Dynasonics TFXP User Manual

Series TFXP
Transit Time Ultrasonic Flow Meter
Operations & Maintenance
Manual
BEFORE OPERATING THE TFXP
Important Notice!
The TFXP flow meter is equipped with a lead-acid Gel Cell battery. This battery will require charging before initial operation.
Apply power, utilizing the enclosed 12 volt DC output line power converter or auto-style power cord, to the TFXP for a period of 16­24 hours prior to using the product for the first time. The power converter connects to the DC IN +12V socket connection located on the side of the enclosure. See Figure 1.1. A fully charged battery will provide up to 24 hours of continuous operation before recharging will be necessary.
Figure 1.1 — Power Connection
When the battery level has decreased to a point where recharging is required, the LOW BATTERY indicator will illuminate on the front panel. At that point, the meter will only operate a short time more until it automatically turns itself off – preventing excessive battery discharge that can damage the Gel Cell battery. The TFXP has an integral charging circuit that prevents overcharging. The instrument can be permanently connected to AC line power without damaging the flow meter or the battery. Page 1.12 of this manual contains additional recommendations to preserve and maximize the power in the TFXP battery.
If the TFXP is to be used for extended periods of operation, the AC power converter or the 12 volt auto-style converter can remain connected indefinitely.
TABLE OF CONTENTS
Part 1 - Introduction
Connections
Inputs and Outputs
Quick-Start Operating Instructions 1.4 - 1.6
Introduction General 1.7 Applications 1.7 Product Matrix 1.8 Product Specifications 1.9
Transmitter Connections 1.10 - 1.11 Battery Charging and Maintenance 1.12 - 1.13
Input/Output Connections and Options 4-20 mA Output 1.14 Optional Data Logger 1.15
Other Optional ISO-MODs 1.15
Pages
Part 2 - Transducer and RTD Installation
Part 3 ­ Operation
General 2.1 Mounting Location 2.2 - 2.3 Transducer Spacing 2.4 - 2.7 Transducer Mounting, Pipe Preparation 2.8 - 2.9 Transducer Mounting, V-Mount and W-Mount 2.9 - 2.11 Transducer Mounting, DTTH High Temp 2.12 Transducer Mounting, DTTS/DTTC Small Pipe 2.12 - 2.13 Transducer Mounting, Z-Mount 2.13 - 2.15 Mounting Track Installation 2.16 - 2.17 RTD Installation 2.18 - 2.20
General Programming Information 3.1 - 3.4 Startup and Configuration 3.1
TABLE OF CONTENTS
Part 3 ­ Operation
(continued)
Part 4 - Software
Pages
Keypad Entry Detail 3.4 - 3.33 BASIC MENU 3.4 - 3.16 DATALOG OPERATION 3.17 - 3.23 OUT2 MENU 4-20 mA 3.24 - 3.30 Optional Input/Output 3.31 - 3.35 SENSOR MENU 3.36 SECURITY MENU 3.36 - 3.37 SERVICE MENU 3.37 - 3.39 Signal Strength 3.37 Setting ZERO Flow 3.38 DISPLAY MENU 3.39 - 3.40
Software Utility Operation ULTRALINK™ 4.1 - 4.14 Data Logger 4.15 - 4.17
Heat Flow Addendum A.1 - A.6
Appendix Keypad Interface Map Error Codes K-Factors Explained Fluid Characteristic Table TFX Communications Using ULTRALINK™ Digital Communications Protocol Pipe Dimension Charts Velocity to Volumetric Conversion Statement of Warranty Terms & Conditions Customer Service
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the TFXP instrument. The following condensed instructions are provided to assist the operator in getting the instrument configured and measuring as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
Transducer Location
1. TRANSDUCER LOCATION
A. In general, select a mounting location on the piping system
with a minimum of 10 pipe diameters (10 × the pipe inside diameter) of straight pipe upstream and 5 straight diameters downstream. See Table 2.1 on page 2.3 for additional configurations.
B. Select a mounting method for the transducers based on pipe
size and liquid characteristics. See Table 2.2 on page 2.5. Transducer mounting configurations are illustrated in
Figure 1.2.
¹ Nominal values for these
parameters are included within the TFXP operating system.
The nominal values may be used as they appear or may be modified if exact system values are known.
C. Enter the following data into the TFXP transmitter via the
integral keypad or ULTRALINK™ software utility.
