Dynasonics TFXP Operating Manual

Series TFXP
Series TFXP
Series TFXPSeries TFXP
Transit Time Ultras oni c Fl ow Me t er
Operations & Maintenance
REV 4/01
BEFORE OPERATING THE TFXP
Important Notice!
Figure 1.1
The TFXP flow meter is equipped with a Lead Acid Gel Cell battery. This battery will require cha rging before ini­tial operation.
Apply power, utilizing the enclosed 12 Volt DC output line power converter or cigarette-style power cord, to the TFXP for a period of 16-24 hours prior to using the prod­uct for the first time. The power converter connects to the socket connection located on the side of the enclosure. See Figure 1.1. A fully charged battery will provide up to 24 hours of contin uous op eration befo re rechargin g will b e necessary.
When the b atte ry le vel ha s de crea sed to a po int where re ­charging is required, th e LOW BATTERY ind icator will illu­minate on the front panel. A t that po int, the me ter will onl y operate a short time more until it automatically turns itself off—preventing excessive battery discharge that can dam­age the Gel Cell battery. The TFXP has an integral charg­ing circuit that prevents overcharging. The instrument can be permanently connected to AC line power without dam­aging the flow meter or the battery. Page 1.10 of this manual contains additional recommendations to preserve and maximize the power in the TFXP battery.
If the TFXP is to be used for extended periods of opera­tion, the AC power converter or the 12 volt cigarette con­verter can remain connected indefinitely.
Rev. 4/01 -1.1- TFXP
TABLE OF CONTENTS
Part 1 - Introduction
Part 1 - Connections
Part 1 - Inputs and Outputs
Quick-Start Operating Instructions 1.4-1.5
Introduction General 1.6 Applications 1.6 Model Matrix 1.7
Product Specifications 1.8
Transmitter Connections Transmitter Limits and Connections 1.9-1.10 Battery Charging and Maintenance 1.10-1.12
Input/Output Connections and Options 4-20 mA Output 1.13 Datalogger 1.14
Pages
optional Dual Control Relay 1.14 optional Rate Pulse Output 1.15 optional RS232C 1.15 optional RS485 1.15 optional RTD-BTU 1.15
Part 2 - Transducer Installation
Rev. 4/01 -1.2- TFXP
Transducer Mounting Mounting Location 2.1-2.2 Transducer Mounting Method 2.3-2.5 Transducer Spacing - Keypad Entry 2.6-2.13 Transducer Spacing - UltraLink 2.13-2.14 Pipe Preparation 2.15 Transducer Mounting 2.15-2.21
TABLE OF CONTENTS
Part 3 - Operation
Part 4 - Software
Programming Entries Instrument Startup 3.1 Keypad Operation 3.2-3.3 Graphics Display Configuration 3.3 Menu Structure 3.3-3.4 Keypad Entry Detail 3.4-3.25
BASIC MENU 3.4-3.13 DATALOG OPERATION 3.14-3.16 OUT2 MENU 4-20 mA 3.17-3.19 Optional Input/Output 3.20-3.24 SECURITY MENU 3.25 SERVICE MENU 3.26-3.27
Signal Strength 3.26 Setting ZERO Flow 3.27
DISPLAY MENU 3.28-3.29
Software Utility Operation UltraLink 4.1-4.9 DataLink 4.10-4.12
Appendix Keypad Interface Map Fluid Characteristic Table TFX Error Codes Modbus Protocol Pipe Dimension Chart: Cast Iron Pipe Dimension Chart: ST, SS, PVC Velocity to Volumetric Conversion RTD-BTU Option Statement of Warranty Customer Service
Pages
Rev. 4/01 -1.3- TFXP
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the TFXP instrument. The following condensed instructions are provided to assist the operator in getting the instrument configured and measuring as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is un­familiar with this type of instrument, refer to the app ropri­ate section in the manual for complete details.
Transducer Location
1. TRANSDUCER LOCATION
A. In general, select a mounting location on the piping
system with a minimum of 10 pipe diameters (10 times the pipe inside diameter) of straight pipe up­stream and 5 straight diameters downsteam. See Table 2.1 for detailed piping configurations and rec­ommended lengths of straight pipe.
