Dynasonics TFXP User Manual

Series TFXP
Transit Time Ultrasonic Flow Meter
Operations & Maintenance
Manual
BEFORE OPERATING THE TFXP
Important Notice!
The TFXP flow meter is equipped with a lead-acid Gel Cell battery. This battery will require charging before initial operation.
Apply power, utilizing the enclosed 12 volt DC output line power converter or auto-style power cord, to the TFXP for a period of 16­24 hours prior to using the product for the first time. The power converter connects to the DC IN +12V socket connection located on the side of the enclosure. See Figure 1.1. A fully charged battery will provide up to 24 hours of continuous operation before recharging will be necessary.
Figure 1.1 — Power Connection
When the battery level has decreased to a point where recharging is required, the LOW BATTERY indicator will illuminate on the front panel. At that point, the meter will only operate a short time more until it automatically turns itself off – preventing excessive battery discharge that can damage the Gel Cell battery. The TFXP has an integral charging circuit that prevents overcharging. The instrument can be permanently connected to AC line power without damaging the flow meter or the battery. Page 1.12 of this manual contains additional recommendations to preserve and maximize the power in the TFXP battery.
If the TFXP is to be used for extended periods of operation, the AC power converter or the 12 volt auto-style converter can remain connected indefinitely.
TABLE OF CONTENTS
Part 1 - Introduction
Connections
Inputs and Outputs
Quick-Start Operating Instructions 1.4 - 1.6
Introduction General 1.7 Applications 1.7 Product Matrix 1.8 Product Specifications 1.9
Transmitter Connections 1.10 - 1.11 Battery Charging and Maintenance 1.12 - 1.13
Input/Output Connections and Options 4-20 mA Output 1.14 Optional Data Logger 1.15
Other Optional ISO-MODs 1.15
Pages
Part 2 - Transducer and RTD Installation
Part 3 ­ Operation
General 2.1 Mounting Location 2.2 - 2.3 Transducer Spacing 2.4 - 2.7 Transducer Mounting, Pipe Preparation 2.8 - 2.9 Transducer Mounting, V-Mount and W-Mount 2.9 - 2.11 Transducer Mounting, DTTH High Temp 2.12 Transducer Mounting, DTTS/DTTC Small Pipe 2.12 - 2.13 Transducer Mounting, Z-Mount 2.13 - 2.15 Mounting Track Installation 2.16 - 2.17 RTD Installation 2.18 - 2.20
General Programming Information 3.1 - 3.4 Startup and Configuration 3.1
TABLE OF CONTENTS
Part 3 ­ Operation
(continued)
Part 4 - Software
Pages
Keypad Entry Detail 3.4 - 3.33 BASIC MENU 3.4 - 3.16 DATALOG OPERATION 3.17 - 3.23 OUT2 MENU 4-20 mA 3.24 - 3.30 Optional Input/Output 3.31 - 3.35 SENSOR MENU 3.36 SECURITY MENU 3.36 - 3.37 SERVICE MENU 3.37 - 3.39 Signal Strength 3.37 Setting ZERO Flow 3.38 DISPLAY MENU 3.39 - 3.40
Software Utility Operation ULTRALINK™ 4.1 - 4.14 Data Logger 4.15 - 4.17
Heat Flow Addendum A.1 - A.6
Appendix Keypad Interface Map Error Codes K-Factors Explained Fluid Characteristic Table TFX Communications Using ULTRALINK™ Digital Communications Protocol Pipe Dimension Charts Velocity to Volumetric Conversion Statement of Warranty Terms & Conditions Customer Service
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the TFXP instrument. The following condensed instructions are provided to assist the operator in getting the instrument configured and measuring as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
Transducer Location
1. TRANSDUCER LOCATION
A. In general, select a mounting location on the piping system
with a minimum of 10 pipe diameters (10 × the pipe inside diameter) of straight pipe upstream and 5 straight diameters downstream. See Table 2.1 on page 2.3 for additional configurations.
B. Select a mounting method for the transducers based on pipe
size and liquid characteristics. See Table 2.2 on page 2.5. Transducer mounting configurations are illustrated in
Figure 1.2.
¹ Nominal values for these
parameters are included within the TFXP operating system.
The nominal values may be used as they appear or may be modified if exact system values are known.
C. Enter the following data into the TFXP transmitter via the
integral keypad or ULTRALINK™ software utility.
1. Transducer mounting method
2. Pipe O.D. (outside diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed ¹
6. Pipe relative roughness ¹
7. Pipe liner thickness (if present)
8. Pipe liner material
9. Fluid type
10. Fluid sound speed ¹
11. Fluid viscosity ¹
12. Fluid specific gravity ¹
(if present)
D. Record the value calculated and displayed as Transducer
Spacing (XDCR SPC).
Figure 1.2 — Transducer Mounting Configurations
QUICK-START OPERATING INSTRUCTIONS
Connections
2. TRANSDUCER/POWER CONNECTIONS
A. Route the transducer cables from the transducer mounting
location back to the TFXP transmitter. If additional cable and connections are required, ensure that they are RG59 75 compatible.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH or DTTS transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional cable and connections are added, ensure that they are RG59 75
Ohm compatible.
B. Refer to the wiring diagram located on the inside of the TFXP
transmitter and Figure 1.3 for proper power and transducer connections.
Ohm
Figure 1.3 — Transmitter Connections
3. PIPE PREPARATION AND TRANSDUCER MOUNTING DTTN and DTTH Transducers
A. Place the flow meter in signal strength measuring mode.
This value is available on the TFXP display (Service Menu) or in the Data display of the ULTRALINK™ software utility.
B. The piping surface, where the transducers are to be
mounted, must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
QUICK-START OPERATING INSTRUCTIONS
C. Apply a single 1/2" (12 mm) bead of couplant grease to the
upstream transducer and secure it to the pipe with a mounting strap.
D. Apply acoustic couplant grease to the downstream
transducer and press it onto the pipe using hand pressure at the lineal distance calculated in Step 1.
E. Move the transducer slowly around the mounting area until
the highest signal strength is observed. Secure with a mounting strap at this location.
DTTS and DTTC Transducers
A. Place the flow meter in signal strength measuring mode.
This value is available on the TFXP display (Service Menu) or in the Data display of the ULTRALINK™ software utility.
B. The pipe surface, where the transducers are to be mounted,
must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
Startup
C. Apply a single 1/2" (12 mm) bead of acoustic couplant grease
to the top half of the transducer and secure it to the pipe with bottom half or U bolts.
D. Tighten the wing nuts so that the grease begins to flow out
from the edges of the transducer and from the gap between the transducer halves. Do not over tighten.
4. INITIAL SETTINGS AND POWER UP
A. Press the ON button on the flow meter keypad. B. From the Service Menu, verify that signal strength is greater
than 2.0%.
C. Input proper units of measure and I/O data.
PART 1 - INTRODUCTION
General
The TFXP ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non­contacting, clamp-on or clamp-around type, which will provide benefits of non-fouling operation and ease of installation.
TFXP transit time flow meters utilize two transducers that function as both ultrasonic transmitters and receivers. See Figure 1.4. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-Mount where the sound transverses the pipe two times, W-Mount where the sound transverses the pipe four times, or in Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. This selection is based on pipe and liquid characteristics.
DTTS and DTTC (small pipe transducers) have both transmit and receive crystals imbedded in a single clamp-around transducer so no measurement between transducers is required.
Ultrasonic Transmission
Figure 1.4 —
Through a Field
Application Versatility
The flow meter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers. The difference in the time interval measured is directly related to the velocity of the liquid in the pipe.
The TFXP flow meter can be successfully applied on a wide range of metering applications. The simple-to-program transmitter allows the standard product to be used on pipe sizes ranging from 1/2 inch (12 mm) and larger. (Transducer sets from 1/2 to 1-1/2 inch require 2 MHz transmitters and dedicated pipe transducers.) A variety of liquid applications can be accommodated:
ultrapure liquids sewage cooling water potable water reclaimed water river water chemicals plant effluent others
Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. The DTTN transducer set is rated to a pipe surface
PART 1 - INTRODUCTION
temperature of 250 °F (121 °C). High temperature DTTH transducers can operate to a pipe surface temperature of 350 °F (177 °C). The DTTS small pipe transducers can be used to a pipe surface temperature of 185 °F (85 °C) and the DTTC high temperature small pipe transducers are rated for 250 °F (121
°C).
User Safety
The TFXP employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 10 VDC. All user connections are made through sealed bulk-head plugs located on the side of the TFXP enclosure.
Data Integrity
Non-volatile FLASH memory retains all user-entered configuration values in memory for several years (at 25 °C), even if power is lost or the unit is turned off. Data Logger values are stored in FLASH memory in the logger. Password protection is provided as part of the Security menu and prevents inadvertent configuration changes or totalizer resets.
Product Identification
The serial number and complete model number of your TFXP are located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasonics Customer Service Department with this information.
Product Matrix
TFXP -    A -  
Power Supply
A) 115 VAC B) 230 VAC
(two round terminals)
C) 100 VAC G) 230 VAC
(three rectangular terminals)
Output 2
1) 4-20 mA (Standard)
3) Rate Pulse
4) RS232
5) RS485
6) 200,000 event Data Logger*
7) BTU (-40 to +200 °C)
8) BTU (0 to +50 °C)
9) BTU (0 to +100 °C)
Output 1
N) None (Standard)
6) 200,000 event Data Logger*
Approvals
N) Ordinary Area F) Intrinsically Safe**
(Class I, Div. 1, Group C, D)
Options
N) None H) High Temp Transducers 350 °F (177 °C)
2) 2 MHz DTTS Transducers (pipe sizes less than 2" (50 mm)
* The data logger records up to 30,000 points per file, with a maximum of 16 files. The total number of
points that can be recorded on the logger is 200,000.
** I.S. DTTN Transducers must be ordered separately.
Replacement Parts Part Number TFXP Flow meter D040-0110-001
Data Logger, 200,000-event D020-1045-104 Padded carrying case D003-1012-002 Transducers, set of two D071-0110-000 High Temp Transducer Cable Set D071-0110-001 Transducer Cable set, 20 ft. (6 m) D005-2112-020 Transducer Cable set, 50 ft. (15 m) D005-2112-050 Transducer Cable set, 100 ft. (30 m) D005-2112-100 Acoustic Grease, temporary mount D002-2011-001 Mounting Track, 10" measuring scale D010-2102-010 Mounting Track, 16" measuring scale D010-2102-016 36 inch SS hose clamp D002-2007-001 Power converter, 115V U.S. D005-2502-001 Power converter, 230V European D005-2502-002 Power converter, 230V U.K. D005-2503-005 Power cord, 230V U.K. D005-2116-002 Power cord, 12V auto-style D005-2116-002 4-20 mA interconnect cable D005-2116-001 Battery D005-1201-001 Infrared serial adapter D005-2115-001 USB to DB-9 serial adapter D005-2116-004 DB-9 Data Logger interface cable D005-2116-003 ULTRALINK™ Software CD D005-0803-104 Manual, TFXP flow meter DTFXP O&M
PART 1 - SPECIFICATIONS
TRANSMITTER
Power Requirements Velocity Range
Inputs/Outputs
Standard Options
4-20 mA 800 Ohm max; 12-bit resolution, passive or active Data Logger
Other Options
Rate Pulse MOSFET, 0.21 Ohms, 100 V max, 0 to 2,500 Hz max Dual Relay 2 separate Form C relays, 200 VAC max at 0.5 A (resistive) RS232C Data rate to 57.6k RS485 Supports up to 119 drops Heat Flow (RTD) Supports two 1000 Ohm RTDs, multiplexed, 12-bit resolution
Display
Units User configured
Rate Gal, liters, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquid barrels (31.5 gal), ft, m, lb, kg, BTU, MBTU,
Time Seconds, minutes, hours, days Totalizer Gal, liters, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquid barrels (31.5 gal), lb, kg, BTU, MBTU, MMBTU, ton
Mode Forward, reverse, net, batch Ambient Conditions Enclosure NEMA 4X (IP-66) while open, NEMA 6 (IP-68) while closed, ABS with SS hardware Size 14.00" H × 6.06" W × 10.56" D (355.6 mm H × 153.9 mm W × 268.2 mm D); 14.8 lbs (6.7 Kg) Flow Rate Accuracy DTTN / DTTH: ±1% of reading at rates > 1 FPS (0.3 MPS), ±0.01 FPS (±0.003 MPS) at rates lower than 1 FPS
Flow Sensitivity 0.001 FPS (0.0003 MPS) Repeatability ±0.01% of reading Response Time (Flow) Security Keypad lockout, user selected 4 digit access code Approvals Ordinary areas Software ULTRALINK™, compatible with Window
Internal 12 V lead-acid Gel Cell battery provides 24 hrs of continuous operation @ 20 °C. Charging: Wall mount power converter. 115 or 230 VAC 50/60 Hz ±15% VA max; 12-15 VDC @ 2.5 VA max
-40
to
+40
FPS (-12 to +12 MPS)
All output modules are optically isolated from earth and system grounds. One module and one data logger may be installed.
200k events in 30k pages, 16-bit, integral DB-9 RS232C connection, can be removed and installed without disconnecting system power, data transfer rates to 57.6k
128 x 64 pixel graphics LCD, LED backlit. Two user selectable font sizes 0.35" (8.9 mm) or 0.2" (5 mm) 8 digit rate, 8 digit totalizer (resettable)
MMBTU, ton
-40
°F to +185 °F
DTTS/DTTC: 1" and larger units, ±1% of reading from 10-100% of measuring range, ±0.01 FPS (±0.003 MPS) at rates lower than 10% of measuring range; 1/2" and 3/4" units, ±1% FS
0.3 to 30 seconds, user configured, to 100% of value, step change in flow
(-40
°C to
+85
°C), 0 to 95% relative humidity (non-condensing)
®
98/2000/XP/Vista®
TRANSDUCERS
Liquid Types Most non-aerated, clean liquids Cable Length Up to 990 ft (300 meters); standard lengths 20, 50, 100 ft (6, 15, 30 meters) Pipe Sizes DTTN / DTTH: 2 inch and larger
Environment NEMA 6 Pipe Surface
Temperature
Ambient Conditions Housing Material DTTN / DTTC: CPVC, Ultem
Approvals Standard: None
DTTS / DTTC (small pipe): 1/2", 3/4", 1", 1-1/4", 1-1/2" (ANSI pipe, copper tube, tube)
-40
DTTN / DTTC: DTTS:
-40
-40
DTTH:
-40
°F to +185 °F
DTTS: PVC, Ultem DTTH: PTFE, Vespel
Optional - DTTN only: CSA Class I, Div 1, Groups C & D; requires intrinsically safe transducer kit with barrier
°F to +250 °F °F to +185 °F °F to +350 °F
(-40
°C to
®
, and nylon
®
, and nickel-plated brass
(-40
(-40
°C to
(-40
°C to +177 °C)
+85
°C)
®
, and nylon
°C to +121 °C)
+85
°C)
PART 1 - TFXP TRANSMITTER CONNECTIONS
Transmitter Installation
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or reshipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
When the TFXP is to be utilized for extended periods of time in one location, the enclosure should be placed in an area that is convenient for servicing, calibration or for observation of the LCD readout.
