Dynasonics TFXD Operating Manual

Series TFXD
Transit Time Ultrasonic Flow Meter
Operations & Maintenance
Manual
REV 5/07
TABLE OF CONTENTS
Part 1 - Introduction
Connections and Wiring
Quick-Start Operating Instructions 1.3-1.5
Introduction
General 1.6 Applications 1.6 Product Matrix 1.7
Product Specifications 1.8
Transmitter Installation 1.9-1.10 Transducer and Power Connections 1.11-1.14 Input/Output Connections
General 1.15 4-20 mA Output 1.16 Dual Control Relays 1.17
Pages
Part 2 ­Transducer and RTD Installation
Rate Pulse Output 1.18 RS232C 1.19 RS485 1.20
Data Logger 1.21 Heat Flow 1.22-1.23 Startup and Configuration 1.24
General 2.1 Mounting Location 2.2 Transducer Spacing 2.3-2.7 Transducer Mounting, Pipe Preparation 2.8 Transducer Mounting, V-Mount and W-Mount 2.9-2.11 Transducer Mounting, DTTS Small-pipe 2.12 Transducer Mounting, Z-Mount 2.13-2.15 Mounting Track Installation 2.16-2.17 RTD Installation 2.17-2.19
Rev. 5/07 -1.1- TFXD
TABLE OF CONTENTS
Part 3 ­Programming
Part 4 ­Software Utilities
General Programming Information 3.1-3.2 BASIC MENU 3.3-3.13 OUTPUT MENU 3.14-3.21 SENSOR MENU 3.22 SECURITY MENU 3.22 SERVICE MENU 3.23-3.28
Liquid Sound Speed 3.23
Signal Strength 3.23
Temperature Values 3.25
Setting ZERO Flow 3.27
Correction Factor Entry 3.28 DISPLAY MENU 3.28-3.29
Software Utility Operation
UltraLink™
Data Logger 4.21-4.24
Pages
4.1-4.21
Appendix
Rev. 5/07 -1.2- TFXD
Appendix
Keypad Interface Map
Fluid Characteristic Table
TFX Error Codes
Digital Communications Protocol
Pipe Dimension Chart: ST, SS, PVC
Pipe Dimension Chart: Ductile Iron
Pipe Dimension Chart: Copper
Pipe Dimension Chart: Cast Iron
Velocity to Volumetric Conversion
Statement of Warranty/Terms & Conditions
Customer Service
QUICK-START OPERATING INSTRUCTIONS
Transducer Location
This manual contains detailed operating instructions for all aspects of the TFX instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
1. TRANSDUCER LOCATION
A. In general, select a mounting location on the piping system
with a minimum of 10 pipe diameters (10 x the pipe inside diameter) of straight pipe upstream and 5 straight diameters downsteam. See Table 2.1 on page 2.4 for additional configurations.
B. Select a mounting method for the transducers, based on pipe
size and liquid characteristics. See Table 2.2 on page 2.5. Transducer configurations are illustrated in Figure 1.1.
1
Nominal values for these
parameters are included within the TFX operating system.
The nominal values may
be used as they appear or may be modified if exact system values are known.
C. Enter the following data into the TFX transmitter via the
integral keypad or UltraLink™ software utility.
1. Transducer mounting method
2. Pipe O.D. (outside diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed
6. Pipe relative roughness
1
1
7. Pipe liner thickness
8. Pipe liner material
9. Fluid type
10. Fluid sound speed
11. Fluid viscosity
12. Fluid specific gravity
1
1
1
D. Record the value calculated and displayed as Transducer
Spacing/XDCR SPC.
Figure 1.1
Transducer Mounting Configurations
Rev. 5/07 -1.3- TFXD
QUICK-START OPERATING INSTRUCTIONS
Connections
2. TRANSDUCER/POWER CONNECTIONS
A. Route the transducer cables from the transducer mount
loc ation back to the TFX enclosure. If additional cable and connections are required, ensure that they are RG59 75 Ohm compatible. Connect the transducer wires to the terminal block J4 in the TFX enclosure. A wiring diagram is located on the inner door label.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH or DTTS transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet [300 meters] are available. If additional cable and connections are added, ensure that they are RG59 75
Ohm compatible. B. Verify that power supply jumpers are properly configured.
