This manual is intended to help you get the TFX-5000 meter up and running quickly.
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
Typographic Conventions
• In step-by-step instructions, bold text indicates items on the screen you need to select or act upon.
Example: Click the Setup menu.
• Names of parameters, options, boxes, columns and fields are italicized.
Example: The value displays in the Status field.
• Messages and special markings are shown in quotation marks.
Example: “Error” displays in the title bar.
• In most cases, software screen text appears in the manual as it does on the screen. For example, if a word is capitalized on
the screen, it is capitalized when referred to in the manual.
UNPACKING AND INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such
as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE: NIf damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
SAFETY
Terminology and Symbols
Indicates a hazardous situation, which, if not avoided, will result in death or serious personal injury.
WARNING
Considerations
• The installation of the TFX-5000 meter must comply with all applicable federal, state, and local rules, regulations,
and codes.
• Do not use sharp objects when operating the device (such as using a pen to press buttons on the keypad).
• When the TFX-5000 meter is a part of a system, it is configured in a fail-safe operation so that if the transmitter signal is
compromised, the TFX-5000 meter will not cause harm to the system.
MPORTANTI
Not following instructions properly may impair safety of equipment and/or personnel.
WARNING
AFTER DEENERGIZING, DELAY 5 MINUTES BEFORE OPENING.
Indicates a hazardous situation, which, if not avoided, could result in death or serious personal injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate personal injury or
damage to property.
Page 5 July 2020TTM-UM-02222-EN-10
Introduction
INTRODUCTION
WARNING
THIS EQUIPMENT INCLUDES SOME EXTERNAL NONMETALLIC PARTS. THE USER SHALL THEREFORE ENSURE THAT
THE EQUIPMENT IS NOT INSTALLED IN A LOCATION WHERE IT MAY BE SUBJECTED TO EXTERNAL CONDITIONS SUCH
AS HIGHPRESSURE STEAM WHICH MIGHT CAUSE A BUILDUP OF ELECTROSTATIC CHARGES ON NONCONDUCTING
SURFACES. ADDITIONALLY, CLEANING OF THE EQUIPMENT SHOULD BE DONE ONLY WITH A DAMP CLOTH.
The TFX-5000 transit time meter measures volumetric flow and heating/cooling energy rates in clean liquids as well as those
with small amounts of suspended solids or aeration, such as surface water or sewage. TFX-5000 ultrasonic flow and energy
meters clamp onto the outside of pipes and do not contact the internal liquid.
The TFX-5000 meter is available in two versions:
• A flow meter for water delivery, sewage, cooling water, alcohols, chemical
• A heating/cooling energy flow meter used in conjunction with dual clamp-on RTDs for temperature measurement—ideal
for hydronic process and HVAC applications
Transit time flow meters measure the time difference between the travel time of an ultrasound wave going with the fluid
flow and against the fluid flow. The time difference is used to calculate the velocity of the fluid traveling in a closed-pipe
system. The transducers used in transit time measurements operate alternately as transmitters and receivers. Transit time
measurements are bi-directional and are most effective for fluids that have low concentrations of suspended solids and are
sonically conductive.
Figure 1: Meter operation
An ultrasonic meter equipped with heat flow capabilities measures the rate and quantity of heat delivered or removed from
devices such as heat exchangers. By measuring the volumetric flow rate of the heat exchanger liquid, the temperature at the
inlet pipe and the temperature at the outlet pipe, the energy usage can be calculated.
By applying a scaling factor, this heat flow measurement can be expressed in various units (Btu, Watts, Joules, Kilowatts
and others).
DIMENSIONS
OTE: NInstallation instructions begin on page 10.
Remote Enclosure
Torque the
cover screws
to 45 in-lb.
6.50 in.
(165.10 mm)
3.63 in.
(92.20)
6.50 in.
(165.10 mm)
0.90 in.
(22.86 mm)
Figure 2: Remote mount enclosure dimensions
Page 6 July 2020TTM-UM-02222-EN-10
Wall Mount Bracket
Dimensions
2.00 in.
(50.80 mm)
2.50 in.
(63.50 mm)
2.00 in.
(50.80 mm)
Figure 3: Wall mount enclosure dimensions
2.00 in.
(50.80 mm)
2.50 in.
(63.50 mm)
2.00 in.
