Dynisco EIT Series Operating Manual

1
Operating manual
EIT Series
Intrinsically safe pressure transmitter for industrial application
II2G
ATEX100A
2
Table of Contents
Content
General
Notes on safety
Technical data
Function
Transport/ delivery
Installation
Commissioning
Maintenance
Accessories
Troubleshooting
-Declaration of conformity
Ex-Declaration of conformity
Chapter
1
2
3
4
5
6
7
8
9
10
11
12
Page
3
3
7
13
15
16
22
24
25
26
27
28
Icon
3
Operating manual
1. General
1.1 Important information 3
1.2 Copyright 3
1.3 Explanation of icons 4
1.4 Abbreviations 4
1.5 Correct use 4
1.6 User’s obligations 4
1.1 Important information
This manual applies to the EIT series only. It must be kept near the equipment in a readily and immediately accessible location at all times.
The content of this manual must be read, understood and followed in all points by all relevant people. This applies in particular to the notes on safety. Following the safety instructions will help to prevent accidents, defects and malfunctions.
DYNISCO will not be held liable for any injury, loss or damage resulting from failure to follow the instructions in this manual.
If malfunctions occur in spite of having followed the operating instructions, please contact the DYNISCO customer service department (see chapter 8, Maintenance).
This applies in particular during the warranty period.
1.2 Copyright
Copyright law requires that this manual be used for in-house purposes only.
All reproduction, even partially and for in-house purposes, requires the approval of DYNISCO. This manual may not be forwarded to third parties.
4
1.3 Explanation of icons
The manual uses icons to indicate information pertaining to safety:
Risk of destruction or damage to equipment, machines or installations
General danger to life or limb
The safety instructions are provided again in the individual chapters of the manual.
1.4 Abbreviations
The following abbreviations are used:
OM operating manual PT pressure transducer f.s. of full scale
1.5 Correct use
The EIT pressure transmitter is for measuring pressure in industrial explosive environments (safety class II 2G EEx ia IIC T5 up to 75°C, II 2G EEx ia IIC T1-T4 up to 80°C) as part of a larger overall system.
Type specific installation of the PT with:
- Internal thread ISO 228/1 - G¼ (EIT 332)
- Screw-in trunnion with external thread DIN 3852-A G¼A (EIT 352)
- Thread M18 x 1.5 (EIT 372)
The safety and accident prevention regulations specific to the application must be followed.
When using the PT as a safety component in accordance with the EC Machine Directive, Annex IIc, the equipment manufacturer must take any necessary precautions to ensure that malfunctions of the PT cannot cause damage or injury.
1.6 User’s obligations
The operator or owner of the larger overall system, e.g. a machine, is responsible for following the safety and accident prevention regulations that apply to the specific application.
5
Operating manual
2. Notes on safety
The operator or owner of the larger overall system is responsible for following the safety and accident prevention regulations that apply to the specific application.
When planning machinery and using the PT, follow the safety and accident prevention regulations that apply to your application, e.g.:
EN 60204, Electrical equipment in machines.
EN 292, Machine safety, general design guidelines.
DIN 57 100 Part 410, Protection against electric shock.
EN 50 014, Electrical equipment for explosive atmospheres, general provisions
EN 50 020, Intrinsic safety “i”
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free,
intrinsically safe condition with the machine switched off.
The machine must be secured against being switched back on!
Ambient temperature for the electronics housing max. +75°C (safety class T5; T1 - T4 max. +80°C). Higher temperatures can result in damage and malfunction. Do not install the pressure transmitter in places where this temperature is exceeded.
Explosion hazard!
Deviation of the supply voltage from the value given in the technical specifications, or false polarity, can damage the pressure transmitter and cause malfunctions that can pose a risk of explosion.
6
Operate only with an intrinsically safe, EMC compliant power supply with the following specifications: Supply voltage max. 28 V DC Current output max. 93 mA Power output max. 690 mW Inductivity max. 1 mH Capacity max. 53 nF
Explosion hazard!
The pressure transmitter must be connected using a 2x2-core, twisted cable (blue cable sheath).
Do not lay connecting cables in the direct vicinity of cables carrying higher voltage or used to switch inductive or capacitive loads.