Reference the wiring diagram located on the TFX inner door. Connect power to the TFX flow meter.
3. PIPE PREPARATION AND TRANSDUCER MOUNTING DTTN and DTTH Transducers
A. Place the flow meter in signal strength measuring mode. This
value is available on the TFXD2 display (Service Menu) or in the Data display of the UltraLink™ software utility.
B. The piping surface, where the transducers are to be mounted,
must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
C. Apply a single 1/2" [12 mm] bead of couplant grease to the
upstream transducer and secure it to the pipe with a mounting strap.
D. Apply acoustic couplant grease to the downstream transducer
and press it onto the pipe using hand pressure at the lineal distance calculated in Step 1.
E. Move the transducer slowly around the mount area until the
highest signal strength is observed. Secure with a mounting strap at this location.
Rev. 5/07 -1.4- TFXD
QUICK-START OPERATING INSTRUCTIONS
Startup
DTTS Transducers
A. Place the flow meter in signal strength measuring mode.
This value is available on the TFXD2 display (Service Menu) or in the Data display of the UltraLink™ software utility.
B. The pipe surface, where the transducers are to be mounted,
must be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds. Grind rough surfaces of pipes to smooth bare metal. Plastic pipes do not require preparation other than cleaning.
C. Apply a single 1/2" [12 mm] bead of acoustic couplant grease
to the top half of the transducer and secure it to the pipe with bottom half or U bolts.
D. Tighten the wing nuts so that the grease begins to flow out
from the edges of the transducer and from the gap between the transducer halves. Do not over tighten.
4. INITIAL SETTINGS AND POWER UP
A. Verify that SIG STR is greater than 2.0%. B. Verify that measured liquid SSPD is within 3% of the
configuration value.
C. Input proper units of measure and I/O data.
Rev. 5/07 -1.5- TFXD
PART 1 - INTRODUCTION
General
Application Versatility
The TFXD ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non­contacting, clamp-on or clamp-around type, which will provide benefits of non-fouling operation and ease of installation.
The TFX family of transit time flow meters utilize transducers that function as both ultrasonic transmitters and receivers. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-Mount where the sound transverses the pipe two times, W-Mount where the sound transverses the pipe four times, or in Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. This selection is based on pipe and liquid characteristics.
DTTS (Small Pipe Transducers) have both transmit and receive crystals imbedded in a single clamp-around transducer so no measurement between transducers is required.
The flow meter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers. The difference in the time interval measured is directly related to the velocity of the liquid in the pipe.
The TFXD flow meter can be successfully applied on a wide range of metering applications. The simple-to-program transmitter allows the standard product to be used on pipe sizes 1/2 inch [12
mm] and larger. (Transducers sets from 1/2 to 1-1/2 inch require 2 MHz transmitters and dedicated pipe transducers.) A variety of liquid applications can be accommodated:
ultrapure liquids sewage cooling water potable water reclaimed water river water chemicals plant effluent others
Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. The DTTN transducer set is rated to a pipe surface
Rev. 5/07 -1.6- TFXD
PART 1 - INTRODUCTION
temperature of 300 °F [150 °C]. High temperature DTTH transducers can operate to a pipe surface temperature of 380 °F [193 °C]. The DTTS series of small pipe transducers can be used to a pipe surface temperature of 185
°F
[85 °C].
User Safety
Data Integrity
Product Identification
Transmitter
The TFX employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 10 Vdc. The display face swings open to allow access to user connections. Disconnect electrical power before opening the instrument enclosure.
Non-volatile FLASH memory retains all user-entered configuration values in memory for several years (at 25 °C), even if power is lost or turned off. Password protection is provided as part of the Security menu and prevents inadvertent configuration changes or totalizer resets.
The serial number and complete model number of the TFX is located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasonics Customer Service Department with this information.
