• “Quick-Start Operating Overview” on page6 is intended to help you get the DFX flow meter up and running quickly.
Refer to the detailed instructions if you require additional information.
• The remaining chapters provide a detailed description of all software settings and hardware installation guidance.
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
UNPACKING AND INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such
as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:NIf damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
SAFETY
Terminology and Symbols
Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing death or serious
personal injury.
Indicates a hazardous situation, which, if not avoided, could result in severe personal injury or death.
Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing minor or moderate
personal injury or damage to property.
Page 5 August 2019DPP-UM-00256-EN-03
Quick-Start Operating Overview
QUICKSTART OPERATING OVERVIEW
This manual contains detailed operating instructions for all aspects of the DFX flow instrument. The following condensed
instructions are provided to help you get the instrument up and running as quickly as possible. This pertains to basic
operation of the clamp-on transducer only. If specific instrument features, a hazardous area installation or an alternate
transducer style are to be used—or if you are unfamiliar with this type of instrument—see the appropriate section in the
manual for complete details.
Transducer Location
Determine the appropriate mounting location for the transducers. (See Figure 1.) Pipe must be filled with liquid for
proper operation.
FLOW
h
Figure 1: Transducer locations
45°
YES
45°
Figure 2: Transducer mounting configuration
Pipe Preparation and Transducer Mounting
h
Top View of Pipe
Top of
Pipe
W and V Mount
1. The piping surface, where the transducers mount, needs to be clean and dry. Remove loose scale, rust and paint for
satisfactory acoustical bonds.
2. Connect the mounting straps around the pipe. Leave the strap loose enough to slip the transducers underneath.
3. Apply a liberal amount of couplant grease onto the transducer faces.
4. Place each transducer under the mounting strap, 180° apart on the pipe. Verify that the transducer cables are facing the
same direction on the downstream side of the ow. See Figure 3.
5. Route the transducer cable back to the monitor, avoiding conduits that contain high voltage AC supply wires.
Page 6 August 2019DPP-UM-00256-EN-03
Quick-Start Operating Overview
FLOW
Figure 3: Transducer direction
Top View
of Pipe
Transducer Connections
1. Mount the monitor within the length of the transducer cables.
2. Route the transducer cables through the center conduit hole in the bottom of the enclosure and connect to terminal block
J4. The terminal blocks are a removable and can be disconnected to simplify wiring access. See the wiring diagram inside
the door for reference.
Startup
Initial Settings and Powerup
1. Verify that the power supply jumper settings are properly congured for the power supply. See “Power Supply Wiring
Connections” on page 21 or the wiring and jumper selection diagram is located inside the door.
OTE:NPower supply selection is specified during order placement and appropriate jumpers are placed at the factory.
If power is changed from AC to DC or vice versa, the fuse requirement changes. Fuse ratings are listed on the
transmitter’s door.
2. Route power connections through the conduit hole farthest to the left and in the enclosure. Then connect power to the J2
terminal block. See Figure 11 on page 17.
3. Apply power. On initial power-up, the DFX ow meter conducts a series of self-diagnostic tests and buering operations
that take approximately 30 seconds.
4. Enter pipe internal diameter (Pipe ID), measuring units and output conguration.
Page 7 August 2019DPP-UM-00256-EN-03
Introduction
INTRODUCTION
General
The DFX ultrasonic flow meter is designed to measure volumetric flow of solids-bearing or aerated liquid within a closed
conduit. Transducers are available as non-contacting (DT9) or insertion probe (DP7) types. DT9 non-contacting transducers
are strapped to the outside of a pipe and are suitable for most installations where the pipe material supports the transmission
of ultrasound. Some pipe materials, such as concrete pressure pipe and some plastic lined pipes do not allow ultrasound to
penetrate to the liquid inside. For these applications, use the DP7 insertion probe.
The flow meter operates by transmitting an ultrasonic sound from a transmitting transducer through the pipe wall or from
the probe tip into the moving liquid. The sound is reflected by sonic reflectors suspended in the liquid and recorded by the
receiving transducer. If the sonic reflectors are moving within the sound transmission path, sound waves are reflected at a
frequency shifted (Doppler frequency) from the transmitted frequency. The shift in frequency is directly related to the speed
of the moving particle or bubble. This shift in frequency is interpreted by the instrument and converted to various user
defined measuring units.