(50.80 mm)
Panel Mount Enclosure
Torque the
cover screws
to 45 in-lb.
6.50 in.
(165.10 mm)
Figure 4: Panel mount enclosure dimensions
6.50 in.
(165.10 mm)
1.38 in.
(35.05 mm)
Customer-supplied panel
1.25 in.
(31.75 mm)
Page 7 July 2020TTM-UM-02222-EN-10
Operation
OPERATION
Keypad Operation on the Home Screen
The MENU/BACK key enters menu structure.
The DOWN ARROW key toggles between flow rate, flow total, velocity and flow rate with flow total.
The RIGHT ARROW key has no function.
The ENTER key has no function.
Keypad Operation in the Menu Structure
The cursor bar highlights the submenu or parameter that will be viewed or edited. The scroll bar on the right indicates the
relative position the cursor bar is at on the list when there are more than 4 items.
• MENU/BACK returns to parent menu (up a level). If at the Main (top level) menu, returns to the Home Screen.
• DOWN ARROW scrolls the list.
• RIGHT ARROW and ENTER have the same function in the menu structure and advance to the submenu or to
read/edit a parameter.
Page 8 July 2020TTM-UM-02222-EN-10
Operation
Selecting an Option in a Parameter Selection List
The active option in the parameter list has a filled-in box on the left side. The scroll bar on the right indicates the relative
position the cursor bar is at on the list when there are more than 4 items.
• DOWN ARROW scrolls the list.
• ENTER selects the option and the box on the left side fills in to show the item is selected.
• MENU/BACK exits parameter editing and returns to the parent menu (up a level).
Entering a Number
The parameter name and current value is displayed in the top portion of the screen. Edit the number on the bottom right of
the screen.
• MENU/BACK exits parameter editing and returns to parent menu (up a level). The parameter remains at the value displayed
in the top portion of the screen.
• DOWN ARROW cycles through the numbers and other options.
• RIGHT ARROW moves the cursor to the right. Once it reaches the rightmost digit or a space, the cursor moves to the
leftmost digit.
• ENTER accepts the value.
Page 9 July 2020TTM-UM-02222-EN-10
Installation
INSTALLATION
Overview
Each of the installation steps that follow is explained in detail on page 11 through page 12 . The actual installation
procedures differ slightly, depending on whether the transducers are fixed or adjustable.
If the transducers are fixed, you will:
1. Install the transducers.
2. Install the transmitter.
3. Wire the transmitter.
4. Program the meter.
If the transducers are adjustable, you will:
1. Install the transmitter.
2. Wire the transmitter.
3. Set up the meter (select the optimum transmission mode, enter the site information, and enter the uid and
pipe properties).
4. Install the transducers.
5. Complete the meter programming.
Installation Considerations
Mount the transmitter in a location:
• Where little vibration exists.
• That is protected from corrosive fluids.
• That is within the transmitters ambient temperature limits:
–4…140° F (–20…60° C); relative humidity 0…85%, non-condensing; altitude 2000 m max.
• That is out of direct sunlight. Direct sunlight may increase transmitter temperature above the maximum limit.
• That protects the oleophobic vent from materials that may plug or seal the vent.
Equipment Required
• Screwdrivers, wide blade and tiny blade (for securing wires to the terminal blocks)
• User manual for the transducers
• Four #8 or M4 screws, if mounting the transmitter on a wall
• Stainless steel banding straps, if mounting the transmitter on a pipe
Installing the Transducers
See the user manual for your particular transducer for installation instructions.
Page 10 July 2020TTM-UM-02222-EN-10
Wall Mounting
Wall Mounting
Installation
Installing a Meter with a Remote Transmitter and Fixed Transducers
• Locate the transmitter within the length of the transducer cables supplied or exchange the cable for one of proper length.
• See Figure 2 on page 6 for enclosure and mounting dimension details. Allow enough room for door swing, maintenance
and conduit entrances.
MPORTANTI
When routing wires to the transmitter, make sure the cables are not twisted, pinched or hanging loosely.
1. Install the xed transducers according to instructions in the transducer user manual.
2. Attach the mounting bracket to a wall (with 4 customer-supplied #8 or M4 screws, see “Wall Mount Bracket” on page7
for dimensions) or to a pipe (with mounting straps).