Product Matrix
Rev. 5/07 -1.7- TFXD
PART 1 - PRODUCT SPECIFICATIONS
TRANSMITTER
Power Requirements 115/230 VAC 50/60 Hz ±15% at 5 VA max or 10-28 VDC at 3.0 W Velocity Range Input/Output Bays 2
Options All modules optically isolated from earth and system ground
4-20 mA 800 Ohm max; 12-bit resolution, internal or external power Dual Relay 2 separate Form C relays, 200 VAC max at 0.5 A [resistive] Rate Pulse Open collector, 0 to 2,500 Hz max; 1.0 A max RS232C Data rate to 57.6k RS485 Supports up to 126 drops on a two-wire network Data Logger 200k events in 30k pages, 16-bit, integral DB-9 RS232C connection Heat Flow (RTD) Supports two 1000 Ohm RTDs, multiplexed, 12-bit resolution
Display (DTFXD2 only)
Units User configured
Rate Gal, liters, million gal, ft³, m³, acre-ft, oil barrels [42 gal], liquid barrels [31.5 gal], ft, m, lb, kg, BTU, MBTU,
Time Seconds, minutes, hours, days Totalizer Gal, liters, million gal, ft³, m³, acre-ft, oil barrels [42 gal], liquid barrels [31.5 gal], lb, kg, BTU, MBTU, MMBTU,
Mode Forward, reverse, net, batch Ambient Conditions Enclosure NEMA 4X [IP-66], polycarbonate, SS, brass, plated steel Size Flow Rate Accuracy ±1% of reading for velocities >
Flow Sensitivity 0.001 FPS [0.0003 MPS] Repeatability ±0.01% of reading Response Time (Flow) 0.3 to 30 seconds, user configured, for 10% to 90% step change in flow Security Keypad lockout, user selected 4 digit access code Approvals Ordinary areas Software UltraLink™, compatible with Window
-40
to
+40
FPS [-12 to +12 MPS]
2 line x 8 character backlit LCD; 8 digit rate, 8 digit re-settable totalizer
Top row: 7 segment, 0.7" [18 mm] high, numeric Bottom row: 14 segment, 0.35" [9mm] high alpha-numeric
MMBTU, kJ, kCal, ton
kJ, kCal, ton
-40
°F to +185 °F
7.00" H × 5.75" W × 3.88" D [178 mm H × 146 mm W × 99 mm D]
±0.1 FPS [0.03 MPS] for velocities < 1 FPS [0.3 MPS]
[-40
°C to
+85
°C], 0 to 95% relative humidity [non-condensing]
1 FPS [0.3 MPS]; ±0.5% of reading for field calibrated units
®
95/98/2000/XP
TRANSDUCERS
Liquid Types Most non-aerated, clean liquids Cable Length Up to 990 ft [300 meters]; standard lengths 20, 50, 100 ft [6, 15, 30 meters] Pipe Sizes DTTN / DTTH: 2 inch and larger
Environment NEMA 6 Pipe Surface
Temperature
Ambient Conditions Housing Material DTTN: CPVC, Ultem
Approvals Standard: None
DTTS [small pipe]: 1/2", 3/4", 1", 1-1/4", 1-1/2" [ANSI pipe, copper tube, tube]
DTTN:
-40 DTTS: DTTH:
-40
DTTS: PVC, Ultem DTTH: PTFE, Vespel
Optional - DTTN only: CSA Class I, Div 1, Groups C & D; requires intrinsically safe transducer kit with barrier
°F to +300 °F
-40
°F to +185 °F
-40
°F to +380 °F
°F to +185 °F
[-40
°C to +150 °C]
[-40
°C to
[-40
[-40
°C to
®
, and nylon
®
, and nylon
®
, and nickel-plated brass
+85
°C to +193 °C]
+85
°C]
°C]
Rev. 5/07 -1.8- TFXD
PART 1 - TRANSMITTER INSTALLATION
Transmitter Installation
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or reshipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The enclosure should be mounted in an area that is convenient for servicing, calibration or for observation of the LCD readout (if so equipped).
1. Locate the transmitter within the length of transducer cable that was supplied with the TFXD system. If this is not possible, it is recommended that the cable be exchanged for one that is of proper length.
NOTE: The transducer cable carries low level, high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH or DTTS transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet [300 meters] are available. If additional cable and connections are added, ensure that they are RG59 75
Ohm compatible.
2. Mount the TFX transmitter in a location that is:
Where little vibration exists.
Protected from corrosive fluids.
Within ambient temperature limits -40 to 185 °F [-40 to 85 °C].
Out of direct sunlight. Direct sunlight may increase tr ansm itte r
temperature to above the maximum limit.
3. Mounting: Refer to Figure 1.2 on page 1.10 for enclosure and mounting dimension details. Ensure that enough room is available to allow for door swing, maintenance and conduit entrances. Secure the enclosure to a flat surface with four appropriate fasteners.