B. Select a mounting method for the transducers
based on pipe size and liquid characteristics. See Figure 1.2. Select W-Mount for plastic pipes flow­ing clean, non-aerated liquids in the 1-3 inch [25-75 mm] internal diameter range. Select V-Mount for pipes of all materials and most liquids in pipe sizes from 1-10 inches [25-250 mm]. Select Z-Mount for pipes larger than 10 inches.
W-Mount V-Mount
Figure 1.2
C. Enter the following data into the TFXP transmitter
via the integral keypad or UltraLink software utility.
Rev. 4/01 -1.4- TFXP
Z-Mount
QUICK-START OPERATING INSTRUCTIONS
*Nominal values for these parameters are included within the TFXP operating system. The nominal values may be used as they appear or may be modified if exact system values are known.
Figure 1.3
1. Transducer mounting method
2. Pipe O.D. (Outside Diameter)
3. Pipe wall thicknes s
4. Pipe material
5. Pipe sound speed*
6. Pipe relative roughness*
7. Pipe liner thickness
8. Pipe liner material
(if present)
(if present)
9. Fluid type
10. Fluid sound speed*
11. Fluid viscosity*
12. Fluid specific gravity*
D. Record the value calculated and displayed as
Transducer Spacing/XDCR SPC.
2. PIPE PREPARATION AND TRANSDUCER MOUNT­ING
A. The piping surface, where the transducers are to be
mounted, needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Attach the transducer mounting rail or saddles to
the pipe at the location(s) determined in Step 1. Refer to Figure 1.1 for proper orientation.
C. Apply a liberal amount of couplant grease onto the
transducer faces. Place each transducer into the rail/saddle ensuring proper linear and radial place­ment.
Connections
3. TRANSDUCER/POWER CONNECTIONS
A. Do not attempt to add additional cable to the trans-
ducers.
B. Refer to the WIRING DIAGRAM located on the in-
ner door of the TFXP transmitter and Figure 1.3 for proper power and transducer connections.
Startup
4. INITIAL SETTINGS AND POWER UP
A. Press the ON button on the flow meter keypad. B. From the Service Menu, verify that signal strength
is greater than 2.0%. C. Input proper units of measure and I/O data.
Rev. 4/01 -1.5- TFXP
PART 1 - INTRODUCTION
General
Application Versatility
The TFXP ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit (pipe). The transducers are a non-contacting, clamp-on type, which will provide benefits of non-fouling operation and ease of installation.
TFXP transit time flow me­ters utilize two transducers that function as both ultra­sonic transmitters and re­ceivers. The transducers are clamped on the out­side of a closed pipe at a specific distance from each other. The transducers can be mounted in V-mode where the sound transverses the pipe two times, W-mode where the sound transverses the pipe four times, or in Z­mode where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. This selection is based on pipe and liquid characteristics. The flowmeter operates by alternately transmitting and re­ceiving a frequency modulated burst of sound energy be­tween the two transducers and measuring the time interval that it takes for sound to travel between the two transduc­ers. The difference in the time interval measured is di­rectly related to the velocity of the liquid in the pipe.
The TFXP flow meter can be successfully applied on a wide range of metering applications. The simple to pro­gram transmitter allows the standard product to be used on pipe sizes ranging from 1 - 100 inch [ 25 - 2540 mm ] internal diameters. A variety of liquid applications can be accommodated: ultrapure liquids, potable water, chemi­cals, raw sewage, reclaimed water, cooling water, river water, plant effluent, etc. Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Stan­dard transducers are rated to 300°F [150°C]. Higher tem­peratures can be accommodated. Please consult the Dy­nasonics factory for assistance.
Rev. 4/01 -1.6- TFXP
PART 1 - INTRODUCTION
User Safety
Data Integrity
Product Identification
Product Matrix
The TFXP employs modular construction and provides electrical safety for the operator. The display face con­tains voltages no greater than 10 Vdc. All user connec­tions are made through sealed bulk-head plugs located on the side of the TFXP enclosure.
Non-volatile flash memory retains all user-entered con­figuration values in memory for several years, even if power is lost or the unit is turned off. Data Logger values are stored in flash memory in the logger. Password pro­tection is provided as part of the Security menu and pre­vents inadvertent configuration changes or totalizer re­sets.
The serial number and complete model number of your TFXP is located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasonics Customer Service Department with this information.
