Dynisco SPX228, SPX538 Operating Manual

P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-1-
SPX Product Family
Smart Industrial Pressure Transmitters
Intrinsically safe and Explosion-proof
pressure transmitters with integrated amplifier
for use in hazardous environments
Operating Manual
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-2-
ATTENTION
ATTENTION
DYNISCO SPX QUICK START CARD
This Quick Start Setup guide can be used by experienced instrumentation technicians to configure the Transmitter using the Zero and Span actuators or via the optional HART Communications. For more detailed information please consult the complete manual before operating. The Quick Start procedure with HART is designed for users already familiar with the use of the HART Communicator and loop powered instrumentation.
QUICK START USING PUSH BUTTONS
1. Insure the process connection is clear of any debris and is machined to the proper dimensions. nstall unit into the process connection. (Do NOT torque transmitter into the hole at this time!)
I Allow time for the transmitter temperature to equalize to the process temperature. This w h
elp eliminate thread galling and ease removal later. There should be NO pressure applied at
this time.
ill
2. Connect power to the transmitter. For conduit output configurations, Red wire is Sig+/Exc +,
Black wire is Sig-/Exc-, Green wire is Ground. For a 6 pin connector version, Pin A is Sig+/Exc+ and pin B is Sig-/Exc-. Insure proper loop supply voltage is applied to transmitter.
3. After temperatures have equalized, tighten transmitter.
4. Perform Zero Function
D
o not remove seal screws when the circuit is live in a hazardous area
Remove zero pushbutton seal screw
Using a 2mm or smaller Allen key, depress the pushbutton for a ½ second
Release pushbutton for a ½ second
Depress the pushbutton again for a ½ second and release
5. Verify loop output is zero (4 mA).
6. Replace the Seal Screw.
Seal screws must remain in place to retain Explosion Proof certification
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-3-
QUICK START UTILIZING HART COMMUNICATOR
ollow Steps 1 through 3 from Quick Start Using Push Buttons.
1. F
2. Connect Communicator to the loop. If unsure on how to do this, refer to “Connecting the HART Handheld Communicator” (Figure 6-1).
3. Power on HART Communicator. See HART Command tree on the following page for reference.
4. From the Main Menu:
a. Enter Tag (Quick Key 1, 3, 1) b. Set Pressure Units (Quick Key 1, 3, 2), if required c. Set URV (Quick Key 1, 3, 3, 2) if output turndown (rescaling), is required d. Perform Zero Trim (Quick Key 1, 2, 5, 1, 3, 1)
5. Verify loop output is zero (4mA).
6. Remove HART Communicator from loop.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-4-
1 Device Setup 1 Proc ess 1 PV Pres 1
Alrms & Wrnings EEPROM Fai lure
Variabl es 2 Pv % rnge Gage Fail ure
3 PV AO 2 Max. Press ure Watchdog Error 4 TV Snout temp Pushbutton Stuck 5 TV % rnge 3 Max. Ele ctronics Low Voltage 6 TV A O Tempe rature Outside URV LRV 7 SV Elect temp 4 Max. Snout Temp Current S IM ON
2 Diag/Se rvice 1 Device S tatus 1 Pressure 1 Rer ange 1 Enter values 1 PV LRV
2 Apply values 2 PV URV
2 Self Test 2 Temperatu re 2 Trim analog 3 PV USL
output 1 Zero trim 4 PV LSL
3 Master reset 3 Recall Fact. Trim 3 Se nsor trim 2 Lower Sensor Tri m
2 PV Pres 3 Upper Sen sor Trim
4 Loop test psi 4 Rcal
bar 1 Rcal Set
5 Calibration kg/S qcm
% 1 Temperatu re 1 Temp Ove rride Disable 6 Restore MPa Overri de Enable Factory De faults KPa 2 Trim analog 2 Tem p Overrid e
Output Value
3 Basi c Set up 1 T ag 1 PV LRV
2 PV URV 1 PV Pres 2 PV Unit 3 TV LR V 2 PV % rgne
4 TV UR V 3 P V AP 1 PV LRV 3 Range valu es 5 PV LSL 4 TV Snout temp 2 PV URV
6 PV USL 5 TV % r nge 3 PV USL
3 TV Snout 4 Dev ice 7 TV LSL 6 TV AO 4 P V LSL Temp Information 8 TV USL 7 SV Elect temp
5 PV Damp
1 Date 1 Enter values
4 Detailed 1 Signal condition 2 Des criptor 2 Apply values Setup 3 Message
2 Output condition psi
1 Process v ariable s bar 3 Field Device Inf. kg/Sqcm
2 Rer ange %
MPa
5 Review 1 Mode l 3 PV Unit KPa
2 Manufacturer 3 Dev id 4 PV Rnge unit psi 4 Distrib utor bar
4 PV LRV 1 PV LRV 5 Poll addr 5 PV Min span kg/Sqcm
2 PV URV 6 Num req preams %
7 PV Unit 6 PV Damp MPa
5 PV URV 1 P V LRV 8 PV USL KPa
2 PV URV 9 PV L SL 7 SV C
PV Min span 1 PV Pres PV Damp 1 Proce ss variabl es 2 PV % rgn e PV % rn ge 3 PV A P PV Xfer fnctn 2 Analog output 4 TV Sno ut temp PV Rnge unit 5 TV % rn ge PV URV 3 HART output 6 TV A O 1 Enter values 1 PV LRV PV LRV 7 SV Elect temp 2 PV URV Lower Tri m Point V … Hi 2 Apply value s 3 PV USL Upper Trim Point V… 1 PV AO Lo 4 PV LSL TV C 2 TV A O Hold last out value TV US L 3 PV AO Alrm typ TV LSL 4 Loop test 1 Pressure 1 Rerang e 1 Zero tri m TV % rn ge 5 Calibration 2 Lower Sensor TV Rnge unit 2 Te mperature 2 Trim AO Trim TV UR V 1 Poll addr 3 Upper Sensor TV LRV 2 Num req preams 3 Recall Fact. Trim 3 Sensor t rim Trim Write protect 3 Burst mode Tag 4 Burst option Off 4 Rcal 1 Rcal Set Descrip tor 1 Tag On Message 2 Date Disable No t used 1 Tem p 1 Te mp Disable Date 3 Descript or Enable None Overri de Override Enable Unive rsal rev 4 Message Std Unknown 2 Trim AO Fld dev rev 5 Mo de l Zero trim Spcl 2 Tem p Softw are rev 6 Local Pushbuttons Overri de Val Hardware re v 7 Revision #'s 1 Univers al rev PV
8 Final asmbly num 2 Fld dev rev % ran ge/current
9 Dev id 3 Softw are rev Proce ss vars/crnt
enu Tree
M
OTE: Above is the Menu Tree for the latest Device Descriptor. For units with software revision < 100
N refer to Appendix 2 for appropriate Menu Tree.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-5-
Table of Contents
1 GENERAL …………………………………………………………………………….6
2 NOTES ON SAFETY ...................................................................... 11
3 TECHNICAL DATA ........................................................................ 16
4
5
6
7
8
9
10
11
12
13
TRANSPORT/DELIVERY ............................................................. 20
INSTALLATION .......................................................................... 21
COMMISSIONING ..................................................................... 23
MAINTENANCE ......................................................................... 35
TROUBLESHOOTING ................................................................. 36
APPROVALS/CERTIFICATES ....................................................... 37
APPENDIX 1 - DEFAULT VALUES ............................................... 41
APPENDIX 2 – Menu Tree (Software Revision < 100) ............... 52
DRAWINGS…………… .................................................................. 53
DYNISCO CONTACT INFORMATION .......................................... 56
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-6-
1 GENERAL
1.1 IMPORTANT INFORMATION
This manual applies to the SPX industrial pressure product family only (SPX228/SPX538). The SPX melt pressure family is covered in a separate manual. This manual must be kept near the equipment in a readily and immediately accessible location at all times. The content of this manual must be read, understood and followed in its entirety. This applies in particular to the notes on safety. Following the safety instructions will help to prevent accidents, defects and malfunctions.