1. Locate the transmitter within the length of transducer cable that was supplied with the TFXP system. If this is not possible, it is recommended that the cable be exchanged for one that is of proper length.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH, DTTS or DTTC transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional are RG59 75
2. Place the TFXP transmitter in a location that is:
cable and connections are added, ensure that they
Ohm compatible.
Where little vibration exists.
Protected from corrosive fluids.
Within ambient temperature limits -40 to 185 °F (-40 to 85 °C).
Out of direct sunlight. Direct sunl ight may increase transmitter temperature to above maximum limit and make viewing the LCD difficult.
3. If the transmitter will be subjected to a wet environment, it is recommended that the cover remain closed and the latches secured after configuration is completed. The faceplate/keypad of the TFXP is watertight, but avoid letting water collect on the keypad area.
Rev. 5/09 -1.10- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Electrical Connections
It is highly recommended that the internal battery in the TFXP be fully charged before using the meter for the first time. Details covering this procedure are located on page 1.1 of this manual.
1. The connectors located on the side of the TFXP cons ist of three 1/4-turn BNC-type and one 5.5 mm power plug. These connectors are environmentally sealed, but it is recommended not to allow water or other liquids to collect in the electrical connections pocket.
2. Connect the appropriate wires to the corresponding connections on the transmitter. The transducer cable has markings of UPSTREAM and DOWNSTREAM to assist in the installation process. The UPSTREAM transducer is the one located closer to the direction from which fluid flow normally comes from. (The fluid normally passes the UPSTREAM transducer before passing the DOWNSTREAM transducer.) If the transducer wires are connected backwards, a negative flow indication will be observed on the flow meter display. See Figure 1.5 or the wiring diagram located on the inner door of the transmitter.
Figure 1.5 — Transmitter Connections
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH, DTTS or DTTC transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet (300 meters) are available. If additional are RG59 75
Rev. 5/09 -1.11- TFXP
cable and connections are added, ensure that they
Ohm compatible.
PART 1 - TFXP TRANSMITTER CONNECTIONS
Battery Charging and External Power Sources
The 12 volt DC power converter and 12 volt auto-style power cord connect to the socket connection located on the side of the enclosure. See Figure 1.5 on page 1.11. A fully charged battery will provide up to 24 hours of continuous operation before recharging will be necessary. When the battery level has decreased to a point where recharging is required, the LOW BATTERY indicator will brightly illuminate on the front panel. At that point, the meter will only operate a short time more until it automatically turns itself off – preventing excessive battery discharge that can damage the Gel Cell battery.
NOTE: When the battery is fully charged the LOW BATTERY indicator may have a very dim glow.
If the TFXP is to be used for extended periods of operation, the 12
VDC line power converter or the 12 V auto-style converter can
remain connected indefinitely. To charge the internal Gel Cell battery, apply power, utilizing the
enclosed 12 VDC line power converter or auto-style power cord, to the TFXP for a period of 16-24 hours. The TFXP has an integral charging circuit that prevents overcharging. The instrument can be permanently connected to AC line power without damaging the flow meter or the battery.
The Gel Cell battery is “maintenance free”, but it still requires a certain amount of attention to prolong its useful life. To obtain the greatest capacity and longevity from the battery, the following practices are recommended:
Do not allow the battery to completely discharge. (Discharging the battery to the point where the LOW BATTERY indicator illuminates will not damage the battery. Allowing the battery to remain discharged for long periods of time can degrade the storage capacity of the battery.) When not in use, continually charge the battery by keeping the 12 VDC line power converter plugged in and connected to the flow meter. The TFXP battery management circuitry will not allow the battery to become “overcharged”.
Rev. 5/09 -1.12- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
NOTE: The TFXP will automatically enter a low power consumption mode approximately 1-1/2 minutes after the LOW BATTERY indicator illuminates. This circuit prevents excessive discharge of the internal battery.
If the TFXP is stored for prolonged periods of time, monthly charging is recommended.
If the TFXP is stored for prolonged periods of time, store at a temperature below 70 ºF (21 ºC).
Use wiring practices that conform to local codes (National Electric Code® Handbook in the USA). Use only the power converters that have been supplied with the TFXP flow meter. The ground terminal, if present on the converter, is mandatory for safe operation.
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (i.e. fluorescent lights, relays, compressors, variable frequency drives, etc.)
The TFXP can be operated from a 11-15 VDC source, using the included auto-style power cord, as long as it is capable of supplying at least 3 watts – observe proper polarity.
General Information Regarding Input/Output: ISO-MODs
The TFXP flow meter may contain two Isolated Input/Output Modules (ISO-MODs); one located inside of the flow meter
enclosure and one for the optional data logger, located under the access door on the keyboard. The standard configuration of these modules powered 4­a data logger.
ISO-MODs are epoxy encapsulated electronic input/output modules that are simple to install and replace in the field. All modules are 2,500 volt optically isolated from TFXP power and earth grounds – eliminating the potential for ground loops and reducing the chance of severe damage in the event of an electrical surge.
is to have the internal module configured as an actively
20 mA module and the optional user accessible one as
Rev. 5/09 -1.13- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Standard
4-20 mA Output
The standard 4-20 mA output may be replaced with one of the following five ISO-MODs: dual-relay, rate pulse, RS232C, RS485 and heat flow (RTD). TFXP supports one ISO-MOD input/output module in addition to the optional data logger. All modules are field configurable by utilizing the keyboard or ULTRALINK™ interface. Field wiring connections to ISO-MODs are quick and easy using pluggable terminals.
The 4-20 mA Output Module interfaces with virtually all recording and logging systems by transmitting an analog current signal that is proportional to system flow rate. Independent 4 mA and 20 mA span settings are established in software using the FL4MA and FL
20MA settings in the OUTPUT2 configuration menu. These entries can be set anywhere in the -40 to +40 fps (-12 to +12 mps) measuring range of the instrument. Output resolution of the module is 12-bits (4,096 discrete points). The module can drive up to 800 Ohms of load with its internally generated 24 volt power source.
A 4-20 mA output interface cable has been included with the TFXP package. Connect the 1/4-turn BNC connection to the jack located on the side of the flow meter. See Figure 1.6. The red clip on the cable provides the positive leg of the output and the black clip provides the negative side. Verify that the sum of the resistances in the loop does not exceed 800 Ohms. The TFXP output is configured to source current.
Figure 1.6 — 4-20 mA Output Connections
Refer to Part 3 of this manual for detailed information regarding the configuration, calibration and testing of the 4-20 mA output.
Rev. 5/09 -1.14- TFXP
PART 1 - TFXP TRANSMITTER CONNECTIONS
Optional
Data Logger
A 200,000-point Data Logger* is located within the weather-tight pocket on the faceplate of the flow meter. See Figure 1.7. Loosen the three thumbscrews located in the corners of the pocket cover and rotate the cover to expose the Data Logger Module. The logger selected intervals ranging from 1 to 30,000 (8.33 hours) seconds. Configuration of and data retrieval from the logger can be accomplished in one of two ways:
The module is removable. The
The Data Logger software utility,
stores time-stamped, high resolution (16-bit) data at user
module can be carried in a shirt pocket back to the office and plugged into a PC serial port via the module’s integral DB-9 connector.
Data Logger, and the serial DB-9 interface cable included with the logger can be used to access the data. The data logging software is loaded at the same time that ULTRALINK™ is installed. Connect the cable to the logger, which is located in the pocket on the front faceplate of the instrument. See Figure 1.7.
Figure 1.7 —
Data Logger Location
Refer to Part 3 of this manual for detailed information regarding the configuration and operation of the Data Logger Module.
*The 200,000 points can be divided into 16 unique files that each may contain up to 30,000 events.
Other
Optional
ISO-Mods
Rev. 5/09 -1.15- TFXP
There are five additional optional ISO-Mods available in replacement of the standard 4-20mA output. If interested in one of these optional ISO-Mods, please contact Dynasonics sales at 800-535-3569 or 262-639-6770 for detailed information.
PART 1 - INTRODUCTION
NOTES
Rev. 5/09 -1.16- TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
General
The transducers that are utilized by the TFXP contain piezoelectric crystals for transmitting and receiving ultrasonic signals through walls of liquid piping systems. DTTN and DTTH transducers are relatively simple and straightforward to install, but spacing and alignment of the transducers is critical to the system's accuracy and performance. Extra care should be taken to ensure that these instructions are carefully executed. DTTS and DTTC, small pipe transducers, have integrated transmitter and receiver elements that eliminate the requirement for spacing measurement and alignment.
Mounting of the DTTN/DTTH clamp-on ultrasonic transit time transducers is comprised of three steps:
1. Selection of the optimum location on a piping system.
2. Entering the pipe and liquid parameters into either the
(ULTRALINK™) software utility or keying the parameters into the TFXP keypad. The ULTRALINK™ software utility or the TFXP firmware will calculate proper transducer spacing based on these entries.
3. Pipe preparation and transducer mounting. TFXP transmitters with an RTD ISO-MOD module installed require
either one or two RTDs to measure heat flow (one RTD) or heat usage (two RTDs). The Dynasonics flow meter utilizes 1,000 Ohm, three-wire, platinum RTDs in two mounting styles. Surface mount RTDs are available for use on well insulated pipe. If the area where the RTD will be located is not insulated, inconsistent temperature readings will result and insertion (wetted) RTDs should be utilized. Instructions for the installation of the RTDs begin on page 2.18.
Rev. 5/09 - 2.1 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
1. Mounting Location
The first step in the installation process is the selection of an optimum location for the flow measurement to be made. For this to be done effectively, a basic knowledge of the piping system and its plumbing are required.
An optimum location is defined as:
A piping system that is completely full of liquid when
measurements are being taken. The pipe may become completely empty during a process cycle – which will result in the error code 0010 (Low Signal Strength) being displayed on the flow meter while the pipe is empty. Error codes will clear automatically once the pipe refills with liquid. It is not recommended to mount the transducers in an area where the pipe may become partially filled. Partially filled pipes will cause erroneous and unpredictable operation of the meter.
A piping system that contains lengths of straight pipe such
as those described in Table 2.1 on page 2.3. The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation. The straight runs in Table 2.1 apply to liquid velocities that are nominally 7 FPS (2.2 MPS). As liquid velocity increases above this nominal rate, the requirement for straight pipe increases proportionally.
Mount the transducers in an area where they will not be
inadvertently bumped or disturbed during normal operation.
Avoid installations on downward flowing pipes unless
adequate downstream head pressure is present to overcome partial filling of or cavitation in the pipe.
Rev. 5/09 - 2.2 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Table 2.1
1
The TFXP system will provide repeatable measurements on piping systems that do not meet these
requirements, but the accuracy
Rev. 5/09 - 2.3 - TFXP
1 —
Piping Configuration and Transducer Positioning
of these readings may be influenced to various degrees.
PART 2 - TRANSDUCER & RTD INSTALLATION
2. Transducer Spacing
TFX transit time flow meters are sold with four different transducer types: DTTN, DTTH, DTTS and DTTC. Meters that utilize DTTN or DTTH transducer sets consist of two separate sensors that function as both ultrasonic transmitters and receivers. DTTS and DTTC transducers integrate both the transmitter and receiver into one assembly that fixes the separation of the piezoelectric crystals. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other.
The transducers can be
W-Mount where the sound transverses the pipe four times.
This mounting method produces the best relative travel time values but the weakest signal strength.
V-Mount where the sound transverses the pipe twice.
V-Mount is a compromise between travel time and signal strength.
Z-Mount where the transducers are mounted on opposite
sides of the pipe and the sound crosses the pipe once. Z-Mount will yield the best signal strength but the smallest relative travel time.
For further details, reference Figure 2.1 located under Table 2.2 on page 2.5. The appropriate mounting configuration is based on pipe and liquid mounting method iterative process. Table 2.2 contains recommended mounting configurations for common applications. These recommended configurations may need to be modified for specific applications if such things as aeration, suspended solids or poor piping conditions are present. Use of the TFX diagnostics in determining the optimum transducer mounting is covered later in this section.
characteristics. Selection of the proper transducer
is not entirely predictable and many times is an
mounted in:
Rev. 5/09 - 2.4 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Transducer
Mounting Mode
W-Mount
V-Mount
Z-Mount
Pipe Material Pipe Size Liquid Composition
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron1
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron
Plastic (all types) Carbon Steel Stainless Steel Copper Ductile Iron Cast Iron
2-4 in (50-100 mm) 2-4 in (50-100 mm) 2-4 in (50-100 mm) 2-4 in (50-100 mm) Not recommended Not recommended
4-12 in (100-300 mm) 4-12 in (100-300 mm) 4-12 in (100-300 mm) 4-30 in (100-750 mm) 2-12 in (50-300 mm) 2-12 in (50-300 mm)
> 30 in (> 750 mm) > 12 in (> 300 mm) > 12 in (> 300 mm) > 30 in (> 750 mm) > 12 in (> 300 mm) > 12 in (> 300 mm)
Low TSS; non-aerated
Low TSS; non-aerated
Low TSS; non-aerated
TSS = Total Suspended Solids
Table 2.2 Transducer Mounting Modes - DTTN / DTTH
Figure 2.1 Transducer Mounting Modes - DTTN / DTTH
Rev. 5/09 - 2.5 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Size Frequency Transducer
DTTSnP
1/2 2 MHz
3/4 2 MHz
2 MHz
1
NOTE: DTTS transducer designation refers to both DTTS and DTTC transducer types.
DTTSnC DTTSnC
DTTSnT DTTSnT DTTSnP DTTSnC DTTSnC
DTTSnT DTTSnT DTTSnP DTTSnC DTTSnC
DTTSnT 2 MHz DTTSnT
Mounting
Mode
W
W
W
Size Frequency Transducer
DTTSnP
1-1/4 2 MHz
1-1/2 2 MHz
1 MHz
2
DTTSnP
DTTSnP
Table 2.3 Transducer Mounting Modes - DTTS / DTTC
Mounting
Mode
W
W
V
W
Entering Pipe and Liquid Data
The TFX system calculates proper transducer spacing by utilizing piping and liquid information entered by the user. This information can be entered via the keypad on a TFXP or via the optional ULTRALINK™ software utility.
NOTE: Transducer spacing is calculated on “ideal” pipe. Ideal pipe is almost never found so the transducer spacing distances should be considered as starting points. An effective way to maximize signal strength is to configure the display to show signal strength, fix one transducer on the pipe and then starting at the calculated spacing move the remaining transducer small distances forward and back to find the maximum signal strength point.
Rev. 5/09 - 2.6 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Important! Enter all of the data on this list, save the data and reset the TFX before mounting transducers
The following information is required before programming the instrument.
NOTE: Much of the data relating to material sound speed, viscosity and specific gravity is preprogrammed into the TFX flow meter. This data only needs to be modified if it is known that a particular liquid’s data varies from the reference value. Refer to Part 3 of this manual for instructions on entering configuration data into the TFX flow meter via the meter keypad. Refer to Part 4 for data entry via ULTRALINK™ software.
