The below listed items are a number of technical points to observe when installing a
Dynasonics PFP-600 partially filled pipe flow meter. It is absolutely necessary to follow
these “guidelines” to insure proper operation of the unit!
1. In order to properly install the meter, access to the bottom-dead-center line of a
horizontal ( <4° ) pipe is necessary. The transducer mounting area should be free
of oxidation, scale, or other foreign accumulations. Clean the mounting surface
down to bare metal when need be.
NOTE: Pipes with well adhered coating such as paint or epoxy will not influence operation and need not
be removed.
2. The transducer cables provided with the unit may be cut to desired length,
however the cables cannot be extended. The maximum cable length available is
50ft.
NOTE: Splicing of the coaxial cables may degrade sensor performance beyond usable levels. The
shielded coaxial leads are designed to isolate the low level signals from undesirable ambient noise and
must be continuous to the transmitter.
3. There must be at least ten (10) straight pipe diameters upstream and five (5)
straight pipe diameters downstream from the transducer mounting location to
maintain the highest level of meter accuracy. Less than these straight pipe
requirements may degrade meter performance.
4. When locating the two transducers on the pipe, the non-connector ends should be
butted up against each other in the track provided. The transducer clamps should
be hand tightened only, over-tightening will squeeze out couplant. The level
sensor should have sufficient couplant to fill the gap between the rubber spacers
when mounted to the pipe. If the mounting location does not allow this
1
configuration, the transducers should be located as close as possible to each other
to maintain system integrity.
2
SECTION 2
SPECIFICATIONS
MODEL PFP-600 TRANSMITTER/INDICATOR/TOTALIZER
Flow Accuracy............................ +\-2.0% (Application Dependent) at 70° F (25° C)
Level Accuracy.......................... Better than +\- 1.% (Application Dependent) at 70° F (25° F)
Linearity...................................... Better than +\-0.5% under flow.
Repeatability............................... Better than +\-0.5% under flow.
Rangeability................................ 10:1 or greater.
Standard Scale........................... Gallons per Minute (as specified). Other engineering
Coupling............................ Silicone based adhesive (supplied), or epoxy.
2
SECTION 3
THEORY OF OPERATION
The Dynasonics PFP-600 partially filled pipe flow meter combines a traditional clap-on
Doppler type velocity sensor with a unique non-invasive bottom-up level monitor to
accurately determine volumetric flow in horizontal pipes that have dynamically changing
velocity and level characteristics. Unlike traditional velocity sensing flow meters which
assume a full pipe condition and make volumetric flow calculations based on a known
fixed cross-sectional pipe area, the Dynasonics flow meter senses both velocity and
level which allows the micro-processor based electronics to calculate the crosssectional area of pipe that is displaced by the liquid and then factored by the sensed
velocity to determine volumetric flow data, regardless of the liquid level in the pipe.
This distinctive technology allows the user to address partially filled pipes as never
before. The major advantages to this type of technology are unparalleled by other
partially filled pipe flow metering devices. First the Dynasonics PFP-600 is noninvasive. This is extremely important in applications where liquid contact is undesirable.
Secondly, because the systems sensors are located external to the pipe, installation
costs are considerably lower. Finally, because the sensors have no moving parts, are
insensitive to coating materials, or have no pressure sensing ports to clog the system it
is virtually maintenance free.
The PFP-600 is designed around three basic building blocks. The Doppler velocity
sensing electronics, the non-invasive level monitor, and a micro-processor which
controls the timing of velocity and level sensing sequences. The micro-processor
evaluates the flow and level data and calculates the instantaneous volumetric flow, the
total volumetric flow, and drives the 4-20 mA dc output for recording instantaneous
volumetric flow information.
The velocity sensor is a Doppler type sensor. This sensing methodology requires that
the liquid being sensed contain a minimum of 25 PPM of 30 micron suspended particles
3
or entrained gas. The system will also sense velocity from turbulence caused by
flowing liquids. It should be noted that in un-pressurized partially filled pipes, most
liquids will contain a sufficient amount of entrained gas for proper operation even though
the liquid may be virtually clean. For sensing velocity, the transmitted signal from the
velocity transducer is passed through the pipe wall material and comes in contact with a
discontinuity in the liquid. The transmitted signal is reflected off of the particle or gas
bubble: This reflected signal, according to Doppler theory, has change in frequency
with respect to the transmitted frequency: This shift in frequency is proportional to the
velocity of the liquid.
The level sensor is a pulsed ultrasonic transit time type. A carefully selected
transmission frequency and beam spread have been incorporated into this non-invasive
transducer. This design allows for bottom-up sensing of liquid level without coming in
contact with the liquid. The transmission frequency has been selected for its unique
ability to penetrate pipe wall material, pass freely through the contained liquid, yet
effectively reflect off the liquid/air/vapor interface within the pipe.