DYNISCO will not be held liable for any injury, loss or damage resulting from failure to follow the instructions in this manual.
If the product malfunctions, in spite of having followed the operating instructions, please contact customer service from our website:
www.dynisco.com/contact
1.2 COPYRIGHT
Copyright law requires that this manual be used for intended purposes only.
It is strictly forbidden to allow reproduction of any kind “in whole or in part” to persons outside of Dynisco, without approval from Dynisco.
HART is a registered trademark of HART Communication Foundation.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-7-
ATTENTION
1.3 EXPLANATION OF ICONS
The manual uses icons to indicate information pertaining to safety:
Risk of destruction or damage to equipment, machines or installations
General danger to life or limb
Specific danger to life or limb
Related to ATEX/Intrinsic Safety requirements
Related to Factory Mutual Approval requirements
Related to Safety Integrity and Performance Level Applications
The safety instructions are provided again in the individual sections of the manual.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-8-
1.4 ABBREVIATIONS
The following abbreviations are used:
BSL Best Straight Line DD Device Descriptor EEPROM Electrically Erasable Programmable Read Only Memory FS Full Scale HART Highway Addressable Remote Transducer LRV Lower Range Value PT Pressure Transmitter PV Primary Variable (Pressure) SV Secondary Variable (Electronics Temperature) URV Upper Range Value Watchdog An internal monitor for the electronics
1.5 NAMING CONVENTION
SPX S
PX Industrial Smart Pressure Transmitters (228 & 538 Series)
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-9-
providing a window into the process
1.6 TRANSMITTER PRINCIPLES OF OPERATION
The mechanical system consists of a gaged diaphragm. One side of the diaphragm is in direct contact with the fluid media (gas or liquid) while a strain gage element in the configuration of a Wheatstone bridge is bonded to the backside.
The deflection of the diaphragm causes a change in the resistance of the strain gage and hence a change in the balance of the bridge. The amount of imbalance is directly proportional to the applied pressure. This completes the translation of pressure applied to the diaphragm into a usable electrical signal.
The low level output signal from the bridge is amplified via an instrumentation amp circuit. The amplified signal then goes to the input of the analog-to-digital (A/D) converter.
Once the microprocessor has the converted voltage input from the A/D converter, the digital signal is sent to a digital-to-analog (D/A) converter which modulates the current of the unit’s power supply between 4 and 20 mA for an output current proportional to the applied pressure.
Figure 1-1 Block Diagram of Operation
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-10-
1.7 CORRECT USE
When using an SPX as a safety component in accordance with the EC Machine Directive, Annex IIc, the equipment manufacturer must take any necessary precautions to ensure that malfunction of the PT cannot cause damage or injury.
For explosive gas the installation of the device must be in accordance with European installation guidelines EN 60079-14 for explosive gas atmospheres. Over voltage protection shall be implemented as mentioned in EN 60079-14.
When planning machinery and using one of the units from the SPX Family, follow the safety and accident prevention regulations that apply to your application, such as:
EN 60204, Electrical equipment in machines
EN 12100, Machine safety, general design guidelines
DIN 57 100 Part 410, Protection against electric shock
EN 60079-0
EN 60079-11 Intrinsically Safe Apparatus
EN 60079-25 Special Requirements for Group II Category 1G
1.8 USER’S OBLIGATIONS
The operator or owner of the larger overall system, e.g. a machine, is responsible for following the safety and accident prevention regulations that apply to the specific application.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-11-
2 NOTES ON SAFETY
he operator or owner of the larger overall system is responsible for following the safety and accident
T prevention regulations that apply to the specific application.
DYNISCO will not be held liable for any injury, loss or damage resulting from failure to follow the instructions in this manual.
Warnings
The SPX is an ESD sensitive component. Electrostatic discharge may damage the SPX. Take ESD precautions.
Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressure-less, voltage-free, intrinsically safe condition with the
machine switched off. The machine must be secured against being switched back on!
EMC/CE Compliant Connection
Earth the machine section with the process connections for the SPX in accordance with regulations. The SPX must be connected to earth via the process connection.
Connect the shield of the connecting cable on both sides, making sure it conducts with full and continuous contact.
When introducing the connecting cable into an EMC compliant switch cabinet, for example, connect the shield correctly (cable gland, conducting, full contact, and continuous) to the conductive housing or route it via a built-in cable connector that is also connected to the conductive housing. Connect unused cable cores or free cable ends correctly to the cable shield on both sides.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-12-
Temperature
The SPX can be used in me
dia temperatures up to +85°C (based on configuration). If the pressure transmitter is used in other applications, the safety and accident prevention regulations specific to that application must be followed. Ambient temperature for the electronics housing is +85°C maximum in areas that are not classified as hazardous.
Higher temperatures can result in damage and malfunction. Do not install the pressure transmitter in places where these temperatures are exceeded.
Use in Hazardous Classified Areas
Se
veral configurations of the SPX are designed and approved for use in hazardous classified areas. Units
intended for installation in these areas must bear the applicable approval agency label.
The SPX is specially designed for measuring pressure in explosive gas atmospheres for Zone 0 under safety class II 1 G Ex ia IIC T6/T4 (T6, Ta = -20 to + 50°C; T4, Ta = -20 to + 85°C). The SPX is also approved for hazardous gas area Zone 1 under safety class II 2 G Ex ia IIC T6/T4 (T6, Ta = -20 to + 60°C; T4, Ta = -20 to + 85°C).