1. Transducer mounting configuration – see Table 2.2 on page
2.5 and Table 2.3 on page 2.6
2. Pipe O.D. (outside diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed1
6. Pipe relative roughness1
7. Pipe liner thickness (if present)
8. Pipe liner material (if present)
9. Fluid type
10. Fluid sound speed1
11. Fluid viscosity1
12. Fluid specific gravity1
1
Nominal values for these parameters are included within the TFX operating system. The nominal values may be used as they appear or may be modified if exact system values are known.
After entering the data listed above, the TFX will calculate proper transducer spacing for the particular data set. This distance will be in inches if the TFX is configured in English units, or millimeters if configured in metric units.
Rev. 5/09 - 2.7 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
3. Transducer Mounting
After selecting an optimal mounting location (Step 1) and successfully determining the proper transducer spacing (Step 2) the transducers may now be mounted onto the pipe.
Pipe Preparation
Before the transducers are mounted onto the pipe surface, an area slightly larger than the flat surface of each transducer must be cleaned of all rust, scale and moisture. For pipes with rough surfaces, such as ductile iron pipe, it is recommended that the pipe surface be ground flat. Paint and other coatings, if not flaked or bubbled, need not be removed. Plastic pipes typically do not require surface preparation other than soap and water cleaning.
The DTTN and DTTH transducers must be properly oriented and spaced on the pipe to provide optimum reliability and performance. On horizontal pipes, when Z-Mount is required, the transducers should be mounted 180 radial degrees from one another and at least 45 degrees from the top-dead-center and bottom-dead-center of the pipe. See Figure 2.2. Also see Z-Mount Transducer Installation on page 2.13. On vertical pipes the orientation is not critical.
Figure 2.2 — Transducer Orientation - Horizontal Pipes
Rev. 5/09 - 2.8 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
The spacing between the transducers is measured between the two spacing marks on the sides of the transducers. These marks are approximately 3/4 inch back from the nose of the transducer. See Figure 2.3.
DTTS and DTTC transducers should be mounted with the cable exiting within Figure 2.2 on page 2.8. On vertical pipes the orientation is not critical.
±45 degrees
of the side of a horizontal pipe. See
V-Mount and W-Mount Transducer Installation
Application of Couplant
Figure 2.3 — Transducer Spacing Marks
V-Mount and W-Mount Installation
1. For DTTN transducers, place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the flat face of the transducer. See Figure 2.4. Generally, a silicone-based grease is used as an acoustic couplant, but any grease-like substance that is rated not to “flow” at the temperature that the pipe may operate at will be acceptable.
Figure 2.4 — Application of Couplant
Rev. 5/09 - 2.9 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Transducer Positioning
2. Place the upstream transducer in position and secure with a mounting strap. Straps should be placed in the arched groove on the end of the transducer. A screw is provided to help hold the transducer onto the strap. Verify that the transducer is true to the pipe — adjust as necessary. Tighten the transducer strap securely.
3. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 2.5. Using firm hand pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal strength. Signal strength can be displayed on the TFX display or on the main data screen in ULTRALINK™. See Part 4 of this manual for details regarding the ULTRALINK™ software utility. Clamp the transducer at the position where the highest signal strength is observed. The factory default signal strength setting is 5 percent, however there are many application specific conditions that may prevent the signal strength from attaining this level. If after trying alternate transducer locations and/or mounting modes the signal strength remains below 5 percent, then reducing the Low Signal Cutoff setting may be necessary. A minimum signal strength of 2 percent is acceptable as long as the 2 percent signal is maintained under all conditions.
(Top view of pipe)
Figure 2.5 — Transducer Positioning
Rev. 5/09 - 2.10 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
4.
If after adjustment of the transducers the signal strength does not rise to above 5 percent, then an alternate transducer mounting method should be selected. If the mounting method was W­TFX, move the downstream transducer to the new location and repeat Step 3 on page 2.10.
5. Certain pipe and liquid characteristics may cause sign al strength to rise to greater than 195 percent. The problem with operating a TFX with very high signal strength is that the signals may saturate the input amplifiers and cause erratic readings. To decrease the signal strength, move one transducer a small distance radially around the pipe, as shown in Figure 2.6.
Mount, then reconfigure the TFX for V-Mount, reset the
Figure 2.6 — High Signal Strength Correction
Rev. 5/09 - 2.11 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
DTTH Transducers for High Temperature
DTTS/DTTC Small Pipe Transducer Installation
DTTH High Temperature Transducers
Mounting of high temperature transducers is similar to standard DTTN transducers. High temperature installations require acoustic couplant that is rated not to “flow” at the temperature that will be present on the pipe surface.
Installation consists of the following steps:
1. Apply a thin coating of high temperature acoustic couplant to the entire surface of the transducer face. The thickness of the application should be approximately 1/16 inch (1.5 mm).
2. Install the two transducers following the procedures detailed in the DTTN instructions on page 2.9 of this manual.
DTTS/DTTC Small Pipe Transducer Installation
The small pipe transducers are designed for specific pipe outside diameters. Do not attempt to mount a DTTS or DTTC transducer onto a pipe that is either too large or too small for the transducer. Contact the Dynasonics factory to arrange for a replacement transducer that is the correct size.
DTTS and DTTC installations consist of the following steps:
1. Apply a thin coating of silicone grease to both halves of the transducer housing where the housing will contact the pipe. See
Figure 2.8.
Figure 2.8 — Application of Grease
DTTS and DTTC Transducers
Rev. 5/09 - 2.12 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
2. On horizontal pipes, mount the transducer in an orientation so that the cable exits at mount with the cable exiting on either the top or bottom of the pipe. On vertical pipes the orientation is not critical. See Figure
2.2 on page 2.8.
3. Tighten the wing nuts or “U” bolts so that the grease begins to flow out from the edges of the transducer and from the gap between the transducer halves. Do not over tighten.
4. If signal strength is less than 5 percent, remount the transducer at another location on the piping system.
5. If signal strength is greater than 195 percent, contact Dynasonics for adjustments to the AGC (Automatic Gain) settings.
±45°
from the side of the pipe. Do not
Z-Mount Transducer Installation
Mounting Transducers in Z-Mount Configuration
Installation on larger pipes requires careful measurements of the linear and radial placement of the DTTN and DTTH transducers. Failure to properly orient and place the transducers on the pipe may lead to weak signal strength and/or inaccurate readings. This section details a method for properly locating the transducers o n lar ger pipes. This method requires a roll of paper such as freezer paper or wrapping paper, masking tape and a marking device.
1. Wrap the paper around the pipe in the manner shown in Figure
2.9. Align the paper ends to within 1/4 inch (6 mm).
Figure 2.9 — Paper Template Alignment
2. Mark the intersection of the two ends of the paper to indicate the circumference. Remove the template and spread it out on a flat surface. Fold the template in half, bisecting the circumference. See Figure 2.10 on page 2.14.
Rev. 5/09 - 2.13 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Figure 2.10 — Bisecting the Pipe Circumference
3.
Crease the paper at the fold line. Mark the crease. Place a mark on the pipe where one of the transducers will be located. See Figure 2.2 on page 2.8 for acceptable radial orientations. Wrap the template back around the pipe, placing the beginning of the paper and one corner in the location of the mark. Move to the other side of the pipe and mark the pipe at the ends of the crease. Measure from the end of the crease (directly across the pipe from the first transducer location) the dimension derived in Step 2, Transducer Spacing. Mark this location on the pipe.
4. The two marks on the pipe are now properly aligned and measured.
If access to the bottom of the pipe prohibits the wrapping of the paper around the circumference, cut a piece of paper 1/2 the circumference of the pipe and lay it over the top of the pipe.
1/2 Circumference = Pipe O.D. × 1.57
The transducer spacing is the same as found in the Transducer Positioning section on page 2.10.
Mark opposite corners of the paper on the pipe. Apply transducers to these two marks.
Rev. 5/09 - 2.14 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
5. For DTTN transducers, place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the flat face of the transducer. See Figure 2.4 on page 2.9. Generally, a silicone­based grease is used as an acoustic couplant, but any grease­like substance that is rated to not “flow” at the temperature that the pipe may operate at will be acceptable.
6. Place the upstream transducer in position and secure with a stainless steel strap or other. Straps should be placed in the arched groove on the end of the transducer. A screw is provided to help hold the transducer onto the strap. Verify that the transdu cer is true to the pipe — adjust as necessary. Tighten the transducer strap securely. Larger pipes may require more than one strap to reach the circumference of the pipe.
7. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 2.11 on page 2.16. Using firm hand pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal strength. Clamp the transducer at the position where the highest signal strength is observed. Signal strength of between 5 and 195 percent is acceptable. The factory default signal strength setting is 5 percent, however there are many application specific conditions that may prevent the signal strength from attaining this level. If after trying alternate transducer locations and/or mounting modes the signal strength remains below 5 percent, then reducing the Low Signal Cutoff setting may be necessary. A minimum signal strength of 2 percent is acceptable as long as the 2 percent signal is maintained under all flow conditions.
On certain pipes, a slight twist to the transducer may cause signal strength to rise to acceptable levels.
8. Certain pipe and liquid characteristics may cause sign al strength to rise to greater than 195 percent. The problem wit h operating a TFX with very high signal strength is that the signals may saturate the input amplifiers and cause erratic readings. To decrease the signal strength, one transducer can be offset rad ial ly, as illustrated in Figure 2.6 on page 2.11, or a V-Mount transducer mounting method may be chosen.
9. Secure the transducer with a stainless steel strap or other fastener.
Rev. 5/09 - 2.15 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Figure 2.11 — Z-Mount Transducer Placement
Mounting Track Installation
D010-2102-010 Mounting Track Installation
1. The D010-2102-010 transducer mounting track is used for
pipes that have outside diameters between 2 and 10 inches (50-250 mm). If the pipe is outside of that range, select a standard V-Mount or Z-Mount mounting method.
2. Install the single mounting rail on the side of the pipe with the
stainless steel bands provided. Do not mount it on the top or bottom of the pipe. Orientation on vertical pipe is not critical. Ensure that the track is parallel to the pipe and that all four mounting feet are touching the pipe.
3. Slide the two transducer clam p brackets towards the center,
5 inch (125 mm) mark on the mounting rail.
4.
Place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the flat face of the transducer. See Figure 2.4 on page 2.9.
5. Place the first transducer in between the mounting rails near
the zero point on the scale. Slide the clamp over the transducer . Adjust the clamp/transducer so that the notch in the clamp aligns with zero on the scale. See Figure 2.12 on page 2.17.
Rev. 5/09 - 2.16 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Figure 2.12 — D010-2102-010 Mounting Track Installation
6. Secure with the thumb screw. Ensure that the screw rests in
the counter bore on the top of the transducer. (Excessive pressure is not required. Apply just enough pressure so that the couplant fills the gap between the pipe and transducer.)
7. Place the second transducer in between the mounting rails
near the dimension derived in the Transducer Spacing section. Read the dimension on the mounting rail scale. Slide the transducer clamp over the transducer and secure with the thumb screw.
Rev. 5/09 - 2.17 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
4. RTD INSTALLATION
For typical installations, the length of RTD wire should equal the length of the flow transducer cable. Ensure that the length of wire included with the RTDs is adequate to reach from the supply and return pipes to the location of the TFX transmitter. If the length of wire is insufficient, wire can be added on but a small temperature offset will result. If additional RTD wire is added, utilize Belden 9939 or equivalent cable and provide proper connections to the shield wires – maintain the color coding.
Surface Mount RTD Installation
Surface Mount RTD Installation
Surface mount RTDs should only be utilized on well insulated pipe. If the area where the RTD is located is not insulated, inconsistent temperature readings will result and insertion (wetted) RTDs should be utilized.
1. Select areas on the supply and return pipes where the RTDs
will be mounted and peel back the insulation all the way around the pipe in the installation area.
2. Clean an area on the pipe slightly larger than the RTD down
to bare metal.
3. Place a small amount of heat sink compound on the pipe in
the RTD installation location. See Figure 2.13 on page 2.19.
4. Press the RTD firmly into the compound. Fasten the RTD to
the pipe with the included stretch tape.
5. Route the RTD cables back to the TFX flow meter. If the
cables are not long enough to reach the TFX, route the cables to an electrical junction box and add additional cable from that point. Use 3-wire shielded cable, such as Belden 9939 or equal, for this purpose.
6. Secure the RTD cable so that it will not be pulled on or
inadvertently abraded.
7. Replace the insulation on the pipe, ensuring that the RTD is
not exposed to air currents.
Rev. 5/09 - 2.18 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Figure 2.13 — Surface Mount RTD Installation
Insertion RTD Installation
Insertion RTD Installation
Insertion RTDs are typically installed through 1/4" compression fittings and isolation ball valves.
1. It is recommended that insertion RTDs be mounted
downstream of the flow measurement transducers to avoid causing flow instability in the flow measurement region.
2. Insert the RTD into the flow stream so that a minimum of
0.25" of the probe tip extends into the pipe. See Figure 2.14 on page 2.20.
3. RTDs should be mounted within ±45 degrees of the side of a
horizontal pipe. See Figure 2.15 on page 2.20. On vertical pipes the orientation is not critical.
4. Route the RTD cables back to the TFX flow meter. If the
cables are not long enough to reach the TFX, route the cables to an electrical junction box and add additional cable from that point. Use 3-wire shielded cable, such as Belden 9939 or equal, for this purpose.
5. Secure the RTD cable so that it will not be pulled on or
inadvertently abraded.
Rev. 5/09 - 2.19 - TFXP
PART 2 - TRANSDUCER & RTD INSTALLATION
Figure 2.14 — Insertion RTD Installation
Figure 2.15 — Insertion RTD Orientation - Horizontal Pipes
Rev. 5/09 - 2.20 - TFXP
PART 3 - STARTUP AND CONFIGURATION
Before Starting the Instrument
Instrument Startup
NOTE: The TFX flow meter system requires a full pipe of liquid before a successful startup can be completed. Do not attempt to make adjustments or change configurations until a full pipe is verified.
NOTE: If Sonotemp® silicone grease was utilized as a couplant, a curing time is not required. However, if Dow 732 or another permanent RTV was used, the adhesive must fully cure before power is applied to the instrument.
Procedure:
1. Verify that all wiring is properly connected and routed as described previously in this manual.
2. Verify that the transducers are properly mounted as described in Part 2 of this manual.
3. Press the ON button to the right of the keypad. The TFX display backlighting will illuminate along with the “On” LED and the software version number will appear on the display.
The display backlighting illuminates for approximately 30 seconds and automatically turns off to preserve battery power. To re­illuminate the display, press any key on the keyboard. Adjustments to the backlighting duration can be made in the Display Menu. Refer to page 3.40 for details.
4. Confirm that Signal Strength is greater than 5%. If it is not, verify that proper transducer mounting methods and liquid/pipe characteristics have been entered. The pipe must be full of liquid in order to make this measurement.