7
Operating manual
3. Technical Data
3.1 Ordering guide 7
3.2 Ordering example 7
3.3 Safety related specifications 8
3.4 Performance characteristics 8
3.4.1 Accuracy 8
3.4.2 Repeatability 8
3.4.3 Resolution 8
3.5 Pressure side connection 8
3.6 Pressure ranges 9
3.6.1 Pressure ranges in bar 9
3.6.2 Max. Overload 9
3.6.3 Burstpressure 9
3.6.4 Limit frequency 9
3.7 Electrical Data 9
3.8 Temperature influence 9
3.9 EMC requirements 10
3.10 Materials 10
3.11 Max. Mounting torque 1 0
3.12 Environmental protection 10
3.13 Weight 10
3.14 Seal 11
3.15 Dimensions 12
3.1 Ordering guide
EIT 3xx - xx - Option
Pressure range Output signal Pressure port
The exact meanings of the letter/digit combinations are given in the corresponding sections of chapter 3.
3.2 Ordering example EIT 352 - 5C
Intrinsically safe PT Press. port: 5 = External thread DIN 3852-A G¼A Output signal: 2 = 4 - 20 mA, 2-wire Press. range: 0 - 500 bar
8
3.3 Safety related specifications
ATEX certificate No.: ZELM 01 ATEX 0071 Ex safety class EEx ia IIC T5 up to 75°C
EEx ia IIC T1-T4 up to 80°C
Safety class EEx ia IIC T5 includes the following other safety classes:
Intrinsic safety “ib” Explosion groups IIA and IIB Temperature classes T1 - T4 up to 80°C
Certified maximum values
Associated electrical equipment must satisfy the following conditions:
Supply voltage max. 28 V DC Current output max. 93 mA Power output max. 690 mW Inductivity max. 1 mH Capacity max. 53 nF
3.4 Performance characteristics (EIT3x2-xx)
3.4.1 Accuracy
(Linearity and hysteresis at T = constant) EIT3x2 ±0.3% typ., ±0.5% of full
scale
3.4.2 Repeatability ± 0.1 % of full scale pressure
3.4.3 Resolution infinite
3.5 Pressure side connection (EIT3X2-xx)
EIT332 Internal thread ISO228/1-G¼ EIT352 Screw-in trunnion with
external thread DIN 3852-A G¼A
EIT372 Screw-in trunnion with
external thread M18 x 1.5 flush diaphragm
9
Operating manual
3.6 Pressure ranges (EIT3x2-XX)
3.6.1 Pressure ranges in bar Model number Permitted pressure range
bar
EIT3x2-20 0 - 20 series 372 only EIT3x2-35 0 - 35 series 372 only EIT3x2-50 0 - 50 EIT3x2-1C 0 - 100 EIT3x2-1,5C 0 - 150 EIT3x2-2C 0 - 200 EIT3x2-3,5C 0 - 350 EIT3x2-5C 0 - 500 EIT3x2-7C 0 - 700 EIT3x2-1M 0 - 1000
Other pressure ranges on request
3.6.2 Max. Overload (without influencing operating data)
2 x full scale pressure up to 700 bar Max. 1500 bar for the 1000 bar range
3.6.3 Burst pressure 4 x full scale pressure
3 x full scale pressure for the 20 bar and 1000 bar range
3.6.4 Limit frequency 1.5 kHz [-3dB]
3.7 Electrical data
Configuration 4-arm Wheatstone bridge
strain gauge with int. amplifier Output signal 2-wire 4 - 20 mA Strain resistance RL < 750 Ω bei US = 28 V
RL < 145 Ω bei US = 15 V Supply voltage 15 - 28 VDC -15 % +0 %
over approved electrical
equipment to EN 50 020 power consumption < 20 mA Calibration function 80 % ± 0,5 % of full scale
(room temperature) output by externally con-
necting contacts E and F Zero balance min. - 2 % / + 10 % f.s Range balance ± 10 % of full scale
10
Leakage resistance > 1000 MΩ bei 50 V
3.8 Temperature influence
Storage temperature - 45°C to + 120°C
(medium temperature)
Operating temperature - 25°C to + 80°C
(medium temperature)
Max. housing temperatures Safety class T1 - T4 - 25°C to + 80°C Safety class T5 - 25°C to + 75°C
Compensated temperature range 0°C to + 70°C
(medium temperature)
Zero shift due to temperature change ± 0.1 % f.s. / 10 °C typ.
Sensitivity shift due to temperature change ± 0.2 % f.s. / 10 °C typ.
