Dynisco 1440 Installation And Operation Manual

Model 1440
Microprocessor-based
Temperature Controller
Installation and Operation Manual
P/N 974073 06/02 Rev. C ECO # 27007
CONTENTS
Quick Start Instructions ....................................................................................................................3
1. Introduction ...............................................................................................................................6
2. Specifications ............................................................................................................................ 6
3. Front Panel Description ............................................................................................................10
4. Alarms ..................................................................................................................................... 12
5. Mounting .................................................................................................................................13
6. Wiring Guidelines ................................................................................................................... 15
7. Instrument Configuration .........................................................................................................21
8. Operating Instructions ............................................................................................................. 35
9. Error Codes ..............................................................................................................................51
10. Repair ......................................................................................................................................53
11. Warranty ................................................................................................................................. 53
1440 Microprocessor-based Temperature Controller 3
MODEL 1440-2-3 QUICK START INSTRUCTIONS
1. MOUNTING
Prepare panel cutout to dimensions shown below.
Remove instrument from case by turning captive safety screw (2) counter clockwise.
Grasp the bezel and slide the instrument out of its case (1).
Slide the supplied rubber gasket over the case.
Slide the instrument case (1) into the panel cutout.
Slide the panel mounting bracket over the instrument case.
Tighten two screws on panel mounting bracket until case is securely mounted in panel cutout.
Slide the instrument back into the case and tighten safety screw.
2. WIRING
Connect an appropriate length of either thermocouple extension wire (e.g.Type J), OR 3 wire RTD leads to the appropriate terminals as shown below.
Connect Outputs for Heat/Cool. Note that Outputs are jumper selectable for Relay/SSR output. Refer to Figure 15, Page 22 for jumper location.
If a current transformer option is to be used for Heater Breakdown Alarm, connect to appropriate terminals.
Connect power to the appropriate terminals as shown below.
3. INSTRUMENT CONFIGURATION
Remove instrument from case by loosening safety screw, grab bezel and slide out of case.
Refer to Figure 15, Page 22, for jumper selection of Relay/SSR selection and AL1 Cool relay NO/ NC selection. Default factory settings are Main/Relay, AL1 Cool/Relay Normally open.
Locate jumper V2 in Figure 14, page 21 and place in the open position.
Slide instrument back in case and apply power. Display will now show CnF.
Press the FUNC button until P1 is displayed.
Refer to Parameter List on page 23. Using the UP arrow, select appropriate P1 code for Input type and standard range.
Press the FUNC button until next parameter is displayed.
Repeat for each parameter to be changed.
When configuration is complete, remove instrument from case, place jumper V2 in the closed position, return instrument into case and secure with safety screw.
Apply power to instrument, Upper display will show process temperature, lower display will show setpoint.
Using UP and DOWN arrows, temperature setpoint can be adjusted.
Refer to Manual page 36 in for Control Parameters if PID tuning is required.
Instrument is now ready for use.
NOTE: The preceding Quick Start instructions are the basic settings required to install, wire, and
get the controller operating. It is assumed that the operator is familiar with PID temperature controllers. Please refer to the complete installation and operation manual for additional functions and instructions.
1440 Microprocessor-based Temperature Controller 5
INDEX
How to: See Section Page
Wire the 1440 6 15
Configuration
Configuration 7 21
Calibration
General Guidelines for Calibration 8.7 43 Calibration Procedure 8.9 45
Operation
Operating Instructions 8 35
Alarms
Main Alarms 4.1 12 Heater Breakdown Alarms 8.5 43
Control Parameters
Control Parameters 8.1 36 Default Control Parameters 8.2 40
Security
Set Safety Lock 3 31
Error Codes
Error Codes 9 51
Instrument Repair
Repair the Instrument 10 53 Get Technical Assistance 10 53
1. INTRODUCTION
The Model 1440 is a highly flexible, field or laboratory reconfigurable controller. This product’s design has been implemented with up-to-date technology and accurate engineering. The following is a summary of the features of the Model 1440:
1/8 DIN size (48 x 96 mm)
IP 54 font protection
SMART function for automatic self-tuning
Measurement of the heater current consumption
Heater breakdown alarm
TC or RTD input with programmable range
Programmable transfer ramp between the set points
Programmable output maximum rate of change
Output power limiter with programmable time duration
Two independent alarms programmable as process, band or deviation alarms
Control outputs: relay or solid state relay (SSR) drive programmable as heating or heating and cooling controls
Output power-off
Direct access to the set point modification
Switching power supply (for 100 to 240 VAC sources)
2. SPECIFICATIONS
2.1 GENERAL
Case: PC/ABS, black; self-extinguishing, level V-0, per UL94
Front panel: IP 54 protection
Installation: Panel mounting by means of tie rods; instrument removable from
case with a screwdriver
Rear terminal block: Screw terminals; terminal identification labels, connection
diagrams and rear safety cover
Dimensions: 48 mm wide x 96 mm high x 89 mm deep
(DIN 43700)
Cutout: 45 x 92 mm
Weight: 600 g maximum
1440 Microprocessor-based Temperature Controller 7
Upper display: 3 green LED digits, 7 segments with decimal point
10 mm high
Lower display: 3 orange LED digits, 7 segments with decimal point
10 mm high
Front indication: red LEDs for alarms and instrument status indication
Power supply: 100 to 240 VAC power source, 50/60 Hz
Power Supply Variations: -15 to +10%
Power consumption: 6 VA maximum
Insulation resistance: >100 MΩ for 500 VDC (IEC 348)
Insulation voltage: 1500 V according to IEC 348
Conversion: Dual slope integration with autozero
Resolution 30,000 counts
Sampling time: 500 msec.
