incidental or s pecial dama ges aris ing in co nne ction with the us e or ina bility to use this product. In no event s hall E agle 's liability for brea ch of warra nty, breech of contract, negligence or s trict lia bility e xcee d the cos t of this produc t hereby. N o pe rs on is authoriz ed to as s ume for E agle any other liability in connection with the sa le of this product.
F or Further Informa tion: P hone (800) 708-8848 / F ax (818) 764-6869
(8)