TFXP - UUU
Power Supply
A) 115 VAC B) 230 VAC
(two round terminals) G) 230 VAC (three rectangular terminals)
Output 2*
1) 4-20mA Output 1*
6) 200,000 event datalogger
Approvals
N) Class 1, Div 2 (pending)
Options
N) None
UUUA ---- UU
UUUUUU
UU
UUUU
Replacement Parts Part Number TFXP Flow meter D040-0110-001
Data Logger, 200,000-event D020-1045-104 Padded carrying case D003-1012-002 Transducers, set of two D071-0105-000 Transducer Cable, 20 ft. [6m] D005-2112-020 Acoustic Grease, temporary mount D002-2011-001 Mounting Track, w/measuring scale D010-2102-010 Mounting Clamp, single D003-0139-002 36 inch SS hose clamp D002-2007-001 Power converter, 115V U.S. D005-2502-001 Power converter, 230V European D005-2502-002 Power converter, 230V U.K. D005-2503-003 Power cord, 12V cigarette-style D005-2116-002 4-20mA interconnect cable D005-2116-001 Infrared communicator and UltraLink D005-2115-100 Infrared communicator D005-2115-001 Manual, TFXP flow meter DTFXP O&M
Rev. 4/01 -1.7- TFXP
Transmitter
PART 1 - SPECIFICATIONS
Transducer
Rev. 4/01 -1.8- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Transmitter Location Considerations
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, no­tify the carrier immediately.
When the TFXP is to be utilized for extend ed periods of time in one location, the enclosure should be placed in an area that is convenient for servicing, calibration or for observation of the LCD readout.
1. Locate the transmitter within the length of transducer cable that was supplied with the TFXP system. If this is not possible, do not attempt to add additional cable to the transducer. Contact the Dynasonics factory to coordinate an exchange for the proper cable length. Transducer cables that are up to 990 feet [300 me­ters] are available.
2. Place the TFXP transmitter in a location that is:
Where little vibration exists. Protected from falling corrosive fluids. Within ambient temperature limits -40 to 185°F [-40 to
85°C]
Out of direct sunlight. Direct sunlight may increase
temperatures within the transmitter to above maxi­mum limit.
3. If the transmitter will be subjected to a wet environ­ment, it is recommended that the cover remain closed and the latches secured after configuration is com­pleted. The faceplate/keypad of the TFXP is water­tight, but avoid letting water collect on the keypad area.
Rev. 4/01 -1.9- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Electrical Connections
Figure 1.4
Battery Charging and External Power Sources
It is highly recommended that the internal battery in the TFXP be fully charged before using the meter for the first time. Details covering this procedure are located on Page 1.1 of this manual.
1. The connectors located on the side of the TFXP con­sist of three 1/4 turn BNC-type and one 5.5mm power plug. These connectors are environmentally sealed, but it is recommended not to allow water or other liq­uids to collect in the electrical connections pocket.
2. Connect the appropriate wires to the corresponding connections on the transmitter. The transducer cable has markings of UPSTREAM and DOWNSTREAM to assist in the installation process. The UPSTREAM transducer is the one located closer to the direction from which fluid flow normally comes from (The fluid normally passes the UPSTREAM transducer before passing the DOWNSTREAM transducer.) If the trans­ducer wires are connected backwards, a negative flow indication will be observed on the flow meter display. See Figure 1.4 or the Wiring Diagram located on the inner door of the transmitter.
NOTE: The transducer cables carry low level signals. Do not attempt to add additional cable to the factory supplied transducer cable. If additional cable is required, contact the Dynasonics factory to arrange for an exchange trans­ducer with the appropriate length of cable. Cables to 990 feet [ 300 meters ] are available.
The 12 Volt DC power converter and 12 Volt cigarette­style power cord connect to the socket connection located on the side of the enclosure. See Figure 1.4. A fully charged battery will provide up to 24 hours of continuous operation before recharging will be necessary. When the battery level has decreased to a point where recharging is required, the LOW BATTERY indicator will illuminate on the front panel. At that point, the meter will only operate a short time more until it automatically turns itself off— preventing excessive battery discharge that can damage
Rev. 4/01 -1.10- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
the Gel Cell battery. If the TFXP is to be used for extended periods of opera-
tion, the 12 Vdc line power converter or the 12 V cigarette converter can remain connected indefinitely.
To charge the internal Gel Cell bat tery, apply power, utiliz­ing the enclosed 12 Vdc line power converter or cigarette­style power cord, to the TFXP for a period of 16-24 hours. The TFXP has an integral charging circuit that prevents overcharging. The instrument can be permanently con­nected to AC line power without damaging the flow meter or the battery.