The maximum T
(medium temperature) for temperature class T6 is +60°C and for T4 is +85°C. The
med
medium temperature for the SPX is defined as the temperature of the pressure transmission fluid below the measuring diaphragm (See Figure 1-1). This temperature can be verified by measuring the surface temperature at the base of the electronics housing.
For category 1 (Zone 0) installations, care must be taken to avoid the danger of ignition due to electrostatic discharges (ESD). The chance for static build up on the cable surface during normal conditions of use, maintenance and cleaning must be eliminated. Install the cable in an appropriate conduit or use some other cable reliable installation technique to avoid static electricity at the cable surface.
The free length of the cable must be below 5 cm. If metallic conduits are used they need to be g
rounded. If nonmetallic conduits are used they need to be antistatic (< 1G Ohm/cm
2
).
The housing shall be connected reliably to the local equipotential bonding system.
Those variants that include the material aluminum shall be installed in such a way that sparking as a
sult of impact or friction between aluminum and steel is excluded. Impact or friction between
re aluminum and stainless steel is allowed if the existence of rust particles can be excluded.
For application as Category-1-E conductive coating (R
surface < 10
quipment the connecting cable shall be equipped with a suitable
9
Ω) to avoid possible electrostatic charge.
After installation before operating the device the user must check that the complete installation and wiring is intrinsically safe. Care must be taken that the power source is a certified apparatus.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-13-
Deviation of the supply voltage from the value given in the technical specifications, or reverse polarity, can damage the pressure transmitter and cause malfunctions that can pose a risk of explosion. Operate only with an intrinsically safe, EMC compliant power supply with the following specifications when employing the pressure 4-20 mA output:
Supply Voltage max. Uo = 30 V DC Current Output max. Io = 100 mA Power max. Po = 0.750 W
The specified values of Lo and Co for the power supply need to be greater than Ci + Ccable and Li + Lcable.
Internal Inductance Li < 40 µH Internal Capacitance Ci < 4.5 nF
If the transmitter is installed in hazardous areas, only passive devices like switches or resistors may be connected between the RCAL+ and RCAL- signals. Connection of any active electronic circuits or voltage or current sources is not allowed.
Certain configurations of the SPX are also designed for use in hazardous areas as Explosion-proof and Dust Ignition-proof by Factory Mutual for Class I, Division 1, Groups A, B, C & D, and Class II, III, Division 1, Groups E, F & G.
For SPX units that are explosion-proof approved for Class I, Division 1, Groups A, B, C & D the power supply rating is 13-30 Vdc.
Additional Comments:
1) Do not remove the transmitter push-button seal screws in explosive environments when the circuit
is live.
2) Transmitter push-button seal screws must be fully engaged to meet Explosion-proof requirements.
3) Before connecting a HART handheld communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-14-
2.1 SAFETY integrity and performance level applications
User’s obligations
The operator or owner of the larger overall system, e.g. a machine, is responsible for following the safety and accident prevention regulations that apply to the specific application.
Intended Use
See Certificate in section 9.4
Safety Function
See Certificate in section 9.4
For units with the optional monitoring channel (Guardian Series, Option Code = GCxxx):
Under normal operating conditions the relay contacts are closed. In the event that a failure is detected the relay contacts open. Detectable failures include:
1) Loss of Power
2) Open Gage
3) Input over a predefined (customer selectable at time of order) threshold
The Guardian Series transducer has been designed to provide a protective measure. This has been done by the avoidance and control of systematic and random failures. This product will:
Measure the pressure and provide a safety relay output. Since this is being used to perform a protective measure, this sensor should only be used for monitoring the pressure and not controlling the process. Best practices declare that safety and control must be independent from each other.
The Guardian Series transducer detects many hardware failures including an open or short in the measuring gage and if there is an overpressure condition. If any of these failures occur, the output relay will open. It is the user’s responsibility to connect this relay to the system in such a way that when this relay opens, it brings the system to a safe state.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-15-
This fault state is not latched. It is up to the user to latch this error if desired.
Recommended practices
This Guardian Series transducer must be installed in such a way that the opening of the output relay will bring the system to a safe state. In this safe state the instrument that is monitoring the pressure should be left operational.
This error indication is not latched. If it is necessary to latch the error until it is manually reset, this is the user’s responsibility.
At startup and on a periodic basis the safety system should be tested to ensure proper operation. This will require applying a pressure to the Guardian Series transducer that is over the safe level but less than the maximum pressure. Verify that the protective measure is initiated to take the machine to a safe operating condition.
Use of qualified personnel
The product may only be assembled, installed, configured, commissioned, operated and maintained by persons with proven skills. Persons with proven skills are suitably experienced to operate devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
It is the user’s responsibility only to employ personnel who:
Are familiar with the basic regulations concerning health and safety and accident prevention
Have read and understood the safety guidelines given in this description
Have a good knowledge of the generic and specialist s ta nd a rds applicable to the specific application
Connecting Safety Relay
Relay specs: Maximum switching voltage: 200Vdc; Maximum switching current: 0.5A
Device pinout
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-16-
XXX
Accuracy
Pressure Reference
Hazardous Area Classification
Process Connections
Electrical Connections
Wiring Connections
Pressure
Option Code Communications
Pressure Range
Model
X
X X
X
XX X
X XX
X
XXXX
228
+/- 0.25%
Gage Pressure (PSI)
Non-Approved
1/8-27 NPTF Internal
PT02A-10-6P Connector
Standard Wiring
PSI
Option Code
4-20mA HART Comms
5000
228
1
N G
A
AA 0
P
21
B
XXXX
3 TECHNICAL DATA
3.1 MODEL CODE BREAKDOWN
e exact meanings of the letter/digit combinations are given in the corresponding sections of this
Th Chapter.
.2 ORDERING EXAMPLE
3
ote(s):
N
1) Review section 3.4 Performance Characteristics for accuracy definition and details.
2) Review “Notes on Safety” (Chapter 2) before installation in Hazardous locations.
3) Certain models are not available in some configurations.
4) For other process connections please consult factory.
5) Other approved ranges may exist, please consult factory.
6) Transmitters are available with certain approved option codes. Please consult factory for list of approved options.
3.3 SAFETY SPECIFICATIONS
Please see “Notes on Safety” (Chapter 2.)
