• “Quick-Start Operating Overview” on page8 is intended to help you get the TFX Ultra flow metering system up and
running quickly. Refer to the detailed instructions if you require additional information.
• The remaining chapters provide a detailed description of all software settings and hardware installation guidance.
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
UNPACKING AND INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such
as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:NIf damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
SAFETY
Terminology and Symbols
Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing death or serious
personal injury.
Indicates a hazardous situation, which, if not avoided, could result in severe personal injury or death.
Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing minor or moderate
personal injury or damage to property.
Considerations
The installation of the TFX Ultra must comply with all applicable federal, state, and local rules, regulations, and codes.
EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
AVERTISSMENT
RISQUE D’EXPLOSION LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CEMATÉRIEL INACCCEPTABLE POUR LES
EMPLACEMENTS DE CLASSE I, DIVISION 2.
DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO
BE NONHAZARDOUS.
AVERTISSMENT
RISQUE D’EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUSTENSION, À MOINS QU’LL NE S’AGISSE
D’UN EMPLACEMENT NON DANGEREUX.
MPORTANTI
Not following instructions properly may impair safety of equipment and/or personnel.
MPORTANTI
Must be operated by a Class 2 supply suitable for the location.
Page 7 March 2018TTM-UM-00136-EN-08
Quick-Start Operating Overview
QUICKSTART OPERATING OVERVIEW
If you are familiar with installing TFX Ultra meters, follow these instructions to get the system up and running quickly. Refer to
the detailed instructions if you require additional information.
OTE:NThe following steps require information supplied by the transmitter itself so it will be necessary to supply power to
the transmitter, at least temporarily, to obtain setup information.
Transducer Location
• In general, select a mounting location on the piping system with a minimum of ten pipe diameters
(10 × the pipe inside diameter) of straight pipe upstream and five straight diameters downstream.
See Table 2 on page16 for additional configurations.
• If the application requires DTTR, DTTN, DTTL or DTTH transducers, select a mounting method for the transducers based on
pipe size and liquid characteristics. See Table 3 on page17. The three transducer mounting configurations are shown in
Figure 1. See “Transducer Mounting Configurations” on page20 for mounting procedures.
• Avoid installations on downward flowing pipes or pipes that may become partially filled.
OTE:NAll DTTS and DTTC transducers use V–Mount configuration.
TOP VIEW
OF PIPE
W-MountV-MountZ-Mount
45°
YES
45°
W and V Mount
Electrical Connections
Transducer/Power Connections
Top of
Pipe
TOP VIEW
OF PIPE
45°
YES
45°
Figure 1: Transducer mounting configurations
TOP VIEW
OF PIPE
Z Mount
Top of
Pipe
45°
YES
45°
1. Route the transducer cables from the transducer mounting location back to the transmitter enclosure. Connect the
transducer wires to the terminal block in the transmitter enclosure.
2. Verify that power supply is correct for the transmitter’s power option.
a. Line voltage AC transmitters require 95…264V AC, 47…63 Hz @ 17 VA maximum.
b. Low voltage AC transmitters require 20…28V AC, 47…63 Hz @ 0.35 VA maximum.
c. DC transmitters require 10…28V DC @ 5 Watts maximum.
Page 8 March 2018TTM-UM-00136-EN-08
Quick-Start Operating Overview
4. Connect power to the transmitter.
5. Enter the following data into the transmitter via the integral keypad or the UltraLink software utility:
1Transducer mounting method7Pipe liner thickness
2Pipe O.D. (Outside Diameter)8Pipe liner material
3Pipe wall thickness9Fluid type
4Pipe material10Fluid sound speed*
5Pipe sound speed*11Fluid viscosity*
6Pipe relative roughness*12Fluid specific gravity*
OTE:N* Nominal values for these parameters are included within the transmitter operating system. The nominal values may
be used as they appear or may be modified if the exact system values are known.
6. Record the value calculated and displayed as transducer spacing XDC SPAC.
Pipe Preparation and Transducer Mounting
DTTR, DTTN, DTTL and DTTH Transducers
1. Place the transmitter in signal strength measuring mode. This value is available on the transmitters display Service Menu or
in the data display of the UltraLink software utility.
2. The pipe surface, where the transducers are to be mounted, must be clean and dry. Remove scale, rust or loose paint to
ensure satisfactory acoustic conduction. Wire brushing the rough surfaces of pipes to smooth bare metal may also be
useful. Plastic pipes do not require preparation other than cleaning.
3. Apply a single 1/2 inch (12 mm) bead of acoustic couplant grease to the upstream transducer and secure it to the pipe
with a mounting strap.
4. Apply acoustic couplant grease to the downstream transducer and press it onto the pipe using hand pressure at the lineal
distance calculated in “Transducer Location” on page8.
5. Space the transducers according to the recommended values found during programming or from the UltraLink software
utility. Secure the transducers with the mounting straps at these locations.
DTTS and DTTC Transducers
1. Place the transmitter in signal strength measuring mode. This value is available on the transmitter’s display Service Menu or
in the data display of the UltraLink software utility.
2. The pipe surface, where the transducers are to be mounted, must be clean and dry. Remove scale, rust or loose paint to
ensure satisfactory acoustic conduction. Wire brushing the rough surfaces of pipes to smooth bare metal may also be
useful. Plastic pipes do not require preparation other than cleaning.
3. Apply a single 1/2 inch (12 mm) bead of acoustic couplant grease to the top half of the transducer and secure it to the pipe
with the bottom half or with U-bolts.
4. Tighten the nuts so the acoustic coupling grease begins to ow out from the edges of the transducer and from the gap
between the transducer and the pipe.
MPORTANTI
Do not overtighten. Overtightening will not improve performance and may damage the transducer.
Initial Settings and Powerup
1. Apply power to the transmitter.
2. Verify that SIG STR is greater than 5.0.
3. Input the units of measure and the I/O data.
Page 9 March 2018TTM-UM-00136-EN-08
Introduction
INTRODUCTION
This transit time ultrasonic transmitter is designed to measure the fluid velocity of liquid within a closed conduit. The
transducers are a non-contacting, clamp-on or clamp-around type, which provide the benefits of non-fouling operation and
ease of installation.