The Gel Cell battery is “maintenance free”, but it still re­quires a certain amount of attention to prolong its useful life. To obtain the greatest capacity and longevity from the battery, the following practices are recommended:
Do not allow the battery to completely discharge. (Discharging the battery to the point where the LOW BATTERY indicator illuminates will not damage the battery. Allowing the battery to remain discharged for long periods of time can degrade the storage capacity of the battery.) When not in use, continually charge the battery by keeping the 12 Vdc line power converter plugged in and connected to the flow meter. The TFXP battery management circuitry will not allow the battery to be come “over-charged”.
NOTE: The TFXP will automatically enter a low power consumption mode approximately 1-1/2 minutes after the LOW BATTERY indicator illuminates. This circuit pre­vents excessive discharge of the internal battery.
If the TFXP is stored for prolonged periods of time, monthly charging is recommended.
If the TFXP is stored for prolonged periods of time, store at a temperature below 70ºF [21ºC].
Use wiring practices that conform to local codes (National Electric Code Handbook in the USA). Use only the power converters that have been supplied with the TFXP flow meter. The ground terminal, if present on the converter, is mandatory for safe operation.
Rev. 4/01 -1.11- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy com­ponents (i.e. Fluorescent lights, relays, compressors, vari­able frequency drives, etc.).
The TFXP can be operated from a 11-15 Vdc source, us­ing the included cigarette-style power cord, as long as it is capable of supplying at least 3 Watts—observe proper po­larity.
Rev. 4/01 -1.12- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
General Information Regarding Input/ Output: ISO-MODs
Standard
4-20 mA Output
The TFXP flow meter contains two Isolated Input/output Modules (ISO-MODs); one located inside of the flow meter
enclosure and one that is user accessible, located under the access door on the keyboard. The standard configu­ration of these modules is to have the internal module configured as an actively powered 4-20 mA module and the user accessible one as a Data Logger.
ISO-MODs are epoxy encapsulated electronic input/output modules that are simple to install and replace in the field. All modules are 2,500 volt optically isolated from TFXP power and Earth grounds -- eliminating the potential for ground loops and reducing the chance of severe damage in the event of an electrical surge.
Seven ISO-MOD options are available including: 4-20 mA, dual-relay, rate pulse, RS232C, RS485, 200k event data­logger and RTD heat-delivered option. TFXP supports any two ISO-MOD input/output modules. All modules are field configurable by utilizing the keyboard or ULTRALINK interface. Field wiring connections to ISO-MODs are quick and easy using pluggable terminals. Features of the various ISO-MODs are described below. See the Series TFXH addendum for details re garding the RTD Heatflow Module option.
The 4-20 mA Output Module interfaces with virtually all re­cording and logging systems by transmitting an analog current signal that is proportional to system flow rate. In­dependent 4 mA and 20 mA span settings are established in software using the FL 4MA and FL 20MA settings in the OUTPUT2 conf iguration menu. The se entries can be set anywhere in the –40 to +40 fps [-12 to +12 mps] measur­ing range of the instrument. Output resolution of the mod­ule is 12-bits (4,096 discrete points). The module can drive more than 800 ohms of load with its internally gener­ated 24 volt power source.
A 4-20 mA output interface cable has been included with the TFXP package. Connect the 1/4-turn BNC connection to the jack located on the side of the flow meter. See Fig-
Figure 1.5
Rev. 4/01 -1.13- TFXP
ure 1.5. The red clip on the cable provides the positive
PART 1 - TFXP TRANSMITTER CONNECTIONS
leg of the output and the black clip provides the negative side. Verify that the sum of the resistances in the loop do not exceed 800 Ohms.
Refer to Section 3 of this manual for detailed information regarding the configuration, calibration and testing of the 4-20 mA output.
Standard
Data Logger
Figure 1.6
A 200,000-event data logger/electronic stripchart recorder is located within the weather-tight pocket on the face plate of the flow meter. See Figure 1.6. Loosen the three thumbscrews located in the corners of the pocket cover and rotate the cover to expose the Data Logger module. The logger stores time-stamped, high resolution (16-bit) data at user selected intervals ranging from 1 to 30,000 (8.33 hours) seconds. Configuration of and data retrieval from the logger can be accomplished in one of two ways:
The module is hot-swappable -- that is, it can be in-
stalled, removed from or replaced within the flow meter without disconnecting power. The module can be car­ried in a shirt pocket back to the office and plugged into a PC serial port via the module's integral DB9 con­nector.