1. Transducer mounting method
2. Pipe O.D. (outside diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed ¹
6. Pipe relative roughness ¹
7. Pipe liner thickness (if present)
8. Pipe liner material
9. Fluid type
10. Fluid sound speed ¹
11. Fluid viscosity ¹
12. Fluid specific gravity ¹
(if present)
D. Record the value calculated and displayed as Transducer
Spacing (XDCR SPC).
Figure 1.2 — Transducer Mounting Configurations
QUICK-START OPERATING INSTRUCTIONS
Connections
2. TRANSDUCER/POWER CONNECTIONS
A. Route the transducer cables from the transducer mounting
location back to the TFXP transmitter. If additional cable and connections are required, ensure that they are RG59 75 compatible.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH or DTTS transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional cable and connections are added, ensure that they are RG59 75
Ohm compatible.
B. Refer to the wiring diagram located on the inside of the TFXP
transmitter and Figure 1.3 for proper power and transducer connections.
Ohm
Figure 1.3 — Transmitter Connections
3. PIPE PREPARATION AND TRANSDUCER MOUNTING DTTN and DTTH Transducers
A. Place the flow meter in signal strength measuring mode.
This value is available on the TFXP display (Service Menu) or in the Data display of the ULTRALINK™ software utility.
B. The piping surface, where the transducers are to be
mounted, must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
QUICK-START OPERATING INSTRUCTIONS
C. Apply a single 1/2" (12 mm) bead of couplant grease to the
upstream transducer and secure it to the pipe with a mounting strap.
D. Apply acoustic couplant grease to the downstream
transducer and press it onto the pipe using hand pressure at the lineal distance calculated in Step 1.
E. Move the transducer slowly around the mounting area until
the highest signal strength is observed. Secure with a mounting strap at this location.
DTTS and DTTC Transducers
A. Place the flow meter in signal strength measuring mode.
This value is available on the TFXP display (Service Menu) or in the Data display of the ULTRALINK™ software utility.
B. The pipe surface, where the transducers are to be mounted,
must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
Startup
C. Apply a single 1/2" (12 mm) bead of acoustic couplant grease
to the top half of the transducer and secure it to the pipe with bottom half or U bolts.
D. Tighten the wing nuts so that the grease begins to flow out
from the edges of the transducer and from the gap between the transducer halves. Do not over tighten.
4. INITIAL SETTINGS AND POWER UP
A. Press the ON button on the flow meter keypad. B. From the Service Menu, verify that signal strength is greater
than 2.0%.
C. Input proper units of measure and I/O data.
PART 1 - INTRODUCTION
General
The TFXP ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non­contacting, clamp-on or clamp-around type, which will provide benefits of non-fouling operation and ease of installation.
TFXP transit time flow meters utilize two transducers that function as both ultrasonic transmitters and receivers. See Figure 1.4. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-Mount where the sound transverses the pipe two times, W-Mount where the sound transverses the pipe four times, or in Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. This selection is based on pipe and liquid characteristics.
DTTS and DTTC (small pipe transducers) have both transmit and receive crystals imbedded in a single clamp-around transducer so no measurement between transducers is required.
Ultrasonic Transmission
Figure 1.4 —
Through a Field
Application Versatility
The flow meter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers. The difference in the time interval measured is directly related to the velocity of the liquid in the pipe.
The TFXP flow meter can be successfully applied on a wide range of metering applications. The simple-to-program transmitter allows the standard product to be used on pipe sizes ranging from 1/2 inch (12 mm) and larger. (Transducer sets from 1/2 to 1-1/2 inch require 2 MHz transmitters and dedicated pipe transducers.) A variety of liquid applications can be accommodated:
ultrapure liquids sewage cooling water potable water reclaimed water river water chemicals plant effluent others
Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. The DTTN transducer set is rated to a pipe surface
PART 1 - INTRODUCTION
temperature of 250 °F (121 °C). High temperature DTTH transducers can operate to a pipe surface temperature of 350 °F (177 °C). The DTTS small pipe transducers can be used to a pipe surface temperature of 185 °F (85 °C) and the DTTC high temperature small pipe transducers are rated for 250 °F (121
°C).
User Safety
The TFXP employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 10 VDC. All user connections are made through sealed bulk-head plugs located on the side of the TFXP enclosure.
Data Integrity
Non-volatile FLASH memory retains all user-entered configuration values in memory for several years (at 25 °C), even if power is lost or the unit is turned off. Data Logger values are stored in FLASH memory in the logger. Password protection is provided as part of the Security menu and prevents inadvertent configuration changes or totalizer resets.
Product Identification
The serial number and complete model number of your TFXP are located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasonics Customer Service Department with this information.