5. Once the meter is properly operating (proper signal strength has been achieved), refer to the later portions of this manual section for additional programming features.
Rev. 5/09 -3.1- TFXP
PART 3 - KEYPAD CONFIGURATION
General
Keypad Operation
After installation of the transducers and connection of appropriate cabling to the TFX, keypad configuration of the instrument can be performed. All entries are saved in non-volatile FLASH memory and will be retained in the event of power loss.
The TFX can be configured through the keypad interface or by using the ULTRALINK™ Windows® compatible software utility. (See Part 4 of this manual for software details.) Of the two configuration methods, the ULTRALINK™ software utility provides more advanced features and offers the ability to store and transfer meter configurations between TFX meters.
The keypad consists of the following:
On key with LED indicator for turning the TFX on — Off key for turning the TFX off.
Two “Soft Keys” that change function depending on the operation being performed.
Up ˄ arrow key for scrolling up a list or incrementing a numeric entry.
Down ˅ arrow key for scrolling down a list or decrementing a numeric entry.
Up/Down arrow keys are also used to adjust the display contrast in Run Mode.
Numeric keys for entering numeric values.
Figure 3.1 —
Graphics Display
and Keypad
Rev. 5/09 -3.2- TFXP
PART 3 - KEYPAD CONFIGURATION
“Soft Key” menu items will be displayed immediately above the two keys located in the lower corners of the graphics display. See Figure 3.1 on page 3.2.
Soft key functions can be any of the following:
The MENU soft key places the meter into Programming mode from Run mode.
The ACK soft key is used to Acknowledge a condition that requires user intervention.
The ACCEPT soft key is used to Accept configuration parameter changes.
The CANCEL soft key returns the user to the next highest menu level without making any changes.
The EDIT soft key allows users to make changes to the current menu items.
The EXIT soft key is used to return to the next highest menu level.
Graphics Display Configuration
The SELECT soft key is used in conjunction with the arrow keys to choose the parameters to be displayed on the graphics display.
Each display line is independently configurable to show any of the following menu items:
Rate (Forward Only) Total (Net Only) Sound Speed FPS Sound Speed MPS SIGNAL STR (Signal Strength) Temp 1 (Heat Flow Option Required) Temp 2 (Heat Flow Option Required) Temp DIFF (Heat Flow Option Required)
The TFXP display can be set up to show 2 lines with large numerals (17 pixels high) or 4 lines with small numerals (9 pixels high). The number of display lines can be toggled between 2 and 4 using the commands in the Display Menu (Menu # 8). Refer to page 3.39 for details.
Rev. 5/09 -3.3- TFXP
PART 3 - KEYPAD CONFIGURATION
Figure 3.2 — 2 Line vs 4 Line Display
In the RUN mode pressing the SELECT soft key highlights one of the display lines. Successively pressing the SELECT soft key cycles through all of the display lines. Use the UP/DOWN arrow keys to select desired parameter. When the correct choice is shown, press the SELECT soft key once again to lock in the choice.
If changes to any configuration parameters have been made, the user will be prompted with a SAVE? YES when returning to RUN mode.
Display Contrast
Menu Structure
Rev. 5/09 -3.4- TFXP
The UP/DOWN arrow keys are also used to adjust the display contrast level. In RUN mode pressing the up arrow key increases the contrast and pressing the down arrow decreases the contrast.
The eight menus used in the structure of the TFXP are as follows:
1. Basic Menu – The Basic operations menu contains all of the configuration parameters necessary to program the meter to measure flow.
2. Datalog Operation – Datalog Operation configures the data logging location, logger interval and logging duration.
3. Datalog Maintenance – Datalog Maintenance allows data logger files to be erased from the logger.
4. Output 2 Menu – Output 2 menu configures the type and operating parameters of the 4-20 mA or other ISO-MOD located internally in the TFXP flow meter.
Units Selection
PART 3 - KEYPAD CONFIGURATION
5. Sensor Menu – The Sensor menu is used to select the sensor type (i.e. DTTN, DTTH, etc.)
6. Security Menu – The Security menu is utilized for resetting totalizers, resetting the operating system and revising security passwords.
7. Service Menu – The Service menu contains system settings that are used by service personnel for troubleshooting.
8. Display Menu – The Display menu is used to configure meter display functions.
The following sections define the configuration parameters located in each of the menus.
1. BSC MENU -- BASIC MENU
The BASIC Menu contains all of the configuration parameters necessary to make the TFX operational.
UNITS (Choice)
1. Englsh
2. Metric
Installs a global measurement standard into the memory of the instrument. The choices are either English or Metric units.
Select Englsh if all configurations (pipe sizes, etc.) are to be
made in inches. Select Metric if the meter is to be configured in millimeters.
The ENGLSH/METRIC selection will also configure the TFX
to display sound speeds in pipe materials and liquids as either feet per second or meters per second, respectively.
IMPORTANT!
Rev. 5/09 -3.5- TFXP
NOTE: If the UNITS entry has been changed from Englsh to Metric or from Metric to Englsh, the entry must be saved and the
instrument reset (power cycled or System Reset entered) in order for the TFX to initiate the change in operating units. Failure to save and reset the instrument will lead to improper transducer spacing calculations and an instrument that may not measure properly.
PART 3 - KEYPAD CONFIGURATION
Transducer Mounting Method
Pipe Diameter
Pipe Wall Thickness
XDCR MNT -- Transducer Mounting Method (Choice)
1. V
2. W
3. Z
Selects the mounting orientation for the transducers. The selection of an appropriate mounting orientation is based on pipe and liquid characteristics. See Part 2 – Transducer & RTD Installation in this manual.
PIPE OD -- Pipe Outside Diameter Entry (Value)
1. ENGLSH (Inches)
2. METRIC (Millimeters)
Enter the pipe outside diameter in inches if Englsh was selected as Units; in millimeters if Metric was selected.
PIPE WT -- Pipe Wall Thickness Entry (Value)
1. ENGLSH (Inches)
2. METRIC (Millimeters)
Enter the pipe wall thickness in inches if Englsh was selected as Units; in millimeters if Metric was selected.
Pipe Material
Rev. 5/09 -3.6- TFXP
PIPE MAT -- Pipe Material Selection (Choice)
1. Acrylic (ACRYLIC)
2. Aluminum (ALUMINUM)
3. Brass [Naval] (BRASS)
4. Carbon Steel (CARB ST)
5. Cast Iron (CAST IRN)
6. Copper (COPPER)
7. Ductile Iron (DCTL IRN)
8. Fiberglass-Epoxy (FBRGLASS)
9. Glass Pyrex (PYREX)
10. Nylon (NYLON)
11. HD Polyethylene (HDPE)
12. LD Polyethylene (LDPE)
13. Polypropylene (POLYPRO)
14. PVC CPVC (PVC/CPVC)
15. PVDF (PVDF)
PART 3 - KEYPAD CONFIGURATION
16. St Steel 302/303 (SS 303)
17. St Steel 304/316 (SS 316)
18. St Steel 410 (SS 410)
19. St Steel 430 (SS 430)
20. PFR (PFR)
21. Titanium (TITAMN)
22. Other (OTHER)
This list is provided as an example. Additional pipe materials may have been added. Select the appropriate pipe material from the list or select Other if the material is not listed.
Pipe Sound Speed
PIPE SS -- Speed of Sound in the Pipe Material (Value)
1. ENGLSH (Feet per Second)
2. METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the pipe wall. If the Units value was set to Englsh, the entry is in FPS (feet per second). Metric entries are made in MPS (meters per second).
If a pipe material was chosen from the Pipe Mat list, a nominal value for speed of sound in that material will be automatically loaded. If the actual sound speed rate is known for the application piping system and that value varies from the automatically loaded value, the value can be revised.
Linear RMS measurement, pipe internal wall surface
PIPE R
If Other was chosen as Pipe Mat, a Pipe SS will need to be entered.
=
Internal Diameter of the pipe
Pipe Roughness
Rev. 5/09 -3.7- TFXP
PIPE R -- Pipe Material Relative Roughness (Value)
Unitless
The TFX provides Reynolds number compensation in its flow measurement calculation. The ratio of average surface imperfection as it relates to the pipe internal diameter is used in this compensation algorithm.
PART 3 - KEYPAD CONFIGURATION
If a pipe material was chosen from the Pipe Mat list, a nominal value for relative roughness in that material will be automatically loaded. If the actual roughness is known for the application piping system and that value varies from the automatically loaded value, the value can be revised.
If Other was chosen as Pipe Mat, a Pipe R must also be entered.
Liner Thickness
Liner Material
LINER T -- Pipe Liner Thickness Entry (Value)
1. ENGLSH (Inches)
2. METRIC (Millimeters)
If the pipe uses a liner, enter the pipe liner thickness. Enter this value in inches if Englsh was selected as Units; in millimeters if Metric was selected.
If a Liner thickness was entered a liner material must then also be chosen along with the liner materials sound speed.
[If a LINER Thickness was selected] LINER MAT -- Liner Material (Choice)
1. Ebonite (EBONITE)
2. Mortar (MORTAR)
3. HD Polyethylene (HDPE)
4. LD Polyethylene (LDPE)
5. Polypropylene (POLYPRO)
6. Polystyrene (POLYSTY)
7. Rubber (RUBBER)
8. Tar Epoxy (TAR EPXY)
9. Teflon (TEFLON)
10. Other (OTHER)
This list is provided as an example. Additional materials may have been added. Select the appropriate material from the list or select Other if the liner material is not listed.
If Other was chosen as Liner Mat, a Liner SS must also be entered.
Rev. 5/09 -3.8- TFXP
PART 3 - KEYPAD CONFIGURATION
Liner Sound Speed
Fluid Type
LINER SS -- Speed of Sound in the Liner (Value)
1. ENGLSH (Feet per Second)
2. METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the liner. If the Units value was set to Englsh, the entry is in FPS (feet per second). Metric entries are made in MPS (meters per second).
If a liner was chosen from the Liner Mat list, a nominal value for speed of sound in that media will be automatically loaded. If the actual sound speed rate is known for the pipe liner and that value varies from the automatically loaded value, the value can be revised.
FL TYPE -- Fluid/Media Type (Choice)
1. Water Tap (WATER)
2. Sewage (SEWAGE)
3. Acetone (ACETONE)
4. Alcohol (ALCOHOL)
5. Ammonia (AMMONIA)
6. Benzene (BENZENE)
7. Brine (BRINE)
8. Ethanol (EHTANOL)
9. Ethylene Glycol (ETH-GLYC)
10. Gasoline (GASOLINE)
11. Glycerin (GLYCERIN)
12. Isopropyl Alcohol (ISO-ALC)
13. Kerosene (KEROSENE)
14. Methanol (METHANOL)
15. Oil Diesel (DIESEL)
16. Oil Hydraulic (HYD OIL) [Petro-based]
17. Oil Lubricating (LUBE OIL)
18. Oil Motor (MTR OIL) [SAE 20/30]
19. Water Distilled (WATR-DST)
20. Water Sea (WATR-SEA)
21. Other (OTHER)
This list is provided as an example. Additional fluid types may have been added. Select the appropriate liquid from the l Other if the liquid is not listed.
ist or select
Rev. 5/09 -3.9- TFXP
PART 3 - KEYPAD CONFIGURATION
Fluid Sound Speed
FLUID SS -- Speed of Sound in the Fluid (Value)
1. ENGLSH (Feet per Second)
2. METRIC (Meters per Second)
Allows adjustments to be made to the speed of sound in the liquid. If the Units value was set to Englsh, the entry is in FPS (feet per second). Metric entries are made in MPS (meters per second).
If a fluid was chosen from the Fl Type list, a nominal value for speed of sound in that media will be automatically loaded. If the actual sound speed is known for the application fluid and that value varies from the automatically loaded value, the value can be revised.
If Other was chosen as Fl Type, a Fluid SS will need to be entered. A list of alternate fluids and their associated sound speeds is located in the Appendix of this manual.
Fluid sound speed may also be found using the Target DBg Data screen available in the ULTRALINK™ software utility.
Fluid Viscosity
Fluid Specific Gravity
FLUID VI -- Absolute Viscosity the Fluid (Value in cP)
cP
Allows adjustments to be made to the absolute viscosity of the liquid.
If a fluid was chosen from the Fl Type list, a nominal value for viscosity in that media will be automatically loaded. If the actual viscosity is known for the application fluid and it varies from the automatically loaded value, the value can be revised.
If Other was chosen as Fl Type, a Fluid Vi will need to be entered. A list of alternate fluids and their associated viscosities are located in the Appendix of this manual.
SP GRVTY -- Fluid Specific Gravity Entry (Value)
Unitless
Allows adjustments to be made to the specific gravity (density) of the liquid.
Rev. 5/09 -3.10- TFXP
PART 3 - KEYPAD CONFIGURATION
If a fluid was chosen from the Fl Type list, a nominal value for specific gravity in that media will be automatically loaded. If the actual specific gravity is known for the application fluid and that value varies from the automatically loaded value, the value can be revised.
If Other was chosen as Fl Type, a Sp Grvty may need to be entered if mass flows are to be calculated. A list of alternate fluids and their associated specific gravities are located in the Appendix of this manual.
Fluid Specific Heat Capacity
SP HEAT -- Fluid Specific Heat Capacity (Value)
(only visible when RTD Module is activated)
Nominal Heat Capacity
Allows adjustments to be made to the specific heat capacity of the liquid.
If a fluid was chosen from the Fl Type list, a default specific heat will be automatically loaded. This default value is displayed as Sp Heat in the Basic Menu. If the actual specific heat of the liquid is known or it differs from the default value, the value can be revised. See Tables 3.1, 3.2, 3.3 and 3.4 on pages 3.11 and 3.12 for specific values. Enter a value that is the mean of both pipes.
Temperature °F Temperature °C Specific Heat BTU/lb °F
32-212 0-100 1.00
250 121 1.02 300 149 1.03 350 177 1.05
Table 3.1 — Specific Heat Capacity Values for Water
Rev. 5/09 -3.11- TFXP
PART 3 - KEYPAD CONFIGURATION
Temperature Ethylene Glycol Solution (% by Volume)
°F °C 25 30 40 50 60 65 100
-40 -40 n/a n/a n/a n/a 0.68 0.70 n/a 0 -17.8 n/a n/a 0.83 0.78 0.72 0.70 0.54
40 4.4 0.91 0.89 0.845 0.80 0.75 0.72 0.56 80 26.7 0.92 0.90 0.86 0.82 0.77 0.74 0.59
120 84.9 0.93 0.92 0.88 0.83 0.79 0.77 0.61 160 71.1 0.94 0.93 0.89 0.85 0.81 0.79 0.64 200 93.3 0.95 0.94 0.91 0.87 0.83 0.81 0.66 240 115.6 n/a n/a n/a n/a n/a 0.83 0.69
Specific Heat Capacity BTU/lb °F
Table 3.2 — Specific Heat Capacity Values
for Ethylene Glycol/Water
Polypropylene Glycol Solution (% by Volume)
0 10 20 30 40 50 60
1.00 0.98 0.96 0.94 0.90 0.85 0.81
Specific Heat Capacity BTU/lb °F
Table 3.3 — Specific Heat Capacity Values
for Propylene Glycol/Water
Fluid
Alcohol, ethyl 32 0 0.65
Alcohol, methyl 54 12 0.60
Brine 32 0 0.71 Brine 60 15 0.72
Sea Water 63 17 0.94
Temperature
°F
Temperature
°C
Specific Heat BTU/lb °F
Table 3.4 — Specific Heat Capacity Values
for Other Common Fluids
Rev. 5/09 -3.12- TFXP
PART 3 - KEYPAD CONFIGURATION
Transducer Spacing
XDCR SPAC -- Transducer Spacing Calculation (Value)
1. ENGLSH (Inches)
2. METRIC (Millimeters)
This value represents the one-dimensional linear measurement between the transducers (the upstream/downstream measurement that runs parallel to the pipe). This value is in inches if Englsh was selected as Units; in millimeters if Metric was selected. This measurement is taken between the alignment marks which are scribed into the sides of the transducer blocks. See Figure 3.3.