Accuracy (@25°C amb. temp.) +0.2% of the input span or +1°C
Common mode rejection ratio: 120 dB
Normal mode rejection ratio: 60 dB
Noise rejection: According to IEC 801-4 level 3
Temperature drift: <200 ppm/°C (Rj excluded); <400 ppm/°C for RTD input with -
19.9/99.9°C ranges Operating temperature: 0 to +50°C Storage temperature: -30 to +70°C
Humidity: 20 to 85% RH non-condensing
Protections: 1) WATCH DOG circuit for automatic restart
2) Internal switch for protection against tampering of configuration
and calibration parameters
2.2 INPUTS
Thermocouple
Type: L,J,K,N programmable by front pushbuttons
Line resistance: 100Ω max, with error <+0.1% of the input span Temperature units: °C of °F programmable
Reference junction: Automatic compensation of the ambient temperature from 0 to
+50°C
Burn-out: Up or down scale selectable
Calibration: According to IEC 584-1 and DIN 43710-1977 (TC type L)
Standard Ranges Table
TC Type Measuring Ranges
L 0 to +800°C 0 to +999°F
J 0 to +800°C 0 to +999°F
K 0 to +999°C 0 to +999°F
N 0 to +999°C 0 to +999°F
RTD (Resistance Temperature Detector)
Type: Pt 100-3-wire connection
Current 135 mA
Line resistance: Automatic compensation up to 20/wire with <+0.1% error of the
input span for range -19.9 at 99.9°C; no measurable error for the
other ranges
Engineering units: °C or °F programmable
Burn-out: Up scale
Calibration: According to DIN 43760
1440 Microprocessor-based Temperature Controller 9
Standard Ranges Table
RTD Type Measuring Ranges
RTD Pt 100 -199 to +500°C -199 to +999°F RTD Pt 100 -19.9 to +99.9°C -21.6 to +217°F
Current Transformer Input (optional)
The 1440 controller is capable of measuring heater band current with the addition of a small remote
transformer.
Ranges: 25A and 100A
Indication: Use P/N 820754 for 25A range; use P/N 820755 for 100 A range
2.3 CONTROL ACTIONS
Control action: PID or SMART
Proportional band: 0.1 to 99.9% of the input span
When setting Pb = 0: Hysteresis (for ON/OFF control action): 0.1 to 10.0% of the input span
Integration time: 10 seconds to 20 minutes; resolution 10 seconds; setting a value
greater than 20 minutes will disable the integration action
Differential time: <10 minutes
Heating cycle time: 1 to 200 seconds
Cooling cycle time: 1 to 200 seconds
Relative cooling gain: 0.20 to 1.00 seconds
NOTE: The Pb, ti, tc and parameters may be limited when the SMART function is enabled.
Overlapping/dead band: -20 to 50%
Rate of rise for set point variations: 1 to 100 units/minute
10
2.4 OUTPUTS
Output 1 - Heating
Relay output with SPDT contact; contact rating 3 A/250 VAC with resistive load. Logic voltages for SSR drive
Logic status 1: 24 V +20% @1 mA; 14 V + 20% @20 mA Logic status 0: <0.5 V Option output: Direct/reverse programmable
The selection between relay or SSR is made by internal jumper.
Output 2 - Cooling or Alarm 1
Relay output with SPST contact; contact rating 1.5 A/250 VAC with resistive load. Select the NC or NO contacts by internal jumper.
Logic voltages for SSR drive:
Logic status 1: 24 V ±20% @1 mA; 14 V ±20% mA
Logic status 0: <0.5V
The selection between relay or SSR is made by internal jumper.
3. FRONT PANEL DESCRIPTION
Figure 1 illustrates the front panel of the Model 1440.