3.9 EMC requirements
Conforming to in accordance with EMC directive. Emitted interference DIN EN 50081-1
(residential area)
Immunity DIN EN 50082-2
(industrial area)
Connecting cables defined as data lines
3.10 Materials
In contact with medium 15-5PH Mat.No. 1.4545
3.11 Max. Mounting torque 22 Nm
3.12 Environmental protection to IEC 529
Pressure transducer IP65 (without connector) Standard female cable
connector DIN IP40
11
Operating manual
Cable connection option D05 IP67
3.13 Weight 0.25 kg
3.14 Seal
Data of the standard seal: Appropriate media Mineral oil, water, air,
oil-water-emulsions Temperature range - 35°C to + 120°C according
to elastomer quality Operating pressure When fitted in a recess up to
1000 bar.
Without recess and outside
of seal < 40 mm up to
400 bar
12
Fig. 01: EIT332
Fig. 02: EIT352
Fig. 03: EIT372
20 bar 35 bar 50 bar 100 bar 150 bar
X 12.55
±0.305
12.61
±0.305
12.78
±0.305
12.95
±0.313
13.12
±0.313
200 bar 350 bar 500 bar 700 bar 1000 bar
X 13.225
±0.313
13.515
±0.313
13.75
±0.313
13.95
±0.313
14.29
±0.313
3.15 Dimensions
13
Operating manual
4. Function
4.1 Construction 13
4.2 Description of functions 13
4.1 Construction
The PTs of series EIT are industry standard. The most important advantages are:
- Intrinsically safe EEx ia IIC T5
- thermal stability
- insensitivity to pressure peaks
- insensitivity to electromagnetic radiation (EMC)
- fully welded housing
- potted electronics
- maximum pressure 1000 bar
4.2 Description of functions
Through a diaphragm, the PT furnishes an electrical signal that is proportional to the pressure of the medium.
The pressure applied by the medium is forwarded to the measuring diaphragm. The deflection of the measuring diaphragm changes the resistance of the strain gauge bonded to the measuring diaphragm. The strain gauge is a Wheatstone bridge.
Dependent on the PT model, an electric signal proportional to the pressure is generated via the supply voltage or the amplifier.
14
Fig. 04: Functioning principle of the PT of the EIT series
Housing of PT
Strain gauge
Sealing surface
Diaphragm
Intrinsic safe mA amplifier
15
Operating manual
5. Transport / delivery
5.1 Transport / packing / transport damage 15
5.2 Storage 15
5.3 Scope of delivery 15
ESD sensitive component. Electrostatic discharge may damage the PT. Take ESD precautions.
5.1 Transport/packing/transport damage
- Do not let the PT be damaged by other items
during transit.
- Use only the original packaging.
- Report transport damage to DYNISCO
immediately in writing.
5.2 Storage
- Store the PT in original packaging only.
- Protect against dust and moisture.
5.3 Scope of delivery
- PT with diaphragm protection cap
- Seal
- Cable socket
- Calibration sheet
- Operating manual
16
6. Installation
6.1 Screw-in trunnion / Mounting hole 16
6.2 Mounting the Pressure Transducer 18
6.3 Electrical connection 19
6.3.1 EMC / compliant connection 20
6.4 Connection assignments 20
6.5 Wiring 21
Ambient temperature for the electronics housing max. +75°C (safety class T5; T1 - T4 max. +80°C).
Higher temperatures can result in damage and malfunction. Do not install the pressure transmitter in places where this temperature is exceeded.
6.1 Screw-in trunnion / Mounting hole
- Make screw-in trunnion / mounting hole as shown in figure 05 / 06 and 07.
Fig. 05: Screw-in trunnion for PT EIT 332 with
internal thread according to ISO 228/1 - G¼
12
R1
1x45°
3
G¼A
17
Operating manual
Fig. 06: Mounting hole form X
for PT EIT 352 with screw-in trunnion according to DIN 3852-A G¼A
1) The recess is not nessecary when no seal is used and the contact area is plain and rectangular to the axis of the thread.
2) Thread counterbored to outside diameter.
Fig. 07: Mounting hole for PT EIT 372 with screw-in
trunnion M18 x 1.5
1) The recess is not nessecary when no seal is used and the contact area is plain and rectangular to the axis of the thread.
2) Thread counterbored to outside diameter.
X min.
see chap. 3.15,
Dimensions
18
When reworking the screw-in trunnion / mounting hole, pay particular attention to the centricity of:
- the hole,
- the thread and
- the sealing surface. Pressure sealing with the standard seal takes place
on the sealing surface and on the front cylindrical section of the PT.