The criteria for a good Doppler reflector are:
• The scattering material must have a sonic impedance (sound speed difference) at least 10% different from the fluid.
• There must be some particles large enough to cause longitudinal reflection—particles larger than 35 micron.
• For a given pipe size, the longitudinal reflection must have sufficient energy to overcome the Rayleigh (energy wasting)
scattering caused by smaller particles.
• The reflecting material must travel at the same velocity as the fluid for good accuracy.
Application Versatility
The DFX flow meter can be successfully applied on a wide range of metering applications. The easy-to-program transmitter
allows the standard product to be used on pipe sizes ranging from 1…120 in. (25…3050 mm) pipe ID. With the small pipe
transducer option, the pipe size range is 0.25…1 in. (6…25 mm). A variety of liquid applications can be accommodated:
• Sewage
• River water
• Plant effluent
• Mining slurries
• Sludge
• Others
Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure,
fouling or wear. Standard transducers are rated to a pipe surface temperature of 250° F (121° C).
Page 8 August 2019DPP-UM-00256-EN-03
Introduction
User Safety
The DFX flow meter employs modular construction and provides electrical safety for the operator. The enclosure is
constructed from rugged polycarbonate plastic with UV inhibitors. The enclosure does not contain any conductive materials
that can become energized while the door is closed. The keypad is made of polycarbonate and is designed for outdoor use.
The AC power transformer provides 4000 Volts of isolation from the power supply mains. The display face contains voltages
no greater than 24V DC. Output modules are optically isolated from external power supplies and provide a great degree of
immunity to ground loops.
CAUTION
IF THE DFX FLOW METER IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED
BY THE EQUIPMENT MAY BE IMPAIRED.
Data Integrity
The DFX flow meter retains all user configuration data and totalizer accumulations in non-volatile FLASH memory indefinitely.
Product Identication
The serial number and complete model number of the transmitter are on the side of the monitor enclosure.
Figure 4: Product labels
Page 9 August 2019DPP-UM-00256-EN-03
Transducer Installation
TRANSDUCER INSTALLATION
Unpacking and Inspection
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such
as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:NIf damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
Mounting Locations
The transducers contain piezoelectric crystals for transmitting and receiving ultrasonic sound energy through the pipe wall
(DT9) and from the probe tip (DP7). Placement of the ultrasonic transducer is the most critical step in achieving an accurate
and reliable flow reading. All flow meters of this type rely on a full-pipe of fluid that is flowing symmetrically (evenly) in
the pipe. Flow in partially filled pipes and immediately downstream of elbows, valves and pumps is unstable and leads to
unstable readings and non-linearity.
The DFX flow meter has software algorithms that assume a full pipe of liquid. Install only in locations where the pipe is filled
at all times when flow measurements are required. Avoid partially filled pipes that can lead to very large flow measurement
errors. See Figure 5 for possible pipe configurations.
h
Figure 5: Pipe configurations and installation recommendations
Page 10 August 2019DPP-UM-00256-EN-03
h
Transducer Installation
Select a transducer mounting location with adequate straight runs of pipe, both upstream and downstream, to achieve stable
readings1. See Figure 6 for examples of minimum upstream and downstream requirements.
Piping Conguration
and Transducer Positioning
Flow
*
Flow
*
Flow
**
**
Upstream
Pipe
Diameters
Downstream
Diameters
***
24
14
10
Pipe
5
5
5
**
**
**
**
10
10
24
5
5
5
*
Flow
*
Flow
*
Flow
*
Figure 6: Upstream/Downstream Pipe Requirements
1
The DFX system provides repeatable measurements on piping systems that do not meet these requirements, but the
accuracy may be affected.
Page 11 August 2019DPP-UM-00256-EN-03
Transducer Installation
Pipe Preparation
Before the transducer heads are mounted to the pipe surface, an area slightly larger than the flat surface of the transducer
face must be prepared. If pipe insulation is present, it must be peeled back to expose the pipe surface. Use a wire brush to
remove loose paint, rust, scale or dirt. Paint, if bonded well to the pipe surface, does not need to be removed. Any bumps
present on ductile iron pipe do not need to be removed. Thoroughly dry the mounting surfaces so that the couplant grease
bonds to the surface.
OTE:NSmall pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception.
Couplant
Use a coupling compound to create an acoustically conductive path between the transducer and the prepared pipe surface.