4. Conduit holes: Conduit hubs should be used where cables enter the enclosure. Holes not used for cable entry should be sealed with plugs.
Rev. 5/07 -1.9- TFXD
PART 1 - TRANSMITTER INSTALLATION
Figure 1.2
TFX Transmitter Installation Dimensions
Rev. 5/07 -1.10- TFXD
PART 1 - TRANSDUCER AND POWER CONNECTIONS
NOTE: Use NEMA 4 [IP-65] rated fittings/plugs to maintain the watertight integrity of the enclosure. Generally, the left conduit hole (viewed from front) is used for line power; the center conduit hole for transducer connections and the right hole is utilized for ISO-MOD I/
O wiring.
5. If additional holes are required, drill the appropriate size hole in the enclosure’s bottom. Use extreme care not to run the drill bit into the wiring or circuit cards.
Transducer Connections
Transmitter Power Connections
To access terminal strips for electronic connectors, loosen the two screws in the enclosure door and open the door.
1. Guide the transducer terminations through the transmitter conduit hole located in the bottom-center of the enclosure. Secure the transducer cable with the supplied conduit nut (if flexible conduit was ordered with the transducer).
2. The terminals within the TFX are a pluggable type – they can be removed, wired and then plugged back in. Connect the appropriate wires to J4 at the corresponding screw terminals in the transmitter. Observe UP/DN Str Xdcr orientation. See Figure 1.3 on page 1.12 and Figure 1.4 on page 1.13 or the wiring diagram located on the inner door of the transmitter.
NOTE: The transducer cable carries low level high frequency signals. In general, it is not recommended to add additional cable to the cable supplied with the DTTN, DTTH or DTTS transducers. If additional cable is required, contact the Dynasonics factory to arrange an exchange for a transducer with the appropriate length of cable. Cables to 990 feet [300 meters] are available. If additional cable and connections are added, ensure that they are RG59 75
Ohm compatible.
Connect power to the screw terminal block marked J2 in the TFX transmitter. See Figure 1.3 and Figure 1.4. Utilize the conduit hole on the left side of the enclosure for this purpose. Use wiring practices that conform to local and national codes (e.g., The National Electric Code Handbook in the U.S.)
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
Rev. 5/07 -1.11- TFXD
PART 1 - TRANSDUCER AND POWER CONNECTIONS
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (i.e., fluorescent lights, relays, compressors, or variable frequency drives). It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
AC POWER CONNECTIONS
Figure 1.3
TFXD Wiring Diagram
Rev. 5/07 -1.12- TFXD
PART 1 - TRANSDUCER AND POWER CONNECTIONS
AC Power Supply
1. Verify that the jumpers at JP3 are properly oriented for the power supply. Verify that the jumpers at JP1 and JP2 are not present.
2. Connect L1, L2 and earth to the terminals referenced in Figure
1.3 on page 1.12. Phase and neutral connections to L1 and L2 are not polarized. Do not operate without an earth ground connection.
3. See Figure 1.4 for AC connection schematic. Wire gauges up to 14 AWG can be accommodated in the TFX terminal blocks.
Figure 1.4
AC Power Connection
Rev. 5/07 -1.13- TFXD
PART 1 - TRANSDUCER AND POWER CONNECTIONS
DC Power Supply
DC POWER CONNECTIONS
The TFX may be operated from a 9-28 Vdc source, as long as the source is capable of supplying a minimum of 3 Watts.
1. Verify that the jumpers are properly placed. See the wiring diagram located on the inside door of the TFX enclosure or see Figure 1.3 on page 1.12. The jumpers at JP3 should not be present and the jumpers at JP1 and JP2 will be in place. The jumper located beneath the microprocessor protection shield – the panel with the wiring diagram label mounted on it – should be positioned at JP2 for 9-16 Vdc input power and in JP1 position for 16-28 Vdc input power.
2. Connect the DC power source as illustrated in the schematic in Figure 1.5. Wire up to 14 AWG can be accommodated in the TFX terminal blocks.
Figure 1.5
DC Power Connection
Rev. 5/07 -1.14- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
General
The TFXD utilizes ISO-MODs for input and output functions. ISO­MODs are epoxy encapsulated electronic input/output modules that are simple to install and replace in the field. See Figure 1.6. All modules are 2,500 V optically isolated from TFXD power and earth grounds. This eliminates the potential for ground loops and reduces the chance of severe damage in the event of an electrical surge.