This family of transit time transmitters uses two transducers that function as both ultrasonic transmitters and receivers. The
transducers are clamped on the outside of a closed pipe at a specific distance from each other.
Application Versatility
The TFX Ultra transmitter can be successfully applied on a wide range of metering applications. The simple-to-program
transmitter allows the standard product to be used on pipe sizes ranging from 1/2 …100 inches (12…2540 mm)*. A variety of
liquid applications can be accommodated:
Because the transducers are non-contacting and have no moving parts, the transmitter is not affected by system pressure,
fouling or wear.
CE Compliance
The transmitter can be installed in conformance to CISPR 11 (EN 55011) standards. See “CE Compliance Drawings” on
page104.
User Safety
The TFX Ultra transmitter employs modular construction and provides electrical safety for the operator. The display face
contains voltages no greater than 28V DC. The display face swings open to allow access to user connections.
DANGER
THE POWER SUPPLY BOARD CAN HAVE LINE VOLTAGES APPLIED TO IT, SO DISCONNECT ELECTRICAL POWER BEFORE
OPENING THE INSTRUMENT ENCLOSURE. WIRING SHOULD ALWAYS CONFORM TO LOCAL CODES AND THE NATIONAL
ELECTRICAL CODE.
Data Integrity
Non-volatile flash memory retains all user-entered configuration values in memory for several years at 77° F (25° C), even if
power is lost or turned off. Password protection is provided as part of the Security menu (SEC MENU) and prevents inadvertent
configuration changes or totalizer resets.
Product Identication
The serial number and complete model number of the transmitter are located on the top outside surface of the transmitter
body. Should technical assistance be required, please provide our customer service department with this information. See
“Product Labels” on page96.
Page 10 March 2018TTM-UM-00136-EN-08
Transmitter Installation
TRANSMITTER INSTALLATION
Transmitter Location
Mount the enclosure in an area that is convenient for servicing and calibration or for observing the LCD readout.
1. Locate the transmitter within the length of the transducer cables supplied or exchange the cable for one that is of
proper length.
2. Mount the transmitter in a location:
• Where little vibration exists.
• That is protected from corrosive fluids.
• That is within the transmitters ambient temperature limits –40 …185° F (–40…85° C).
• That is out of direct sunlight. Direct sunlight may increase transmitter temperature to above the maximum limit.
B
A
C
D
ABCD
6.00 in. (152.4 mm)4.20 in. (106.7 mm)4.32 in. (109.7 mm)2.06 in. (52.3 mm)
Figure 2: Transmitter enclosure dimensions
3. Refer to Figure 2 for enclosure and mounting dimension details. Allow enough room for door swing, maintenance and
conduit entrances. Secure the enclosure to a at surface with two fasteners.
4. Use conduit holes where cables enter the enclosure from the bottom. Use plugs to seal any holes that are not used for
cable entry. An optional cable gland kit (part number D010-1100-000 ) is available for inserting the transducer and power
cables. Order the kit directly from the manufacturer.
OTE:NUse NEMA 4 (IP-65) rated fittings/plugs to maintain the watertight integrity of the enclosure. Generally, the right
conduit hole (viewed from front) is used for power, the left conduit hole for transducer connections, and the center
hole is used for I/O wiring.
1. To access terminal strips for wiring, loosen the two screws in the enclosure door and open.
2. Guide the transducer terminations through the transmitter conduit hole in the bottom-left of the enclosure.
3. Secure the transducer cable with the supplied conduit nut (if exible conduit was ordered with the transducer).
4. The terminals within transmitter are screw-down barrier terminals. Connect the wires at the corresponding screw
terminals in the transmitter. Observe upstream and downstream orientation and wire polarity. See Figure 3.
372
VE
D
ACL
C US
E167432
PRODUCT SERVICE
TUV
RoHS
DC OUT :
R
+15V / 0.3A
$
R2807
1500mA250V
C US
R
W
AC IN : 100-240VAC,50/60Hz
PWC-15E
www.astrodyne.com
0.15A
-Vo
ACN
strodyne
+Vo
O
N
1 2 3 4
+
+
-
-
-
-
+
+
Downstream
Downstream
Upstream
Upstream
RS485 Gnd
RS485 A(-)
RS485 B(+)
Modbus
TFX Rx
TFX Tx
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
95 - 264 VAC
AC Neutral
To Transducers
Figure 3: Transducer connections
OTE:NTransducer cables have two wire color combinations. For the blue and white combination, the blue wire is positive
(+) and the white wire is negative (–). For the red and black combination, the red wire is positive (+) and the black
wire is negative (–). The transducer wires are labeled to indicate which pair is upstream or downstream.
5. Connect power to the screw terminal block in the transmitter using the conduit hole on the right side of the enclosure.
See Figure 4 and Figure 5. Use wiring practices that conform to local and national codes such as The National Electrical
Code Handbook in the U.S.
ANY OTHER WIRING METHOD MAY BE UNSAFE OR CAUSE IMPROPER OPERATION OF THE TRANSMITTER.
OTE:NThis transmitter requires clean electrical line power. Do not operate this transmitter on circuits with noisy
components (such as fluorescent lights, relays, compressors, or variable frequency drives). Do not use step-down
transformers from high voltage, high amperage sources. Do not to run signal wires with line power within the same
wiring tray or conduit.
Page 12 March 2018TTM-UM-00136-EN-08
Line Voltage AC Power Connections
Connect 95…264V AC, AC neutral and chassis ground to the
terminals shown in Figure 4. Do not operate without an earth (chassis)
ground connection.
MPORTANTI
Permanently connected equipment and multi-phase equipment uses a
switch or circuit breaker as a means of disconnect. The switch or circuit
breaker conforms to the following:
• A switch or circuit breaker is included in the building installation.
• The switch is in close proximity to the equipment and within easy reach
of the operator.
• The switch is marked as the disconnecting device for the equipment.
Wiring of this equipment in ordinary locations must be in accordance with
ANSI/NFPA 70, National Electrical Code (NEC), Canadian Electrical Code
(CEC) or IEC 60364 as required by local codes. Wiring of this equipment in
hazardous locations requires special considerations such a those described
in National Electrical Code (NEC) Article 500, Canadian Electrical Code
(CEC), CSA C22.1 or IEC 60079-14.