Clamp-on ultrasonic meters do not operate without coupling compound mounted between the pipe wall and the transducer
face. Enclosed with the DFX system is a tube of coupling compound that is adequate for general purpose applications. Use
a silicone-based valve grease or RTV (Room Temperature Vulcanizing) products or grease for Doppler installations as they
operate over a very wide temperature range. In some installations, such as automotive, silicone is not permitted. Alternate
petroleum-based products can be used, but verify that the grease is rated not to flow at the maximum surface temperature
anticipated on the pipe.
In general, use the following couplants with these transducers:
Clamp-on transducers should be mounted on the pipe 180° apart and facing each other on the pipe, with the cables on the
downstream side of the transducers. If the pipe is horizontal, the preferred mounting orientation is 3 and 9 o’clock, with
12 o’clock being the top of the pipe. See Figure 7. Orientation on vertical pipes does not matter.
FLOW
Figure 7: Transducer Placement
Large pipe installations use stainless steel straps to secure the transducers to the outside of the pipe. The DFX system is
shipped with four 36 in. (900 mm) straps, which are suitable for pipes up to 39 in. (1000 mm) diameter.
1. Select the proper number of transducer straps to allow a complete strap to go around the circumference of the pipe. If a
pipe is larger than 39 in. (1000 mm), use a single strap/buckle arrangement to reduce the number of strap connections.
The straps can be connected together to make a continuous length. Small pipe installations use an integral clamping
mechanism built into the transducer.
Pipe SizeStraps Required
1…9 in. (25…225 mm)1
10…19 in. (250…480 mm)2
20…29 in. (500…740 mm)3
30…39 in. (760…1000 mm)4
Table 2: Straps required vs. pipe size
Top View
of Pipe
Page 12 August 2019DPP-UM-00256-EN-03
Transducer Installation
2. Wrap the strap around the pipe where the transducers mount. Leave the strap loose enough to allow the transducers to
be placed underneath. If multiple straps are being used, wrap electrical tape around all but one strap connection to secure
the strap worm screws in place.
3. Spread an even layer of coupling compound, approximately 1/8 in. (3 mm) thick, to the prepared transducer mounting
areas of the pipe.
4. Spread an even layer of coupling compound, approximately 1/8 in. (3 mm) thick, to the at face of the two transducers.
5. Place each transducer under the strap with the at face—amber plastic window—positioned towards the pipe. The notch
on the back of the transducer provides a mounting surface for the strap. The transducer cables must be facing in the same
direction and downstream of the transducers for proper operation.
OTE:NLarge pipes may require two people for this procedure.
6. Tighten the strap enough to hold the transducers in place, but not so tight that all of the couplant squeezes out of the gap
between the transducer face and pipe. Make sure that the transducers are squarely aligned on the pipe and 180° apart. If
RTV is used, avoid moving the transducers during the curing time (typically 24 hours) as bubbles may form between the
transducer and pipe that can reduce ultrasonic signal transmission to unsatisfactory levels.
7. Route the transducer cables back to the area where the transmitter mounts, avoiding high voltage cable trays and
conduits. While transducer cable extension is not generally recommended, if additional transducer cable length is
required, use cable and connectors of the correct type and impedance. In many cases, especially if a splice my be exposed
to water or other liquids, it may be more eective to replace the entire cable. Transducers use RG59, 75 Ohm coaxial cable
or Twinax (Belden #9463) or (Belden # 9463DB) 78 Ohm two conductor cable.
8. If the transducers are permanently mounted using Dow 732, the RTV must be completely cured before proceeding to
Instrument Startup. Make sure that no relative motion between the transducer and pipe occurs during the 24 hour curing
process. If Dow 111 grease was used for temporary operation of the DFX system, proceed with the Startup procedures.
DP7 Probe Transducer Mounting
The DP7 insertion transducer that is used by the DFX flow meter contains piezoelectric crystals for transmitting and receiving
ultrasonic sound energy. The black Ultem® plastic tip of the DP7 transducer contains these crystals, which are designed to be
inserted just into the path of the flowing liquid.
Select a transducer mounting location that is completely filled with liquid when flow measurements are made (see
Figure 5) and with adequate straight runs (without disturbances) of pipe, both upstream and downstream, to achieve stable
and accurate readings. Examples of minimum upstream and downstream requirements are included in Figure 5 on page 10.