Holes for
Screws for
Figure 5: Wall mountFigure 6: Pipe Mount
Holes for
Screws for
Slots for
Straps for
Pipe Mounting
Slots for
Straps for
Pipe Mounting
3. Align the transmitter's bracket with the mounted bracket. Use a 4 mm hex tool to secure the 4 provided screws from the
sides through the mating holes. See Figure 8.
4. If necessary, you can rotate the mounting bracket in 90° increments to accommodate the nal orientation of the
transmitter. From inside the enclosure, remove the 4 screws holding the bracket. Rotate the bracket and replace the
screws. See Figure 7.
Figure 7: Rotatable adapter plateFigure 8: Secure the bracket
5. Insert a wire for earth ground under the grounding bracket (see Figure 10) and screw it down tight.
6. Partially loosen the 2 enclosure captive screws on the left side of the transmitter cover. Completely loosen the 2 screws on
the right side. Grasp and lift the cover and open it to the left. The cover remains attached and the left screws act as a hinge.
Unscrew
Captive Screws
Figure 9: Captive cover screwsFigure 10: Lift cover from baseFigure 11: Open cover to the left
7. Use conduit holes where cables enter the enclosure from the bottom. Use suitably certied plugs to seal any holes that are
not used for cable entry. A cable gland kit is included for inserting the transducer and power cables.
1/2 in. NPT,
1/2 in. BSPP, or
M20 Threads
Figure 12: Conduit holes
Page 11 July 2020TTM-UM-02222-EN-10
Wall Mounting
Wall Mounting
Installation
OTE: NUse suitably certied fittings/plugs to maintain the watertight integrity of the enclosure. Generally, the right conduit
hole (viewed from front) is used for power, the left conduit hole for transducer connections, and the center holes are
used for I/O wiring.
8. Install the wires through the gland nuts and connect the wires to the removable terminal blocks. See “Wiring the
Transmitter” on page14.
9. Wire the transducers to the transmitter.
10. Plug the wired terminal blocks into the main board.
11. Reassemble the cover. Torque the cover screws to 45 in-lb.
12. Set up the meter. See “Initial Meter Setup” on page21 for instructions.
Installing a Meter with a Remote Transmitter and Adjustable Transducers
• Locate the transmitter within the length of the transducer cables supplied or exchange the cable for one of proper length.
• Install the transducers after entering the pipe settings into the transmitter and determining the spacing and
mounting method.
• See Figure 2 on page 6 for enclosure and mounting dimension details. Allow enough room for door swing, maintenance
and conduit entrances.
MPORTANTI
When routing wires to the transmitter, make sure the cables are not twisted, pinched or hanging loosely.
1. Attach the mounting bracket to a wall (with 4 customer-supplied #8 or M4 screws, see “Wall Mount Bracket” on page7
for dimensions) or to a pipe (with mounting straps).
Holes for
Screws for
Figure 13: Wall mountFigure 14: Pipe Mount
Holes for
Screws for
Slots for
Straps for
Pipe Mounting
Slots for
Straps for
Pipe Mounting
2. Align the transmitter's bracket with the mounted bracket. Use a 4 mm hex tool to secure the 4 provided screws from the
sides through the mating holes. See Figure 16.
3. If necessary, you can rotate the mounting bracket in 90° increments to accommodate the nal orientation of the
transmitter. From inside the enclosure, remove the 4 screws holding the bracket. Rotate the bracket and replace the
screws. See Figure 15.
Figure 15: Rotatable adapter plateFigure 16: Secure the bracket
4. Insert a wire for earth ground under the grounding bracket (see Figure 18) and screw it down tight.
5. Partially loosen the 2 enclosure captive screws on the left side of the transmitter cover. Completely loosen the 2 screws on
the right side. Grasp and lift the cover and open it to the left. The cover remains attached and the left screws act as a hinge.
Page 12 July 2020TTM-UM-02222-EN-10
Unscrew
Captive Screws
Figure 17: Captive cover screwsFigure 18: Lift cover from baseFigure 19: Open cover to the left
Installation
6. Use conduit holes where cables enter the enclosure from the bottom. Use suitably certied plugs to seal any holes that are
not used for cable entry. A cable gland kit is included for inserting the transducer and power cables.