Via the DataLink software utility and the serial DB9 in-
terface cable included with the logger. Data can be ac­cessed by connecting the cable to the logger, which is located in the pocket on the front faceplate of the in­strument. See Figure 1.6.
Refer to Section 3 of this manual for detailed information regarding the configuration and operation of the Data Log­ger Module.
Optional
Control Relay
Rev. 4/01 -1.14- TFXP
Two independent SPDT (single-pole, double-throw, Form C) relays are contained in this module. The relay opera­tions are user configured via software to act in either a
PART 1 - ISO-MOD
flow rate alarm, signal strength alarm or totalizer/batching mode. The relays are rated for 200 Vac max. and have a current rating of 0.5 A resistive load [175 Vdc @ 0.25 A re­sistive]. It is highly recommended that a slave relay be utilized whenever the Control Relay ISO-MOD is used to control inductive loads such as solenoids and motors.
Optional
0-10 kHz Output
Optional
RS232C I/O
The Rate Pulse Output Module is utilized to transmit infor­mation to external counters and PID systems via a fre­quency output that is proportional to system flow rate. This module does not source voltage at its output, it must be connected in an “open-collector” fashion with an exter­nal power source and pull-up resistor. Independent Zero and Span settings are established in software using the Flow Measuring Range entries. These entries can be set anywhere in the –40 to +40 fps [-12 to +12 mps] measur­ing range of the instrument. Output resolution of the mod­ule is 12-bits (4,096 discrete points) and the maximum output frequency setting is 10,000 Hz. The MOSFET can support loads of 100V @ 9A.
The RS232 Module can be interfaced with the serial com­munication ports of PCs, PLCs and SCADA systems that are used to monitor flow rate information in piping sys­tems. The RS232 Module may also be used to form a hardwire connection to a PC that is running the UltraLink software utility. Baud rates up to 19.2k are supported.
Optional
RS485 I/O
Optional
RTD-BTU
Rev. 4/01 -1.15- TFXP
The RS485 Module allows up to 126 TFXP systems to be placed on a single three-wire cable bus. All meters are assigned a unique one byte serial number that allows all of the meters on the cable network to be independently accessed. Baud rates up to 19.2k and cable lengths to 1,000 feet [300 meters] are supported .
See the Appendix of this manual for information regarding connection and operation of the optional RTD-BTU option.
PART 2 - TRANSDUCER POSITIONING
General
The transducers that are u tilized by the Series TFXP contain piezoelectric crystals for transmitting and receiving ultrasound signals through walls of liquid piping systems. The transducers are relatively simple and straight-forward to install, but spacing and alignment of the transducers is critical to the system's accuracy and performance. Extra care should be taken to ensure that these instructions are carefully executed.
Mounting of the clamp-on ultrasonic transit time transducers is comprised of three steps. In general, these steps consist of:
1. Selection of the optimum location on a piping system.
2. Entering the pipe and liquid parameters into either the optional software utility (UltraLink) or keying in the parameters into the TFXP keypad. The software embedded in UltraLink and TFXP will calculate proper transducer spacing based on these entries.
3. Pipe preparation and transducer mounting.
1. Mounting Location
1. Mounting Location
1. Mounting Location1. Mounting Location
The first step in the installation process is the selection of an optimum location for the flow measurement to be made. For this to be done effectively, a basic knowledge of the piping system and its plumbing are required.
An optimum location would be defined as a piping system that is completely full of liquid when measurements are being taken and has lengths of straight pipe such as those described in Table 2.1. The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation.
Rev. 4/01 - 2.1 - TFXP
PART 2 - TRANSDUCER POSITIONING
Table 2.1
1
The TFXP system will provide repeatable measurements on piping systems that do not meet these
requirements, but the accuracy
of these readings may be influenced to various degrees.
1
Rev. 4/01 - 2.2 - TFXP
PART 2 - TRANSDUCER POSITIONING
2. Transducer Spacing
2. Transducer Spacing
2. Transducer Spacing2. Transducer Spacing
TFXP transit time flowmeters utilize two transducers that function as both ultrasonic transmitters and receivers. The transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V­mode where the sound transverses the pipe two times, W-mode where the sound transverses the pipe four times, or in Z-mode where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. See Figures 2.1-2.3. This selection is based on pipe and liquid characteristics. The flowmeter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers.