Figure 3.3 —
Transducer
Alignment Marks
If the transducers are being mounted using a transducer track assembly, a measuring scale is etched into the track. Using the alignment marks, place one transducer at 0 and the other at the appropriate measurement.
Figure 3.3 — Mounting Track Spacing
Engineering Units RATE
Rev. 5/09 -3.13- TFXP
RATE UNT -- Engineering Units for Flow Rate (Choice)
1. Gallons (GALLONS)
2. Liters (LITERS)
3. Millions of Gallons (MGAL)
4. Cubic Feet (CUBIC FT)
5. Cubic Meters (CUBIC ME)
6. Acre Feet (ACRE FT)
7. Oil Barrels (OIL BARR) [42 Gallons]
PART 3 - KEYPAD CONFIGURATION
8. Liquid Barrels (LIQ BARR) [31.5 Gallons]
9. Feet (FEET)
10. Meters (METERS)
11. Pounds (LB)
12. Kilograms (KG)
13. British Thermal (BTU) Units
14. Thousands of BTUs (MBTU)
15. Millions of BTUs (MMBTU)
16. Tons (TON)
Select a desired engineering unit for flow rate measurements.
Engineering Units RATE INTERVAL
Engineering Units TOTALIZER
RATE INT -- Time Interval for Flow Rate (Choice)
1. Seconds (SEC)
2. Minutes (MIN)
3. Hour (HOUR)
4. Day (DAY)
Select a desired engineering unit for flow rate measurements.
TOTL UNT -- Engineering Units for Flow Totalizer (Choice)
1. Gallons (GALLONS)
2. Liters (LITERS)
3. Millions of Gallons (MGAL)
4. Cubic Feet (CUBIC FT)
5. Cubic Meters (CUBIC ME)
6. Acre Feet (ACRE FT)
7. Oil Barrels (OIL BARR)
[42 Gallons]
8. Liquid Barrels (LIQ BARR) [31.5 Gallons]
9. Feet (FEET)
10. Meters (METERS)
11. Pounds (LB)
12. Kilograms (KG)
13. British Thermal (BTU)
Units
12. Thousands of BTUs (MBTU)
Rev. 5/09 -3.14- TFXP
PART 3 - KEYPAD CONFIGURATION
13. Millions of BTUs (MMBTU)
14. Tons (TON)
Select a desired engineering unit for flow accumulator (totalizer) measurements.
Engineering Units TOTAL Exponent
TOTL E -- Flow Totalizer Exponent Value (Choice)
E-1 to E6
Utilized for setting the flow totalizer exponent. This feature is useful for accommodating a very large accumulated flow. The exponent is a ×10n multiplier, where "n" can be from -1 (×0.1) to +6 (×1,000,000). Table 3.5 should be referenced for valid entries and their influence on the TFX display.
Exponent Display Multiplier E-1 E0 E1 E2
E3 E4
E5
× 0.1 × 1 (no multiplier) × 10 × 100
× 1,000 × 10,000
× 100,000
E6
Table 3.5 — Totalizer Exponent Values
Minimum Flow Rate
Rev. 5/09 -3.15- TFXP
MIN RATE -- Minimum Flow Rate Settings (Value)
Rate Unit/Rate Interval
A minimum volumetric flow rate setting is entered to establish filter software settings. Volumetric entries will be in the Engineering Rate Units and Interval selected on pages 3.13 and 3.14. For unidirectional measurements, set Min Rate to zero. For bi­directional measurements, set Min Rate to the highest negative (reverse) flow rate expected in the piping system.
× 1,000,000
PART 3 - KEYPAD CONFIGURATION
Maximum Flow Rate
Low Flow Cut-off
MAX RATE -- Maximum Flow Rate Settings (Value)
Rate Unit/Rate Interval
A maximum volumetric flow rate setting is entered to establish filter software settings. Volumetric entries will be in the Engineering Rate Units and Interval selected on pages 3.13 and 3.14. Set Max Rate to the highest (positive) flow rate expected in the piping system.
FL C-OFF -- Low Flow Cut-off (Value)
Percent of the range between MIN RATE and MAX RATE Relative Percent Entry: 0-100%
A Low Flow Cut-off entry is provided to allow very low flow rates (that can be present when pumps are off and valves are closed) to be displayed as zero flow. Typical values that should be entered are between 1.0% and 5.0% of the flow range between Min Rate and Max Rate.
Generally a Low Flow Cutoff value that equates to a velocity of 0.5 fps is a good starting point. For example, using a 4" pipe and a maximum flow of 500 GPM, the volumetric flow at 0.5 fps is about 20 GPM. 20 GPM is 4% of the 500 GPM maximum so the Low Flow Cutoff should be set to 4.
System Damping
Rev. 5/09 -3.16- TFXP
DAMP PER -- System Damping (Value)
Relative Percent Entry: 0-100%
Flow Filter Damping establishes a maximum Under stable flow conditions (flow varies less than 10% of reading), this adaptive filter will increase the number of successive flow readings that are averaged together up to this maximum value. If flow changes outside of the 10% window, the flow filter adapts by decreasing successive flow readings and allows the meter to react faster. Increasing this value tends to provide smoother steady-state flow readings and outputs. If erratic flow conditions are present or expected, more advanced filters are available for use in the ULTRALINK™ software utility. See Part 4 for further information.
adaptive filter value.
PART 3 - KEYPAD CONFIGURATION
ISO-MOD: Data Logger Module (Optional)
I/O module bay number 1 is reserved exclusively for the ISO Data Logger module.
The 200,000 event data logger/electronic stripchart recorder can be configured to match most user applications. The logger stores time­stamped, high resolution (16-bit) data at user selected intervals ranging from 1 to 30,000 (8.33 hours) second(s).
The module can be carried in a shirt pocket back to the office and plugged into an RS232 serial port via the module’s integral DB-9 connector. This eliminates the requirement to carry a computer to the installation site. The data in the logger can also be accessed without removing the module from the flow meter. Open the door of the flow meter and connect the 9-pin cable between the data logger and the PC’s RS232 serial communications port.
Figure 3.5 —
Data Logger Location
NOTE: Not all serial ports have the same load capabilities. If the data logger is not accessible, the problem may be inadequate power from the serial port. In these instances an external power supply, available from Dynasonics, is required.
The logger is capable of storing up to 200,000 measurements. The measurements are broken into 16 locations or pages with a maximum number of data points per location of 30,000.
If each location (page) is filled to the maximum then 6 2/3 locations would be used.
If all 16 locations are to be used, each location could hold a maximum of 12,500 data points.
Rev. 5/09 -3.17- TFXP
PART 3 - KEYPAD CONFIGURATION
NOTE: The logger will not automatically go to the next location if the previous location is filled. In this case when the location exceeds 30,000 data points the oldest points will be discarded in favor of new points. This is the classic FIFO memory stack.
Up to 16 separate logging sessions are possible with up to 12,500 points each but for each new measurement session the logger must be stopped, a new page selected using the keypad or data logger utility, and then the logging must be started again. Similarly if a single data acquisition session were to exceed 30,000 points the logger must be stopped, a new location selected using the keypad or data logger utility, and then the logging must be started again.
NOTE: The data logger is not accessible using the TFX’s infrared adapter. Communications between the data logger and computer must be established using a directly connected RS232C or RS485 connection.
NOTE: If the data logger is accessed during a logging session the logger will stop logging as soon as the data retrieval is started. The logger must be started again when the retrieval process is complete.
NOTE: The flow meter must be on to supply power to the data logger if information is to be retrieved while the logger is still installed.
2. DATALOG OPERATION MENU
Data Logger Configuration
File Number or Location
Rev. 5/09 -3.18- TFXP
DATALOG PRESENT -- Datalog Present (Choice)
1. Yes
2. No
The TFX must be “told” the data logger is present before any data can be collected.
DATALOG LOC -- Datalog Location (Value)
1 to 16
PART 3 - KEYPAD CONFIGURATION
Logging Interval
DATALOG INT -- Datalog Interval (Value) ((Sec))
1 to 30,000
From the Datalog Operation menu, adjust the time Interval between readings. Interval values between 1 and 30,000 seconds are acceptable.
For reference there are:
60 seconds in 1 minute 300 seconds in 5 minutes 1,800 seconds in 30 minutes 3,600 seconds in 1 hour 30,000 seconds in 8.33 hours
Table 3.6 on page 3.20 describes some typical configurations of the Interval and Duration times with what the expected data samples
collected count will be.
NOTE: Data points are collected continuously but written to the logger at fixed 1 minute intervals. If logging is stopped during the first minute of operation the logger will not have any stored values. Whenever the logger is stopped, values for the minute previous to the logger being stopped will be lost.
Logging Duration
Rev. 5/09 -3.19- TFXP
DATALOG DUR -- Datalog Duration (Value) ((Hours))
1 to 30,000
If the TFXP is going to be left unattended logging flow data for extended periods of time, the Duration time can be configured to stop logging after the Duration of time has passed. Duration is configured in hours and values between 1 and 30,000 hours are acceptable.
The Datalog software utility and the serial DB-9 interface cable included with the logger can be used to access the data. Connect the male end of the cable to the logger, which is located in the pocket on the faceplate of the instrument. See Figure 3.5 on page 3.17. The female end is plugged into an RS232 serial port on a Windows logger is then accessed using the Datalog utility that is loaded automatically with the ULTRALINK™ software utility.
®
co mpatib le PC. The data stored in the data
PART 3 - KEYPAD CONFIGURATION
Example No.
INTERVAL
Seconds
DURATION
Hours
Operated
Samples
Collected
1 1 6 21,600 2 10 72 (3 days) 25,920 3 60 (1 min) 480 (20 days) 28,800 4 300 (5 min) 2,016 (12 wks) 24,192 5 1,800 (30 min) 8,760 (1 yr) 17,520 6 3,600 (1 hr) 8,760 (1 yr) 8,760 7 18,000 (5 hr) 26,280 (3 yr) 17,520
Table 3.6 — Logging Interval and Duration Times
Also included with the data logging package is a stand-alone power supply for use when the data logger is not installed in the TFXP. Most RS232C serial ports do not supply enough power to enable data retrieval from the data logger module. When accessing data stored in the logger without it being connected to the TFXP, this special power supply should be used.
Figure 3.6 —
Data Logger
Power Supply
See Part 4 for details regarding operation of the Data Logger and the ULTRALINK™ software utility.
Rev. 5/09 -3.20- TFXP
PART 3 - KEYPAD CONFIGURATION
3. DATALOG MAINTENANCE
Datalog Maintenance permits files to be deleted from the data logger module. The menu contains three options for deleting files.
Erase All (Choice)
1. Yes
2. No
Deletes all files stored in the data logger.
Erase First (Choice)
1. Yes
2. No
Deletes the first file generated. This would be the oldest file in the loggers memory.
Start Data Logger
Erase Last (Choice)
1. Yes
2. No
Deletes the last file generated. This would be the newest file in the loggers memory.
To Start the Data Logger
1. From the RUN mode data screen press the MENU soft key.
2. Use the UP/DOWN arrow keys to highlight 2.Datalog Operation and press SELECT soft key. The display will say “Datalog Present - Yes”.
NOTE: The TFX does not automatically detect if a data logger is present. The firmware will allow selection of “Datalog Present - Yes” and “Datalog – Start Datalog – Yes” without a data logger being installed. Always check the data logger pocket on the TFXP front panel to be sure a logger is present.
3. Select the Datalog Location ID number shown or using the UP/ DOWN arrow keys choose another number between 1 and 16.
Rev. 5/09 -3.21- TFXP
PART 3 - KEYPAD CONFIGURATION
This number will appear in the “Name” column on the computer screen before data is downloaded.
NOTE: The firmware will accept any Datalog Location number between 1 and 30,000 however only 1 thru 16 are valid locations.
4. Accept Datalog Interval number shown or choose another number between 1 and 30,000 seconds as the logging interval. Use the UP/DOWN arrow keys to change the logging interval values.
5. Choose a Datalog Duration between 1 and 30,000. This value is in hours. To change the duration value use the UP/DOWN arrow keys.
6. Press EXIT. The display will ask “Datalog Start Datalog?” Start the logging session by pressing the YES soft key. The display will return automatically to the Menu screen.
7. Press EXIT to return to Data Display Screen.
Confirm Data Logger Operation
Stop Data Logger
To Confirm that Data Logger is Running
1. From the RUN mode data screen press the MENU soft key
2. Use the UP/DOWN arrow keys to highlight 2.Datalog Operation and press SELECT soft key. The display will say “Datalogger is Running”.
3. Press CANCEL, then EXIT, to return to the data screen.
To Stop Data Logger
1. From the RUN mode data screen press the MENU soft key.
2. Use the UP/DOWN arrow keys to highlight 2.Datalog Operation and press SELECT soft key. The display will say “Datalogger is Running”.
3. Press STOP. Indicator will say “Stop Datalog Are you sure?”.
4. Press YES - takes you back to Menu Screen.
5. Press EXIT to return to Data Screen.
Rev. 5/09 -3.22- TFXP
PART 3 - KEYPAD CONFIGURATION
NOTES:
Data logger must be stopped before downloading data. If data logger is not stopped before downloading data, an erroneous file will be recorded on the data logger.
The serial cable should not be connected to the data logger while data logger is running. If the serial cable is connected to the data logger while data logger is running, error message 3007 will appear on the display and data will be lost.
When using the DataLink software utility on your computer, the important column is the one entitled “points”. This column shows the number of points recorded. For example, if 10 seconds is chosen for Interval and 2 hours is chosen for Duration, the number of points would be:
6 points per minute × 120 minutes = 720 data points. Files will save to a Microsoft Excel® spreadsheet by highlighting
the file and clicking the “Save” icon. The Save command saves the file as a Comma Separated Value (.csv) file, not an *.xls. CSV files are directly importable into Microsoft Excel®.
The operator must be disciplined about stopping, selecting a new memory block, and restarting the logger or data may be lost. To avoid losing data, the operator may want to use only one location to log. After the logging session is complete, move the data to an Excel® spread sheet via a computer, delete the data on the data logger, then start fresh if a new session is required. This normally will prevent losing important data because it has already been stored on a computer.