Product Matrix
TFXP -    A -  
Power Supply
A) 115 VAC B) 230 VAC
(two round terminals)
C) 100 VAC G) 230 VAC
(three rectangular terminals)
Output 2
1) 4-20 mA (Standard)
3) Rate Pulse
4) RS232
5) RS485
6) 200,000 event Data Logger*
7) BTU (-40 to +200 °C)
8) BTU (0 to +50 °C)
9) BTU (0 to +100 °C)
Output 1
N) None (Standard)
6) 200,000 event Data Logger*
Approvals
N) Ordinary Area F) Intrinsically Safe**
(Class I, Div. 1, Group C, D)
Options
N) None H) High Temp Transducers 350 °F (177 °C)
2) 2 MHz DTTS Transducers (pipe sizes less than 2" (50 mm)
* The data logger records up to 30,000 points per file, with a maximum of 16 files. The total number of
points that can be recorded on the logger is 200,000.
** I.S. DTTN Transducers must be ordered separately.
Replacement Parts Part Number TFXP Flow meter D040-0110-001
Data Logger, 200,000-event D020-1045-104 Padded carrying case D003-1012-002 Transducers, set of two D071-0110-000 High Temp Transducer Cable Set D071-0110-001 Transducer Cable set, 20 ft. (6 m) D005-2112-020 Transducer Cable set, 50 ft. (15 m) D005-2112-050 Transducer Cable set, 100 ft. (30 m) D005-2112-100 Acoustic Grease, temporary mount D002-2011-001 Mounting Track, 10" measuring scale D010-2102-010 Mounting Track, 16" measuring scale D010-2102-016 36 inch SS hose clamp D002-2007-001 Power converter, 115V U.S. D005-2502-001 Power converter, 230V European D005-2502-002 Power converter, 230V U.K. D005-2503-005 Power cord, 230V U.K. D005-2116-002 Power cord, 12V auto-style D005-2116-002 4-20 mA interconnect cable D005-2116-001 Battery D005-1201-001 Infrared serial adapter D005-2115-001 USB to DB-9 serial adapter D005-2116-004 DB-9 Data Logger interface cable D005-2116-003 ULTRALINK™ Software CD D005-0803-104 Manual, TFXP flow meter DTFXP O&M
PART 1 - SPECIFICATIONS
TRANSMITTER
Power Requirements Velocity Range
Inputs/Outputs
Standard Options
4-20 mA 800 Ohm max; 12-bit resolution, passive or active Data Logger
Other Options
Rate Pulse MOSFET, 0.21 Ohms, 100 V max, 0 to 2,500 Hz max Dual Relay 2 separate Form C relays, 200 VAC max at 0.5 A (resistive) RS232C Data rate to 57.6k RS485 Supports up to 119 drops Heat Flow (RTD) Supports two 1000 Ohm RTDs, multiplexed, 12-bit resolution
Display
Units User configured
Rate Gal, liters, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquid barrels (31.5 gal), ft, m, lb, kg, BTU, MBTU,
Time Seconds, minutes, hours, days Totalizer Gal, liters, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquid barrels (31.5 gal), lb, kg, BTU, MBTU, MMBTU, ton
Mode Forward, reverse, net, batch Ambient Conditions Enclosure NEMA 4X (IP-66) while open, NEMA 6 (IP-68) while closed, ABS with SS hardware Size 14.00" H × 6.06" W × 10.56" D (355.6 mm H × 153.9 mm W × 268.2 mm D); 14.8 lbs (6.7 Kg) Flow Rate Accuracy DTTN / DTTH: ±1% of reading at rates > 1 FPS (0.3 MPS), ±0.01 FPS (±0.003 MPS) at rates lower than 1 FPS
Flow Sensitivity 0.001 FPS (0.0003 MPS) Repeatability ±0.01% of reading Response Time (Flow) Security Keypad lockout, user selected 4 digit access code Approvals Ordinary areas Software ULTRALINK™, compatible with Window
Internal 12 V lead-acid Gel Cell battery provides 24 hrs of continuous operation @ 20 °C. Charging: Wall mount power converter. 115 or 230 VAC 50/60 Hz ±15% VA max; 12-15 VDC @ 2.5 VA max
-40
to
+40
FPS (-12 to +12 MPS)
All output modules are optically isolated from earth and system grounds. One module and one data logger may be installed.