IMPORTANT: Since the time interval being measured is influenced by the transducer spacing, it is critical that the transducer spacing be measured on the pipe accurately to assure optimum performance from the TFXP system.
The TFXP system calculates proper transducer spacing by utilizing piping and liquid information entered by the user. This information can be entered via the keypad or the UltraLink Windows software utility and a laptop computer.
The following information will be required before programming the instrument:
1. Transducer mounting configuration. Use the following guide to determine the optimum mounting method for a particular installati o n:
Rev. 4/01 - 2.3 - TFXP
PART 2 - TRANSDUCER POSITIONING
V-Mount Configuration
W-Mount Configuration
Figure 2.1 V-Mount. Reflective type (transducers
mounted on one side of the pipe) of installation used primarily on pipe sizes in the 3-10 inch [75-250 mm] internal diameter range.
Figure 2.1 - Transducer V-Mount
Figure 2.2 W-Mount. Reflective type (transducers
mounted on one side of the pipe) of installation used primarily on plastic pipe sizes in the 1-3 inch [25-75 mm] internal diameter range. Metal pipes will typically require the V-Mount for proper operation.
Figure 2.2 - Transducer W-Mount
Rev. 4/01 - 2.4 - TFXP
PART 2 - TRANSDUCER POSITIONING
Z-Mount Configuration
Figure 2.3 Z-Mount. Direct type (transducers
mounted on opposite sides of the pipe) of installation used primarily on pipe sizes in the 10-100 inch [250­2540 mm] internal diameter range.
Figure 2.3 - Transducer Z-Mount
In addition, the following information is required before mounting the transducers on the pipe.
2. Pipe O.D. (Outside Diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed1
1
6. Pipe relative roughness
7. Pipe liner thickness (if present)
8. Pipe liner material (if present)
9. Fluid type
10. Fluid sound speed
1
11. Fluid viscosity1
1
12. Fluid specific gravity
1
Nominal values for these parameters are included within the TFXP operating system. The nominal values may be used as they appear or may be modified if exact system values are known.
Rev. 4/01 - 2.5 - TFXP
PART 2 - TRANSDUCER POSITIONING
Keypad Entry
The TFXP contains a tactile feedback keypad interface that allows the user to configure parameters used by the TFXP operating system.
Graphics Display Soft Keys Arrow Keys Numeric Keys Infrared Communications Port
The TFXP system can be configured using UltraLink and a laptop computer. Please refer to page 2.13 for details regarding data entry in UltraLink.
The following “Soft Key” menu items will be displayed immediately above the two keys located in the lower corners of the Graphics Display.
1. The (soft)MENU key is pressed from RUN mode to
enter PROGRAM mode. The (soft)EXIT key is pressed in PROGRAM mode to exit configuration parameters and menus. If changes to any configuration parameters have been made, the user will be prompted with a SAVE? (soft)YES or (soft)NO when returning to RUN mode. If no changes have been made, the user will not be prompted for to SAVE.
2. The UP/DOWN ARROW keys are used to scroll
through menus and configuration parameters. The ARROW keys can also be used to adjust parameter numerical values. In RUN mode the UP/DOWN ARROW keys are used to adjust the display contrast level.
3. The Numerical Keypad is used for entering
numerical values.
Rev. 4/01 - 2.6 - TFXP
PART 2 - TRANSDUCER POSITIONING
4. The (soft)EDIT key is used to
access the configuration parameters in the various
menus.
initiate changes in configuration parameters.
5. The (soft)ACCEPT key is used to
accept configuration parameter changes.
Graphics Display Configuration
6. The (soft)SELECT key is used to
Configure the engineering units on the graphics
display—Press the (soft)SELECT key from RUN mode to highlight the engineering unit presently being displayed on the graphics display (pressing the SELECT key multiple times will toggle the highlighted unit from line to line). Use the UP/ DOWN ARROW keys to select display units of
RATE
TOTALizer
VELocity
SIGNAL STRength
From Menu 7, Display Menu, the number of
graphics display lines can be toggled between two and four lines.
Menu 1, the BASIC menu contains all of the configuration parameters necessary to make the transducer spacing calculation.
UNITS Entry
UNITS ENGLSH
METRIC
Installs a global measurement standard into the operation of the instrument. The choices are either English or Metric measurements.