Figure 8: Installation locations
When installing the DP7 transducer in a horizontal pipe, the preferred orientation is at least 20 degrees from the top or
bottom of the pipe. Verify that the mounting location allows for adequate clearance to install and retract the probe fully from
the pipe.
The following instructions cover hot tapping applications where the installation or removal of the transducer probe must
be done without shutting down the process pressure. If the product is being installed without an isolation valve, ignore
the steps that pertain to its installation. Figure 9 illustrates an exploded view of an isolation valve assembly and names the
various components.
Page 13 August 2019DPP-UM-00256-EN-03
Transducer Installation
Seal
Fitting
Full Port
Ball Valve
Close
Nipple
Weld
Coupling
Figure 9: Hot tap installation
The Bronze Hot Tap Kit (p.n. D030-1006-001) and the Stainless Steel Hot Tap Kit (p.n. D030-1006-002) include an isolation valve
assembly and are designed for installation in pipes under pressure, up to 700 psi (48 bar) at 70° F (21° C).
All items required for installation are provided with the kit, except for the 1-1/2 in. NPT weld coupling or service saddle and
the drilling and welding equipment. These instructions call for the use of a drilling machine designed for operations under
pressure (for example, Mueller Co., Water Products Division).
1. Verify that the pipe’s line pressure is within the rated limits of the pressure drilling machine being used.
2. Grind o paint or other coatings from the pipe in the DP7 probe mounting area.
3. Tack weld a 1-1/2 in. NPT weld coupling to the pipe or install a service saddle according to the supplier’s instructions. The
coupling or saddle must be aligned perpendicular to the pipe axis and square to its plane.
4. Complete welding. A water tight, 0.25 in. minimum weld bead is recommended.
5. Install the close nipple (supplied with assembly) into the weld coupling. Use appropriate pipe sealants.
6. Install the isolating ball valve on the close nipple. Verify that the valve is in the fully open position.
7. Install drill bit and adapter into the pressure drilling machine. Then attach the machine to the isolation valve.
8. Drill through the pipe wall in accordance with the instructions supplied with the drilling machine.
9. Withdraw the drill bit through the isolating valve.
10. Close the valve and remove the drilling machine.
11. Check for leakage at valve and connections.
12. Place pipe sealant on the 1-1/2 in. NPT threads of the insertion tting assembly.
13. Screw the assembly into the isolation valve and tighten with a 2-1/2 in. pump wrench.
Page 14 August 2019DPP-UM-00256-EN-03
Transducer Installation
Probe Cables
Before inserting the probe into the pipe, the sensor cables should be routed to the transmitter location. Verify that the
supplied cable length is sufficient to meet the installation requirements. While transducer cable extension is not generally
recommended, if additional transducer cable length is required, use cable and connectors of the correct type and
impedance. In many cases, especially if a splice my be exposed to water or other liquids, it may be more effective to replace
the entire cable. Transducers use RG59, 75 Ohm coaxial cable, Twinax (Belden #9463) or (Belden # 9463DB) 78 Ohm
two-conductor cable.
CAUTION
THE PROBE CABLES ARE DESIGNED TO CARRY LOW LEVEL SIGNALS THAT ARE DEVELOPED BY THE SENSOR. CARE
SHOULD BE TAKEN IN ROUTING THE CABLES. AVOID RUNNING CABLES NEAR SOURCES OF HIGH VOLTAGE OR EMI/RFI.
ALSO AVOID ROUTING THE CABLES IN CABLE TRAY CONFIGURATIONS, UNLESS THE TRAYS ARE SPECIFICALLY USED
FOR OTHER LOW VOLTAGE, LOW LEVEL SIGNAL CABLES.
CAUTION
THE INTERNAL DP7 PROBE WIRING IS EPOXY ENCAPSULATED TO SEAL IT FROM MOISTURE. THE DP7 PROBE IS
PROVIDED WITH TWO COAXIAL CABLES TO SHIELD THE LOW LEVEL SIGNALS AND MUST BE CONTINUOUS TO THE DP7
PROBE TRANSMITTER. EXCESS WIRE MAY BE CUTOFF OR SIMPLY COILED NEAR THE DFX FLOW METER.