Transmitter Installation
ACN
strodyne
1500mA250V
372
W
C US
VE
D
R
O
1 2 3 4
N
www.astrodyne.com
PWC-15E
AC IN : 100-240VAC,50/60HzDC OUT :
C US
ACL
E167432
95 - 264 VAC
95 - 264 VAC
AC Neutral
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
RS485 Gnd
RS485 A(-)
RS485 B(+)
R
+15V / 0.3A
Figure 4: Line voltage AC power connections
+Vo
-Vo
0.15A
R2807
$
TUV
RoHS
PRODUCT SERVICE
Modbus
TFX Rx
TFX Tx
Downstream
Upstream
-
-
+
+
Switch
or
Circuit
Breaker
Low Voltage AC Power Connections
Connect 20…28V AC, AC neutral and chassis ground to the
terminals shown in Figure 5.
372
strodyne
1500mA250V
IN: 18-36VAC
W
C US
VE
-IN+
OUT: 15VDC
D
R
ASD06-24S15
OUT−
OUT+
DANGER
Chassis Gnd.
DO NOT OPERATE WITHOUT AN EARTH CHASSIS
GROUND CONNECTION.
The 24V AC power supply option for this transmitter
is intended for a typical HVAC and Building Control
Systems (BCS) powered by a 24V AC, nominal, power
source. This power source is provided by AC line power
to 24V AC drop-down transformer and is installed by the
installation electricians.
OTE:NIn electrically noisy applications, grounding the
transmitter to the pipe where the transducers are
mounted may provide additional noise suppression.
This approach is only effective with conductive metal
pipes. The earth (chassis) ground derived from the
line voltage power supply should be removed at
the transmitter and a new earth ground connected
between the transmitter and the pipe
being measured.
OTE:NWire gauges up to 14 AWG can be accommodated in the transmitter terminal blocks.
OTE:NAC-powered transmitters are protected by a field-replaceable fuse. The fuse is a time delay fuse rated at 0.5A/250V
and is equivalent to Wickmann P.N. 3720500041 or 37405000410.
24 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
RS485 Gnd
RS485 A(-)
RS485 B(+)
Test
P1
O
1 2 3 4
N
Modbus
TFX Rx
TFX Tx
Downstream
Upstream
-
-
+
+
Switch
or
Circuit
Breaker
24V AC Transformer
Figure 5: Low voltage AC power connections
Page 13 March 2018TTM-UM-00136-EN-08
Transmitter Installation
DC Power Connections
The transmitter may be operated from a 10…28V DC source, as
long as the source is capable of supplying a minimum of 5 Watts
of power.
Connect the DC power to 10…28V DC In, power ground, and
chassis ground, as in Figure 6.
OTE:NDC-powered transmitters are protected by an
automatically resetting fuse. This fuse does not
require replacement.
For CE compliance, a Class 2 DC power supply is required.
O
N
1 2 3 4
10 - 28 VDC
10 - 28 VDC
Power Gnd.
Power Gnd.
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
RS485 Gnd
RS485 A(-)
RS485 B(+)
Modbus
TFX Rx
TFX Tx
Downstream
Upstream
-
-
+
+
Figure 6: DC power connections
Power
Ground
Switch
or
Circuit
Breaker
10…28 VDC
Chassis
Ground
Page 14 March 2018TTM-UM-00136-EN-08
Transducer Installation
TRANSDUCER INSTALLATION
The transducers for the TFX Ultra transmitter contain piezoelectric crystals that transmit and receive ultrasonic signals through
the walls of liquid piping systems.
DTTR, DTTN, DTTL and DTTH transducers are relatively simple and straightforward to install, but spacing and alignment of the
transducers is critical to the system’s accuracy and performance. CAREFULLY EXECUTE THESE INSTRUCTIONS.
DTTS and DTTC small pipe transducers have integrated transmitter and receiver elements that eliminate the requirement for
spacing measurement and alignment.
Mounting the DTTR, DTTN, DTTL and DTTH clamp-on ultrasonic transit time transducers takes five steps:
1. Select the optimum location on a piping system.
2. Select a mounting conguration.
3. Enter the pipe and liquid parameters into the UltraLink software utility or key them into the transmitter. The UltraLink
software utility or the transmitter’s rmware calculates proper transducer spacing based on these entries.
4. Prepare the pipe and mount the transducers.
5. Wire the transducers to the transmitter.
Downstream+
DownstreamUpstreamUpstream+
Figure 7: Transducer connections
The Energy model transmitter requires two 1000 Ohm, three-wire, platinum RTDs. The RTDs are available in surface-mount
and insertion (wetted) styles. Use surface-mount RTDs on well insulated pipes. Use insertion RTDs on non-insulated pipes.
Select a Mounting Location
The first step in the installation process is the selection of an optimum location for the flow measurement to be made. For this
to be done effectively, a basic knowledge of the piping system and its plumbing are required.
An optimum location is defined as:
• A piping system that is completely full of liquid when measurements are being taken. The pipe may become completely
empty during a process cycle, which will result in the error code 0010 (Low Signal Strength) displaying on the transmitter
while the pipe is empty. This error code will clear automatically once the pipe refills with liquid. Do not mount the
transducers in an area where the pipe may become partially filled, such as the highest point in a flow loop. Partially filled
pipes will cause erroneous and unpredictable operation of the transmitter.
• A piping system that contains lengths of straight pipe such as those described in Table 2. The optimum straight pipe
diameter recommendations apply to pipes in both horizontal and vertical orientation. The straight runs in Table 2 apply to
liquid velocities that are nominally 7 fps (2.2 mps). As liquid velocity increases above this nominal rate, the requirement for
straight pipe increases proportionally.
• An area where the transducers will not be inadvertently bumped or disturbed during normal operation.
• NOT on downward flowing pipes unless adequate downstream head pressure is present to overcome partial filling of or
cavitation in the pipe.
Page 15 March 2018TTM-UM-00136-EN-08
Transducer Installation
Piping Conguration
and Transducer Positioning
Flow
*
Flow
*
Flow
**
**
Upstream
Pipe
Diameters
Downstream
***
24
14
10
Pipe
Diameters
5
5
5
*
Flow
*
Flow
*
Flow
*
Table 2: Piping configuration and transducer positioning
The TFX Ultra system will provide repeatable measurements on piping systems that do not meet these pipe diameter
requirements, but the accuracy of the readings may be influenced.