200k events in 30k pages, 16-bit, integral DB-9 RS232C connection, can be removed and installed without disconnecting system power, data transfer rates to 57.6k
128 x 64 pixel graphics LCD, LED backlit. Two user selectable font sizes 0.35" (8.9 mm) or 0.2" (5 mm) 8 digit rate, 8 digit totalizer (resettable)
MMBTU, ton
-40
°F to +185 °F
DTTS/DTTC: 1" and larger units, ±1% of reading from 10-100% of measuring range, ±0.01 FPS (±0.003 MPS) at rates lower than 10% of measuring range; 1/2" and 3/4" units, ±1% FS
0.3 to 30 seconds, user configured, to 100% of value, step change in flow
(-40
°C to
+85
°C), 0 to 95% relative humidity (non-condensing)
®
98/2000/XP/Vista®
TRANSDUCERS
Liquid Types Most non-aerated, clean liquids Cable Length Up to 990 ft (300 meters); standard lengths 20, 50, 100 ft (6, 15, 30 meters) Pipe Sizes DTTN / DTTH: 2 inch and larger
Environment NEMA 6 Pipe Surface
Temperature
Ambient Conditions Housing Material DTTN / DTTC: CPVC, Ultem
Approvals Standard: None
DTTS / DTTC (small pipe): 1/2", 3/4", 1", 1-1/4", 1-1/2" (ANSI pipe, copper tube, tube)
-40
DTTN / DTTC: DTTS:
-40
-40
DTTH:
-40
°F to +185 °F
DTTS: PVC, Ultem DTTH: PTFE, Vespel
Optional - DTTN only: CSA Class I, Div 1, Groups C & D; requires intrinsically safe transducer kit with barrier
°F to +250 °F °F to +185 °F °F to +350 °F
(-40
°C to
®
, and nylon
®
, and nickel-plated brass
(-40
(-40
°C to
(-40
°C to +177 °C)
+85
°C)
®
, and nylon
°C to +121 °C)
+85
°C)
PART 1 - TFXP TRANSMITTER CONNECTIONS
Transmitter Installation
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or reshipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
When the TFXP is to be utilized for extended periods of time in one location, the enclosure should be placed in an area that is convenient for servicing, calibration or for observation of the LCD readout.
1. Locate the transmitter within the length of transducer cable that was supplied with the TFXP system. If this is not possible, it is recommended that the cable be exchanged for one that is of proper length.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH, DTTS or DTTC transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional are RG59 75
2. Place the TFXP transmitter in a location that is:
cable and connections are added, ensure that they
Ohm compatible.
Where little vibration exists.
Protected from corrosive fluids.
Within ambient temperature limits -40 to 185 °F (-40 to 85 °C).
Out of direct sunlight. Direct sunl ight may increase transmitter temperature to above maximum limit and make viewing the LCD difficult.
3. If the transmitter will be subjected to a wet environment, it is recommended that the cover remain closed and the latches secured after configuration is completed. The faceplate/keypad of the TFXP is watertight, but avoid letting water collect on the keypad area.
Rev. 5/09 -1.10- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Electrical Connections
It is highly recommended that the internal battery in the TFXP be fully charged before using the meter for the first time. Details covering this procedure are located on page 1.1 of this manual.
1. The connectors located on the side of the TFXP cons ist of three 1/4-turn BNC-type and one 5.5 mm power plug. These connectors are environmentally sealed, but it is recommended not to allow water or other liquids to collect in the electrical connections pocket.
2. Connect the appropriate wires to the corresponding connections on the transmitter. The transducer cable has markings of UPSTREAM and DOWNSTREAM to assist in the installation process. The UPSTREAM transducer is the one located closer to the direction from which fluid flow normally comes from. (The fluid normally passes the UPSTREAM transducer before passing the DOWNSTREAM transducer.) If the transducer wires are connected backwards, a negative flow indication will be observed on the flow meter display. See Figure 1.5 or the wiring diagram located on the inner door of the transmitter.
Figure 1.5 — Transmitter Connections
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH, DTTS or DTTC transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional are RG59 75
Rev. 5/09 -1.11- TFXP
cable and connections are added, ensure that they
Ohm compatible.
PART 1 - TFXP TRANSMITTER CONNECTIONS
Battery Charging and External Power Sources
The 12 volt DC power converter and 12 volt auto-style power cord connect to the socket connection located on the side of the enclosure. See Figure 1.5 on page 1.11. A fully charged battery will provide up to 24 hours of continuous operation before recharging will be necessary. When the battery level has decreased to a point where recharging is required, the LOW BATTERY indicator will brightly illuminate on the front panel. At that point, the meter will only operate a short time more until it automatically turns itself off – preventing excessive battery discharge that can damage the Gel Cell battery.
NOTE: When the battery is fully charged the LOW BATTERY indicator may have a very dim glow.