The electronics is designed to emit a short duration ultrasonic pulse. during the
transmitter “off” period the transducer then “listens” for a reflected signal. At the
moment of transmission a timer determines the beginning of the transmit cycle to the
end of the received cycle. The circuit then divides this time by two and then relates this
time to distance or level in the case of the PFP-600.
The micro-processor acts as a controller for the timing of the periods (1 second) in
which the Doppler circuit detects velocity and the level monitor senses level. This circuit
is essential to eliminate the possibility of flow and level data from becoming entangled
with each other thus producing erroneous information. The micro-processor essentially
turns on the Doppler circuit while turning off the level circuits and visa versa on a
continual basis to keep the micro-processor updated as to the latest occurrences in
velocity and level changes. The micro-processor section of the PFP-600 is the heart of
the system. This is the portion of the electronics that evaluates the flow and level data
and then, converts the data to volumetric flow information based on the equation:
4
Q = V x A
Where: Q = Volumetric Flow.
V = The velocity of the liquid.
A = The cross-sectional area of the pipe displaced by liquid.
In addition, the micro-processor performs other evaluations to insure the integrity of the
volumetric flow information.
5
SECTION 4
INSTALLATION
Installation is simple but should be done correctly to assure proper operation. The
transmitter can be mounted in any position. The enclosure is weather-resistant;
however, it should be protected from direct exposure to sun or rain (NEMA 4X). In
order to achieve the best possible results with this flow meter sufficient straight metering
runs of pipe are required. The recommended mounting location for both the velocity
and level sensors is ten (10) straight pipe diameters down stream and five (5) straight
diameters upstream from elbows or fittings. The sensors must be mounted to the
bottom of the pipe. In the case of control valves or other disrupting hardware the
straight diameters should be doubled.
The PFP-600 is designed to determine volumetric flow in partially filled closed horizontal
(<4°) piping systems. Do not use this meter in open channel or open sewer
applications whereby the transducers may be submerged, or on vertical closed pipes
that may be partially full.
For proper operation in applications for partially filled horizontal pipes, the bottom of the
pipe must be accessible. Select a convenient location for the transmitter, one that will
accommodate the length of transducer cable supplied. Supply 115 VAC+/-10%, and
connect the velocity and level sensors to the appropriate terminals, connect 4-20mA as
needed. Refer to the marked terminals inside the transmitter enclosure terminal
identification. The level detection sensor must be mounted to the bottom-dead-center of
the horizontal pipe to insure proper operation. Diagnostic LED’s on the front of the
enclosure will assist in sensor location. With some level of liquid in the pipe, place two
beads of silicone adhesive on the face of the level transducer. Using the track level
locate the bottom-dead-center of the pipe you are going to be mounting the level sensor
to. With the transducer centerline parallel to the centerline of the pipe contact the
transducer to the pipe, do not apply a lot of pressure to the transducer, it is essential
that the silicone coupling be maintained to assure proper transmission of the ultrasonic
6
signal. At this time the diagnostic LED’s should be observed at the transmitter. A red
“fault”LED indicated that the transducer must be repositioned on the pipe. By moving
the sensor + or - the original position toward the top of the pipe a green “read” LED
should be achieved.
NOTE: For applications that may be turbulent in nature, the green “read” LED, and red “fault” LED may
blink intermittently. Under these conditions, position the level transducer such that the green LED is on
more than the red LED. At this point the Transducer clamp can be used to hold the transducer in place,
again, do not over tighten the clamp such that the couplant may be lost.
The Velocity sensor is mounted in much the same manner as the level sensor. the
velocity sensor should also be mounted at the bottom-dead-center of the pipe. The
non-connector ends of the two transducers should be butted up to each other. For
those applications where this type of orientation is not possible, the two sensors should
be mounted as close to one another as possible to avoid system degradation. Apply
two beads of silicone adhesive to the face of the velocity sensor. Install the sensor in
the mounting track. Using minimal pressure, contact the sensor to the pipe and secure
with the Transducer clamp. It should be noted that the velocity sensor is less position
sensitive than the level transducer and alignment by eye is typically sufficient. Set
meter to read FPS (UNITS=0), meter should indicate flow, and indicate both sufficient
particulate or bubble content in the liquid being measured as well as proper transducer
placement.