1/2 in. NPT,
1/2 in. BSPP, or
M20 Threads
Figure 20: Conduit holes
OTE: NUse suitably certied fittings/plugs to maintain the watertight integrity of the enclosure. Generally, the right conduit
hole (viewed from front) is used for power, the left conduit hole for transducer connections, and the center holes are
used for I/O wiring.
7. Install the wires through the gland nuts and connect the wires to the removable terminal blocks. See “Wiring the
Transmitter” on page14.
8. Set up the meter. See “Initial Meter Setup” on page21 for instructions.
9. Install the adjustable transducers according to instructions in the transducer user manual.
10. Wire the transducers to the transmitter.
11. Plug the wired terminal blocks into the main board.
12. Reassemble the cover. Torque the cover screws to 45 in-lb.
Installing a Panel-Mount Meter
1. Measure and cut a mounting hole into the customer-supplied panel to the dimensions shown in Figure 21.
2. Remove the 4 screws and 4 O-rings holding the front of the unit to the frame.
3. Verify that the gasket is secure in the mounting bezel.
4. Guide the front of the unit through the panel cutout.
5. Insert the 4 screws through the front of the unit and the panel.
6. Apply one O-ring to each screw from the back of the panel.
7. Align the front of the unit to the frame.
8. Tighten the 4 screws and torque them to 45 in-lb.
Frame
Customer-supplied panel
Ø 0.252 in. thru
typ.
(144.78 mm)
2.85 in.
(72.93 mm)
5.50 in.
(139.70 mm)
5.70 in.
4.80 in.
(121.92 mm)
2.85 in.
(72.39 mm)
(144.78 mm)
Screws (×4)
5.70 in.
O-rings (×4)
Figure 21: Panel cutout dimensions and installation exploded view
Page 13 July 2020TTM-UM-02222-EN-10
TB400
Wiring the Transmitter
WIRING THE TRANSMITTER
IMPORTANT: Select field wiring means rated for 5° C above the maximum area temperature when it is possible that the
temperature will exceed 55° C.
To access terminal strips for wiring, loosen the 4 enclosure captive screws. Grasp and lift the cover and open it to the left. The
cover remains attached and the left screws act as a hinge.
Torque Requirements
The tightening torque requirements for the screw connections of the plug-in terminals are 4.4 lb-in. (0.5 Nm) minimum to
Conductor cross section solid0.2 mm²2.5 mm²
Conductor cross section flexible0.2 mm²2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm²2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve0.25 mm²2.5 mm²
Conductor cross section AWG2412
2 conductors with same cross section, solid0.2 mm²1 mm²
2 conductors with same cross section, stranded 0.2 mm²1.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve0.25 mm²1 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve0.5 mm²1.5 mm²
AWG according to UL/CUL3012
Page 14 July 2020TTM-UM-02222-EN-10
Rated Conditions of Terminals
• Mains AC 85…264V AC
Wire 18…12 AWG UL AWM 1007 Type 1007
• 9…28V DC, 20…26V AC
Wire 20 AWG UL AWM 1007 Type 1007
• Transducer Cables
Badger Meter supplied cable
• Digital Outputs/Inputs, Current Output, RS485, RTD or Encoder Interface
• Wire 28…12 AWG UL AWM 1007 Type 1007
Wiring the Transducer
Wiring the Transmitter
Figure 24: Wiring connections
OTE: NSubmersible transducer cables are larger diameter. Each cable requires a separate conduit hole. The standard yellow
cable and high temperature cables are small enough to use a single cable gland with a 2-hole grommet.
OTE: NTransducer cables have two wire-color combinations. For the blue and white combination, the blue wire is positive
(+) and the white wire is negative (–). For the red and black combination, the red wire is positive (+) and the black
wire is negative (–). The transducer wires are labeled to indicate which pair is upstream or downstream.
1. Guide the transducer terminations through a conduit hole in the bottom of the enclosure.
2. Secure the transducer cable with the supplied conduit nut (if exible conduit was ordered with the transducer).
3. Install the ferrite to the cable:
a. To open the ferrite, pull the fastener away from the
body of the ferrite.
b. Wrap the cable tightly around half of the ferrite and
place the cable into the groove.
c. Snap the ferrite shut.
4. The terminals within the transmitter are screw-down barrier terminals. Connect the wires at the corresponding screw
terminals in the transmitter. Observe upstream and downstream orientation and wire polarity. See Figure 25.