If the TFXP is to be used for extended periods of operation, the 12
VDC line power converter or the 12 V auto-style converter can
remain connected indefinitely. To charge the internal Gel Cell battery, apply power, utilizing the
enclosed 12 VDC line power converter or auto-style power cord, to the TFXP for a period of 16-24 hours. The TFXP has an integral charging circuit that prevents overcharging. The instrument can be permanently connected to AC line power without damaging the flow meter or the battery.
The Gel Cell battery is “maintenance free”, but it still requires a certain amount of attention to prolong its useful life. To obtain the greatest capacity and longevity from the battery, the following practices are recommended:
Do not allow the battery to completely discharge. (Discharging the battery to the point where the LOW BATTERY indicator illuminates will not damage the battery. Allowing the battery to remain discharged for long periods of time can degrade the storage capacity of the battery.) When not in use, continually charge the battery by keeping the 12 VDC line power converter plugged in and connected to the flow meter. The TFXP battery management circuitry will not allow the battery to become “overcharged”.
Rev. 5/09 -1.12- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
NOTE: The TFXP will automatically enter a low power consumption mode approximately 1-1/2 minutes after the LOW BATTERY indicator illuminates. This circuit prevents excessive discharge of the internal battery.
If the TFXP is stored for prolonged periods of time, monthly charging is recommended.
If the TFXP is stored for prolonged periods of time, store at a temperature below 70 ºF (21 ºC).
Use wiring practices that conform to local codes (National Electric Code® Handbook in the USA). Use only the power converters that have been supplied with the TFXP flow meter. The ground terminal, if present on the converter, is mandatory for safe operation.
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (i.e. fluorescent lights, relays, compressors, variable frequency drives, etc.)
The TFXP can be operated from a 11-15 VDC source, using the included auto-style power cord, as long as it is capable of supplying at least 3 watts – observe proper polarity.
General Information Regarding Input/Output: ISO-MODs
The TFXP flow meter may contain two Isolated Input/Output Modules (ISO-MODs); one located inside of the flow meter
enclosure and one for the optional data logger, located under the access door on the keyboard. The standard configuration of these modules powered 4­a data logger.
ISO-MODs are epoxy encapsulated electronic input/output modules that are simple to install and replace in the field. All modules are 2,500 volt optically isolated from TFXP power and earth grounds – eliminating the potential for ground loops and reducing the chance of severe damage in the event of an electrical surge.
is to have the internal module configured as an actively
20 mA module and the optional user accessible one as
Rev. 5/09 -1.13- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Standard
4-20 mA Output
The standard 4-20 mA output may be replaced with one of the following five ISO-MODs: dual-relay, rate pulse, RS232C, RS485 and heat flow (RTD). TFXP supports one ISO-MOD input/output module in addition to the optional data logger. All modules are field configurable by utilizing the keyboard or ULTRALINK™ interface. Field wiring connections to ISO-MODs are quick and easy using pluggable terminals.
The 4-20 mA Output Module interfaces with virtually all recording and logging systems by transmitting an analog current signal that is proportional to system flow rate. Independent 4 mA and 20 mA span settings are established in software using the FL4MA and FL
20MA settings in the OUTPUT2 configuration menu. These entries can be set anywhere in the -40 to +40 fps (-12 to +12 mps) measuring range of the instrument. Output resolution of the module is 12-bits (4,096 discrete points). The module can drive up to 800 Ohms of load with its internally generated 24 volt power source.
A 4-20 mA output interface cable has been included with the TFXP package. Connect the 1/4-turn BNC connection to the jack located on the side of the flow meter. See Figure 1.6. The red clip on the cable provides the positive leg of the output and the black clip provides the negative side. Verify that the sum of the resistances in the loop does not exceed 800 Ohms. The TFXP output is configured to source current.
Figure 1.6 — 4-20 mA Output Connections
Refer to Part 3 of this manual for detailed information regarding the configuration, calibration and testing of the 4-20 mA output.
Rev. 5/09 -1.14- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Optional
Data Logger
A 200,000-point Data Logger* is located within the weather-tight pocket on the faceplate of the flow meter. See Figure 1.7. Loosen the three thumbscrews located in the corners of the pocket cover and rotate the cover to expose the Data Logger Module. The logger selected intervals ranging from 1 to 30,000 (8.33 hours) seconds. Configuration of and data retrieval from the logger can be accomplished in one of two ways:
The module is removable. The
The Data Logger software utility,
stores time-stamped, high resolution (16-bit) data at user
module can be carried in a shirt pocket back to the office and plugged into a PC serial port via the module’s integral DB-9 connector.