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-17-
Model
Range
Accuracy (% of FS)
2280
15 – 72,500 PSI
+/- 0.50
2281
15 – 72,500 PSI
+/- 0.25
2282
5 – 10,000 PSI
+/- 0.15
Model
Pressure
5-25 psi, w/ overload stop
10 x range
50-750 psi, w/ overload stop
5 x range
250 – 30,000 psi
1.5 x range
Greater than 30,000 psi
1.2 x range
Model
Pressure
250 psi
10 x range
500-3,000 psi
5 x range
5,000 – 10,000 psi
3 x range
15,000 – 30,000 psi
2.5 x range
40,000 – 60,000 psi
1.5 x range
3.4 PERFORMANCE CHARACTERISTICS
3.4.1 ACCURACY Accuracy is defined as combined error expressed as a percentage of full scale (% F.S.) output based on the following standard configurations/conditions:
1) Best Straight Line % F.S. as per ISA-37.3
2) +20°C ambient electronics
*Consult factory for non-standard configurations.
.4.2 RESOLUTION
3
±0.035% full scale @ 50% F.S. (average resolution)
3.4.3 REPEATABILITY
± 0.10% of full scale
3.4.4 OVERLOAD PRESSURE (MAX PRESSURE WITHOUT INVALIDATING SPECIFIED ACCURACY)
3.4.5 BURST PRESSURE
3.4.6 FREQUENCY RESONSE
20 Hz [-3db]
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-18-
3.4.7 RESPONSE TIME
50 mS
3.5 ELECTRICAL DATA
Configuration 4-arm Wheatstone bridge strain gauge with internal amplifier
Output Signal 2-wire 4 - 20 mA
Saturation Levels 3.8 mA and 20.5 mA
Fail Safe Levels 3.6 mA for Low Level
Current Consumption < 25 mA Supply Voltage 13 - 30 VDC for PTB ATEX IS and FM XP approved models
>21mA for High Level
13 - 32 VDC for non-approved models
Note: Transmitter incorporates overvoltage protection and reverse polarity protection and will not operate if inputs are reversed.
Sense Resistor Load Line
250 ohms minimum for HART communication
3.6 TEMPERATURE INFLUENCE
ELECTRONICS HOUSING
Operating Temperature Range -29°C to +85°C
Compensated Temperature Range -17°C to +65°C
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-19-
Zero Shift due to temperature change on electronics housing
0.01% FS/°F max. (0.02% FS/°C max.)
Span shift due to temperature change on electronics housing
0.01% FS/°F max. (0.02% FS/°C max.)
PROCESS CONNECTION
Zero shift due to temperature change on the diaphragm
0.01% FS/°F max. (0.02% FS/°C max.)
Span shift due to temperature change on diaphragm
0.02% FS/°F max. (0.04% FS/°C max.)
3.7 EMC REQUIREMENTS
The SPX Conforms to CE in accordance with EMC directive. See Declaration of Conformity for more details.
3.8 MATERIALS
Standard Diaphragm 15-5PH Mat. No. 1.4545 Standard Wetted Parts 17-4PH Mat No. 517400
Please note other diaphragm and stem materials may be substituted.
3.9 ENVIRONMENTAL PROTECTION TO ANSI/IEC-60529 & ANSI/NEMA-250
SPX with sealed conduit to IP67, NEMA 4X
3.10 WEIGHT
The weight varies depending on product configuration. Average weight range is 1 to 3 pounds.
3.11 DIMENSIONS
The dimensions vary based on product configurations. Contact Dynisco if product dimensions are required.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-20-
ATTENTION
providing a window into the process
4 TRANSPORT/DELIVERY
The SPX is an ESD sensitive component. Electrostatic discharge may damage the SPX. Take ESD precautions.
4.1 TRANSPORT/PACKING/TRANSPORT DAMAGE
Do not let the SPX be damaged by other items during transit
• Use only the original packaging
Report transport damage to DYNISCO immediately in writing
4.2 STORAGE
Store the SPX in original packaging only
• Protect against dust and moisture
4.3 SCOPE OF DELIVERY
SPX with diaphragm protection cap
• Calibration sheet
• Operating manual with declaration of conformity
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-21-
providing a window into the process
5 INSTALLATION
NOTES: Follow all Notes on Safety in Section 2 during installation.
5.1 GENERAL MOUNTING INFORMATION
Do not remove the protective cap on the SPX until ready to install.
Before mounting the SPX, check the process connection carefully. The SPX must only be mounted in process connections that satisfy the requirements below. A process connection that does not satisfy these requirements can damage the transmitter.
Insure the process connection is clear of any debris and is machined to the proper dimensions. In applications involving high temperature operation and/or repeated thermal cycling a good high quality anti-seize compound should be applied to the threaded surfaces.
Install unit into the process connection (Do NOT torque transmitter into the hole at this time!). Allow time for the transmitter snout temperature to equalize to the process temperature. This will help eliminate thread galling and ease removal later. There should be NO pressure applied at this time.
Always use a torque wrench applied to the designated wrench flats while screwing the transmitter in and out. Do not apply the tool to the housing or housing/sensor connection.
After temperatures have equalized tighten transmitter into process connection.
When removing the SPX, carefully clean the diaphragm of the transmitter with a soft cloth while the medium is still malleable.
Always remove the SPX prior to cleaning the machine with abrasives or steel wire brushes. Also, do not clean the SPX with hard objects, such as a screwdriver, a wire brush, etc. This will possibly damage the transmitter.
Burn Hazard! The SPX can be very hot when removed. WEAR PROTECTIVE GLOVES!
Careful attention should be paid to correctly machine the mounting port. Failure to use the recommended mounting port may result in erroneous pressure measurement, difficult transducer removal, premature sensor failure, process fluid leaks, and personnel hazard.
5.2 ELECTRICAL CONNECTION
Connect power to the transmitter. For conduit output configuration, Red wire is Sig+/Exc +, Black wire is Sig-/Exc-, Green wire is Ground. For a 6 pin connector version, Pin A is Sig+/Exc+ and pin B is Sig-/Exc-. Insure proper loop supply voltage is applied to transmitter.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-22-
Connection Type
Terminal
Description
Conduit-Lead
Wire Color
PWR+/SIG+
Red
A
PWR-/SIG-
Black
B
CASE
Green
-
RCAL+
Orange
F
RCAL-
Blue
E
ATTENTION
he SPX is an ESD sensitive component. Electrostatic discharge may damage the PT. Take ESD
T precautions.
Mounting and electrical connection of the SPX must be done by specialists with EMC training, following all applicable regulations, and in pressure less, voltage-free,
intrinsically safe condition with the machine switched off.
he machine must be secured against being switched back on!
T
5.3 CONNECTION ASSIGNMENTS
The device must be connected to a certified power supply. Each unit will include a primary 4-20mA output. The unit may also have one of the options listed in the table below. See section 2.1 details of units with GCxxx option code.
for wiring
Signal
6-Pin
Primary 4-20mA
Optional RCAL
If the transmitter is installed in hazardous areas, only passive devices like switches or resistors may be connected between the RCAL+ and RCAL- signals. Connection of any active electronic circuits or voltage or current source is not allowed.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-23-
6 COMMISSIONING
ere are two ways of commissioning the SPX transmitters. This can be done by utilizing the ZERO and
Th SPAN actuators or by HART Communications via a communicator connected to the pressure loop.