TB300
Red
Black
Green (2)
Red
Black
Inner Shield
Outer Shield
Upstream+
Upstream-
69039, Triax Cable
Downstream+
Downstream-
Transducer
Figure 25: Upstream/downstream transducer
Page 15 July 2020TTM-UM-02222-EN-10
Wiring the Transmitter
Power
Connect power to the screw terminal block in the transmitter.
• Low voltage power can use any available conduit hole in the enclosure.
• Line voltage AC power must use the right conduit hole, which is aligned with the terminal block on the AC power board.
• Use wiring practices that conform to local and national codes such as The National Electrical Code Handbook in the U.S.
ANY OTHER WIRING METHOD MAY BE UNSAFE OR CAUSE IMPROPER OPERATION OF THE TRANSMITTER.
OTE: NThis transmitter requires clean electrical line power. Do not operate this transmitter on circuits with noisy
components (such as fluorescent lights, relays, compressors, or variable frequency drives). Do not use step-down
transformers from high voltage, high amperage sources. Do not to run signal wires with line power within the same
wiring tray or conduit.
9…28V DC Power
The transmitter may be operated from a 9…28V DC source, as long as the source supplies a maximum of 8 Watts of power.
Connect the DC power to 9…28V DC In, power return, and chassis ground, as in Figure 26.
OTE: NDC-powered transmitters are protected from major catastrophe with an internal 2.0 Amp slow-blow fuse. If this fuse
is blown, replace the transmitter or return it to the factory for repair.
IMPORTANT: A Class II DC power supply is required.
TB400
+
-
Switch
or
Circuit
Breaker
Chassis Ground
Figure 26: Power supply 9…28V DC
External Equipment
Power Supply (9 . . . 28V DC)
Power Supply (Return)
(Acceptable wire sizes: 28…12 AWG)
20…26V AC Power
The transmitter may be operated from a 20…26V AC source, as long as the source supplies a maximum of 8 Watts of power.
Connect the AC power to 20…26V AC In, power return, and chassis ground, as in Figure 27.
OTE: N24V AC powered transmitters are protected from major catastrophe with an internal 2.0 Amp slow-blow fuse. If this
fuse is blown, replace the transmitter or return it to the factory for repair.
TB400External Equipment
+
-
Switch
or
Circuit
Breaker
Chassis Ground
Figure 27: Power supply 20…28V AC
Power Supply (20 . . . 26V AC)
Power Supply (Return)
(Acceptable wire sizes: 28…12 AWG)
Page 16 July 2020TTM-UM-02222-EN-10
Wiring the Transmitter
Mains Power
IMPORTANT: The measuring device does not have an internal circuit breaker. For compliance with IEC 61010-1, a switch in close
proximity to the transmitter is required so that the power supply line can be easily disconnected from the mains.
The transmitter may be operated from 90…250V AC, 47…63 Hz, 24VA maximum power source.
OTE: NMains AC-powered transmitters are protected with 1A, 250V AC, 5×20 mm, slow-blow, field-replaceable fuse.
WARNING
TO PREVENT SHORTING OUT THE MAINS AC POWER, YOU MUST REPLACE THE TERMINAL BLOCK COVER ON THE AC
MODULE AFTER WIRING THE POWER.
Remove the terminal block covers before wiring and replace them after wiring:
1. Grasp the sides of the cover and gently pull it up.
2. Insert wires into the slots on the cover and screw them down to secure.
3. Align the cover in its original orientation over the terminal block and push down to connect.
TB400External 85…264V
+
-
Factory Wired
AC-DC Power Module
(24VA max.)
Red
Black
Green
24V DC
0V DC
Chassis Ground
AC-L
AC-N
.
Connect protective earth conductor to terminal 3.
TB100
1
2
3
Switch
or
Circuit
Breaker
85 . . . 264V AC
Return
(Main power wiring must be of material
VW-1 or better.)
(Acceptable wire sizes: 18…12 AWG)
Protective
Ground
Figure 28: AC/DC power connections
4…20 mA Output Wiring
The 4…20 mA output transmits an analog current signal that is proportional to system flow rate. The 4…20 mA output can be
internally or externally powered and can span negative to positive flow rates.
Both current loops are ISOLATED from DC GND or Power.