Data Logger, and the serial DB-9 interface cable included with the logger can be used to access the data. The data logging software is loaded at the same time that ULTRALINK™ is installed. Connect the cable to the logger, which is located in the pocket on the front faceplate of the instrument. See Figure 1.7.
Figure 1.7 —
Data Logger Location
Refer to Part 3 of this manual for detailed information regarding the configuration and operation of the Data Logger Module.
*The 200,000 points can be divided into 16 unique files that each may contain up to 30,000 events.
Other
Optional
ISO-Mods
Rev. 5/09 -1.15- TFXP
There are five additional optional ISO-Mods available in replacement of the standard 4-20mA output. If interested in one of these optional ISO-Mods, please contact Dynasonics sales at 800-535-3569 or 262-639-6770 for detailed information.
PART 1 - INTRODUCTION
NOTES
Rev. 5/09 -1.16- TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
General
The transducers that are utilized by the TFXP contain piezoelectric crystals for transmitting and receiving ultrasonic signals through walls of liquid piping systems. DTTN and DTTH transducers are relatively simple and straightforward to install, but spacing and alignment of the transducers is critical to the system's accuracy and performance. Extra care should be taken to ensure that these instructions are carefully executed. DTTS and DTTC, small pipe transducers, have integrated transmitter and receiver elements that eliminate the requirement for spacing measurement and alignment.
Mounting of the DTTN/DTTH clamp-on ultrasonic transit time transducers is comprised of three steps:
1. Selection of the optimum location on a piping system.
2. Entering the pipe and liquid parameters into either the
(ULTRALINK™) software utility or keying the parameters into the TFXP keypad. The ULTRALINK™ software utility or the TFXP firmware will calculate proper transducer spacing based on these entries.
3. Pipe preparation and transducer mounting. TFXP transmitters with an RTD ISO-MOD module installed require
either one or two RTDs to measure heat flow (one RTD) or heat usage (two RTDs). The Dynasonics flow meter utilizes 1,000 Ohm, three-wire, platinum RTDs in two mounting styles. Surface mount RTDs are available for use on well insulated pipe. If the area where the RTD will be located is not insulated, inconsistent temperature readings will result and insertion (wetted) RTDs should be utilized. Instructions for the installation of the RTDs begin on page 2.18.
Rev. 5/09 - 2.1 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
1. Mounting Location
The first step in the installation process is the selection of an optimum location for the flow measurement to be made. For this to be done effectively, a basic knowledge of the piping system and its plumbing are required.
An optimum location is defined as:
A piping system that is completely full of liquid when
measurements are being taken. The pipe may become completely empty during a process cycle – which will result in the error code 0010 (Low Signal Strength) being displayed on the flow meter while the pipe is empty. Error codes will clear automatically once the pipe refills with liquid. It is not recommended to mount the transducers in an area where the pipe may become partially filled. Partially filled pipes will cause erroneous and unpredictable operation of the meter.
A piping system that contains lengths of straight pipe such
as those described in Table 2.1 on page 2.3. The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation. The straight runs in Table 2.1 apply to liquid velocities that are nominally 7 FPS (2.2 MPS). As liquid velocity increases above this nominal rate, the requirement for straight pipe increases proportionally.
Mount the transducers in an area where they will not be
inadvertently bumped or disturbed during normal operation.
Avoid installations on downward flowing pipes unless
adequate downstream head pressure is present to overcome partial filling of or cavitation in the pipe.
Rev. 5/09 - 2.2 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Table 2.1
1
The TFXP system will provide repeatable measurements on piping systems that do not meet these
requirements, but the accuracy
Rev. 5/09 - 2.3 - TFXP
1 —
Piping Configuration and Transducer Positioning
of these readings may be influenced to various degrees.
PART 2 - TRANSDUCER & RTD INSTALLATION
2. Transducer Spacing
TFX transit time flow meters are sold with four different transducer types: DTTN, DTTH, DTTS and DTTC. Meters that utilize DTTN or DTTH transducer sets consist of two separate sensors that function as both ultrasonic transmitters and receivers. DTTS and DTTC transducers integrate both the transmitter and receiver into one assembly that fixes the separation of the piezoelectric crystals. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other.
The transducers can be
W-Mount where the sound transverses the pipe four times.
This mounting method produces the best relative travel time values but the weakest signal strength.
V-Mount where the sound transverses the pipe twice.
V-Mount is a compromise between travel time and signal strength.