If the SPX is equipped with the optional HART Communications, it is not necessary to access the zero/span actuators on the sensor.
If the transmitter is not equipped with HART then the zero/span actuators must be utilized. However, Sections 6.3 through 6.8 and 6.11 may be skipped.
6.1 WHY A TRANSMITTER MUST BE REZEROED
The transmitter output must be nulled at zero pressure after installation when the machine has stabilized at operating temperature. This is easy to understand why when considering the mechanical properties of the sensor.
Depending on the orientation of the sensor, the weight of the diaphragm will have an effect on the sensing diaphragm. The weight of the diaphragm will either increase or decrease deflection of the diaphragm, creating a shift in the strain gage output that can appear as a positive or negative pressure.
There are some other effects that may affect the zero as well, such as torque, side loading, etc. For more information contact Dynisco.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-24-
ATTENTION
ATTENTION
providing a window into the process
All of these effects can be compensated for by setting the transmitter zero after the machine has stabilized at operating temperature.
6.2 UTILIZING THE ZERO AND SPAN ACTUATORS
When the transmitter output needs to be corrected due to mounting location and temperature shift the zero actuator can be used (if a HART Communicator is not available.) Please wait until the process has been brought to operating temperature before zeroing. The zero procedure is only recommended after the process temperature has stabilized and the SPX electronics housing has been permanently installed.
When the actuator is depressed in a certain sequence, the output will be corrected to reflect 4 mA. This is done by the transmitter electronics automatically by adjusting the LRV and URV settings simultaneously to the offset required to obtain 4 mA. Normally a Zero calibration is all that is required after installation since the Transmitter span has been calibrated at the factory. In the event the Full Scale output is not correct when checked against a calibrated pressure source or dead weight tester, the transmitter span can be adjusted via the Span actuator. This is performed by applying a known calibrated full scale pressure to the transmitter and depressing the Span actuator in a certain sequence. When complete, the transmitter electronics will have adjusted the URV to correct to output to equal 20 mA.
The span actuator should never be used to set the URV without zeroing the PT with the zero actuator first.
If for some reason the calibration is incorrect and the user wishes to revert back to the Factory Calibration, a procedure can be performed to revert the calibration back to factory state. Refer to “Resetting to Factory Default Settings” in this Chapter.
6.2.1 ZERO AND SPAN PROCEDURE
1. Connect Power Supply to SPX signal leads with 250 Ohm load and milliamp meter in series with
loop.
2. If commissioning on the bench with a dead weight tester or calibrated pressure source, ensure
pressure connection is free of leaks.
3. Apply power to the SPX transmitter and observe loop current with zero pressure applied. It
should be 4 mA. If other than 4 mA proceed to step 4.
4. Perform Zero Function.
i. Do not remove seal screw when the circuit is live in a hazardous area.
ii. Remove zero pushbutton seal screw. iii. Using a 2mm or smaller Allen key, depress the pushbutton for a ½ second. iv. Release pushbutton for a ½ second.
v. Depress the pushbutton again for a ½ second and release.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-25-
ATTENTION
ATTENTION
ATTENTION
providing a window into the process
The available pressure is now adopted as the new lower range value.
Steps past this point are not part of a normal bench setup and should only be performed by qualified individuals, as the SPX is highly stable and has been factory calibrated with highly accurate pressure generators. This function should only be performed on such equipment.
5. Apply Full Scale pressure and verify output is 20 mA. If output is other than 20 mA, perform
Local Span adjustment:
i. Do not remove seal screw when the circuit is live in a hazardous area.
ii. Remove span pushbutton seal screw. iii. Using a 2mm or smaller Allen key, depress the pushbutton for a ½ second. iv. Release pushbutton for a ½ second.
v. Depress the pushbutton again for a ½ second and release.
The available pressure is now adopted as the new upper range value.
6.3 UTILIZING THE HART COMMUNICATIONS
The zero procedure is only recommended after the process temperature has stabilized and the SPX electronics housing has been permanently installed. When the zero trim function is selected (HART Quick key 1,2,5,1,3,1) the output will be corrected to reflect zero pressure. This is done by the transmitter electronics automatically by adjusting digital PV to zero and analog output will be 4 mA. Normally a Zero Trim is all that is required after installation since the Transmitter span has been calibrated at the factory
In the event the Full Scale output is not correct when checked against a calibrated pressure source or dead weight tester, the Transmitter span can be adjusted by performing the Sensor Trim function. This is performed by first applying Zero Pressure and selecting Lower Sensor Trim (HART Quick Key 1, 2, 5, 1, 3,
2) and following the prompts on the HART Communicator. When complete, apply a known calibrated full scale pressure to the Transmitter and selecting Upper Sensor Trim (HART Quick Key 1, 2, 5, 1, 3, 3) and follow the prompts on the HART Communicator. When complete, the transmitter electronics will have adjusted the digital PV to correct to full scale output.
Never perform upper sensor trim without performing lower sensor trim first.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-26-
ATTENTION
providing a window into the process
6.3.2 CONNECTING THE HART HANDHELD COMMUNICATOR
In hazardous areas, refer to the handheld communicator instruction manual for instructions for HART Communicator to function properly.
A minimum of 250 Ohms resistance must be present in the loop.
The HART Communicator does not measure loop current directly.
The HART Communicator can interface with the SPX anywhere along the 4 - 20 mA cable as shown in the following figure.
Figure 6-1 HART Communicator Interface
6.3.3 PROCEDURE
1. Connect Power Supply and HART Communicator per the above diagram.
2. If commissioning on the bench with a dead weight tester or calibrated pressure source, insure
pressure connection is free of leaks.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-27-
ATTENTION
providing a window into the process
3. Apply power to the SPX transmitter and turn on the HART Communicator by pressing the
ON/OFF key. The LCD display should show [SPX-T or SPX depending on model] in the upper left corner. If this is not present, consult the Troubleshooting section of this manual.
4. Set PV Units (Fast Key 1,3,2) to appropriate pressure unit. (e.g. psi, Bar, kgf/cm2, MPa)
5. Set Tag (Fast Key 1,3,1).
6. If transmitter output needs to be re-ranged, set the appropriate LRV (Fast Key 4,1) and URV
(Fast Key 4,2)
Note: URV cannot be turned down below the PV Minimum span (Fast Key 1,4,1,5)
7. Set Lower Trim (Fast Key 1,2,5,1,3,1)
8. Verify SPX transmitter output. Zero pressure output should read 4 mA.
Steps past this point are not part of a normal bench setup and should only be performed by qualified individuals, as the SPX is highly stable and has been factory calibrated with highly accurate pressure generators. This function should only be performed on such equipment.