Seven ISO-MOD options are available, including: 4-20 mA, dual­relay, rate pulse, RS232C, RS485, BTU and 200k point data logger. The TFXD supports any two ISO-MOD input/output modules. All modules are field configurable by utilizing the keyboard or
UltraLink™ interface. Field wiring connections to ISO-MODs are
quick and easy using removable plug-in terminals. Configuration and connection of the various ISO-MODs are described on the following pages.
ISO-MOD Replacement
Figure 1.6 Two ISO-MOD I/O Modules Installed
To remove an ISO-MOD, remove the two machine screws that sec ure the module in place and pull the module straight out of the enclosure. A 10-pin connection is on the bottom of the module that mates with the circuit board underneath. Installation of a module is simply the reverse operation of removal. 4-20 mA modules will require calibration parameters to be entered if the module is replaced. See Part 3 of this manual for instructions on entry of calibration parameters.
Rev. 5/07 -1.15- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
4-20 mA Output
The 4-20 mA Output Module interfaces with most recording and logging systems by transmitting an analog current signal that is proportional to system flow rate. The 4-20 mA ISO-MOD may be configured via jumper selections for either an internally powered mode (current sourcing) Figure 1.7A or externally powered mode (current sinking) Figure 1.7B.
Internal Power Configuration: Ensure that jumpers are in place at JP1 and JP2 on the module. See Figure 1.7A. In this con figur ation the 4-20 mA output is driven from a +24 Vdc source located within the TFX flow meter. The 24 Vdc source is isolated from DC ground and earth ground connections within the TFX instrument. The module can accommodate loop loads up to 800 Ohms in this configuration.
NOTE: The +24 internal supply, if configured to power the 4-20 mA output, shares a common ground with another ISO-MOD (if ins t a ll e d). If another module is connected to earth ground, as is the case with a PC connection to an RS232 module or data logger, a ground loop may occur. The solution to this problem is to configure the 4-20 mA module for external power and utilize an external isolated supply to power the 4-20 mA loop.
External Power Configuration: Remove the two jumpers located at JP1 and JP2 on the module. See Figure 1.7B. In this configuration the 4-20 mA module requires power from an external DC power supply. The voltage of the external power source must
Figure 1.7A
Internally Powered
4-20mA
Figure 1.7B
Externally Powered
4-20mA
Rev. 5/07 -1.16- TFXD
Control Relays
PART 1 - INPUT/OUTPUT CONNECTIONS
be sufficient to power the module and drive the loop load. The loop loss attributed to the ISO-MOD is 7 Vdc, so the minimum voltage required to power a loop can be calculated using the following formula:
Loop voltage (min) = (loop load Ohms x 0.02) + 7
Two independent SPDT (single-pole, double-throw) Form C relays are contained in this module. The relay operations are user configured via software to act in either a flow rate alarm, signal strength alarm or totalizer/batching mode. The relays are rated for 200 Vac maximum and have a current rating of 0.5 A resistive load [175 Vdc @ 0.25 A resistive]. It is highly recommended that a secondary relay be utilized whenever the Control Relay ISO-MOD is used to control inductive loads such as solenoids and motors.
Typical relay connections are illustrated in Figure 1.8A. The reed relays located within the relay module can interface directly with small pilot lights, PLCs, electronic counters and SCADA systems.
Figure 1.8B describes the connection of an external power relay to the Relay ISO-MOD. It is recommended that external power relays are utilized whenever the load to be switched exceeds the switch rating of the reed relays, or if the load is inductive in nature.
Figure 1.8A
Typical Relay
Connections
Figure 1.8B Slave Relay
Connections
POWER SOURCE
Rev. 5/07 -1.17- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
Rate Pulse
The Rate Pulse Output Module is utilized to transmit information to external counters and PID systems via a frequency output that is proportional to system flow rate. The frequency output range of the Rate Pulse Module is 0–2,500 Hz. This module has two types of outputs: one simulates the output of the coil of a turbine flow meter, and the other is an open-collector type that does not source voltage at its output. Both outputs may be connected simultaneously.