Z-Mount where the transducers are mounted on opposite
sides of the pipe and the sound crosses the pipe once. Z-Mount will yield the best signal strength but the smallest relative travel time.
For further details, reference Figure 2.1 located under Table 2.2 on page 2.5. The appropriate mounting configuration is based on pipe and liquid mounting method iterative process. Table 2.2 contains recommended mounting configurations for common applications. These recommended configurations may need to be modified for specific applications if such things as aeration, suspended solids or poor piping conditions are present. Use of the TFX diagnostics in determining the optimum transducer mounting is covered later in this section.
characteristics. Selection of the proper transducer
is not entirely predictable and many times is an
mounted in:
Rev. 5/09 - 2.4 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Transducer
Mounting Mode
W-Mount
V-Mount
Z-Mount
Pipe Material Pipe Size Liquid Composition
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron1
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron
2-4 in (50-100 mm) 2-4 in (50-100 mm) 2-4 in (50-100 mm) 2-4 in (50-100 mm) Not recommended Not recommended
4-12 in (100-300 mm) 4-12 in (100-300 mm) 4-12 in (100-300 mm) 4-30 in (100-750 mm) 2-12 in (50-300 mm) 2-12 in (50-300 mm)
> 30 in (> 750 mm) > 12 in (> 300 mm) > 12 in (> 300 mm) > 30 in (> 750 mm) > 12 in (> 300 mm) > 12 in (> 300 mm)
Low TSS; non-aerated
Low TSS; non-aerated
Low TSS; non-aerated
TSS = Total Suspended Solids
Table 2.2 Transducer Mounting Modes - DTTN / DTTH
Figure 2.1 Transducer Mounting Modes - DTTN / DTTH
Rev. 5/09 - 2.5 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Size Frequency Transducer
DTTSnP
1/2 2 MHz
3/4 2 MHz
2 MHz
1
NOTE: DTTS transducer designation refers to both DTTS and DTTC transducer types.
DTTSnC DTTSnC
DTTSnT DTTSnT DTTSnP DTTSnC DTTSnC
DTTSnT DTTSnT DTTSnP DTTSnC DTTSnC
DTTSnT 2 MHz DTTSnT
Mounting
Mode
W
W
W
Size Frequency Transducer
DTTSnP
1-1/4 2 MHz
1-1/2 2 MHz
1 MHz
2
DTTSnP
DTTSnP
Table 2.3 Transducer Mounting Modes - DTTS / DTTC
Mounting
Mode
W
W
V
W
Entering Pipe and Liquid Data
The TFX system calculates proper transducer spacing by utilizing piping and liquid information entered by the user. This information can be entered via the keypad on a TFXP or via the optional ULTRALINK™ software utility.
NOTE: Transducer spacing is calculated on “ideal” pipe. Ideal pipe is almost never found so the transducer spacing distances should be considered as starting points. An effective way to maximize signal strength is to configure the display to show signal strength, fix one transducer on the pipe and then starting at the calculated spacing move the remaining transducer small distances forward and back to find the maximum signal strength point.
Rev. 5/09 - 2.6 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Important! Enter all of the data on this list, save the data and reset the TFX before mounting transducers
The following information is required before programming the instrument.
NOTE: Much of the data relating to material sound speed, viscosity and specific gravity is preprogrammed into the TFX flow meter. This data only needs to be modified if it is known that a particular liquid’s data varies from the reference value. Refer to Part 3 of this manual for instructions on entering configuration data into the TFX flow meter via the meter keypad. Refer to Part 4 for data entry via ULTRALINK™ software.
1. Transducer mounting configuration – see Table 2.2 on page
2.5 and Table 2.3 on page 2.6
2. Pipe O.D. (outside diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed1
6. Pipe relative roughness1
7. Pipe liner thickness (if present)
8. Pipe liner material (if present)
9. Fluid type
10. Fluid sound speed1
11. Fluid viscosity1
12. Fluid specific gravity1
1
Nominal values for these parameters are included within the TFX operating system. The nominal values may be used as they appear or may be modified if exact system values are known.
After entering the data listed above, the TFX will calculate proper transducer spacing for the particular data set. This distance will be in inches if the TFX is configured in English units, or millimeters if configured in metric units.
Rev. 5/09 - 2.7 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
3. Transducer Mounting
After selecting an optimal mounting location (Step 1) and successfully determining the proper transducer spacing (Step 2) the transducers may now be mounted onto the pipe.