Upon flowing liquid the display will indicate GPM (Standard) or other engineering units
as specified and the totalizer will begin to accumulate flow data over time. The
diagnostic LED’s should be observed after 24 hrs. of operation (the curing time for the
transducer couplant to insure proper adhesion had occurred). If the diagnostic LED’s
indicate a level or velocity sensing failure, determine if pipe has liquid in it and/or the
liquid is flowing. If the level status indicates a red “fault” light the level sensor may need
to be remounted. Likewise should the micro-processor display show OFPS, the velocity
sensor may need to be remounted. Should these steps not solve the indicated
difficulties contact the factory for further direction.
7
8
9
PFP µP FUNCTIONS
To set engineering units press “UNITS” key. The µP display will show “UNITS”. Use
the “SCROLL” keys to increase or decrease value. The default value is 1. When
finished, press “ENTER” key to exit.
NOTE: after units has been changed, all other levels for FULL-SCALE, ID, ALARMS, must be reentered.
To set 4-20 mA full-scale, press “FULL-SCALE” key. The µP display will show “FULLSCALE”. Use the “SCROLL” keys to increase or decrease value. The default value is
10.00 . When finished, press “ENTER” key to exit.
units = 1-4 GPM
full-scale range is 1.00 - 20.00 FPS F.S (FPS) = ID∗ ID∗ 2.45
units =5-8 LPM
full-scale range is 0.304 - 6.08 MPS F.S (MPS) = ID∗ID∗ .047
units =9
full-scale range is 4.00” - 60.00”
units = 10
full-scale range is 10.2 cm. - 152.00 cm.
To set pipe ID, press “I.D.” key. The µP display will show “ID (IN)” or “ID(MM)”. Use the
“SCROLL” keys to increase or decrease value. The default value is 10.00. When
finished, press “ENTER” key to exit.
units = 1-4, and 9
pipe ID range is 4.00” - 60.00”
10
units = 5-8, and 10
pipe ID range is 102 mm. - 1524 mm.
To set high alarm (RELAY-2), press “HIGH ALARM” key. The µP display will show
“ALARM HIGH”. Use the “SCROLL” keys to increase or decrease value. The default
value is 20.00. When finished, press “ENTER” key to exit.
units = 1-4
high alarm range is 0.00” - 60.00”
units =5-8
high alarm range is 0.00 - 6.08 MPS
units =9
high alarm range is 0.00” - 60.00”
units = 10
high alarm range is 0.00 cm. - 152.00 cm.
To set low alarm (RELAY-1), press “LOW ALARM” key. The µP display will show
“ALARM LOW”. Use the “SCROLL” keys to increase or decrease value. Default value
is 00.00. When finished, press “ENTER” key to exit.
units = 1-4 (flow)
low alarm range is 0.00 - 20.00 FPS
units = 5-8 (flow)
low alarm range is 0.00 - 6.08 MPS
units = 9 (level)
low alarm range is 0.00” - 60.00”
units = 10 (level)
low alarm range is 0.00 cm. - 152.00 cm.
Totalizer operation display with or without multiplier
units = 2 - 4
totalizer range is 0 - 99999999 GALS (GALLONS)
units = 6 - 8
totalizer range is 0 - 99999999 LTRS (liters)
11
units = 1 & 9
totalizer is off and no display
units = 5 & 10
totalizer is off and no display
To set totalizer multiplier, press “TOT MULT” key. The µP display will show “TOTAL
MULT.” Use the “SCROLL” keys to increase or decrease value. The default value is 0.
When finished, press “ENTER” key to exit.
0 = X1
1 = X10
2 = X100
3 = X1000
4 = X10,000
To set totalizer on, off or reset, press “TOT ON/OFF” key once to stop totalizing, twice
to reset, and third to start. Note: when changing engineering units, totalizer will stop
totalizing.
To enable key board lock out, press “LOCK ON” key, display will show “LOCK ON”,
then press “ENTER” key to exit. To turn off lock, use arrows to set a value of 125, and
press “ENTER” key, display will show “LOCK OFF”.
“F1” & “F2” keys are not used.
To set velocity calibration factor, press “CAL” key. The µP display will show “VEL.
CAL”. Use the “SCROLL” keys to increase or decrease value, cal. range is 0-255%,
default is 100%. When finished, press “ENTER” key to exit. NOTE: calibration factor
will affect the display, alarms, and 4-20mA.
To set damping factor, press “DAMP” key. The µP display will show “DAMPING”. Use
the “SCROLL” keys to increase or decrease value, damping range is 1-10 seconds,
default is 2 seconds. When finished, press “ENTER” key to exit.
12
NOTE: damping factor will affect the display, alarms, and 4-20mA.
To turn on test mode, press “TEST” key, display will show “TEST MODE”. The 4-20mA
output will be set to 20mA. Press “ENTER” key to exit function.