Select ENGLSH if all configurations (pipe sizes,
etc.) are to be made in inches. Select METRIC if the meter is to be configured in millimete rs.
The ENGLSH/METRIC selection will also co nfigure
Rev. 4/01 - 2.7 - TFXP
PART 2 - TRANSDUCER POSITIONING
the TFXP to display sound speeds in pipe materials and liquids as either feet per second or meters per second respectively.
Transducer Mount Configuration
XDCR MNT -- Transducer Mounting Method V
W Z
Selects the mounting orientation for the transducers. The selection of an appropriate mounting orientation is based on pipe and liquid characteristics. Refer to
Figures 2.1-2.3 in this manual.
V -- Mount. A reflective type (transducers mounted on
one side of the pipe) of installation used primarily on pipe sizes in the 3-10 inch [75-250 mm] internal diameter range.
W -- Mount. A reflective type (transducers mounted on one side of the pipe) of installation used primarily on pipe sizes in the 1-3 inch [25-75 mm] internal diameter range.
Z -- Mount. A direct type (transducers mounted on opposite sides of the pipe) of installation used primarily on pipe sizes in the 10-100 inch [250-2540 mm] internal diameter range.
Pipe O.D. Entry
Pipe Wall Entry
Rev. 4/01 - 2.8 - TFXP
PIPE OD -- Pipe Outside Diameter Entry ENGLSH (Inches)
METRIC (Millimeters)
Enter the pipe outside diameter was selected as UNITS; in millimeters if METRIC was selected.
PIPE WT -- Pipe Wall Thickness Entry ENGLSH (Inches)
METRIC (Millimeters)
in inches if ENGLSH
PART 2 - TRANSDUCER POSITIONING
Pipe Material Entry
Pipe Sound Speed Entry
Enter the pipe wall thickness in inches if ENGLSH was selected as UNITS; in millimeters if METRIC was selected.
PIPE MAT -- Pipe Material Selection CARBON S - Carbon Steel
STAINLES - Stainless Steel CAST IRO - Cast Iron DUCTILE - Ductile Iron COPPER - Copper PVC - Polyvinylchloride PVDF LOW ­ PVDF HI - High Density Polyvinylidene Flouride ALUMINUM - Aluminum ASBESTOS - Asbestos Cement FIBERGLA - Fiberglass OTHER
This list is provided as an example. Additional materials are being added continuously. Select the appropriate pipe material from the list or select OTHER if the material is not listed.
PIPE SS -- Speed of Sound in the Pipe Material ENGLSH (Feet per Second)
METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the pipe wall. If the UNITS value was set to ENGLSH, the entry is in FPS (feet per second). METRIC entries are made in MPS (meters per second).
Low Density Polyvinylidene Flouride
If a pipe material was chosen from the PIPE MAT list, a nominal value for speed of sound in that material will be automatically loaded. If the actual sound speed rate is known for the application piping system and that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as PIPE MAT, a PIPE SS will need to be entered.
Rev. 4/01 - 2.9 - TFXP
PART 2 - TRANSDUCER POSITIONING
Pipe Roughness Entry
Liner Material Entry
Liner Thickness Entry
PIPE R -- Pipe Material Relative Roughness UNITLESS VALUE
The DTFXP provides Reynolds Number compensation in its flow measurement calculation. The ratio of average surface imperfection as it relates to the pipe internal diameter is used in this comp ensation.
Linear RMS measurement of the pipe PIPE R = internal wall surface Internal Diameter of the pipe
If a pipe material was chosen from the PIPE MAT list, a nominal value relative roughness in that material will be automatically loaded. If the actual roughness is known for the application piping system and that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as PIPE MAT, a PIPE R may to be entered.
LINER T -- Pipe Liner Thickness Entry ENGLSH (Inches)
METRIC (Millimeters)
Enter the pipe liner thickness inches if ENGLSH was selected as UNITS; in millimeters if METRIC was selected.
[If a LINER Thickness was selected] LINER MAT - Liner Material
TAR EPOXY RUBBER MORTAR POLYPROPYLENE POLYSTYROL POLYSTYRENE POLYESTER
. Enter this value in
Rev. 4/01 - 2.10 - TFXP
PART 2 - TRANSDUCER POSITIONING
Liner Sound Speed Entry
Fluid Type Entry
POLYETHYLENE EBONITE TEFLON Other
This list is provided as an example. Additional materials are being added continuously. Select the appropriate material from the list or select OTHER if the liner material is not listed.