Fig. 1 1440 Temperature Controller Front Panel
1440 Microprocessor-based Temperature Controller 11
3.1 INDICATOR DESCRIPTION
MAIN
Indicator Indicator lit Main output is
AL1/COOL
Indicator Indicator lit Cooling output is On or Alarm 1
AL2/HB
Indicator Indicator lit Alarm 2 is in alarm condition Indicator flashing Heater breakdown is in alarm condition
SMRT
Indicator Indicator flashing First step of the SMART function is running Indicator lit Second step of the SMART function is running
OFF
OFF
OFF
OFF
Main output is
OFF On
Cooling output is
Alarm 2 and heater breakdown
SMART function is disabled
OFF
or Alarm 1
is not
in alarm condition
is in
alarm condition
are not
in alarm condition
3.2 DISPLAY DESCRIPTION
Upper Display
The upper display continuously shows the process variable in amperes. During the programming procedure, this display shows the numerical value of the selected parameters or functions.
Lower Display
The lower display continuously shows the current set point value. Pressing the pushbutton for less than 1.5 seconds causes the heater consumption in amperes to be shown. Pressing the
pushbutton again causes the set point value to be re-shown. During configuration, calibration, and parameter setup, the lower display will show the code of the selected parameter.
12
3.3 KEYBOARD DESCRIPTION
Selects the parameters. Pressing the FUNC pushbutton causes the parameters to be shown sequentially on the upper and lower displays. Simultaneously, the value of the previous parameter will be stored.
In operating mode, the SMRT pushbutton enables or disables the SMART function. In configuration and calibration mode it is used to scroll the configuration and calibration parameters backwards without storing the modified value.
Decreases the parameter value. When the instrument is in operating mode, it allows direct access to the set point modification.
Increases the parameter value. When the instrument is in operating mode, it allows the display of the heater consumption or direct access to the set point modification.
Loads the default control parameters.
Turns the control output
OFF
or On.
4. ALARMS
4.1 MAIN ALARMS
Two independent alarms are available, each of which can be configured in one of three modes, as follows:
Process alarm
Band alarm
Deviation high or deviation low
Action: Direct or Reverse Action Threshold resolution: 1 digit Alarm hysteresis: Programmable between 0.1% and 10.0% of the input span Alarm indication: Two LEDs (Al1, Al2) lit for alarm ON
Alarm 1: See Outputs, page 18 Alarm 2: Relay output with SPST contact; contract rating 2 A/250 VAC with resistive load
1440 Microprocessor-based Temperature Controller 13
4.2 HEATER BREAKDOWN ALARM
This function uses a measurement (in amperes) of the main load consumption along with a user-set alarm threshold to indicate either a partial or complete heater malfunction. This alarm output is linked to Alarm 2 with a logical OR.
NOTE: This is supplied with the current transformer input option.
Threshold resolution: 1 digit Alarm hysteresis: 1 digit Alarm indication: LED Al2/HB flashes when alarm is On Alarm output: See Alarm 2
5. MOUNTING
Select a mounting location where there is minimum vibration and the ambient temperature range is
between 0 and 50°C. The instrument can be mounted in a panel up to 15 mm thick with a
rectangular cutout of 45 x 92 mm. To mount the Model 1440, insert the instrument through the panel cutout. While holding the instrument against the panel, slide bracket over case and tighten the screws until the instrument is held tightly against the panel (see figure 2).
Fig. 2 Mounting the Model 1440
14
5.1 OUTLINE DIMENSIONS
Figure 3 shows the outline dimensions of the Model 1440.
Fig. 3 Outline Dimensions
1440 Microprocessor-based Temperature Controller 15
5.2 CUTOUT DIMENSIONS
Figure 4 shows the panel cutout dimensions of the Model 1440.
Fig. 4 Cutout Dimensions
5.3 VERTICAL PACKING
The minimum distance between cutouts is 20 mm.
Horizontal Packing for More Instruments in a Single Cutout
The total dimension of the cutout is the addition of the front dimensions minus 3 mm. The horizontal dimension of the cutout equals (n x 48) - 3 mm, where n is the number if instruments to be packed (maximum 10 instruments).
6. WIRING GUIDELINES
Connections should be made with the instrument housing installed in its proper location. Figure 5 illustrates the rear terminal block of the Model 1440.
16
Fig. 5 Rear Terminal Block
6.1 POWER LINE AND EARTH WIRING
Figure 6 illustrates the power line wiring for the Model 1440.
Fig. 6 Power Line Wiring
6.2 INPUTS
Figure 7 illustrates the thermocouple input wiring for the Model 1440.
1440 Microprocessor-based Temperature Controller 17
Fig. 7 Thermocouple Input Wiring
NOTE: DO NOT run input wires together with power cables. For TC wiring, use proper
compensating cable, preferable shielded. If shielded cable is used, it should be grounded at one point only.
Figure 8 illustrates the RTD input wiring for the Model 1440.
Fig. 8 RTD Input Wiring
NOTE: DO NOT run RTD wires together with power cables. If shielded cable is used, it should be
grounded at one point only. Use copper wires of appropriate size (see Product Specifications). The resistance of the three wires must be the same
Any external components (e.g., zener barriers) connected between sensor and input terminals may cause errors in measurement due to excessive and/or unbalanced line resistance or possible leakage currents.
Loading...
+ 39 hidden pages