To access the 2nd function, press the “2nd FUNCT” key, display will show “SERVICE
MODE”. Then select any function that is located in the yellow part of the key pad.
Press “ENTER” key to exit function.
To view the Doppler’s signal strength level, press “2nd FUNCT” key, then “SIGNAL
STR” key. The display will show “SERVICE MODE” and “SIGNAL STR.”. When flow is
present, a good signal strength level is 150 or higher. Press ‘ENTER’ key to exit
function.
To adjust the 4mA output press “2nd FUNCT” key then the “4mA” key. The µP display
will show “SERVICE MODE” and “4mA”. Use the ‘SCROLL” keys to increase or
decrease the 4-20mA output level. When finished with function, press “ENTER” key.
To view the Doppler’s raw velocity level, press “2nd FUNCT” key and then “VEL ADC”
key. The µP display will show “SERVICE MODE” and “VEL ADC1”. When flow is at 10
FPS, a level of 1024 will be displayed. Press “ENTER” key to exit function.
To set the liquid Blanking time, press “2nd FUNCT” key and then the “BLANKING” key.
The µP display will show “SERVICE MODE” and “BLANKING”. Use the “SCROLL”
keys to increase or decease the minimum liquid level the unit can read. This is done by
rejecting receive signals that are less than the set value 17 (0” -2.0”) or (1 blanking
change is equal to 0.2” liquid level). Changing the Blanking setting may also alleviate
unstable readings in some applications. Default level is 20 [0” - 2.6”]. Press “ENTER”
key to exit function.
NOTE: never set the blanking range greater than 75% of the minimum level you desire to detect.
13
To set the liquid detection level, press “2nd FUNCT” key and then the “DETECT LEVEL”
key. The µP display will show “SERVICE MODE” and “DET LEVEL”. Use the
“SCROLL” keys to increase or decrease level in which the receive signal is filtered.
Lowering the value will allow the unit to produce a reading when none existed before.
Raising the value will allow the unit to stabilize unwanted “Fault Light” occurrences as
well as helping to stabilize readings and outputs. Default level is 150. Press ‘ENTER”
key to exit function.
To adjust the 20mA output press “2nd FUNCT” key then the “20mA” key. The µP
display will show “SERVICE MODE” and “20mA”. Use the “SCROLL” keys to increase
or decrease the 4-20mA output level. When finished with function, press “ENTER”
KEY.
To set the liquid level gain, press 2nd FUNCT” key and then the “LL GAIN “ key. The
µP display will show “SERVICE MODE” and “GAIN”. Use the “SCROLL” keys to
increase or decrease level in which the receive signal is amplified. Lowering the value
will help to stabilize unstable readings and outputs. Raising the value will allow the unit
to produce a reading when none existed before. Default level is 55. Press “ENTER”
key to exit function.
To set the Doppler’s velocity signal strength cutoff level, press “2nd FUNCT” key and
then the ‘VEL SS CUTOFF” key. The µP display will show “SERVICE MODE” and “VEL
SS CUTOFF”. Use the “SCROLL” keys to increase or decrease level in which the
microprocessor stops reading the velocity because of low signal strength. Default level
is 100. Press “ENTER” key to exit function. Note: if velocity signal strength cutoff level
is set higher than velocity signal strength, the meter will not show flow.
To set the power fail level, press “2nd FUNCT” key and then the “POWER FAIL” key.
The µP display will show “SERVICE MODE” and “PWR FAIL”. Use the “SCROLL” keys
to increase of decrease voltage level in which triggers a power failure warning. The
microprocessor will then store totalizer readings. The default level is 200. Press
14
“ENTER” key to exit function. Note: It is not recommended to alter this level from
factory settings.
To set liquid level calibration factor, press “2nd FUNCT” key and then the “CAL LEVEL”
key. The µP display will show “SERVICE MODE” and “VEL CAL.”. Use the “SCROLL”
keys to increase or decrease value, cal. range is 0 - 255%. When finished, press
“ENTER” key to exit.
NOTE: calibration factor will affect the display, alarms, and 4-20mA.
“INPUT F.S.” key is not used.
“DAC -- 3” key is not used.
To toggle backlight on or off, press “2nd FUNCT” key and then “BACKLIGHT” key. The
µP display will show “SERVICE MODE” and backlight will toggle when “BACKLIGHT”
key is depressed. Press “ENTER” key to exit function.
To adjusted the display contrast press “2nd FUNCT” key then the “CONTRAST” key.
The µP display will show “SERVICE MODE” and “CONTRAST”. Use the “SCROLL”
keys to increase or decrease the contrast level, defaults is10. When finished with
function, press “ENTER” key.
15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.