The turbine meter output creates a 500 mV peak-to-peak saw-tooth waveform that is not referenced to ground. This output can be run to electronic monitors that are compatible with variable reluctance outputs from coils, such as those found in turbine and paddle-wheel flow meters. The input impedance of the receiving device should not be smaller than 2,000 Ohms.
The standard pulse output does not output a voltage, but acts as an “open-collector” output requiring an external power source and pull­up resistor. See Figure 1.9. The MOSFET in the Rate Pulse Module can support loads of 100 V @ 1A. Resistor selection is based on the input impedance of the receiving device. Select a resistor that is a maximum of 10% of the input impedance of the receiving device, but do not exceed 10k Ohms.
Figure 1.9
Rate Pulse Module
Rev. 5/07 -1.18- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
RS232C
The RS232C Module will interface with the serial communication ports of PCs, PLCs and SCADA systems that are used to monitor flow rate information in piping systems. A proprietary digital communications protocol is used for this communication. An explanation of the command structure is detailed in the Appendix of this manual. Flow rate, total, signal strength and temperature (if so equipped) can be monitored over the digital communications module. The RS232C Module may also be used to form a hardwire
connection to a PC that is running the UltraLink
software utility.
Baud rates up to 19.2k are supported. Figure 1.10 illustrates typical connections.
Figure 1.10
RS232 Connections
Rev. 5/07 -1.19- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
RS485
The RS485 Module allows up to 128 TFX systems to be placed on a single three-wire cable bus. All meters are assigned a unique one byte serial number that allows all of the meters on the cable netwo rk to be independently accessed. A proprietary digital communications protocol is used for this communication. An explanation of the command structure is detailed in the Appendix of this manual. Flow rate, total, signal strength and temperature (if so equipped) can be monitored over the digital communications bus. Baud rates up to 9600 and cable lengths to 5,000 feet [1,500 meters] are supported without repeaters or “end of line” resistors. UltraLink™ is also compatible with a multiple TFX network, allowing individual meters to be accessed, programmed, diagnosed and calibrated.
To interconnect meters, utilize three-wire shielded cable such as Belden 9939 or equal. In noisy environments the shield should be connected on one end to a good earth ground connection. An RS232 to RS485 scond, such as B&B electronics p/n 485SD9TB (illustrated in Figure 1.11) is required to interconnect the RS485 network to a communication port on a PC. If more than 128 meters must be monitored, an additional scond and communication port is required.
Figure 1.11
RS485 Network
Connections
Rev. 5/07 -1.20- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
Data Logger The 200,000 event data logger/electronic stripchart recorder can be
configured to match most user applications. The logger stores time­stamped, high resolution (16-bit) data at user selected intervals ranging from 1 to 1,000 seconds. Configuration of and data retrieval from the logger are detailed in Sections 3 and 4 of this manual.
The module can be carried in a shirt pocket back to the office and plugged into a PC serial port via the module’s integral DB-9 connector. See Figure 1.12. This eliminates the requirement to carry a computer to the flow meter site. The data in the logger can also be accessed without removing the module from the flow meter. Open the door of the flow meter and interconnect the 9-pin cable between the data logger and the PC serial communications port.
Figure 1.12
Data Logger Connection
The logger is capable of storing up to 200,000 measurements. The measurements are broken into 16 blocks or pages with a maximum number of data points per block of 30,000.
If each block (page) is filled to the maximum 6-2/3 blocks would be used:
200,000 Points
30,000 Points
= 6-2/3 Pages
If all 16 blocks are to be used, each block could hold 12,500 data points:
200,000 Points
16 Pages
= 12,500 Points per page
NOTE: The logger will not automatically go to the next page if the previous page is filled. In this case when the page exceeds 30,000 data points the oldest points will be discarded in favor of new points. This is the classic FIFO memory stack.
Rev. 5/07 -1.21- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
Up to 16 separate logging sessions are possible with up to 12,500 points each but for each new measurement session the logger must be stopped, a new page selected using the data logger utility, and then the logging must be started again. Similarly if a single point data acquisition session were to exceed 30,000 points the logger must be stopped, a new page selected using the data logger utility, and then the logging must be started again.
NOTE: The data logger is not accessible using the TFXD’s infrared adapter. Communications between the data logger and computer must be accomplished using a directly connected RS232C or RS485 connection.
NOTE: When a PC is connected to the data logger, it inhibits the logger from collecting additional data.