ISO_GND
TP605
TP604
TB600
Black
Red
8
7
6
5
4
3
2
1
No Connect
No Connect
4…20 OUT 2 Current #2 Output
4…20 OUT 1 Current #1 Output
(Acceptable wire sizes: 28…12 AWG)
External Equipment
800 Ohms max.
Power Supply
Common
800 Ohms max.
NOTE: 4…20 OUT 2 available
with Energy model only.
Figure 29: Typical 4 . . . 20 mA interface using internal isolated 24V DC source
Page 17 July 2020TTM-UM-02222-EN-10
Wiring the Transmitter
NOTE: 4…20 OUT 2 available
with Energy model only.
Digital Outputs Wiring
NOTE: Control Output 3
available with Energy
model only.
TP605
Black
TP604
Red
8
No Connect
7
No Connect
TB600
6
5
4
3
2
1
4…20 OUT 2 Current #2 Output
4…20 OUT 1 Current #1 Output
+24V DC Source In
No Connect
(Acceptable wire sizes: 28…12 AWG)
ISO_GND
Figure 30: Typical 4 . . . 20 mA interface using external isolated 24V DC source
ISO 24V
10k
TB700
External Equipment
800 Ohms max.
Power Supply
Common
800 Ohms max.
Power
TYP 24V DC
ISO_GND
NOTE: Control Output 3
available with Energy
model only.
10 Ohms
50 mA max. Sink
ISO_GND
10 Ohms
R12
R12
(Acceptable wire sizes: 28…12 AWG)
Figure 31: Typical control out 1, 2 and 3 interface with internal pullups active
Control Output #1
Control Output #2
Control Output #3
ISO_GND
(Acceptable wire sizes: 28…12 AWG)
Figure 32: Typical control out 1, 2 and 3 interface with external pullups passive
Control Output #1
Control Output #2
Control Output #3
ISO_GND
ISO_GND
TB700
5
6
7
8
9
10
5
6
7
8
9
10
IF REQUIRED
IF REQUIRED
IF REQUIRED
IF REQUIRED
External Equipment
External Equipment
V DC (5 . . . 30V DC)
R-Pullup
R-Pullup
R-Pullup
Control Output #1
Control Output #2
Control Output #3
Control Output #1
Control Output #2
Control Output #3
Page 18 July 2020TTM-UM-02222-EN-10
Wiring the Transmitter
RS485 Output
The RS485 feature allows up to 126 transmitters to be placed on a single three-wire cable up to 4000 feet. All transmitters are
assigned a unique numeric address that allows all of the transmitters on the cable network to be independently accessed.
Either Modbus RTU or BACnet MS/TP protocol is used to interrogate the transmitters.
Flow rate and total can be monitored over the digital communications bus.
When a USB programming cable is connected, the RS485 and frequency outputs are disabled.
Terminator Resistors
(Enabled through Parameter Setting)
60.4 Ohms
60.4 Ohms
A B
TB700
3
4
External Equipment
RS485 +
RS485 −
Figure 33: Typical RS485 interface
Digital Input WiringAquaCUE/BEACON Endpoint Wiring
1
2
3
4
5
6
7
8
9
10
TB700
Reset Total +
Reset Total -
Push-button
5…30V DC
TB500
4
3
2
1
NOTE: Non-isolated
Endpoint Data Pulse Out (Green Wire)
DGND (Black Wire)
Endpoint VccClk In (Red Wire)
(Acceptable wire sizes: 28…12 AWG)
AquaCUE/BEACON
Endpoint
Figure 34: Digital input—reset totalizerFigure 35: AquaCUE/BEACON wiring
IN A HAZARDOUS LOCATION WHERE EXPLOSIVE GAS OR DUST IS PRESENT, DISCONNECT THE POWER BEFORE
OPENING THE ENCLOSURE AND INSERTING OR REMOVING THE MICROSD CARD. AFTER THE CARD IS INSERTED OR
REMOVED, CLOSE THE ENCLOSURE BEFORE REAPPLYING POWER.
1. In all locations, turn o power to the unit.
2. Remove the enclosure cover.
3. Put your nger in the groove of the tray and slide the tray downward. The tray springs open.
5. Insert the MicroSD card.
6. Slide the cover up to close.
7. Replace the enclosure cover.
Page 20 July 2020TTM-UM-02222-EN-10
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.