9. Next, using calibrated pressure source, apply pressure equal to value set in URV in step 6.
Output should equal 20 mA. If output does not equal 20 mA proceed to step 10.
10. To calibrate full scale output, first apply pressure equal to full scale pressure of unit. Next
perform Upper Sensor Trim (Fast Key 1,2,5,1,3,2). Output should now equal full scale pressure.
11. If Transmitter Output Damping is required, set PV Damping (Fast Key 1,3,5) to the appropriate
value.
12. Press the left arrow key until the HART Communicator is off-line then turn the power off.
The SPX pressure transmitter is now ready to be installed in the process.
6.4 SPX ANALOG OUTPUT
The SPX has a 4-20 mA output proportional to pressure for normal operating conditions. However, unlike a traditional sensor, the SPX performs self-diagnostic routines continually during operation. If a special condition is detected, the transmitter drives its analog output outside the normal saturation values to indicate that investigation is necessary (this condition is called fail-safe mode alarm). The conditions detected by the self-diagnostic routines (and the corresponding effect on the analog output) are listed later in this section.
When a special condition is detected, the SPX goes into fail-safe mode and the transmitter output goes high, by default. However, using a HART communicator, the transmitter can also be configured to drive its output low or to freeze the output where it was just before the fail-safe was detected. The actual analog output levels are indicated below.
A low alarm (3.6 mA) is possible but not recommended because HART communications are not guaranteed until the cause of the alarm is removed.
Using the HART communicator, the specific condition that triggered the fail-safe mode alarm can be read for diagnostic purposes (see Status in the HART menu tree).
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-28-
n a fail-safe condition the PV is not affected and can still be read using the handheld HART
I communicator. For process related fail-safe conditions, the transmitter will remain in the alarm state until the source of error disappears. If certain electronics errors are detected, the fail-safe condition will latch until a reset is performed by either cycling the power or through a software command.
NAMUR Compliant Saturation and Alarm Values
4 - 20 mA Saturation 4 - 20 mA Alarm
ow 3.8 mA 3.6 mA
L High 20.5 mA >21 mA You can alter the actual transmitter mA output values by performing an analog output trim using the HART Communicator.
When a transmitter is in an alarm condition, the analog output displayed by the handheld indicates the alarm value of the analog output – NOT the value the transmitter would have, if the sensor had not detected the failure.
Special Conditions and the Corresponding Analog Output
Condition Alarm Value (fail safe) EEPROM failure detected Set to configured fail safe mode Cold start Set to fail safe mode low Pressure above upper limit Unchanged Pressure below lower limit Unchanged Electronics temp above upper limit Unchanged Electronics temp above lower limit Unchanged Strain gage open detected Set to configured fail safe mode Analog output saturated Unchanged Watchdog error detected Unchanged Zero/Span Actuator stuck Set to configured fail safe mode Low voltage detected Unchanged Outside URV or LRV Unchanged Rcal simulation on Unchanged
6.5 ALARM & SATURATION VALUES BURST MODE
No special requirements are defined for the burst mode.
6.6 ALARM & SATURATION VALUES IN MULTIDROP MODE
If the device is in multidrop mode, the NAMUR levels are no longer achievable. Instead the fail safe condition is indicated by the field device status and the additional diagnostics.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-29-
ATTENTION
providing a window into the process
6.7 SPX TRANSMITTER FUNCTIONS VIA HART
Zero Trim (1,2,5,1,3,1)
Digital Correction to zero which affects the digital output. This differs from Lower Sensor Trim in that zero trim is ONLY performed at zero pressure.
Lower Sensor Trim (1,2,5,1,3,2)
Digital Correction to zero which affects the digital output. This differs from Zero Trim in that Lower Sensor Trim can be performed at pressures above zero. Note: This must be performed before Upper Sensor Trim. Only perform this function with a known calibrated pressure source.
Upper Sensor Trim (1,2,5,1,3,3)
Digital correction to Full Scale which affect digital output. Note: Lower Sensor Trim must be performed before Upper Sensor Trim. Only perform this function with a known calibrated pressure source.
Digital to Analog trim (1,2,5,1,2)
This is used to match the digital representation of the analog output with its actual analog loop current. Note: This should only be performed with a known Calibrated Current (mA) meter.
Reranging
The SPX allows for the 4 mA and 20 mA points (LRV and URV respectively) to be adjusted so that output resolution can be improved. A Re-range or “Turndown” ratio of 6:1 is possible. Accuracy specifications remain dependent upon the Full Sensor Range without any turndown applied. Three methods of Re­ranging the SPX Transmitter are outlined below. Note: If pressure applied to the transmitter is not in the range of the 6:1 turndown ratio, the transmitter will reject the Span attempt. This will be indicated by the output not adjusting to 20 mA after a few attempts using the Span Actuator.
Reranging via Zero/Span Actuators
When HART Communication is not used, LRV and URV values are entered by applying zero pressure to the SPX-T and “Rezeroing” by:
i. Do not remove seal screw when the circuit is live in a hazardous area.
ii. Remove zero pushbutton seal screw. iii. Using a 2mm or smaller Allen key, depress the pushbutton for a ½ second. iv. Release pushbutton for a ½ second.
v. Depress the pushbutton again for a ½ second and release.
The LRV and URV have now been adjusted to zero the device without affecting the span.
After Rezeroing, it is possible to set the span by adjusting the URV with the span actuator. The span actuator should never be used to adjust the URV without using the zero actuator to set the LRV first.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-30-
ATTENTION
providing a window into the process
URV or Full Scale Turndown is performed by applying any pressure, within the 6:1 ratio of the transmitter that you want to be the 20 mA point. When the pressure is held steady:
i. Do not remove seal screw when the circuit is live in a hazardous area.
ii. Remove span pushbutton seal screw. iii. Using a 2mm or smaller Allen key, depress the pushbutton for a ½ second. iv. Release pushbutton for a ½ second.
v. Depress the pushbutton again for a ½ second and release.
The SPX has now adjusted the URV 20 mA point to match the pressure applied.
6.8 RERANGING VIA HART
Rerange LRV (4)
This is the pressure at which the transmitter will output 4 mA as entered directly by the user. Changing the LRV affects the transmitter span so the is range is limited by the minimum span value found in Fast Key (1,4,1,5)
Rerange URV (5)
This is the pressure at which the transmitter will output 20 mA as entered directly by the user. This range is limited by the minimum span value found in Fast Key (1,4,1,5)
Rerange LRV By Applying Pressure (1,2,5,1,1,1,1)
This is done by applying a known pressure and initiating the procedure so that the transmitter adopts the pressure as the 4 mA point.