Rev. 5/09 -3.23- TFXP
PART 3 - KEYPAD CONFIGURATION
4. OUTPUT 2 MENU
The second I/O bay is internal to the TFXP and can perform a number of different functions depending on the ISO Module installed. The following is a list of the current options and their menu designations.
OUT2 MEN -- OUTPUT #2 MENU (Choice)
1. 4-20 mA Output (4-20MA)
2. Rate (RATE)
3. Relay (RELAY)
4. Heat Flow (RTD)
5. RS232C Communications (RS232)
6. RS485 Communications (RS485)
Depending on the I/O module installed there will be connections specific to that output on the side of the TFXP.
ISO-MOD: 4-20 mA Module (Optional)
4-20MA -- 4-20 mA Output (Values)
1. Flow at 4 mA (FL 4MA)
2. Flow at 20 mA (FL 20MA)
3. 4 mA Calibration (CAL 4MA)
4. 20 mA Calibration (CAL 20MA)
5. 4-20 mA Test (4-20 TST)
Figure 3.7 — 4-20 mA Output Connection
Rev. 5/09 -3.24- TFXP
PART 3 - KEYPAD CONFIGURATION
Figure 3.8 — 4-20 mA Output Wiring
The 4-20 mA output can be configured to source current (internally powered) or sink current (externally powered). The choice of sink or source is configured at the factory to source current unless otherwise instructed at the time the TFX is ordered.
The 4-20 mA output module interfaces with virtually all recording and logging systems by transmitting an analog current that is proportional to system flow rate.
Independent 4 mA and 20 mA span settings are established in software using the Flow range entries. These entries can be set to
-40
to
+40
any flow values equivalent to the pipe the instrument is measuring. Output resolution of the module is 12-bits (4096 discrete points) and the module can drive up to 850 Ohms of load with its internal 24 VDC isolated power source.
Internal Power Configuration (Current Source): This is the factory default condition for the 4-20 mA output. In this configuration the 4-20 mA output is driven from a +24 VDC source located within the flow meter. The 24 VDC source is isolated from DC ground and earth ground connections.
FPS (-12 to +12 MPS) for
Rev. 5/09 -3.25- TFXP
PART 3 - KEYPAD CONFIGURATION
External Power Configuration (Current Sink): If the 4-20 mA output module was ordered from the factory for external power the 4-20 mA module requires power from an external DC power supply. The voltage of the external power source must be sufficient to power the module and drive the loop load. The loop loss attributed to the ISO-MOD is 7 VDC, so the minimum voltage required to power a loop can be calculated using the following formula:
Loop Voltage (minimum) = (loop load Ohms × 0.02) + 7
Figure 3.9 — Loop Load Chart
4-20 mA Span
Rev. 5/09 -3.26- TFXP
The FL 4MA and FL 20MA entries are used to set the span of the 4-20 mA analog output. These entries are volumetric rate units that are equal to the volumetric units configured as Engineering Rate Units and Engineering Units Rate Interval discussed on pages 3.13 and 3.14.
PART 3 - KEYPAD CONFIGURATION
Example 1: To span the 4-20 mA output from -100 GPM to +100 GPM, with 12 mA being 0 GPM, set the FL 4MA and FL 20MA inputs as follows:
FL 4MA = -100.0 FL 20MA = 100.0
Example 2: To span the 4-20 mA output from 0 GPM to +100 GPM, with 12 mA being 50 GPM, set the FL 4MA and FL 20MA inputs as follows:
FL 4MA = 0.0 FL 20MA = 100.0
The 4-20 mA ISO-MOD is factory calibrated and should not require adjustment unless it is replaced.
4-20 mA Calibration
The CAL 4MA entry allows fine adjustments to be made to the “zero” of the 4-20 mA output. To adjust the 4 mA output, an ammeter or reliable reference connection to the 4-20 mA output must be present.
Figure 3.10 — Typical Multimeter Connection
Rev. 5/09 -3.27- TFXP
PART 3 - KEYPAD CONFIGURATION
NOTE: The CAL 4MA and CAL 20MA entries should not be used in an attempt to set the 4-20 mA range. Utilize the FL 4MA and FL 20MA, detailed on page 3.26, for this purpose.
Procedure:
1. Disconnect any wires presently connected to the spring clips on the end of the 4-20 mA output cable. Connect the ammeter in series with the spring clips on the end of the 4-20 mA output cable.
NOTE: Be sure to connect the multimeter test leads for current measurement. If necessary consult the mulitmeters instruction manual for the correct procedure to perform a current measurement.
2. Using the UP/DOWN arrow keys, increase the numerical value to increase the current in the loop to 4 mA. Decrease the value to decrease the current in the loop to 4 mA. Typical values range between 40-80 counts.
3. Reconnect the 4-20 mA output circuitry as required.
Calibration of the 20 mA setting is conducted much the same way as the 4 mA adjustments.
Procedure:
1. Disconnect any wires presently connected to the spring clips on the end of the 4-20 mA output cable. Connect the ammeter in series with the spring clips on the end of the 4-20 mA output cable.
NOTE: Be sure to connect the multimeter test leads for current measurement. If necessary consult the mulitmeters instruction manual for the correct procedure to perform a current measurement.
2. Using the UP/DOWN arrow keys, increase the numerical value to increase the current in the loop to 4 mA. Decrease the value to decrease the current in the loop to 4 mA. Typical values range between 3700 - 3900 counts.
3. Reconnect the 4-20 mA output circuitry as required.
Rev. 5/09 -3.28- TFXP
PART 3 - KEYPAD CONFIGURATION
4-20 mA Test
ISO-MOD: Rate Pulse Module (Optional)
4-20 TST -- 4-20mA Output Test
Allows a simulated value to be output from the 4-20 mA module. By incrementing this value, the 4-20 mA output will transmit the indicated current value.
NOTE: This test is only available when the 4-20 mA module is set up to source current.
The Rate Pulse Output Module is utilized to transmit information to external counters and PID systems via a frequency output that is proportional to system flow rate. Independent zero and span settings are established in software using the flow measuring range entries. Output resolution of the module is 12-bits (4096 points) and the maximum output frequency setting is 2,500 The pulse width is designed to give a 50% duty cycle. The module has two output modes, turbine meter simulation and “open collector”. The turbine meter simulation sources a non-ground referenced saw-tooth waveform with a maximum amplitude of approximately 500 mV p-p. The open collector output utilizes a 0.21 Ohm FET output that is rated to operate at 100 V and 1 A maximum. If the open collector output is utilized, an external voltage source and limit resistor must be present.
discrete
Hz.
RATE -- Rate Pulse (Value)
1. Flow at 0 Hz (FL 0H)
2. Flow at 2.5k Hz (FL 25KH)
The
FL 0H
0 to
2.5k Hz frequency output. These entries are volumetric rate units that are equal to the volumetric units configured as Engineering Rate Units and Engineering Units Rate Interval entered on pages 3.13 and 3.14.
Example 1: In a bi-directional system, to span the 0 to 2.5k Hz output from -100 GPM to +100 GPM, with 1.25k Hz being 0 GPM, set the FL 100H and FL 25KH inputs as follows:
FL 0H = -100.0 FL 25KH = 100.0
Rev. 5/09 -3.29- TFXP
and
FL 25KH
entries are used to set the span of the
PART 3 - KEYPAD CONFIGURATION
Example 2: To span the 0 to 2.5k Hz output from 0 GPM to +100 GPM, with 1.25k Hz being 50 GPM, set the FL 0H and FL 25KH inputs as follows:
FL 0H = 0.0 FL 25KH = 100.0
K-Factor Programming
K-Factor Programming
If the device receiving the pulse output is capable of K-factor scaling, it is possible to use the rate pulse output in a totalizing function. See K-Factors Explained in the Appendix.
Figure 3.11 — Rate Pulse Output Wiring
Rev. 5/09 -3.30- TFXP
PART 3 - KEYPAD CONFIGURATION
ISO-MOD: Dual Relay Module (Optional)
RELAY -- Dual Relay (Choices and Values)
RELAY 1 AND RELAY 2
1. None (NONE)
2. Totalizer (TOTALIZE) a. Totalizer Multiplier (TOT MULT)
3. Flow (FLOW) a. On Setting (ON) b. Off Setting (OFF)
4. Signal Strength (SIG STR) a. On Setting (ON) b. Off Setting (OFF)
5. Errors (ERRORS)
Two independent SPDT (single-pole, double-throw) Form C relays are contained in this module. The relay operations are user configured via software to act in either a flow rate alarm, signal strength alarm, error alarm or totalizer/batching mode. Th e r e la ys are rated for 200 VAC maximum and a have current rating of
0.5 A resistive load (175 VDC @ 0.25 A resistive). It is highly recommended that a secondary relay be utilized whenever the dual relay module is used to control inductive loads such as solenoids and motors.
Figure 3.12 —
Typical Relay
Connections
Rev. 5/09 -3.31- TFXP
PART 3 - KEYPAD CONFIGURATION
Batch/Totalize Mode
Flow Rate Relay
Totalize mode configures the relay(s) to output a 50 mSec pulse (contact changeover) each time the display totalizer increments – divided by the Total Mult. The Total Mult value must be a whole, positive, numeric value.
Example 1: If the Totalizer Exponent is set to E0 (×1) and the Totalizer Multiplier is set to 1, then the relay will pulse each time the totalizer increments one count, or each single, whole measurement unit totalized.
Example 2: If the Totalizer Exponent is set to E2 (×100) and the Totalizer Multiplier is set to 1, then the relay will pulse each time the display totalizer increments or once per 100 measurement units totalized.
Example 3: If the Totalizer Exponent is set to E0 (×1) and the Totalizer Multiplier is set to 2, the relay will pulse once for every two counts that the totalizer increments.
Flow rate relay configuration permits relay changeover at two separate flow rates allowing operation with an adjustable switch deadband. Figure 3.13 illustrates how the setting of the two set points influences rate alarm operation.
A single-point flow rate alarm would place the ON> setting slightly higher than the OFF< setting – allowing a switch deadband to be established. If a deadband is not established, switch chatter (rapid switching) may result if the flow rate is very close to the switch point.
Figure 3.13 — Single Point Alarm Operation
Rev. 5/09 -3.32- TFXP
PART 3 - KEYPAD CONFIGURATION
Signal Strength Alarm
Errors Alarm Relay
ISO-MOD: RTD (Optional)
The Sig Str alarm will provide an indication that the flow meter signals between the transducers have fallen to a point where flow measurements may not be possible. It can also be used to indicate that the pipe has emptied. Like the flow rate alarm described on page 3.13, the signal strength alarm requires that two points be entered, establishing an alarm deadband. A valid switch point exists when the ON> is a value lower than OFF<. If a deadband is not established and the signal strength decreases to approximately the value of the switch point, the relay may chatter.
When a relay is set to Errors mode, the relay will activate when any error occurs in the flow meter that has caused the meter to stop measuring reliably. See the Appendix of this manual for a list of potential error codes.
RTD -- RTD (Value)
Calibration Value for:
1. RTD1 A (RTD1 A)
2. RTD1 B (RTD1 B)
3. RTD2 A (RTD2 A)
4. RTD2 B (RTD2 B)
Inputs from one or two 1000 Ohm RTD temperature sensors allows measurements of heat flow (one RTD) or heat usage (two RTDs).
The values used to calibrate the RTD temperature sensors are derived in the laboratory and are specific to an individual RTD. The RTDs on new units come already attached to the RTD Module and should not be changed.
Field replacement of RTDs without ISO module replacement is possible using ULTRALINK ™ . See Part 4.
Rev. 5/09 -3.33- TFXP
PART 3 - KEYPAD CONFIGURATION
Figure 3.14 — RTD Connections
ISO-MOD: RS232C Module (Optional)
RS232C -- RS232C (Choice)
Baud Rate (RS232 BA)
1. 1200 Baud (1200)
2. 2400 Baud (2400)
3. 9600 Baud (9600)
4. 19,200 Baud (19200)
The RS232C module can be interfaced with serial communication ports of PCs, PLCs and SCADA systems. This module runs a proprietary digital protocol, detailed in the Appendix of this manual, that is used to monitor flow rate information in piping systems. The RS232C module may also be used to form a hardwire connection to a PC that is running the ULTRALINK™ software utility. Baud rates up to 19.2k are supported.
Figure 3.15 —
RS232C and RS485
Connections
Rev. 5/09 -3.34- TFXP
PART 3 - KEYPAD CONFIGURATION
ISO-MOD: RS485 Module (Optional)
RS485 Mode
RS485 -- RS485 (Choices and Values)
RS485 Mode (RS485 MO)
1. Slave (SLAVE)
2. Master (MASTER)
Baud Rate (RS485 BA)
1. 1200 Baud (1200)
2. 2400 Baud (2400)
3. 9600 Baud (9600)
4. 19,200 Baud (19200)
Device Address (Addr) (1-127)
The RS485 module allows up to 126 TFX systems to be daisy­chained on a single three-wire cable network. Communications are through a proprietary digital protocol, detailed in the Appendix of this manual. All meters are assigned a unique one byte serial number that allows all of the meters on the cable network to be accessed independently. Baud rates up to 19.2k and cable lengths to 5,000 feet (1,500 meters) are supported without the need for repeaters.
RS485 MO
Select Slave for all of the TFX meters connected to the unit designated as Master.
RS485 Baud Rate
RS485 Address
Rev. 5/09 -3.35- TFXP
RS485 BA
Select a Baud rate that is compatible with the operating system.
ADDRESS
Each TFX connected on the communications bus must have a unique address number assigned. Address 127 is a universal address that will result in all TFX instruments on the network responding simultaneously – regardless of address – resulting in CRC errors. Only select address location 127 if one meter is on the network.
PART 3 - KEYPAD CONFIGURATION
Transducer Type
5. SEN MENU -- SENSOR MENU
The SEN MENU is utilized to select the type of transducer that will be interfaced with the TFX. Select the appropriate transducer from the list and save the configuration. If the transducer selection is modified, a system reset is required.
XDUCER TYP -- Transducer Type (Choices and Values)
1. DTTN Standard Transducers (DTTN Clamp-On)
2. DTTH High Temperature Transducers (DTTH Clamp-On)
3. DTT1500 (DTT 1500)
4. Small Pipe Copper (DTTSnC)
5. Small Pipe ANSI (DTTSnP)
6. Small Pipe Tubing (DTTSnT)
6. SEC MENU -- SECURITY MENU
Totalizer RESET
System RESET
The SEC MENU allows the user to make password revisions, reset the flow totalizer and reset the transmitter microprocessor.
TOT RES -- Totalizer Reset (Choice)
1. NO
2. YES
Select YES to reset all flow totalizers/accumulators to zero.
SYS RSET -- System Reset (Choice)
1. NO
2. YES
Select YES to initiate a microprocessor reset.
NOTE: All system configurations and totalizer values will be retained.
