Dynisco EIT Series Operating Manual

1
Operating manual
EIT Series
Intrinsically safe pressure transmitter for industrial application
II2G
ATEX100A
2
Table of Contents
Content
General
Notes on safety
Technical data
Function
Transport/ delivery
Installation
Commissioning
Maintenance
Accessories
Troubleshooting
-Declaration of conformity
Ex-Declaration of conformity
Chapter
1
2
3
4
5
6
7
8
9
10
11
12
Page
3
3
7
13
15
16
22
24
25
26
27
28
Icon
3
Operating manual
1. General
1.1 Important information 3
1.2 Copyright 3
1.3 Explanation of icons 4
1.4 Abbreviations 4
1.5 Correct use 4
1.6 User’s obligations 4
1.1 Important information
This manual applies to the EIT series only. It must be kept near the equipment in a readily and immediately accessible location at all times.
The content of this manual must be read, understood and followed in all points by all relevant people. This applies in particular to the notes on safety. Following the safety instructions will help to prevent accidents, defects and malfunctions.
DYNISCO will not be held liable for any injury, loss or damage resulting from failure to follow the instructions in this manual.
If malfunctions occur in spite of having followed the operating instructions, please contact the DYNISCO customer service department (see chapter 8, Maintenance).
This applies in particular during the warranty period.
1.2 Copyright
Copyright law requires that this manual be used for in-house purposes only.
All reproduction, even partially and for in-house purposes, requires the approval of DYNISCO. This manual may not be forwarded to third parties.
4
1.3 Explanation of icons
The manual uses icons to indicate information pertaining to safety:
Risk of destruction or damage to equipment, machines or installations
General danger to life or limb
The safety instructions are provided again in the individual chapters of the manual.
1.4 Abbreviations
The following abbreviations are used:
OM operating manual PT pressure transducer f.s. of full scale
1.5 Correct use
The EIT pressure transmitter is for measuring pressure in industrial explosive environments (safety class II 2G EEx ia IIC T5 up to 75°C, II 2G EEx ia IIC T1-T4 up to 80°C) as part of a larger overall system.
Type specific installation of the PT with:
- Internal thread ISO 228/1 - G¼ (EIT 332)
- Screw-in trunnion with external thread DIN 3852-A G¼A (EIT 352)
- Thread M18 x 1.5 (EIT 372)
The safety and accident prevention regulations specific to the application must be followed.
When using the PT as a safety component in accordance with the EC Machine Directive, Annex IIc, the equipment manufacturer must take any necessary precautions to ensure that malfunctions of the PT cannot cause damage or injury.
1.6 User’s obligations
The operator or owner of the larger overall system, e.g. a machine, is responsible for following the safety and accident prevention regulations that apply to the specific application.
5
Operating manual
2. Notes on safety
The operator or owner of the larger overall system is responsible for following the safety and accident prevention regulations that apply to the specific application.
When planning machinery and using the PT, follow the safety and accident prevention regulations that apply to your application, e.g.:
EN 60204, Electrical equipment in machines.
EN 292, Machine safety, general design guidelines.
DIN 57 100 Part 410, Protection against electric shock.
EN 50 014, Electrical equipment for explosive atmospheres, general provisions
EN 50 020, Intrinsic safety “i”
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free,
intrinsically safe condition with the machine switched off.
The machine must be secured against being switched back on!
Ambient temperature for the electronics housing max. +75°C (safety class T5; T1 - T4 max. +80°C). Higher temperatures can result in damage and malfunction. Do not install the pressure transmitter in places where this temperature is exceeded.
Explosion hazard!
Deviation of the supply voltage from the value given in the technical specifications, or false polarity, can damage the pressure transmitter and cause malfunctions that can pose a risk of explosion.
6
Operate only with an intrinsically safe, EMC compliant power supply with the following specifications: Supply voltage max. 28 V DC Current output max. 93 mA Power output max. 690 mW Inductivity max. 1 mH Capacity max. 53 nF
Explosion hazard!
The pressure transmitter must be connected using a 2x2-core, twisted cable (blue cable sheath).