The sealing surface must be:
- correctly machined
- free from marks and rough edges
6.2 Mounting the Pressure Transducer
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free,
intrinsically safe condition with the machine switched off.
The machine must be secured against being switched back on!
ESD sensitive component. Electrostatic discharge may damage the PT. Take ESD precautions.
Before mounting the PT, check the screw­in trunnion / mounting hole carefully. The
PT must only be mounted when the screw-in trunnion / mounting hole satisfy the require-ments stipulated in chapter 6.1. Screw-in trunnion / mounting hole that does not satisfy these requirements can damage the PT.
For pressure sealing use always the seal that is delivered with the PT!
To prevent the PT from sticking permanently at the screw-in trunnion / mounting hole, coat the thread section of the transducer with high temperature resistant grease or a suitable parting agent.
Always use a spanner applied to the designated hexagon collar when screwing the PT in and out.
19
Operating manual
Do not apply the tool to the housing! Maximum mounting torque 22 Nm.
If the mounting torque is too high, the PT may be damaged or its zero point may shift.
- put the seal between PT and screw-in trunnion / mounting hole. The seal has to fit plain to the surface and must not be damaged.
- screw the PT to the screw-in trunnion / mounting hole and tighten.
6.3 Electrical connection
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free,
intrinsically safe condition with the machine switched off.
The machine must be secured against being switched back on!
Explosion hazard!
The pressure transmitter must be connected using a 2x2-core, twisted cable (blue cable sheath).
Do not lay connecting cables in the direct vicinity of cables carrying higher voltage or used to switch inductive or capacitive loads.
Operate only with an intrinsically safe, EMC compliant power supply with the following specifications: Supply voltage max. 28 V DC Current output max. 93 mA Power output max. 690 mW Inductivity max. 1 mH Capacity max. 53 nF
ESD sensitive component. Electrostatic discharge may damage the PT. Take ESD precautions.
The electrical connection must comply with EMC requirements.
If the electrical connection is not made as described in chapter 6.3.1, or if cables /
20
cable connectors / cable glands other than those stipulated by DYNISCO are used, DYNISCO cannot guarantee that EMC requirements will be satisfied.
6.3.1 EMC / compliant connection
- Earth the machine section with the screw-in trunnion / mounting hole for the PT in accordance with regulations. The PT must be connected to earth via the screw-in trunnion / mounting hole.
- Connect the shield of the connecting cable on both sides, making sure it conducts with full and continuous contact.
- When introducing the connecting cable into an EMC compliant switch cabinet, for example, connect the shield correctely (cable gland, conducting, full contact, continuous) to the conductive housing or route it via built-in cable connector that is also connected to the conducti­ve housing.
- Connect unused cable cores or free cable ends correctely to the cable shield on both sides..
For order numbers of EMC compliant cable connectors required for connecting the PT, see chapter 9, Accessories.
6.4 Connection assignments Standard models EIT:
Equipment connector: 7-pin male connector,
DIN
Female connector: DIN Fig. 08: 7-pin female connector
The connector housing is connected conductively to the housing of the PT.
Top view solderside
PIN Designation
1 supply voltage (+) 2 supply voltage (-) 3 signal (+) 4 signal (-) 5 calibration 6 calibration 7
21
Operating manual
Models EIT3x2 with option D21:
Equipment connector: 6-pin male connector,
Bendix PT02A-10-6P
Female connector: PT06A-10-6S(SR) Fig. 09: 6-pin female connector
The connector housing is connected conductively to the housing of the PT.
6.5 Wiring
Fig. 10: Wiring proposal for 2-wire mA with
measuring transducer supply unit to EN 50 020
Fig. 11: Wiring proposal for 2-wire mA with Zener
barriers to EN 50 020
PIN Designation
A signal (+) B signal (-) C supply voltage (+) D supply voltage (-) E calibration F calibration
Top view solder side
P
I
EMT
A
B
EF
Ex area
twisted
Cal.
RL1 Ex i
4 - 20 mA
4 - 20 mA
R
L
Signal converter Ex i
Non-Ex area
P
I
EMT
A
B
EF
Ex area
Cal.
RL
Non-Ex area
Zener barriers
+ UB
0
V
twisted
22
7. Commissioning
7.1 Supply voltage 22
7.2 Calibration 22
7.3 Zero adjustment 23
7.4 Operation 23
Before putting the PT into operation, make sure the PT is securely mounted and sealed.