Rev. 5/09 -3.36- TFXP
PART 3 - KEYPAD CONFIGURATION
Change Password
Signal Strength Cutoff
CH PSWD? -- Change the Security Password (Value)
0-9999
By changing the Security Password from 0 to some other value (any value between 1 to 9999), configuration parameters will not be accessible without first entering that value when prompted. If the value is left at 0, no security is invoked and unauthorized changes could be made.
7. SER MENU -- SERVICE MENU
The SER MENU has features that allow adjustment of Low Signal Strength Cutoff, Error-Mode outputs, Zero Flow Rate Set and entry of a universal correction factor.
SIG C-OFF -- Low Signal Strength Cutoff (Value)
The Low Signal Strength Cutoff is used to drive the flow meter and its outputs to the Substitute Flow value if conditions occur that cause low signal strength to occur. A signal strength indication below 2% is inadequate for measuring flow reliably, so minimum setting for Low Signal Strength Cutoff is 2%. A good practice is to set the Low Signal Strength Cutoff at approximately 60-70% of actual measured signal strength (described above).
NOTE: The factory default “Low Signal Strength Cutoff” is 5%.
If the measured signal strength is lower than Low Signal Strength Cutoff setting, an ERROR 0010 will be appear on the TFX display until the measured signal strength becomes greater than the cutoff value.
Substitute Flow Entry
Rev. 5/09 -3.37- TFXP
SUB FLOW -- Substitute Flow (Value)
Substitute Flow is a value that the analog outputs and the rate display will indicate when an error condition in the flow meter occurs. The typical setting for this entry is a value that will make the instrument display zero flow during an error condition.
Table 3.8 on page 3.38 lists some typical settings to achieve “Zero” with respect to minimum and maximum rate settings.
PART 3 - KEYPAD CONFIGURATION
Factory Default Zero Calibration
MINIMUM
RATE SETTING
MAXIMUM
RATE SETTING
SUBSTITUTE
FLOW SETTING
DISPLAY
READING
DURING ERRORS
0.0 1,000.0 0.0 0.000
-500.0 500.00 50.0 0.000
-100.0 200.0 33.3 0.000
0.0 1,000.0 -5.0* -50.00
* NOTE: ULTRALINK™ is required to set values outside of 0.0 - 100.0.
Table 3.8 — Typical Zero Settings
SET ZERO -- Calibrating Zero Flow (Choice)
1. No
2. Yes
Because every flow meter installation is slightly different and sound waves can travel in slightly different ways through these various installations, it is important to remove the zero offset at zero flow to maintain the meter’s accuracy. A provision is made using this entry to establish “Zero” flow and eliminate the offset.
To zero the meter:
1. The pipe must be full of liquid.
2. Flow must be absolute zero – securely close any valves and
allow time for any settling to occur.
3. Press EDIT at the Set Zero prompt, use the arrow keys to make
the display read Yes.
4. Press ACCEPT. The procedure is complete.
Setting/ Calibrating Zero Flow
D-FLT 0 -- Setting a Zero Flow Point (Choice)
1. No
2. Yes
If the flow in a piping system cannot be shut off, allow the Set Zero procedure described above to be performed, then the default zero should be utilized. This procedure places an actual value of zero in
Rev. 5/09 -3.38- TFXP
PART 3 - KEYPAD CONFIGURATION
the meter. This is not as desirable as the Set Zero and should only be used with large pipes.
1. Press EDIT at the Reset Zero prompt, use the arrow keys to
make the display read Yes.
2. Press ACCEPT.
Correction Factor
Graphics Display Mode
COR FTR -- Correction Factor (Value)
(0.500 – 1.500)
This function can be used to make the TFX system agree with a different or reference flow meter by applying a correction factor/ multiplier to the readings and outputs. A factory calibrated system should be set to 1.000 (no correction factor). The range of settings for this entry is 0.500 to 1.500. The following example describes a possible use for the Correction Factor entry.
Example: The TFX meter is indicating a flow rate that is 4% higher than another flow meter located in the same pipe line. To make the TFX indicate the same flow rate as the other meter, enter a Correction Factor of 0.960 to lower the readings by 4%.
8. DSP MENU -- DISPLAY MENU
DISPLAY LINES -- Number of Display Lines
1. 2 Lines
2. 4 Lines
Allows the selection of a two line or four line display format on the graphics display module.
In 2 line mode, the display will show flow measurements with larger characters on the top half of the window and smaller standard sized characters on the lower half of the window. In 4 line mode, the display will show flow measurements with standard sized characters on four lines in the window.
Rev. 5/09 -3.39- TFXP
PART 3 - KEYPAD CONFIGURATION
Back Light Timeout
BACK LIGHT -- Back Light Timeout (Choice)
1. 30 Seconds (30 Sec)
2. 1 Minute (1 Min)
3. 5 Minutes (5 Min)
4. On (Always On)
The LED backlighting is used to assist the operator in viewing the display in poorly lit areas. The backlighting, when activated, doubles the power consumption of the flow meter. If left on continuously, the charge in the battery will be depleted much more rapidly than if the backlighting is only activated for short periods of time. If the instrument is being operated while powered from an external power source, the backlight may be left on permanently.
Adjust the Back Light Timeout to approximate the amount of seconds that the backlighting should remain active. The timeout can be set anywhere between 30 seconds and 5 minutes, or left on continuously. If continuous backlighting is desired, set the Back Light Timeout to Always On.
Rev. 5/09 -3.40- TFXP
PART 4 - SOFTWARE UTILITIES
Important Notice!
The TFXP flow meter can be used with two software utilities, ULTRALINK™ and Data Logger. The ULTRALINK™ utility is used for configuration, calibration and communication with the TFXP flow meter. The Data Logger utility is used for uploading and translating data accumulated in the data logger module located in the pocket on the front faceplate of the flow meter.
ULTRALINK™ has been designed to provide a TFX user a powerful and convenient way to configure and calibrate TFX family flow meters. ULTRALINK™ can be used in conjunction with the infrared communications adapter included in the TFXP case or the optional ISO-MOD RS232 or ISO-MOD RS485.
System Requirements
Computer type – PC, operating system Windows® 95/98/2000/NT/ Vista®, a communications port for the infrared adapter, access to the Dynasonics website.
Installation
1. Go to www.dynasonics.com.
2. Click the ULTRALINK™ icon at the bottom of page.
3. Follow downloading instructions.
4. Setup.exe will automatically extract and install on the hard disk
and place a short-cut icon on the desktop.
5. Some PCs may require a restart after a successful installation. A CD of the ULTRALINK™ software may also be purchased by
contacting Dynasonics sales at 800-535-3569 or 262-639-6770. Please refer to part number D005-0803-104.
Rev. 5/09 -4.1- TFXP
PART 4 - SOFTWARE UTILITIES
Initialization
Connect the infrared communications adapter to a PC communication port and point the communicator at the TFXP infrared window located in the lower right-hand corner of the keypad. If meter is ordered with either ISO-MOD RS232 or ISO­MOD RS485 options, connect the PC communications cable directly to the DB-9 connection located on the side of the TFXP meter.
Click on the Communications button in the menu bar. Next click on Initialize. Choose the appropriate COM port and interface type. For the IR adapter choose IrDA Actisys IR220L. If either an RS232C or RS485 communications module are used, select the appropriate choice in the same drop down menu.
Figure 1 — Serial Port Selection
Successful communications between the TFX meter and computer are indicated by a green “OK” in the COMM box in the lower right­hand corner of the Data Display screen and Time” near the bottom of the text area of the left-hand side is tracking the time of the computer the TFX is connected to.
NOTE: For help in establishing communications with the TFX meter, see “TFX Communications Using ULTRALINK™” in the Appendix of this manual.
The first screen is the “Data Display” screen, see Figure 4.2 on page 4.3, which contains real-time information regarding flow rate, totalizer accumulation, system signal strength, diagnostic data and the flow meter’s serial number. Click on the button labeled Configuration for updating flow range, liquid, pipe and I/O operating information.
Rev. 5/09 -4.2- TFXP
the “Last Update
PART 4 - SOFTWARE UTILITIES
Pipe and Liquid Configuration
Figure 4.2 — “Data Display” Screen
The first screen that appears after clicking the Configuration button is the BASIC tab. See Figure 4.3 on page 4.5.
Basic Tab General Units allows selection of either English (U.S.) or Metric
units of measure. If measurements of the pipe are to be entered in inches, select English. If measurements are to be entered in millimeters, select Metric. If the General Units are altered from those at instrument startup, then click the Download button in the lower right-hand portion of the screen and recycle power to the TFXP.
Transducer Type selects the transducer that will be connected to the TFX flow meter. Select from DTTN, DTTH, DTTS or DTTC models. This selection will influence transducer spacing and flow meter performance. If you are unsure about the type of t ra ns du c er to which the TFX will be connected, consult the shipment packing list or call the Dynasonics factory for assistance. A change of Transducer Type will cause a System Configuration Error to occur. This error will clear when t he mi cr opr oce ss or is reset or power is cycled on the flow meter.
Rev. 5/09 -4.3- TFXP
PART 4 - SOFTWARE UTILITIES
Transducer Mount selects the orientation of the transducers on the piping system. See Part 2 of this manual and Table 2.2 on page
2.5 for detailed information regarding mounting modes for particular pipe and liquid characteristics. Whenever Transducer Mount is changed, a download command and subsequent microprocessor reset or flow meter power cycle must be conducted.
Transducer Spacing is a value calculated by the TFX flow met er that takes into account pipe, liquid, transducer and mounting information. This spacing will adapt as these parameters are modified. The spacing is given in inches for English units selection and millimeters for Metric. This value is the lineal distance that must be between the transducer spacing marks. (See Figure 2.3 on page
2.9.) Pipe Material is selected from the pull-down list. If the pipe material
utilized is not located on the list, select Other and enter pipe material sound speed (much of this information is available via websites such as www.ultrasonic.com) and relative roughness (the RMS value of the internal surface regularities/the pipe internal diameter) of the pipe.
Pipe O.D. and Wall Thickness are based on the physical dimensions of the pipe on which the transducers will be mounted. Enter this value in inches for English units or millimeters for Metric units.
Liner Material is selected from the pull-down list. If the pipe liner material utilized is not located on the list, select Other and enter liner material sound speed (much of this information is available at websites such as www.ultrasonic.com) and relative roughness (the RMS value of the internal surface regularities/the pipe internal diameter) of the pipe liner.
Fluid Type is selected from the pull-down list. If the liquid is not located on the list, select Other and enter the liquid sound speed and viscosity into the appropriate boxes. Liquid Specific Gravity is required if mass measur ements are to be made, and Specific Heat is required for energy measurements.
Rev. 5/09 -4.4- TFXP
PART 4 - SOFTWARE UTILITIES
Figure 4.3 — Basic Tab Layout
Flow Units Configuration
Flow Tab Flow Rate Units are selected from the pull-down lists. Select an
appropriate rate unit and time from the two lists. Totalizer Units are selected from the pull-down lists. Select an
appropriate totalizer unit and totalizer exponent. The totalizer exponents are in scientific notation and permit the eight digit totalizer to accumulate large values before the totalizer “rolls over” and starts again at zero. Table 4.1 on page 4.6 illustrates the scientific notation values and their respective decimal equivalents.
MIN Flow is used by the TFX to establish filter settings in its operating system. Enter a flow rate that is the minimum flow rate anticipated within the system. For unidirectional systems, this value is typically zero. For bi-directional systems this value is set to a negative number that is equal to the maximum negative flow rate that is anticipated within the system.
MAX Flow is used by the TFX to establish filter settings in its operating system. Enter a flow rate that is the maximum, positive flow rate anticipated within the system.
Rev. 5/09 -4.5- TFXP
PART 4 - SOFTWARE UTILITIES
Exponent Display Multiplier E-1 E0 E1 E2 E3 E4 E5 E6
Table 4.1 — Totalizer Exponent Values
The Damping value is increased to improve stability of the flow rate readings. Damping values are decreased to allow the flow meter to react faster to changing flow rates.
Low Flow Cutoff is entered as a percentage between MAX Flow and MIN Flow and influences how the meter will act at flows very close to zero. Generally, an entry of 5% provides a stable zero indication.
Low Signal Cutoff is a relative value that should be entered after a successful startup. For an initial value, enter 5%. (Signal Strength indications below 2% are considered to be below the noise ceiling and should not be indicative of a successful flow meter startup.)
× 0.1 × 1 (no multiplier) × 10 × 100 × 1,000 × 10,000 × 100,000 × 1,000,000
The Low Signal Cutoff has three purposes:
1. It provides an error indication – Low Signal Strength (Error 0010 on the TFX display) when liquid conditions within the pipe have changed to the point where flow measurements may not be possible.
2. It warns if the pipe’s liquid level has fallen below the level of the transducers.
3. It can also signal that something with the flow meter installation or configuration may have changed. For example, the couplant used to mount the transducer has become compromised, a cable has been disconnected or a pipe size has been altered.
Rev. 5/09 -4.6- TFXP
Downloading the Configuration
PART 4 - SOFTWARE UTILITIES
Substitute Flow is used to provide an indication and output that signifies that an error exists with the flow meter or its setup. It is set as a percentage between MIN Flow and MAX Flow. In a unidirectional system this value is typically set to zero to indicate zero flow while in an error condition. In a bi-directional system, the percentage can be set such that zero is displayed in an error condition. To calculate where to set the Substitute Flow value in a bi-directional system, perform the following operation:
Substitute Flow = 100
(
Entry of data in the Basic and Flow tabs is all that is required to provide flow measurement functions to the flow meter. If the user is not going to utilize input/output functions, click the Download button to transfer the configuration to the TFX instrument.
100 × MAX Flow
MAX Flow MIN Flow
)
Meter Filter Configuration
Figure 4.4 — Flow Tab Layout
Advanced Tab
The Advanced tab contains several filter settings for the TFX flow meter. These filters can be adjusted to match response times and data “smoothing” performance to a particular application. The factory settings are suitable for most installations.
Rev. 5/09 -4.7- TFXP
PART 4 - SOFTWARE UTILITIES
Time Domain Filter adjusts the number of raw data sets (the wave forms viewed on the ULTRALINK™ Diagnostics Screen) that are averaged together. Increasing this value will provide greater damping of the data and slow the response time of the flow meter. This filter is not adaptive – it is operational to the value set at all times.
Low Signal Cutoff is a duplicate entry from Flow tab. Adjusting this value adjusts the value on the Flow tab.
Substitute Flow is a duplicate entry from Flow tab. Adjusting this value adjusts the value on the Flow tab.
Short Pulse Duration is a function used on pipes larger than 8 inches (200 mm). If the pipe has an outer diameter of 8 inches or more, make sure that the Auto Short Pulse box is checked. Set this value to zero to disable the function.
Flow Filter Damping establishes a maximum adaptive filter value. Under stable flow conditions (flow that varies less than the Flow Filter Hysteresis entry) this adaptive filter will increase the number of successive flow readings that are averaged together up to the maximum value entered in this field. If flow changes outside of the Flow Filter Hysteresis window, the Flow Filter adapts by decreasing the number of averaged readings and allows the meter to react faster. Increasing this value tends to provide smoother steady-state flow readings and outputs.