**
**
**
**
10
10
24
5
5
5
Page 16 March 2018TTM-UM-00136-EN-08
Transducer Installation
Select a Mounting Conguration
The transmitter can be used with six different transducer types: DTTR, DTTN, DTTL, DTTH DTTS and DTTC. Meters that use
the DTTR, DTTN, DTTL or DTTH, transducer sets consist of two separate sensors that function as both ultrasonic transmitters
and receivers. These transducers are clamped on the outside of a closed pipe at a specific distance from each other. DTTS
and DTTC transducers integrate both the transmitter and receiver into one assembly that fixes the separation of the
piezoelectric crystals.
The DTTR, DTTN, DTTL and DTTH transducers can be mounted in:
• W-Mount where the sound traverses the pipe four times. This mounting method produces the best relative travel time
values but the weakest signal strength.
• V-Mount where the sound traverses the pipe twice. V-Mount is a compromise between travel time and signal strength.
• Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. Z-Mount
will yield the best signal strength but the smallest relative travel time.
Transducer Mounting
Configuration
Pipe MaterialPipe SizeLiquid Composition
Plastic (all types)
W-Mount
Carbon Steel
Stainless Steel
Copper
Ductile Iron
2…4 in. (50…100 mm)
Not recommended
Cast Iron
Plastic (all types)
V-Mount
Carbon Steel
Stainless Steel
Copper4…30 in. (100…750 mm)
Ductile Iron
Cast Iron
4…12 in. (100…300 mm)
Low TSS (Total Suspended
Solids); non-aerated
2…12 in. (50…300 mm)
Plastic (all types)> 30 in. (> 750 mm)
Z-Mount
Carbon Steel
Stainless Steel
Copper> 30 in. (> 750 mm)
Ductile Iron
Cast Iron
Table 3: Transducer mounting modes for DTTR, DTTN, DTTL and DTTH
> 12 in. (> 300 mm)
> 12 in. (> 300 mm)
The transducers can be mounted in V-Mount where the sound transverses the pipe two times, W-Mount where the sound
transverses the pipe four times, or in Z-Mount where the transducers are mounted on opposite sides of the pipe and the
sound crosses the pipe once. The selection of mounting method is based on pipe and liquid characteristics which both have
an effect on how much signal is generated. The transmitter operates by alternately transmitting and receiving a frequency
modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to
travel between the two transducers. The difference in the time interval measured is directly related to the velocity of the liquid
in the pipe.
The appropriate mounting configuration is based on pipe and liquid characteristics. Selecting the proper transducer
mounting method is an iterative process. Table 3 contains recommended mounting configurations for common applications.
These recommended configurations may need to be modified for specific applications if such things as aeration, suspended
solids, out-of-round piping or poor piping conditions are present.
TOP VIEW
OF PIPE
TOP VIEW
OF PIPE
TOP VIEW
W-MountV-MountZ-Mount
Figure 8: Transducer mounting modes for DTTR, DTTN, DTTL and DTTH
OF PIPE
Page 17 March 2018TTM-UM-00136-EN-08
Transducer Installation
Top of
45°
YES
45°
W and V Mount
Top of
45°
YES
45°
Flow Meter
Mounting Orientation
2” DTTS and DTTC Transducers
Pipe
Pipe
YES
45°
YES
45°
DTTR, DTTN, DTTL and DTTH Transducers
45°
45°
45°
YES
45°
Top of
Pipe
Z-Mount
Flow Meter
Mounting Orientation
Top of
Pipe
Flow Meter
Mounting Orientation
DTTS and DTTC Transducers
45°
YES
45°
45°
YES
45°
Figure 9: Transducer orientation for horizontal pipes
For pipes 24 inches (600 mm) and larger, use the DTTL transducers with a transmission frequency of 500 kHz.
DTTL transducers may also be advantageous on pipes between 4…24 inches if there are less quantifiable complicating
aspects, such as sludge, tuberculation, scale, rubber liners, plastic liners, thick mortar, gas bubbles, suspended solids,
emulsions, or pipes that are partially buried where a V-mount is required or desired.
For DTTS and DTTC transducers, the transducers are V-mount. The frequency setting depends on the pipe material.
DTTS transducer designation refers to both DTTS and DTTC transducer types.
Table 4: Transducer mounting modes for DTTS / DTTC
Integral
Transducer
Pipe
Mounting
Configuration
V
Page 18 March 2018TTM-UM-00136-EN-08
Transducer Installation
Enter the Pipe and Liquid Parameters
The TFX Ultra metering system calculates proper transducer spacing based on the piping and liquid information you enter
into the transmitter via the integral keypad or the UltraLink software utility.
The most accuracy is achieved when the transducer spacing is exactly what the transmitter calculates, so use the calculated
spacing if the signal strength is satisfactory. If the pipe is not round, the wall thickness not correct or the actual liquid being
measured has a different sound speed than the liquid programmed into the transmitter, the spacing can vary from the
calculated value. In that case, place the transducers at the highest signal level observed when moving the transducers slowly
around the mount area.
OTE:NTransducer spacing is calculated on “ideal” pipe. Ideal pipe almost never exists, so you may need to alter the
transducer spacing. An effective way to maximize signal strength is to configure the display to show signal strength,
fix one transducer on the pipe and then—starting at the calculated spacing—move the remaining transducer small
distances forward and back to find the maximum signal strength point.
MPORTANTI
Enter all of the data on this list, save the data and reset the transmitter before mounting the transducers.
The following information is required before programming the instrument:
Nominal values for these parameters are included within the transmitter’s operating system. The nominal values may be used as they appear or may be modied if exact system
values are known.
1
Fluid viscosity
1
Table 5: Parameters required
Pipe relative roughness
1
Fluid specific gravity
OTE:NMuch of the data relating to material sound speed, viscosity and specific gravity is pre-programmed into the
transmitter. You need to modify this data only if you know that a particular application’s data varies from the
reference values. See “Configuration” on page35 for instructions on entering configuration data into the transmitter
via the transmitter’s keypad. See “Parameter Configuration Using UltraLink Software” on page48 for data entry via
the software.