7.1 Supply voltage
Explosion hazard!
Deviation of the supply voltage from the value given in the technical specifications, or false polarity, can damage the pressure transmitter and cause malfunctions that can pose a risk of explosion.
7.2 Calibration
PTs of series EIT 3x2 have an internal calibration signal. Connecting terminals 5 and 6 switches the calibration signal to the signal output. It is 80% of the full scale pressure of the transmitter.
Calibrate in pressureless state and at room temperature. Other ambient temperatures will corrupt the signal. Use an adjustment screwdriver!
Do not change the installed position of the PT after calibration. If the position is changed you must re-calibrate the PT.
The adjustment is made at two potentiometer screws in the cover section of the electronic housing.
- Remove the cap screws from the potentiometers. Potentiometer adjusting screw “N” for zero
adjustment.
Potentiometer adjusting screw “B” for range
adjustment.
Fig. 12: Electronics housing cover
B
N
23
Operating manual
- Connect a meter or suitable instrument to the signal output to verify the settings.
- Adjust zero at potentiometer adjusting screw “N” and verify on the meter.
- Connect terminals 5 and 6. The calibration signal is connected to the output.
- Adjust calibration value (80% of full scale pressure) at potentiometer adjusting screw “B” and verify on the meter.
- Check the zero setting again.
- Repeat the zero adjustment and calibration value as necessary.
7.3 Zero adjustment
Adjust zero at operating temperature!
- Wait until a steady operating temperature is reached at the pressure sensor.
- Adjust zero at potentiometer adjusting screw “N” and verify on the meter.
- Replace the cover screws on the potentiometers.
7.4 Operation
Operating temperature at the PT diaphragm max. 80°C. Higher temperatures will damage the PT.
Ambient temperature for the electronics housing max. +75°C (safety class T5; T1 - T4 max. +80°C). Higher temperatures can result in damage and malfunction. Do not install the pressure transmitter in places where this temperature is exceeded.
24
8. Maintenance
8.1 Maintenance 24
8.2 Repair/disposal 24
8.1 Maintenance
Mounting and electrical connection of the PT must be done by specialists with EMC training, following all applicable regulations, and in pressureless, voltage-free,
intrinsically safe condition with the machine switched off.
The machine must be secured against being switched back on!
ESD sensitive component. Electrostatic discharge may damage the PT. Take ESD precautions.
Do not clean PT with hard objects. This will damage the PT!
Always use a spanner applied to the designated hexagon collar when screwing the PT in and out. Do not apply the tool to the housing!
The PT is almost maintenance free.
- Clean the PT with soft and dry cloth during the machine maintenance.
8.2 Repair/disposal
Please send defective PTs to your DYNISCO representative.
For addresses, see the back cover of the operating manual.
25
Operating manual
9. Accessories
- Pressure sensor simulator
- Pressure sensor calibrating device
Cable connector, cable gland, cable
Designation Order no. Cable connector DIN 7-pin E311 0035 Cable connector Bendix E311 0029 Cable gland PG 7 CE E447 0037 Connection cable VT 460 - 6 Meter 9VT0 0017 Connection cable VT 460 - 10 Meter 9VT0 0018
26
10. Troubleshooting
10.1 Troubleshooting 26
10.1 Troubleshooting
Fault No signal
Strong zero shift when screwing in
No signal change despite pressure rise
Resolution Check cable
and contact, or replace
Check supply voltage
Check hole, rework if necessary
Adjust to max. 22 Nm mounting torque
Send pressure transducer to DYNISCO for repair
Possible cause Cable breakage or
poor contact
No supply voltage
Mounting hole incorrectly produced (alignment error)
Mounting torque too high
Diaphragm damaged
27
Operating manual
11. Declaration of conformity