Note: This should only be performed with a Calibrated Pressure Source.
Rerange URV By Applying Pressure (1,2,5,1,1,1,2)
This is done by applying a known pressure and initiating the procedure so that the transmitter adopts the pressure as the 20 mA point. Note: This should only be performed with a Calibrated Pressure Source.
Recall Factory Trim (1,2,5,3)
This is used to restore the Zero, Lower, and Upper Trim to the Values as set from the Factory.
R-Cal Set % (1,2,5,1,4,1)
This is used on versions with a Rcal. By activating R-Cal, the output will be set to the percentage of span set by this function. Default is 80%. Setting Rcal to 0%, disables the Rcal function.
Damping (1,3,5)
The damping time constant affects the speed with which the primary output signal reacts to changes in pressure as shown in the figure on the following page. Damping is off by default but values between 0 and 30 seconds can be set using the handheld communicator. The damping value must be entered in integers. If non-integers are entered, the system rounds to the next integer.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-31-
providing a window into the process
Local Actuator Disable (1,4,3,6)
Local zero and span actuators can be disabled using the HART handheld communicator function “Local Push-buttons.” When turned off, the software Lock Out prevents changes to transmitter range points via the local zero and span actuators. With local Push-buttons disabled, changes to configuration are still possible via HART.
Status (1,2,1,2)
Reads Device Status from SPX.
PV Unit (1,3,2)
The pressure unit defines the unit of measure that the pressure-specific parameters are transmitted in. The SPX can be configured in the engineering units of psi, Bar, MPa, and kgf/cm² or as a percentage of Full Scale (FS). After selecting a new pressure unit, all entries for pressure are recalculated to the new unit, using the following conversion rules:
1 psi = 0.068947 Bar = 0.0068947 MPa = 0.070309 kgf/cm²
Tag (1,3,1)
An inventory “Tag” identification number may be stored in transmitter memory (8 characters maximum). Software tag is a single question mark by default.
Descriptor (1,3,4,2)
A 16 character text can be entered for further description of transmitter e.g. location, function, position, etc.
Message (1,3,4,3)
A 20 character message can be set and displayed on the HART Communicator.
SV Electronics Temperature (1,1,7)
Temperature measured on the Electronics Assembly is used for reference and factory diagnostics only.
Poll Address (1,4,3,3,3)
Use in Multidrop mode allows more than one transmitter (up to 15) on a single loop. If this value is other than zero, the transmitter is in Multidrop mode. An example of Multidrop mode would be a
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-32-
ATTENTION
group of HART devices wired in parallel on a single powered loop and each device being assigned a unique Poll address (1-15). The HART communicator would prompt for the individual address of the transmitter to communicate with and would only poll that specific device. All others would remain unchanged. Note: Analog output is set to 4mA when in multi-drop mode.
Burst Mode (1,4,2,3,1)
When the SPX-T is used in Burst Mode, the transmitter outputs one-way digital communications from the transmitter to the Host. Communication rate is faster since the transmitter does not have to be polled to send data. Information transmitted in Burst Mode includes Pressure Variable, Analog Output value, Pressure in % of range. Access to other information can still be obtained through normal HART Comms.
6.9 RESETTING TO FACTORY DEFAULT SETTINGS
The factory settings for the sensor (including zero and span) can be restored if they are changed inadvertently using the Zero/Span Actuators or the HART communicator. The list of parameters restored is shown below.
Make sure Control System is in Manual mode. Temporary loss of Loop Output during Electronics Re-boot may occur.
To reset the sensor using the actuators, use the following procedure:
i. Do not remove seal screw when the circuit is live in a hazardous area.
ii. Remove zero and span pushbutton seal screws. iii. Using a 2mm or smaller Allen key, depress the pushbuttons for a ½ second. iv. Release pushbuttons for a ½ second.
v. Depress the pushbuttons again for a ½ second and release.
At this point, the LRV and URV will be set to factory defaults.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-33-
providing a window into the process
6.10 DEFINITION OF “RESTORE FACTORY DEFAULTS”
1. Restore LRV and URV to their values at shipment.
2. Restore the Pressure Unit (psi, Bar, etc.) to its value at shipment.
3. Set the Analog Output Alarm Level to its value at shipment.
4. Remove all Pressure Damping.
5. Clear all Sensor and Analog Output Trim values.
6. Clear Burst Mode.
7. Restore the Address to Zero.
8. Restore the Rcal option to its value at shipment (enable or disable the Rcal option).
9. Set actuators to the settings they were when shipped from DYNISCO.
6.11 HART COMMUNICATOR FAST KEY SEQUENCES
Below defines the HART Communicator Fast Key sequences. Fast Keys are a means of supplying a shortcut to navigate through the menu tree.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-34-
Function
Fast Key Sequence
Read PV Pressure
2
Read % of Full Scale
1,1,2
Read Analog Output (PV)
1,1,3
Read SV Electronics Temperature
1,1,7
Read Peak Pressure Value
1,2,1,2
Read Peak Electronic Temp Value (SV)
1,2,1,3
Read Sensor Diagnostic Status
1,2,1,1
Read PV Minimum Span
1,4,1,5
Perform Sensor Self-Test
1,2,2
Perform Sensor Master Reset
1,2,3
Perform Loop Test
1,2,4
Perform D/A Trim (PV)
1,2,5,1,2
Perform Zero Trim
1,2,1,3,1
Perform Lower Sensor Trim
1,2,5,1,3,2
Perform Upper Sensor Trim
1,2,5,1,3,3
Recall Factory Trim
1,2,5,3
Set Rcal %
1,2,5,1,4,1
Set Tag
1,3,1
Set PV Unit
1,3,2
Set Lower Range Value (LRV) (PV)
1,3,3,1
Set Upper Range Value (URV) (PV)
1,3,3,2
Display Lower Set Limit (LSL) (PV)
1,3,3,5
Display Upper Set Limit (USL) (PV)
1,3,3,6
Set Date
1,3,4,1
Set Descriptor
1,3,4,2
Set Message
1,3,4,3
Set PV Damping
1,3,5
Set SV Temperature Unit
1,4,1,7
Set PV Analog Output Alarm Type
1,4,2,2,3
Set Poll Address
1,4,2,3,1
Set # of Request Preambles
1,4,2,3,2
Set Burst Mode
1,4,2,3,3
Set Burst Option
1,4,2,3,4
Read Analog Output (TV)
1,1,6
Read Peak Temp Value (TV)
1,2,3,4
Perform D/A Trim (TV)
1,2,5,2,2
Set Lower Range Value (LRV) (TV)
1,3,3,3
Set Upper Range Value (URV) (TV)
1,3,3,4
Temperature Override
1,2,5,2,1,1
Temperature Override Value
1,2,5,2,1,2
HART Communicator Fast Key sequences
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-35-
Symptom
Corrective Actions
Milliamp Reading is Zero
1) Check if Power Polarity is Reversed
2) Verify Voltage Across Transmitter Pins
providing a window into the process
7 MAINTENANCE
7.1 MAINTENANCE
Mounting and electrical connection of the SPX must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free, intrinsically safe condition with the
machine switched off.