After entering the data listed above, the transmitter will calculate proper transducer spacing for the particular data set. The
distance will be in inches if the transmitter is configured in English units, or millimeters if configured in metric units.
1
1
Mount the Transducer
After selecting an optimal mounting location and determining the proper transducer spacing, mount the transducers onto
the pipe.
1. Clean the surface of the pipe. If the pipe has external corrosion or dirt, wire brush, sand or grind the mounting location
until it is smooth and clean. Paint and other coatings, if not flaked or bubbled, need not be removed. Plastic pipes typically
do not require surface preparation other than soap and water cleaning.
2. Orient and space the DTTR, DTTN, DTTL and DTTH transducers on the pipe to provide optimum reliability and
performance. On horizontal pipes, when Z-Mount is required, mount the transducers 180 radial degrees from one another
and at least 45 degrees from the top-dead-center and bottom-dead-center of the pipe. See Figure 9. Alsosee “Z-Mount
Configuration” on page22. On vertical pipes, the orientation is not critical.
The spacing between the transducers is measured between the two spacing marks on the sides of the transducers. These
marks are approximately 0.75 inches (19 mm) back from the nose of the DTTR, DTTN and DTTH transducers, and 1.2 inches
(30 mm) back from the nose of the DTTL transducers. See Figure 10.
Mount DTTS and DTTC transducers with the cable exiting within ±45 degrees of the side of a horizontal pipe. On vertical
pipes, the orientation does not apply.
Alignment
Marks
Figure 10: Transducer alignment marks
Page 19 March 2018TTM-UM-00136-EN-08
Transducer Installation
Transducer Mounting Congurations
V-Mount and W-Mount Configurations
Apply the Couplant
For DTTR, DTTN, DTTL and DTTH transducers, place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the
flat face of the transducer. See Figure 11. Couplant is provided with the transducers. Generally, a silicone-based grease is used
as an acoustic couplant, but any good quality grease-like substance that is rated to not ow at the operating temperature
of the pipe is acceptable. For pipe surface temperature over 130° F (55° C), use high temperature acoustic coupant such as
Krytox® LVP (P.N. D002-2011-012). For installations that must be silicone free, use Molykote G-N couplant (P.N. D002-2011-009).
½ in.
(12 mm)
Figure 11: Application of couplant
Position and Secure the Transducer
1. Place the upstream transducer in position on the pipe. Slide the strap into the arched groove on the end of the transducer.
Wrap the strap around the pipe. Slide the free end of the strap into the end clip of the strap with the screw at 90 degrees
to the strap. Pull the strap through until it loosely ts around the pipe. Rotate the screw so it is parallel to the strap and
tighten the screw slightly to help hold the transducer onto the pipe. Verify that the transducer is true to the pipe and
adjust as necessary. Tighten the strap screw to secure the transducer to the pipe.
2. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 12 on page21. Apply rm
hand pressure. If signal strength is greater than ve, secure the transducer at this location. If the signal strength is not ve
or greater, using rm hand pressure slowly move the transducer both towards and away from the upstream transducer
while observing signal strength.
Signal strength can be displayed on the transmitter’s display or on the main data screen in the UltraLink software utility.
See “Parameter Configuration Using UltraLink Software” on page48. Clamp the transducer at the position where the
highest signal strength is observed. The factory default signal strength setting is ve. However, there are many applicationspecic conditions that may prevent the signal strength from attaining this level. Signal levels less than ve will probably
not be acceptable for reliable readings.
OTE:NSignal strength readings update only every few second. Move the transducer 1/8 inch then wait to see if the signal is
increasing or decreasing. Repeat until the highest level is achieved.
3. If, after adjusting the transducers, the signal strength does not rise to above ve, use an alternate transducer mounting
conguration. If the mounting conguration was W-Mount, re-congure the transmitter for V-Mount, move the
downstream transducer to the new spacing distance and repeat the procedure “Mount the Transducer” on page19.
Page 20 March 2018TTM-UM-00136-EN-08
Transducer Installation
OTE:NMounting the high temperature transducers is similar
to mounting the DTTR/DTTN/DTTL transducers. High
temperature installations require acoustic couplant
that is rated not to flow at the operating temperature
of the pipe surface.
OTE:NUse the DTTL on pipes 24 inches and larger and not
on pipes smaller than 4 inches. You can consider
using the DTTL transducers on pipes smaller than
24 inches if there are less quantifiable aspects—such
as sludge, tuberculation, scale, rubber liners, plastic
liners, thick mortar liners, gas bubbles, suspended
solids, emulsions—and smaller pipes that are
perhaps partially buried where a V-Mount is required
or desired.
Transducer
Spacing
Figure 12: Transducer positioning
DTTS/DTTC Small Pipe Transducer Installation
The small pipe transducers are designed for specific pipe outside diameters. Do not attempt to mount a DTTS/DTTC
transducer onto a pipe that is either too large or too small for the transducer. Instead, contact the manufacturer to arrange for
a replacement transducer that is the correct size.
1. Apply a thin coating of acoustic coupling grease to both halves of the transducer housing where the housing will contact
the pipe. See Figure 13.
2. On horizontal pipes, mount the transducer in an orientation so the cable exits at ±45 degrees from the side of the pipe.
Do not mount with the cable exiting on either the top or bottom of the pipe. On vertical pipes, the orientation does not
matter.
3. Tighten the wing nuts or U-bolts so the acoustic coupling grease begins to ow out from the edges of the transducer or
from the gap between the transducer halves.
MPORTANTI
Do not overtighten. Overtightening will not improve performance and may damage the transducer.
4. If signal strength is less than ve, remount the transducer at another location on the piping system.
1/16 in. (1.5 mm)
Acoustic Couplant
Grease
Figure 13: Application of acoustic couplant — DTTS/DTTC transducers
OTE:NIf a DTTS/DTTC small pipe transducer was purchased separately from the transmitter, the following configuration
procedure is required.
Page 21 March 2018TTM-UM-00136-EN-08
Transducer Installation
DTTS/DTTC Small Pipe Transducer Calibration Procedure
1. Establish communications with the transit time transmitter.
2. From the tool bar, select Calibration. See Figure 16.
3. On the pop-up screen, click Next twice to get to
Page 3 of 3. See Figure 14.