Heat Flow
The RTD Module allows integration of two 1000 Ohm, platinum RTDs with the TFXD flow meter, effectively providing an instrument for measuring energy delivered in liquid cooling and heating systems. The RTD Module is installed in the base of the TFX flow transmitter. Each module is factory configured and encapsulated; it cannot be altered. The configuration of the module will be indicated by a factory mark in the box next to the module part number (see Figure 1.13). If the module is not configured for the appropriate temperature range for the installation, please contact the Dynasonics factory to arrange for a replacement.
Module Temperature Range
D020-1045-106 -40 to +200 °C [-40 to +400 °F] D020-1045-112 0 to +50 °C [+32 to +122 °F]
D020-1045-113 0 to +100 °C [+32 to +212 °F]
Figure 1.13
RTD Module Configuration
If RTDs were ordered with the TFXD flow meter they have been factory calibrated and shipped connected to the module as they were calibrated. If necessary, the green terminal block on the module can be disconnected from the RTD module and the plug routed out through the conduit hole in the bottom of the enclosure. Simply turn the plug lengthwise and guide it through the hole. If the
Rev. 5/07 -1.22- TFXD
PART 1 - INPUT/OUTPUT CONNECTIONS
RTDs must be disconnected from the terminal block, it is recommended that the RTDs and the wires be marked so that they may be returned to their respective terminals – retaining the factory calibration.
Dynasonics offers two types of RTDs:
SURFACE MOUNT RTDS D010-3000-102 set of two, 130 °C Maximum Temperature D010-3000-105 set of two, 200 °C Maximum Temperature
INSERTION RTDS D010-3000-103 single, 3 inch [75 mm], 0.25 inch OD D010-3000-104 single, 6 inch [150 mm], 0.25 inch OD
All RTDs are 1,000 Ohm platinum, three-wire connection and have 20 feet [6 meters] of shielded cable attached. Additional wire may be attached so long as the wiring convention is retained. Figure 1.14 illustrates the connection of surface mount RTDs, D010-3000-105 and D010-3000-102. The wire color code on the insertion RTDs is identical to the surface mount types. A schematic of the RTD connections is illustrated in Figure 1.15.
Figure 1.14
RTD
Connections
Figure 1.15
RTD
Connection
Schematic
NOTE: Connect the shield to earth ground of the power connector
J2 (see Figure 1.15).
Rev. 5/07 -1.23- TFXD
PART 1 - STARTUP AND CONFIGURATION
Before Starting the Instrument
Instrument Startup
Important!
NOTE: The TFX flow meter system requires a full pipe of liquid before a successful startup can be completed. Do not attempt to
make adjustments or change configurations until a full pipe is verified.
NOTE: If Dow 732 RTV was utilized to couple the transducers to the pipe, the adhesive must fully cure before power is applied to the instrument. Dow 732 requires 24 hours to cure satisfactorily. If Dow 111 silicone grease was utilized as a couplant, the curing time is not required.
Procedure:
1. Verify that all wiring is properly connected and routed, as described in Part 1 of this manual.
2. Verify that the transducers are properly mounted, as described in Part 2 of this manual.
3. Apply power. The display of a TFXD2 will display a software version number and then all of the segments will illuminate in succession. (TFXD1 systems do not have a display or keypad, so UltraLink
or an electronic I/O module must be monitored.)
The meter will then enter run mode.
In order to complete the installation of the TFX flow meter, the pipe must be full of liquid.
To verify proper installation and flow measurement operation:
1. Go to the SER MENU. Confirm that signal strength (SIG STR) is between 2.0% and 195%. If the signal strength is lower than
2.0%, verify that proper transducer mounting methods and liquid/ pipe characteristics have been entered. To increase signal strength, if a W-Mount transducer installation has been selected, reconfigure for a V-Mount installation; if V-Mount has been selected, reconfigure for Z-Mount.
2. Verify that the actual measured liquid sound speed is very close to the expected value (see page 2.11 for further details). The measured liquid sound speed (SSPD FPS and MPS) is displayed in the SERVICE Menu. Verify that the measured sound speed is within 2% of the value entered as FLUID SS in the BASIC Menu. The pipe must be full of liquid in order to make this measurement.