Do not lay connecting cables in the direct vicinity of cables carrying higher voltage or used to switch inductive or capacitive loads.
7
Operating manual
3. Technical Data
3.1 Ordering guide 7
3.2 Ordering example 7
3.3 Safety related specifications 8
3.4 Performance characteristics 8
3.4.1 Accuracy 8
3.4.2 Repeatability 8
3.4.3 Resolution 8
3.5 Pressure side connection 8
3.6 Pressure ranges 9
3.6.1 Pressure ranges in bar 9
3.6.2 Max. Overload 9
3.6.3 Burstpressure 9
3.6.4 Limit frequency 9
3.7 Electrical Data 9
3.8 Temperature influence 9
3.9 EMC requirements 10
3.10 Materials 10
3.11 Max. Mounting torque 1 0
3.12 Environmental protection 10
3.13 Weight 10
3.14 Seal 11
3.15 Dimensions 12
3.1 Ordering guide
EIT 3xx - xx - Option
Pressure range Output signal Pressure port
The exact meanings of the letter/digit combinations are given in the corresponding sections of chapter 3.
3.2 Ordering example EIT 352 - 5C
Intrinsically safe PT Press. port: 5 = External thread DIN 3852-A G¼A Output signal: 2 = 4 - 20 mA, 2-wire Press. range: 0 - 500 bar
8
3.3 Safety related specifications
ATEX certificate No.: ZELM 01 ATEX 0071 Ex safety class EEx ia IIC T5 up to 75°C
EEx ia IIC T1-T4 up to 80°C
Safety class EEx ia IIC T5 includes the following other safety classes:
Intrinsic safety “ib” Explosion groups IIA and IIB Temperature classes T1 - T4 up to 80°C
Certified maximum values
Associated electrical equipment must satisfy the following conditions:
Supply voltage max. 28 V DC Current output max. 93 mA Power output max. 690 mW Inductivity max. 1 mH Capacity max. 53 nF
3.4 Performance characteristics (EIT3x2-xx)
3.4.1 Accuracy
(Linearity and hysteresis at T = constant) EIT3x2 ±0.3% typ., ±0.5% of full
scale
3.4.2 Repeatability ± 0.1 % of full scale pressure
3.4.3 Resolution infinite
3.5 Pressure side connection (EIT3X2-xx)
EIT332 Internal thread ISO228/1-G¼ EIT352 Screw-in trunnion with
external thread DIN 3852-A G¼A
EIT372 Screw-in trunnion with
external thread M18 x 1.5 flush diaphragm
9
Operating manual
3.6 Pressure ranges (EIT3x2-XX)
3.6.1 Pressure ranges in bar Model number Permitted pressure range
bar
EIT3x2-20 0 - 20 series 372 only EIT3x2-35 0 - 35 series 372 only EIT3x2-50 0 - 50 EIT3x2-1C 0 - 100 EIT3x2-1,5C 0 - 150 EIT3x2-2C 0 - 200 EIT3x2-3,5C 0 - 350 EIT3x2-5C 0 - 500 EIT3x2-7C 0 - 700 EIT3x2-1M 0 - 1000
Other pressure ranges on request
3.6.2 Max. Overload (without influencing operating data)
2 x full scale pressure up to 700 bar Max. 1500 bar for the 1000 bar range
3.6.3 Burst pressure 4 x full scale pressure
3 x full scale pressure for the 20 bar and 1000 bar range
3.6.4 Limit frequency 1.5 kHz [-3dB]
3.7 Electrical data
Configuration 4-arm Wheatstone bridge
strain gauge with int. amplifier Output signal 2-wire 4 - 20 mA Strain resistance RL < 750 Ω bei US = 28 V
RL < 145 Ω bei US = 15 V Supply voltage 15 - 28 VDC -15 % +0 %
over approved electrical
equipment to EN 50 020 power consumption < 20 mA Calibration function 80 % ± 0,5 % of full scale
(room temperature) output by externally con-
necting contacts E and F Zero balance min. - 2 % / + 10 % f.s Range balance ± 10 % of full scale