4. Click Edit.
5. If a calibration point is displayed in Calibration Points Editor,
record the information, then highlight and click Remove.
See Figure 15.
6. Click ADD...
7. Enter Delta T, Un-calibrated Flow, and Calibrated Flow
values from the DTTS/DTTC calibration label, then click OK.
See Figure 17.
8. Click OK in the Edit Calibration Points screen.
9. The display will return to Page 3 of 3. Click Finish.
See Figure 14.
10. After Writing Conguration File is complete, turn o the
power. Turn on the power again to activate the new
settings.
Calibration (Page 3 of 3) - Linearization
28.2
Gal/M
Figure 14: Calibration points editor
Calibration Points Editor
Select point(s) to edit or remove:
30.00 ns 2000.00 Gal/Min 1.000
Delta Time
< Back
1) Please establish a
reference ow rate.
1FPS / 0.3MPS Minimum.
2) Enter the reference ow
rate below. (Do not enter 0)
Installation on larger pipes requires careful measurements of the linear and radial placement of the DTTR, DTTN, DTTL and
DTTH transducers. Failure to properly orient and place the transducers on the pipe may lead to weak signal strength and/or
inaccurate readings. This section details a method for properly locating the transducers on larger pipes. This method requires
a roll of paper such as freezer paper or wrapping paper, masking tape and a marking device.
1. Wrap the paper around the pipe in the manner shown in Figure 18. Align the paper ends to within 1/4 inch (6 mm).
2. Mark the intersection of the two ends of the paper to indicate the circumference. Remove the template and spread it out
on a at surface. Fold the template in half, bisecting the circumference. See Figure 19.
3. Crease the paper at the fold line. Mark the crease. Place a mark on the pipe where one of the transducers will be located.
See Figure 9 for acceptable radial orientations. Wrap the template back around the pipe, placing the beginning of the
paper and one corner in the location of the mark. Move to the other side of the pipe and mark the pipe at the ends of
the crease. Measure from the end of the crease (directly across the pipe from the rst transducer location) the dimension
derived in “Select a Mounting Configuration” on page17. Mark this location on the pipe.
Page 22 March 2018TTM-UM-00136-EN-08
Transducer Installation
4. The two marks on the pipe are now properly aligned and measured. If access to the bottom of the pipe prohibits the
wrapping of the paper around the circumference, cut a piece of paper 1/2 the circumference of the pipe and lay it over the
top of the pipe. The equation for the length of 1/2 the circumference is: 1/2 Circumference = Pipe O.D. × 1.57
The transducer spacing is the same as found in “Position and Secure the Transducer” on page20. Mark opposite corners of the
paper on the pipe. Apply transducers to these two marks.
Edge of
Paper
Line Marking
Circumference
Fold
Pipe Circumference
Transducer
Spacing
LESS THAN ¼” (6 mm)
Crease
(Center of Pipe)
Figure 18: Paper template alignment
Figure 19: Bisecting the pipe circumference
5. For DTTR, DTTN, DTTL and DTTH transducers, place a single bead of
couplant, approximately 1/2 inch (12 mm) thick, on the at face of the
transducer. See Figure 11. Generally, a silicone-based grease is used
as an acoustic couplant, but any good quality grease-like substance
that is rated to not ow at the operating temperature of the pipe
is acceptable.
6. Place the upstream transducer in position and secure with a stainless
TOP VIEW
OF PIPE
steel strap or other fastening device. Straps should be placed in the
arched groove on the end of the transducer. A screw is provided to help
hold the transducer onto the strap. Verify that the transducer is true to
the pipe, adjust as necessary. Tighten transducer strap securely. Larger
pipes may require more than one strap to reach the circumference of
the pipe.
Figure 20: Z-Mount transducer placement
7. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 20. Using rm hand
pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal
strength. Clamp the transducer at the position where the highest signal strength is observed. A signal strength between
5…98 is acceptable.
The factory default signal strength setting is five. However there are many application-specific conditions that may
prevent the signal strength from attaining this level. A minimum signal strength of five is acceptable as long as this signal
level is maintained under all flow conditions.
On certain pipes, a slight twist to the transducer may cause signal strength to rise to acceptable levels. Certain pipe and
liquid characteristics may cause signal strength to rise to greater than 98. The problem with operating this transmitter with
very high signal strength is that the signals may saturate the input amplifiers and cause erratic readings. Strategies for
lowering signal strength would be changing the transducer mounting method to the next longest transmission path. For
example, if there is excessive signal strength and the transducers are mounted in a Z-Mount, try changing to V-Mount or
W-Mount. Finally, you can also move one transducer slightly off-line with the other transducer to lower signal strength.
8. Secure the transducer with a stainless steel strap or other fastener.
Page 23 March 2018TTM-UM-00136-EN-08
Transducer Installation
Mounting Rail System Installation for DTTR
For remote flow DTTR transducers with outside diameters between 2…10 inches (50…250 mm) , the rail mounting kit aids
in installation and positioning of the transducers. Transducers slide on the rails, which have measurement markings that are
viewable through the sight opening.
1. Install the single mounting rail on the side of the pipe with the stainless steel bands provided. Do not mount it on the top
or bottom of the pipe. On vertical pipe, orientation is not critical. Check that the track is parallel to the pipe and that all
four mounting feet are touching the pipe.
2. Slide the two transducer clamp brackets toward the center mark on the mounting rail.
3. Place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the at face of the transducer.
See Figure 11 on page20.
4. Place the rst transducer in between the mounting rails near the zero point on the scale. Slide the clamp over the
transducer. Adjust the clamp and transducer so the notch in the clamp aligns with the zero on the scale. See Figure 22.
5. Secure with the thumb screw. Check that the screw rests in the counter bore on the top of the transducer. (Excessive
pressure is not required. Apply just enough pressure so that the couplant lls the gap between the pipe and transducer.)
6. Place the second transducer in between the mounting rails near the dimension derived in the transducer spacing section.
Read the dimension on the mounting rail scale. Slide the transducer clamp over the transducer and secure with the
thumb screw.
Figure 21: Mounting rail system for DTTR
Mounting Track Installation for DTTN/DTTH
A convenient transducer mounting track can be used for pipes that have outside diameters between 2…10 inches
(50…250 mm) and for DTTN/DTTH transducers. If the pipe is outside of that range, mount the transducers separately.