Dynisco Europe GmbH Wannenäckerstraße 24 D 74078 Heilbronn Tel. (0 71 31) 2 97 - 0 Fax (0 71 31) 2 32 60
Dichiarazione di conformità Verklaring van overeenstemming Konformitetserklæring
Ah/lwsh summo/rfwshs EOK
Konformitätserklärung
Declaration of conformity Déclaration de conformité Declaración de conformidad Declaração de conformidade
Hiermit erklären wir, daß unser Produkt, Typ: We hereby declare that our product, type: Nous déclarons par la présente que notre produit, type: Por la presente declaramos que nuestro producto, tipo: Com a presente, declaramos que o nosso produto, tipo: Con la presente dichiariamo che il nostro prodotto tipo: Hiermee verklaren wij dat ons produkt, type: Hermed erklærer vi, at vores produkt af typen:
Me thn parou/sa dhlw/noume, o/ ti to proio/n mas tu/pou :
folgenden einschlägigen Bestimmungen entspricht: complies with the following relevant provisions: correspond aux dispositions pertinentes suivantes: satisface las disposiciones pertinentes siguientes: está em conformidade com as disposições pertinentes, a saber: è conforme alle seguenti disposizioni pertinenti: voldoet aan de eisen van de in het vervolg genoemde bepalingen: overholder følgende relevante bestemmelser:
antapokri/netai stous ako/louqous sxetikou/s kanonismou/s:
Angewendete harmonisierte Normen,insbesondere: Applied harmonized standards, in particular: Normes harmonisée utilisées, notamment: Normas armonizadas utilzadas particularmente: Normas harmonizadas utilizadas, em particular: Norme armonizzate applicate in particolare: Gebruikte geharmoniseerde normen, in het bijzondere: Anvendte harmoniserede normer, især:
Efarmosqe/nta enarmonisme/na pro/ tupa, eidiko/tera:
Drucktransmitter / Druckaufnehmer Pressure Transmitter / Pressure Transducer Serie MDT, EMT, EIT, MDA, IDA, TDA, LDA, PT, Dyna4
EN 50081-1 / EN 50082-2
EMV-Richtline (89/336/EWG, 93/68/EWG, 93/44 EWG) EMC guidelines (89/336/EEC, 93/68/EEC, 93/44/EEC) Direcitve EMV (89/336/CEE, 93/68/CEE, 93/44/CEE) Reglamento de compatibilidad electromagnética (89/336/MCE, 93/68/MCE, 93/44/MCE) Directriz relativa à compatibilidade electro-magnética (89/336/EWG, 93/68/EWG, 93/44/EWG) Direttiva sulla compatibilità elettromagnetica (89/336/CEE, 93/68/CEE, 93/44/CEE) EMV-richtlijn (89/336/EEG, 93/68/EEG, 93/44/EEG) Direktiv om elektromagnetisk forligelighed (89/336/EØF, 93/68/EØF, 93/44/EØF)
kateuqunth/ria odhgia peri hlektromagnhtikh/s sumbato/thtas
(89/336/EWG, 93/68/EWG, kai 93/44/EWG)
Heilbronn, den 1. Mai 1996
Daniel Nigg, Geschäftsführer
28
12. Ex-Declaration of conformity
29
Operating manual
30
Technische Änderungen vorbehalten 9LIT0225 02/2003 Technical subject to change Sous réserve de modifications techniques Con riserva di modifiche tecniche
Visit us
in the world wide web:
www.dynisco.com
Ser vice
24 H OURS A DAY - 7 D AYS A WEEK
ww w.dy nisco .com
OO - 8OO - DYNISCO - O
OO - 8OO - 3964726 - O
Dynisco Instruments 38 Forge Parkway Franklin, MA 02038 USA
T el: +1 508 541 9400 Fax: +1 508 541 9437 Email: InfoInst@dynisco.com
Dynisco Europe GmbH Wannenäckerstraße 24 74078 Heilbronn Deutschland
T el: +49 7131 2970 Fax:+49 7131 23260 Email: DyniscoEurope@dynisco.com
Dynisco Instruments S.a.r.l. 466, rue du Marché Rollay 94500 Champigny sur Marne France
T el: +33 1 4881 8459 Fax: +33 1 4881 8334 Email. DyniscoFrance@dynisco.com
Dynisco.s.r.l. Via Adriatico, 2/2 20162 Milano Italia
T el: +39 02 661 01733 Fax: +39 02 661 02908 Email: DyniscoItaly@dynisco.com
Dynisco UK Ltd. Silver Birches Business Park Aston Road, Bromsgrove Worcestershire B60 3EU Great Britain
T el: +44 1527 577077 Fax: +44 1527 577070 Email: DyniscoUK@dynisco.com
Dynisco SPOL, S.R.O. cp. 579 756 55 Dolni Becva Czech Republic
T el: +42 0571 647228 Fax: +42 0571 647224 Email: Dyniscocz@nextra.cz
Dynisco B.V . Muziekplein 67 PO Box 666 NL-5400 AR Uden The Netherlands
T el: +31 413 250665 Fax: +31 413 260548 Email: Dynisco-BV@dynisco.com
Loading...