Flow Filter Hysteresis creates a window around the average flow measurement reading whereby if the flow varies within that window, Flow Filter Damping will increase up to the maximum value entered in the Flow Filter Damping field. The filter also establishes a flow rate window where measurements outside of the window are captured by the Bad Data Rejection Filter. The value is entered as a percentage of actual flow rate.
Example: If the average flow rate is 100 GPM and the Flow Filter Hysteresis is set to 5%, a filter window of 95-105 GPM is
established. Successive flow measurements that are measured within that window are recorded and averaged in accordance with the Flow Filter Damping setting. Flow readings outside of the window are held up in accordance with the Bad Data Rejection Filter.
Rev. 5/09 -4.8- TFXP
PART 4 - SOFTWARE UTILITIES
Flow Filter MinHysteresis sets a minimum hysteresis window that is invoked at sub 0.25 FPS (0.08 MPS) flow rates, where the “of rate” Flow Filter Hysteresis is very small and ineffective. This entry is entered in picoseconds and is differential time. If very small fluid velocities are to be measured, increasing the Flow Filter
MinHysteresis valu e c a n i n c r e a s e reading stability. Flow Filter Sensitivity allows configuration of how fast the Flow
Filter Damping will adapt in the positive
value allows greater damping to occur faster than lower values. Adaptation in the negative direction is not user adjustable.
Bad Data Rejection is a value related to the number of successive readings that must be measured outside of the Flow Filter Hysteresis and Flow Filter MinHysteresis windows before the flow meter will assume the change is actual. Larger values are entered into the Bad Data Rejection when measuring liquids that contain gas bubbles, as the gas bubbles tend to disturb the ultrasonic signals and cause more extraneous flow readings to occur. Larger Bad Data Rejection values tend to make the flow meter more sluggish to rapid changes in actual flow rate.
direction. Increasing this
Figure 4.5 — Advanced Tab Layout
Rev. 5/09 -4.9- TFXP
PART 4 - SOFTWARE UTILITIES
Output Configuration
Output Tab
The entries made in the Output tab establish input and output calibration and ranges for ISO-MOD modules installed in the TFX flow meter. If a module was ordered from and installed at the factory, then the Output tab will contain information and configuration for that module.
If a module has been changed from the factory setting, a configuration error will result. This error will be cleared by resetting the TFX microprocessor from the Communications/ Commands/Reset Target button or by cycling power on the TFX flow meter. Once the proper output module is selected and the microprocessor is reset, calibration and configuration of the module can be completed. If a module slot is empty in the TFX enclosure, select NONE as the module type.
Standard TFXP flow meters contain a single 4-20 mA output module located in Module #2 position with the capability of accepting an optional data logger located in Module #1 position. The window will appear as shown in Figure 4.6 on page 4.11. (The 4-20 mA module is mounted internally in the flow meter and requires meter disassembly to replace the module. The data logger is located under the sealed front plate on the meter face and is designed for repeated installation and removal.) Detailed information regarding all of the module and configuration options is available in Part 3 of this manual. To disable the data logger, select None for Module #1, and select any other module for Module #2.
4-20 mA Module Configuration If the 4-20 mA output has been installed, the screen shown in Figure
4.6 on page 4.11 will appear in ULTRALINK™ at the Output tab. Flow @4mA and Flow @20mA set the span of the 4-20 mA output.
The entry is made in the same flow measurement units that were entered in the Flow tab. The output can be set to span across zero (4 mA can be set to a negative flow value) so that the module will output bi-directional flow. For example, if a flow
-100 to +100, the TFX will output 4 mA at ­+100 and output 12 mA (50% of the output) at 0.
range spans from
100 and 20 mA at
Rev. 5/09 -4.10- TFXP
PART 4 - SOFTWARE UTILITIES
Calibration/Test is used to adjust the factory calibration span of the 4-20 mA output and to test the output. The 4-20 mA output is factory calibrated and should not require adjustment in the field. If the module is replaced or if recalibration is required, the following procedure is used to calibrate the span of the module:
1. Connect a milliamp meter serially within the 4-20 mA module output.
2. Check the Calibration/Test box.
3. Select the 4 mA Calibration box.
4. Adj ust the count value to the right of the 4 mA button until the milliamp meter registers 4.00 mA.
5. Select the 20 mA Calibration box.
6. Adjust the count value to th e right of the 20 mA button until the milliamp meter registers 20.00 mA.
7. Press the Test button.
8. Adjust the count value to 12.
9. Verify that the milliamp meter registers 12.00 mA.
10. Uncheck the Calibration/Test box.
Figure 4.6 — Output Tab Layout
Rev. 5/09 -4.11- TFXP
PART 4 - SOFTWARE UTILITIES
Setting Zero and Calibration
ULTRALINK™ contains a powerful multi-point calibration routine that can be used to calibrate the TFX flow meter to a primary measuring standard in a particular installation. To initialize the three­step calibration routine, click on the Calibration button located on the top of the ULTRALINK™ Data Screen. The display shown in Figure 4.7 will appear. The first step (Page 1 of 3) in the calibration process is the selection of the engineering units with which the calibration will be performed. Select the units and click the Next button at the bottom of the window.
Figure 4.7 — Calibration (Page 1 of 3)
The second screen (Page 2 of 3) Figure 4.8 on page 4.13, establishes a baseline zero flow rate measurement for the instrument. To zero the flow meter, establish zero flow in the pipe (turn off all pumps and close a dead-heading valve). Wait until the delta-time interval shown in Figure 4.8 is stable (and typically very close to zero). Click the Set button. Click the Next button when prompted, then click the Finish button on the Calibration Screen.
Important!
Rev. 5/09 -4.12- TFXP
NOTE: If the Set button was clicked, do not proceed with Flow Rate Calibration before clicking the Finish button to save the Zero setting.
PART 4 - SOFTWARE UTILITIES
Important!
Figure 4.8 — Calibration (Page 2 of 3)
The final screen (Page 3 of 3) shown in Figure 4.9 on page 4.14 allows multiple actual flow rates to be recorded by the TFX. To calibrate a point, establish a stable, known flow rate (verified by a real-time primary flow instrument), enter the actual flow rate in the Figure 4.9 window and click the Set button.
NOTE: If only two points are to be used (zero and span), it is preferable to use the highest flow rate anticipated in normal operation as the calibration point. If an erroneous data point is collected, the point can be removed by pressing the Edit button, selecting the bad point and then selecting Remove.
Press the Finish button when all points have been gathered.
NOTE: Do not enter a zero flow rate under page 3 of 3 above. NOTE: Dynasonics recommends only using one span point to
achieve highest results.
Rev. 5/09 -4.13- TFXP
PART 4 - SOFTWARE UTILITIES
Saving the Configuration
Printing a Report
Figure 4.9 — Calibration (Page 3 of 3)
Saving Meter Configuration on a PC
The complete configuration of the flow meter can be saved from the Configuration screen. Select File Save button located in the lower left-hand corner of the screen and name the file. Files are saved as a *.dcf extension. This file may be transferred to other flow meters or may be recalled should the same pipe be surveyed again or multiple meters programmed with the same information.
Printing a Flow Meter Configuration and Calibration Report
Select File from the upper task bar and Print to print a calibration/ configuration information sheet for the flow meter installation.
Rev. 5/09 -4.14- TFXP
PART 4 - SOFTWARE UTILITIES
Using the Data Logger Software
During the installation of ULTRALINK™, a file called Data Logger was installed and its icon will appear in the ULTRALINK™ folder under Program Files. Double-click on the Datalog.exe icon to start the utility. The screen shown in Figure 4.10 will appear as the computer is attempting to establish communications with the logger module.
Figure 4.10 — Data Logger Connection Screen
Connect the logger to the computer’s serial communications port with the enclosed DB-9 cable. After a few moments, the Please Wait window will disappear and a green OK will appear in the lower right-hand corner of the window. After communications are established (and the OK is displayed) the utility will scan the logger for all existing files. If the logger module is very full, uploading of the file data may take several minutes. A bar graph showing upload progress will provide status. The files will appear on the table (see Figure 4.11 on page 4.16). Information regarding starting time, date and points collected will appear.
If a file is selected, the time-stamped data will appear on the strip chart located on the bottom of the window. The mouse can be used to select a small portion of the graph and expand the data to the width of the screen. To revert to the entire data file, right-click the graph.
To save the file to a computer, select the file from the file table and click the Save button located on the top task bar (see Figure 4.12 on page 4.16). Data Logger saves the files in *.csv (comma separated value) format. These files can be opened in any programs that can read comma separated value files.
Rev. 5/09 -4.15- TFXP
PART 4 - SOFTWARE UTILITIES
Figure 4.12 — Saving Data Logger Files
Figure 4.11 — File Uploading
Rev. 5/09 -4.16- TFXP
PART 4 - SOFTWARE UTILITIES
The data logger module contains a real-time clock that can be set by clicking the Clock button on the top task bar (see Figure 4.13). Activating the window compares the data logger clock to the clock located in the PC. Adjustments can be made and uploaded to the logger.
Figure 4.13 — Data Logger Clock
Rev. 5/09 -4.17- TFXP
PART 4 - SOFTWARE UTILITIES
NOTES
Rev. 5/09 -4.18- TFXP
HEAT FLOW ADDENDUM
General
The TFX flow meter with the optional RTD (heat flow) Module installed is designed to measure the rate and quantity of heat delivered to a given building, area or heat exchanger. The instrument measures the volumetric flow rate of the heat exchanger liquid (water, water/glycol mixture, brine, etc.), the temperature at the inlet pipe and the temperature at the out let pip e. Heat delive ry is calculated by the following equation:
Rate of heat delivery = Q × (Tin – T
out
) × c
Where Q = volumetric flow rate T T
= temperature at the inlet
in
= temperature at the outlet
out
c = specific heat of the liquid The RTD module installed in the TFX measures the differential
temperature of two 1,000 Ohm three-wire platinum RTDs. The three-wire configuration allows the temperature sensors to be located several hundred feet away from the TFX meter without influencing system temperature measuring accuracy or stability.
The RTDs included with the TFX heat flow option have been factory calibrated and are marked with an identification as to which input number, 1 or 2, the RTD has been calibrated. The RTDs are 1,000 Ohm platinum and are designed to be mounted on the exterior surface of the pipe. The RTDs are rated for a te mperatur e range of
-40 to +200 °C in three steps: 0 to + 50 °C
0 to +100 °C
-40 to +200 °C
The RTD temperature range should be chosen referencing the maximum temperature of the liquid to be measured. By using the narrowest temperature range, the resolution of the temperature measurement will be maximized.
Rev. 5/09 -A.1- TFXP
HEAT FLOW ADDENDUM
Installation
Installation
1. Follow the instructions outlined in the standard TFX manual for proper installation of the ultrasonic transducers. After installation, verify that the signal strength is sufficient for stable flow readings and, if possible, perform a Zero flow calibration on the pipe. Please note that all readings require a full pipe of liquid.
2. Select ar eas on the inlet and outlet pipes where the RTDs will be mounted. Remove or peel back the insulation all the way around the pipe in the installation area. Clean an area slightly larger than the RTD down to bare metal on the pipe.
3. Place a small amount of heat sink co mpound on the pip e in th e RTD installation location. Se e Figure A.1 Press the RTD firmly into the compound. Fasten the RTD to the pipe with the included heater tape.
Figure A.1 — Surface Mount RTD Installation
4. Route the RTD wires to an electrical junction box in close proximity to the installation location. Secure the RTD wires such that they will not be pulled on or abraded inadvertently. Replace the insulation on the pipe.
Rev. 5/09 -A.2- TFXP
HEAT FLOW ADDENDUM
5. Rout e a cable from the electr ical junction box back to the TFX flow meter. Connect the RTDs as illustrated in Figure A.2. Note that th e SNS1 and DRV1 wires originate from the same loca tion on the RTD.
Figure A.2 — RTD Connection
Programming
Transmitter Programming
1. The RTDs included with the TFX heat flow option have been factory calibrated and are marked with an identification as to which terminal, #1 or #2, the RTD has been calibrated. If recal ibration of the RTDs is require d or RTDs other than those supplied with the TFX are being utilized, the ULTRALINK™ software utility will be required to enter calibration values. ULTRALINK™ can also be used to configure all operating parameters of the heat flow ins trument.
2. T o pro perl y mea sure heat d eliv ery, the specific heat capacity of the liquid must be enter ed. W hen a liq ui d i s c hosen from the FL TYPE list, a default specific heat will be loaded. This default value is displayed as SP HEAT in the BASIC MENU. If the actual specific heat of the liquid is known or if it differs from the default value, press the ENTER key and modify the value. Press the ENTER key to save the value. See the values listed in Tables 1 and 2 for specif ic values. E nter a value that is the mean of both pipes.
3. The RATE UNIT can be displayed as four different values; BTUs, MBTU, MMBTU, or TON. Select the proper unit from the RATE
Rev. 5/09 -A.3- TFXP
HEAT FLOW DDENDUM
HEAT FLOW ADDENDUM
UNIT list. Select the appropriate RATE INTERVAL from the list (seconds, minutes, hours, days). Be aware that the instrument can only display values as large as 99,999,999.
4. Select an appropriate TOTALIZER UNIT from the list; BTUs, MBTU, MMBTU, or TON .
5. From t he main display, three values can be accessed that may aid in troubleshooting the heat flow instrument. The temperature being read by RTD1 is indicated as TEMP1 (all values are degrees Celsius) , RTD2 as TEMP2 and the absolute difference as TEMPDIFF.
Heat Capacity of Water (J/g°C)
°C 0 1 2 3 4 5 6 7 8 9
0 4.2174 4.2138 4.2104 4.2074 4.2045 4.2019 4.1996 4.1974 4.1954 4.1936 10 4.1919 4.1904 4.1890 4.1877 4.1866 4.1855 4.1846 4.1837 4.1829 4.1822 20 4.1816 4.0310 4.1805 4.1801 4.1797 4.1793 4.1790 4.1787 4.1785 4.1783 30 4.1782 4.1781 4.1780 4.1780 4.1779 4.1779 4.1780 4.1780 4.1781 4.1782 40 4.1783 4.1784 4.1786 4.1788 4.1789 4.1792 4.1794 4.1796 4.1799 4.1801 50 4.1804 4.0307 4.1811 4.1814 4.1817 4.1821 4.1825 4.1829 4.1833 4.1837 60 4.1841 4.1846 4.1850 4.1855 4.1860 4.1865 4.1871 4.1876 4.1882 4.1887 70 4.1893 4.1899 4.1905 4.1912 4.1918 4.1925 4.1932 4.1939 4.1946 4.1954 80 4.1961 4.1969 4.1977 4.1985 4.1994 4.2002 4.2011 4.2020 4.2029 4.2039 90 4.2048 4.2058 4.2068 4.2078 4.2089 4.2100 4.2111 4.2122 4.2133 4.2145
Table A.1 — Heat Capacity of Water
Rev. 5/09 -A.4- TFXP
Loading...