Pipe Preparation
Before the transducers are mounted onto the pipe surface, an area slightly larger than the flat surface of each transducer must be cleaned of all rust, scale and moisture. For pipes with rough surfaces, such as ductile iron pipe, it is recommended that the pipe surface be ground flat. Paint and other coatings, if not flaked or bubbled, need not be removed. Plastic pipes typically do not require surface preparation other than soap and water cleaning.
The DTTN and DTTH transducers must be properly oriented and spaced on the pipe to provide optimum reliability and performance. On horizontal pipes, when Z-Mount is required, the transducers should be mounted 180 radial degrees from one another and at least 45 degrees from the top-dead-center and bottom-dead-center of the pipe. See Figure 2.2. Also see Z-Mount Transducer Installation on page 2.13. On vertical pipes the orientation is not critical.
Figure 2.2 — Transducer Orientation - Horizontal Pipes
Rev. 5/09 - 2.8 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
The spacing between the transducers is measured between the two spacing marks on the sides of the transducers. These marks are approximately 3/4 inch back from the nose of the transducer. See Figure 2.3.
DTTS and DTTC transducers should be mounted with the cable exiting within Figure 2.2 on page 2.8. On vertical pipes the orientation is not critical.
±45 degrees
of the side of a horizontal pipe. See
V-Mount and W-Mount Transducer Installation
Application of Couplant
Figure 2.3 — Transducer Spacing Marks
V-Mount and W-Mount Installation
1. For DTTN transducers, place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the flat face of the transducer. See Figure 2.4. Generally, a silicone-based grease is used as an acoustic couplant, but any grease-like substance that is rated not to “flow” at the temperature that the pipe may operate at will be acceptable.
Figure 2.4 — Application of Couplant
Rev. 5/09 - 2.9 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Transducer Positioning
2. Place the upstream transducer in position and secure with a mounting strap. Straps should be placed in the arched groove on the end of the transducer. A screw is provided to help hold the transducer onto the strap. Verify that the transducer is true to the pipe — adjust as necessary. Tighten the transducer strap securely.
3. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 2.5. Using firm hand pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal strength. Signal strength can be displayed on the TFX display or on the main data screen in ULTRALINK™. See Part 4 of this manual for details regarding the ULTRALINK™ software utility. Clamp the transducer at the position where the highest signal strength is observed. The factory default signal strength setting is 5 percent, however there are many application specific conditions that may prevent the signal strength from attaining this level. If after trying alternate transducer locations and/or mounting modes the signal strength remains below 5 percent, then reducing the Low Signal Cutoff setting may be necessary. A minimum signal strength of 2 percent is acceptable as long as the 2 percent signal is maintained under all conditions.
(Top view of pipe)
Figure 2.5 — Transducer Positioning
Rev. 5/09 - 2.10 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
4.
If after adjustment of the transducers the signal strength does not rise to above 5 percent, then an alternate transducer mounting method should be selected. If the mounting method was W­TFX, move the downstream transducer to the new location and repeat Step 3 on page 2.10.
5. Certain pipe and liquid characteristics may cause sign al strength to rise to greater than 195 percent. The problem with operating a TFX with very high signal strength is that the signals may saturate the input amplifiers and cause erratic readings. To decrease the signal strength, move one transducer a small distance radially around the pipe, as shown in Figure 2.6.
Mount, then reconfigure the TFX for V-Mount, reset the
Figure 2.6 — High Signal Strength Correction
Rev. 5/09 - 2.11 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
DTTH Transducers for High Temperature
DTTS/DTTC Small Pipe Transducer Installation
DTTH High Temperature Transducers
Mounting of high temperature transducers is similar to standard DTTN transducers. High temperature installations require acoustic couplant that is rated not to “flow” at the temperature that will be present on the pipe surface.
Installation consists of the following steps:
1. Apply a thin coating of high temperature acoustic couplant to the entire surface of the transducer face. The thickness of the application should be approximately 1/16 inch (1.5 mm).
2. Install the two transducers following the procedures detailed in the DTTN instructions on page 2.9 of this manual.
DTTS/DTTC Small Pipe Transducer Installation
The small pipe transducers are designed for specific pipe outside diameters. Do not attempt to mount a DTTS or DTTC transducer onto a pipe that is either too large or too small for the transducer. Contact the Dynasonics factory to arrange for a replacement transducer that is the correct size.
DTTS and DTTC installations consist of the following steps:
1. Apply a thin coating of silicone grease to both halves of the transducer housing where the housing will contact the pipe. See
Figure 2.8.
Figure 2.8 — Application of Grease
DTTS and DTTC Transducers
Rev. 5/09 - 2.12 - TFXP
Loading...
+ 102 hidden pages