LINER SS -- Speed of Sound in the Liner ENGLSH (Feet per Second)
METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the liner. If the UNITS value was set to ENGLSH, the entry is in FPS (feet per second). METRIC entries are made in MPS (meters per second). If a liner was chosen from the LINER MAT list, a nominal value for speed of sound in tha t media will be automatically loaded. If the actual sound speed rate is known for the pipe liner and that value varies from the automatically loaded value, the value can be revised.
FL TYPE - Fluid/Media Type
TAP WATER SEWAGE SEA WATE KEROSENE GASOLINE FUEL OIL CRUDE OI PROPANE BUTANE OTHER
This list is provided as an example. Additional liquids are being added continuously. Select the appropriate liquid from the list or sele ct OTHER if the liquid is not listed.
Rev. 4/01 - 2.11 - TFXP
PART 2 - TRANSDUCER POSITIONING
Fluid Sound Speed Entry
Fluid Viscosity Entry
FLUID SS -- Speed of Sound in the Fluid ENGLSH (Feet per Second)
METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the liquid. If the UNITS value was set to ENGLSH, the entry is in FPS (feet per second). METRIC entries are made in MPS (meters per second).
If a fluid was chosen from the FL TYPE list, a nominal value for speed of sound in that media will be automatically loaded. If the actual sound speed rate is known for the application fluid and that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as FL TYPE, a FLUID S S will need to be entered. A list of alternate fluids and their associated sound speeds are located the Appendix located at the back of this manual.
FLUID VI -- Absolute Viscosity the Fluid cps
Allows adjustments to be made to the absolute viscosity of the liquid.
If a fluid was chosen from the FL TYPE list, a nominal value for viscosity in that media will be automatically loaded. If the actual viscosity is known for the application fluid and that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as FL TYPE, a FLUID VI will need to be entered. A list of alternate fluids and their associated viscosities are located the Appendix located at the back of this manual.
Fluid Specific Gravity Entr y
Rev. 4/01 - 2.12 - TFXP
SP GRVTY -- Fluid Specific Gravity Entry unitless
Allows adjustments to be made to the specific gravity (density) of the liquid.
PART 2 - TRANSDUCER POSITIONING
Transducer Spacing Calculation
If a fluid was chosen from the FL TYPE list, a nominal value for specific gravity in that media will be automatically loaded. If the actual specific gravity is known for the application fluid and that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as FL TYPE, a SP GRVTY may need to be entered if mass flows are to be calculated. A list of alternate fluids and their associated specific gravities are located the Appendix located at the back of this manual.
XDCR SPAC -- Transducer Spacing Calculation ENGLSH (Inches)
METRIC (Millimeters)
This value represents the one-dimensional linear measurement between the transducers (the upstream/ downstream measurement that runs parallel to the pipe). This value is in inches if ENGLSH was selected as UNITS, in millimeters if METRIC was selected. This measurement is taken from the line which is scribed into the side of the transducer block.
Important note for pipe sizes under 2 inches [50 mm]. If the transducer spacing that is calculated is lower than 2.65 inches [67 mm], enter W-mount as the transducer mount method or enter V- mou nt and pl ace the transducers at 2.65 inches [67 mm]. See Page
2.21 for additional details .
UltraLink Entry
Rev. 4/01 - 2.13 - TFXP
UltraLink Data Entry
The UltraLink Windows®-based software utility provides an efficient means for entering piping and liquid parameters through the use of pop-up window/ pull-down menu structures. Data can be entered into UltraLink, stored, later retrieved and downloaded at
PART 2 - TRANSDUCER POSITIONING
the TFXP installation site (provided that UltraLink and TFXP communications are not enabled at the time of data entry) or it can be downloaded immediately to the TFXP meter (provided that UltraLink and TFXP communications are enabled during data entry).
To install UltraLink and establish communications with a PC, please follow the instructions enclosed with the UltraLink software package or in the Appendix of this manual.
The system information required for entry into the UltraLink package is identical to that required for Keypad Entry covered in the previous section. See pages 2.3-2.5.
After initializing UltraLink, click on the button labeled
Transducer spacing appears here.
Figure 2.4 UltraLink Windows-based software utility configuration screen.
Rev. 4/01 - 2.14 - TFXP
Loading...
+ 68 hidden pages