1. Install the single mounting rail on the side of the pipe with the stainless steel bands provided. Do not mount it on the top
or bottom of the pipe. On vertical pipe, orientation is not critical. Check that the track is parallel to the pipe and that all
four mounting feet are touching the pipe.
2. Slide the two transducer clamp brackets toward the center mark on the mounting rail.
3. Place a single bead of couplant, approximately 1/2 inch (12 mm) thick, on the at face of the transducer.
See Figure 11 on page20.
4. Place the rst transducer in between the mounting rails near the zero point on the scale. Slide the clamp over the
transducer. Adjust the clamp and transducer so the notch in the clamp aligns with the zero on the scale. See Figure 22.
5. Secure with the thumb screw. Check that the screw rests in the counter bore on the top of the transducer. (Excessive
pressure is not required. Apply just enough pressure so that the couplant lls the gap between the pipe and transducer.)
6. Place the second transducer in between the mounting rails near the dimension derived in the transducer spacing section.
Read the dimension on the mounting rail scale. Slide the transducer clamp over the transducer and secure with the
thumb screw.
Top View
of Pipe
Figure 22: Mounting track installation
Page 24 March 2018TTM-UM-00136-EN-08
Loop Load (Ohms)
Inputs/Outputs
INPUTS/OUTPUTS
General
The transmitting system is available in two configurations:
• The Flow-Onlymodel is equipped with a 4-20 mA output, two open collector outputs, a rate frequency output, and
RS485 communications using the Modbus RTU command set.
• The Energy(BTU) model has inputs for two 1000 Ohm RTD sensors in place of the rate frequency and alarm outputs. This
model allows the measurement of pipe input and output temperatures so energy usage calculations can be performed.
4-20 mA Output
The 4-20 mA output interfaces with most recording and logging systems by transmitting an analog current signal that is
proportional to system flow rate. The 4-20 mA output is internally powered (current sourcing) and can span negative to
positive flow/energy rates.
For AC-powered transmitters, the 4-20 mA output is driven from a 15V DC source located within the transmitter. The source
is isolated from earth ground connections within the transmitter. The AC-powered transmitter can accommodate loop loads
up to 400 Ohms. DC-powered transmitters use the DC power supply voltage to drive the current loop. The current loop
is not isolated from DC ground or power. Figure 23 shows graphically the allowable loads for various input voltages. The
combination of input voltage and loop load must stay within the shaded area of Figure 23.
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Signal Ground
7 VDC
Drop
Meter Power
Figure 24: 4-20 mA output
The 4-20 mA output signal is available between the 4-20 mA Out and Signal Gnd terminals as shown in Figure 24.
Page 25 March 2018TTM-UM-00136-EN-08
Inputs/Outputs
Reset Total Input
The Reset Total Input can be used with a push-button to reset the flow totals. When the Reset Total Input is connected to
signal ground, the total displayed on the meter is reset to zero.
Figure 25: Reset total input
Control Outputs (Flow-Only Model)
Two independent open collector transistor outputs are included with the Flow-Only model. Each output can be configured
for one of the following functions:
• Rate Alarm
• Signal Strength Alarm
O
1 2 3 4
N
• Totalizing/Totalizing Pulse
• Errors
Figure 26: Switch settings
• None
Both control outputs are rated for a maximum of 100 mA and 10…28V DC. A pullup resistor can be added externally or an
internal 10k Ohm pullup resistor can be selected using DIP switches on the power supply board.
SwitchS1S2S3S4
On
Off
Control 1 Pullup
Resistor IN circuit
Control 1 Pullup
Resistor OUT of circuit
Control 2 Pullup
Resistor IN circuit
Control 2 Pullup
Resistor OUT of circuit
Table 6: Dip switch functions
Frequency output Pullup Resistor
IN circuit
Frequency Output Pullup Resistor
OUT of circuit
Square Wave Output
Simulated Turbine
Output
OTE:NAll control outputs are disabled when a USB cable is connected.
For the Rate Alarm and Signal Strength Alarm the on/off values are set using either the keypad or the UltraLink
software utility.
Typical control connections are illustrated in Figure 27. Please note that only the Control 1 output is shown. Control 2 is
identical except the pullup resistor is governed by SW2.
VCC
10k
O
90-265 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
1 2 3 4
N
SW1/SW2
Figure 27: Typical control connections
Page 26 March 2018TTM-UM-00136-EN-08
Inputs/Outputs
Rate Alarm Outputs
The flow rate output permits output changeover at two separate flow rates, allowing operation with an adjustable switch
deadband. Figure 28 illustrates how the setting of the two setpoints influences rate alarm operation.
A single-point flow rate alarm would place the ON setting slightly higher than the OFF setting, allowing a switch deadband to
be established. If a deadband is not established, switch chatter (rapid switching) may result if the flow rate is very close to the
switch point.
Minimum
Flow
Maximum
Flow
Output ON
Output OFF
Figure 28: Single point alarm operation
Set OFF
Deadband
Set ON
OTE:NAll control outputs are disabled when a USB cable is connected.
Signal Strength Alarm
The SIG STR alarm will provide an indication that the signal level reported by the transducers has fallen to a point where flow
measurements may not be possible. It can also be used to indicate that the pipe has emptied. Like the rate alarm described
previously, the signal strength alarm requires that two points be entered, establishing an alarm deadband. A valid switch
point exists when the ON value is lower than the OFF value. If a deadband is not established and the signal strength decreases
to approximately the value of the switch point, the output may chatter.
Batch/Totalizer Output (Flow-Only Model)
Totalizer mode configures the output to send a 100 mSec pulse each time the display totalizer increments divided by the
TOT MULT. The TOT MULT value must be a whole, positive numerical value. This output is limited to 1 Hz maximum.
For example, if the totalizer exponent TOTL E is set to E0 ×1 and the totalizer multiplier TOT MULT is set to 1, then the
output will pulse each time the totalizer increments one count, or each single, whole measurement unit totalized.
If the totalizer exponent TOTL E is set to E2 ×100 and the totalizer multiplier TOT MULT is set to 1, then the control output
will pulse each time the display totalizer increments or once per 100 measurement units totalized.