The machine must be secured against being switched back on!
Burn Hazard! The SPX can be very hot when removed. WEAR PROTECTIVE GLOVES!
Installation and Removal Instructions
DO NOT REMOVE PROTECTIVE CAP UNTIL READY TO INSTALL.
PRIOR TO INITIAL INSTALLATION, VERIFY CORRECT MACHINING OF MOUNTING HOLE.
WHEN REINSTALLING, MAKE SURE THE PROCESS CONNECTION IS CLEAR OF DEBRIS.
ALWAYS REMOVE THE SPX BEFORE CLEANING THE MACHINE WITH ABRASIVES OR STEEL WIRE
BRUSHES, ETC.
DO NOT CLEAN THE “SCREWED-IN” SECTION OF THE SPX WITH HARD OBJECTS – THIS WILL
DAMAGE THE SPX.
ALWAYS USE A TORQUE WRENCH APPLIED TO THE DESIGNATED WRENCH FLATS. DO NOT
APPLY THE TOOL TO THE HOUSING OR HOUSING/ SENSOR CONNECTION.
ELECTROSTATIC DISCHARGE MAY DAMAGE THE SPX – TAKE ESD PRECAUTIONS.
7.2 REPAIR/DISPOSAL
For SPX repair and disposal please contact customer service from our website:
www.dynisco.com/contact
7.3 WARRANTY
The SPX Series Dynisco Pressure transmitters will provide excellent service and superior performance if proper care is taken during handling, installation, and use. This DYNISCO product is warranted under terms and conditions set forth in the DYNISCO web pages. Go to www.dynisco.com "warranty" link under the “Post-Sales Support” tab at the top of the web page for complete details.
8 TROUBLESHOOTING
and click on the
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-36-
Large Zero Shift when Screwing In
1) Check Hole with Gage Plug and Rework Hole as Required
2) Check Mounting Torque
Primary Milliamp Reading is Low or
1) Check Pressure Variable Reading for Saturation
4) Perform 4 - 20 mA Output Trim with HART Communicator
No Response to Changes in Applied
1) Check Test Equipment
4) Check if in multi-drop mode
Pressure Variable Reading is Low or
1) Check Test Equipment
3) Perform Full Sensor Trim
Pressure Variable Reading is Erratic
1) Check Port/Pipe for Blockage or Solidified Plastic
3) Check for EMI
Transmitter Not Communicating with HART Communicator
1) Check Power Supply Voltage at Transmitter
5) Confirm HART communicator is connected to primary (Pressure) output 4-20mA
HART Communicator missing SPX Features Described in Manual
From the Communicator’s Main Menu, Access the On-Line
Arrange for DD Upgrade
Primary output =3.6mA or > 21mA
4) Unit is in fail safe, consult fail safe section
High
Pressure
High
2) Check if Output in Alarm Condition
3)Verify 4 and 20 mA Range Points or Simply Reset
2) Check Port/Pipe for Blockage or Solidified Plastic
3)Check if Output in Alarm Condition
2) Check Port/Pipe for Blockage or Solidified Plastic
2) Check Damping
2) Check Load Resistance (250 Ohm minimum)
3)Check Communicator Connection Across Power Supply
4)Check if Unit is Addressed Properly
Menu. The Name SPX Should be Displayed on the Top Line of the LCD. If the Name is not Present, Contact Dynisco to
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-37-
9 APPROVALS/CERTIFICATES
9.1 CE DECLARATION OF CONFORMITY .................................................................................... 388
9.2 EC-TYPE EXAMINATION CERTIFICATE ................................................................................. 400
9.3 EX FM CERTIFICATE OF COMPLIANCE ................................................................................. 445
9.4 SAFETY INTEGRITY AND PERFORMANCE LEVEL APPLICATION …………………………………………409
Note additional approvals available; please consult factory.
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-38-
9.1 CE DECLARATION OF CONFORMITY
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-39-
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-40-
9.2 EC-TYPE EXAMINATION CERTIFICATE
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-41-
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-42-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-43-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-44-
providing a window into the process
9.3 EX FM CERTIFICATE OF COMPLIANCE
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-45-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-46-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-47-
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-48-
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-49-
9.4 Safety Integrity and Performance Level Applications
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
providing a window into the process
-50-
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-51-
Variable
Default Value
Access
Options
Analog Output Alarm Flag
Low
RW
High
Hold Last
Burst Command Enable
Off
RW Burst Option Variable
PV
RW
Date of Last Factory Calibration
Date of Calibration
RO
User Selectable Date
Date of Calibration
RW Manufacturer Identification Code
0 x 72
RO Dev ID (Device Identifier)
Unique number set by Factory
RO Final Assembly Number
<BLANK>
RW
Local Push-button Enable
Enable
RW
Enabled Disabled
Factory Default LRV
0
RO Lower Sensor Limit
-0.04 * full scale of SPX-T
RO Message Text
HTTP://WWW.DYNISCO.COM/
RW PV Minimum Span Value
Factory Default PV_URV divided by 5
RO Number of Request Preambles
5
RW PV Damping Constant Value
0 Seconds
RW
0-30
PV Lower Range Value
0
RW
0-30
PV Engineering Unit Code
Per Customer Order
RW
0 x 06 – PSI
0 x ED – MPa
PV Upper Range Value
Full scale (same as on label)
RW PV Transfer Function Code
Linear
RO Rcal Calibration Percentage
80%
RW
20 - 100%
Field Device Serial Number
As Set at Factory
RO Tag ? RW Transmit Address
0
RW
0 - 15
Factory Default URV
Per Customer Order
RO Upper Sensor Limit
1.5 * full scale of SPX
RO
providing a window into the process
APPENDIX 1 - DEFAULT VALUES
Low
www.dynisco.com
0 x 07 – Bar 0 x 0A – kg/cm² 0 x 39 – % of FS
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-52-
providing a window into the process
11 APPENDIX 2 – Menu Tree (Software Revision < 100)
for software revision < 100
www.dynisco.com
Menu Tree
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-53-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-54-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-55-
providing a window into the process
www.dynisco.com
P/N: 974153 | Rev: 072016 | ECO: 46503
From lab to production,
-56-
providing a window into the process
12 DYNISCO CONTACT INFORMATION
Please visit our website for up to date contact information:
www.dynisco.com/contact
www.dynisco.com
Loading...