3. Once the meter is properly operating, refer to Part 3 of this manual for additional programming features.
Rev. 5/07 -1.24- TFXD
PART 2 - TRANSDUCER & RTD INSTALLATION
General
The transducers that are utilized by the TFXD contain piezoelectric crystals for transmitting and receiving ultrasound signals through walls of liquid piping systems. DTTN and DTTH transducers are relatively simple and straightforward to install, but spacing and alignment of the transducers is critical to the system's accuracy and performance. Extra care should be taken to ensure that these instructions are carefully executed. DTTS, small-pipe transducers, have integrated transmitter and receiver elements that eliminate the requirement for spacing measurement and alignment.
Mounting of the DTTN/DTTH clamp-on ultrasonic transit time transducers is comprised of three steps:
1. Selection of the optimum location on a piping system.
2. Entering the pipe and liquid parameters into either the optional software utility (UltraLink™) or keying the parameters into the TFXD keypad. (TFXD systems that do not have an integral keypad will require the use of UltraLink™ and a PC computer.) The software embedded in UltraLink™ and the TFXD firmware will calculate proper transducer spacing based on these entries.
3. Pipe preparation and transducer mounting.
TFXD transmitters with an RTD ISO-MOD module installed require either one or two RTDs to measure heat flow (one RTD) or heat usage (two RTDs). The Dynasonics flow meter utilizes 1,000 Ohm, three-wire, platinum RTDs in two mounting styles. Surface mount RTDs are available for use on well insulated pipe. If the area where the RTD will be located is not insulated, inconsistent temperature readings will result and insertion (wetted) RTDs should be utilized. Instructions for the installation of the RTDs begin on page 2.17.
Rev. 5/07 - 2.1 - TFXD
PART 2 - TRANSDUCER & RTD INSTALLATION
1. Mounting Location
The first step in the installation process is the selection of an optimum location for the flow measurement to be made. For this to be done effectively, a basic knowledge of the piping system and its plumbing is required.
An optimum location is defined as:
A piping system that is completely full of liquid when
measurements are being taken. The pipe may become completely empty during a process cycle - which will result in an error code being displayed on the flow meter while the pipe is empty. Error codes will clear automatically once the pipe refills with liquid. It is not recommended to mount the transducers in an area where the pipe may become partially filled. Partially filled pipes will cause erroneous and unpredictable operation of the meter.
A piping system that contains lengths of straight pipe such
as those described in Table 2.1 on page 2.4. The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation. The straight runs in Table 2.1 apply to liquid velocities that are nominally 7 FPS [2.2 MPS]. As liquid velocity increases above this nominal rate, the requirement for straight pipe increases proportionally.
Mount the transducers in an area where they will not be
inadvertently bumped or disturbed during normal operation.
Avoid installations on downward flowing pipes unless
adequate downstream head pressure is present to overcome cavitation in the pipe.
Rev. 5/07 - 2.2 - TFXD
PART 2 - TRANSDUCER & RTD INSTALLATION
2. Transducer Spacing
TFX transit time flow meters are sold with three different transducer types: DTTN, DTTH and DTTS. Meters that utilize DTTN and DTTH transducers consist of two separate sensors that function as both ultrasonic transmitters and receivers. DTTS transducers integrate both the transmitter and receiver into one assembly that fixes the separation of the piezoelectric elements. DTTN and DTTH transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-Mount where the sound transverses the pipe twice, W-Mount where the sound transverses the pipe four times, or in Z-
Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. For further details, reference pictures located under Table 2.2 on page 2.5. The appropriate mounting configuration is based on pipe and liquid characteristics. Selection of the proper transducer mounting method is not entirely predictable and many times is an iterative process. Table 2.2 contains recommended mounting configurations for common applications. These recommended configurations may need to be modified for specific applications if such things as aeration, suspended solids or poor piping conditions are present. W-Mount provides the longest sound path length between the transducers - but the weakest signal strength. Z-Mount provides the strongest signal strength - but has the shortest sound path length. On pipes smaller than 3 inches [75 mm], it is desirable to have a longer sound path length, so that the differential time can be measured more accurately. Use of the TFX diagnostics in determining the optimum transducer mounting is covered later in this section.
Rev. 5/07 - 2.3 - TFXD
PART 2 - TRANSDUCER & RTD INSTALLATION
Table 2.1
Straight Pipe Requirements
Rev. 5/07 - 2.4 - TFXD
Loading...
+ 92 hidden pages