If the totalizer exponent TOTL E is set to E0 ×1 and the totalizer multiplier TOT MULT is set to 2, the control output will
pulse once for every two counts that the totalizer increments.
Error Alarm Outputs
When a control output is set to ERROR mode, the output will activate when any error occurs in the transmitter that has caused
the transmitter to stop measuring reliably. See “Brad Harrison® Connector Option” on page95.
Page 27 March 2018TTM-UM-00136-EN-08
Inputs/Outputs
Frequency Output (Flow-Only Model)
The frequency output is an open-collector transistor circuit that outputs a pulse waveform that varies proportionally with flow
rate. This type of frequency output is also know as a Rate Pulse output. The output spans from 0 Hz, normally at zero flow rate
to 1000 Hz at full flow rate (configuration of the MAX RATE parameter is described in “Startup” on page35.
+V
10k
90-265 VAC
SW4 Closed
SW4 Open
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
O
1 2 3 4
N
Frequency Output
Figure 29: Frequency output switch settings
OTE:NWhen a USB programming cable is connected, the RS485 and frequency outputs are disabled.
The frequency output is proportional to the maximum flow rate entered into the transmitter. The maximum output frequency
is 1000 Hz.
If, for example, the MAX RATE parameter was set to 400 gpm, then an output frequency of 500 Hz (half of the full scale
frequency of 1000 Hz) would represent 200 gpm.
In addition to the control outputs, the frequency output can be used to provide total information by use of a Kfactor. A
Kfactor simply relates the number of pulses from the frequency output to the number of accumulated pulses that equates to
a specific volume.
For this transmitter, the relationship is described by the following equation. The 60,000 relates to measurement units in
volume/min. Measurement units in seconds, hours or days would require a different numerator.
K factor
60,000
=
Full Scale Units
A practical example would be if the MAX RATE for the application were 400 gpm, the Kfactor (representing the number of
pulses accumulated needed to equal one gallon) would be:
K factor
60,000
==
400
gpm
150
Pulses Per Gallon
If the frequency output is to be used as a totalizing output, the transmitter and the receiving instrument must have identical
Kfactor values programmed into them to ensure that accurate readings are being recorded by the receiving instrument.
Unlike standard mechanical transmitters such as turbines, gear or nutating disc meters, the Kfactor can be changed by
modifying the MAX RATE flow rate value. See “Calculating KFactors” on page106.
Page 28 March 2018TTM-UM-00136-EN-08
Inputs/Outputs
There are two frequency output options available:
• The Turbine Meter Simulation option is used when a receiving instrument is capable of interfacing directly with a
turbine transmitter’s magnetic pickup. The output is a relatively low voltage AC signal whose amplitude swings above and
below the signal ground reference. The minimum AC amplitude is approximately 500 mV peak-to-peak. To activate the
turbine output circuit, turn SW4 OFF.
500 mV
p-p
0
Figure 30: Frequency output waveform (simulated turbine)
• The Square-Wave Frequency option is used when a receiving instrument requires that the pulse voltage level be either
of a higher potential and/or referenced to DC ground. The output is a square-wave with a peak voltage equaling the
instrument supply voltage when the SW3 is ON. If desired, an external pullup resistor and power source can be used by
leaving SW3 OFF. Set SW4 to ON for a square-wave output.
+V
0
Figure 31: Frequency output waveform (square wave)
Totalizer Output Option (Energy Model)
Energy models can be ordered with a totalizer pulse output option. This option is installed in the position where the Ethernet
option would normally be installed.
Optional Totalizing Pulse Specifications
ParameterSpecication
SignalOne pulse for each increment of the totalizer’s least significant digit
TypeOpto-isolated, open collector transistor
Pulse Width30 mSec, maximum pulse rate 16 Hz
Voltage28V DC maximum
Current100 mA maximum (current sink)
Pullup Resistor2.8 …10 k Ohms
Table 7: Optional energy usage totalizing pulse output
OTE:NThe totalizer pulse output option and the Ethernet communications output cannot be installed in the same Energy
model at the same time.
Page 29 March 2018TTM-UM-00136-EN-08
RS-485 Converter
Inputs/Outputs
Totalizing
Pulse Output
Option
TB1
RxD
Total Pulse
100 mA
Maximum
V
CC
2.8k…10k
Pullup
Resistor
Isolated Output
Total Pulse
Internal
Figure 32: Energy model auxiliary totalizer output option
Wiring and configuration of the Energy model is similar to the totalizing pulse output for the Flow-Only model. This option
must use an external current limiting resistor.
RS485 Port
The RS485 feature allows up to 126 transmitters to be placed on a single three-wire cable bus. All transmitters are assigned a
unique numeric address that allows all of the transmitters on the cable network to be independently accessed. A Modbus RTU
command protocol is used to interrogate the transmitters. See “Communications Protocols” on page66.
Flow rate, total, signal strength and temperature (if so equipped) can be monitored over the digital communications bus.
Baud rates up to 9600 and cable lengths to 5000 feet (1500 meters) are supported without repeaters or end-of-line resistors.
To interconnect transmitters, use three-wire shielded cable (like the Belden 9939 or equal). In noisy environments, connect
the shield on one end to a good earth-ground connection. Use a USB-to-RS485 converter (like the B&B Electronics
P/N 485USBTB-2W) to communicate with a PC running Windows XP, Windows Vista and Windows 7. For computers with
RS232C serial ports, use an RS232C-to-RS485 converter (like the B&B Electronics P/N 485SD9TB illustrated in Figure 33), to
interconnect the RS485 network to a communication port on a PC. If more than 126 transmitters must be monitored, an
additional converter and communication port are required.
OTE:NWhen a USB programming cable is connected, the RS485 and frequency outputs are disabled.
4-20 mA Out
Reset Total
TD(A)-
TD(B)+
GND
GND
+12V
RS485 Gnd
RS485 A(-)
RS485 B(+)
4-20 mA Out
Reset Total
RS485 Gnd
RS485 A(-)
RS485 B(+)
Model 485USBTB-2W
A (-)
B (+)
A (-)
B (+)
GND
USB to RS485
Figure 33: RS485 network connections
Page 30 March 2018TTM-UM-00136-EN-08
RS-485
Model 485SD9TB
RS-232
To 12V DC
Supply
RS232 to RS485
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.