Probe Retraction Procedure
1. Retract the probe by loosening the upper jam nuts counterclockwise as viewed from the top of the probe using the proper
size wrench. If the pipe is under pressure, the nuts must be turned alternately about two turns at a time to prevent binding
as a result of non-equal seal loading. In many cases, the line pressure causes the probe to retract. Should the probe bind,
use the retraction nuts on the lower side of the probe ange to assist in the probe retraction. Continue this procedure until
the probe is fully retracted into the isolation valve.
CAUTION
DO NOT RUN THE DRIVE NUTS OFF THE RODS UNTIL THE ISOLATION VALVE IS FULLY CLOSED.
2. After the probe is retracted past the “ball” in the isolation valve, the isolation valve may be closed to isolate the probe from
the line so the probe can be removed entirely.
CAUTION
IF THE INSERTION PROBE IS NOT ABOVE THE “BALL” OF THE ISOLATION VALVE, THE VALVE CANNOT BE CLOSED. IF
THE VALVE WILL NOT CLOSE SMOOTHLY, THE BODY OR TIP OF THE PROBE IS MOST LIKELY NOT ABOVE THE “BALL”.
ATTEMPTING TO FORCE THE VALVE INTO THE CLOSED POSITION MAY RESULT IN DAMAGE TO THE PROBE.
Page 15 August 2019DPP-UM-00256-EN-03
Transducer Installation
Probe Insertion
Before inserting the DP7 probe into the piping system, calculate the probe insertion depth. Refer to the paragraphs that
follow and Figure 10 on page 17 for information regarding this process. The variables required are:
• The overall probe length
• Pipe internal diameter (ID)
• Pipe wall thickness
• The length of the valve stack
• Amount of straight pipe diameters in the system
To Calculate Insertion Depth
Using this information and referring to Figure 10, proper insertion depth can be determined.
• Measurement A — The typical depth that the DP7 probe tip is inserted into the piping system is 1/8 (12.5%) of the pipe
internal diameter.
• Measurement B — Pipe wall thickness. This information can be obtained from standard pipe wall charts (see
“Specifications” on page40) or ideally can be measured using an ultrasonic wall thickness gauge.
• Measurement C — Measure the distance that is going to be taken up by the pipe tap, nipple, full-flow ball valve and the
insertion fitting. DP7 probes use 1-1/2 in. NPT hardware and the insertion fitting is approximately 2-1/2 in. in height.
• Measurement D — The length of DP7 probe that protrudes from the insertion fitting after it is inserted to the proper
depth in the fluid stream.
• Measurement E — This is the overall length of the probe measured from the black measurement tip to the top flange on
the probe.
Measure and record the following linear dimensions.
A=0.125 x Pipe OD=
B=Pipe Wall Thickness=
C=Seal Fitting to Pipe Wall=
D=E - C - B - A
D=
E=Probe Length=
Page 16 August 2019DPP-UM-00256-EN-03
Transducer Installation
Full Port
Ball Valve
Seal
Fitting
DP7 Probe
Pipe WallB
E
A
1/8 Pipe
Diameter
DP7
Length
Insertion
Measurement
D
Valve and
Seal Stack
C
Internal
Diameter
OTE:NFor some low pressure/low temperature applications less than 30 psi (2.1 bar) and less than 100° F (38° C), the probe
may be pushed in by hand to decrease the insertion time.
Figure 10: Installation measurements
Flow Direction
Arrow
Figure 11: Flow direction arrow
1. Lubricate the O-rings located within the DP7 probe seal tting so that the seals are not damaged during probe insertion.
2. Run the lower jam nuts down to a point that approximates the nal insertion position or at least far enough to allow
insertion into the insertion tting.
3. Using the threaded rods as a guide, position the probe in the insertion tting. Continue to insert the probe into the
isolation assembly until the probe tip comes in contact with the closed “ball” in the isolation valve.
CAUTION
DO NOT FORCE THE PROBE TIP AGAINST THE “BALL”, AS DAMAGE TO THE PROBE TIP MAY RESULT.
4. Replace the upper jam nuts (2 on each rod) and the cotter pins. The nuts should be run down to the top side of the
retaining collar and the cotter pins replaced.
5. Orient the probe in the direction of ow as indicated by the ow direction arrow located on the top of the probe ange.
6. Lock the probe in position with the enclosed Allen wrench.
CAUTION
THE NUTS ON BOTH ENDS OF THE RETAINING RODS MUST ALWAYS BE IN PLACE AS A SAFETY MEASURE TO PREVENT
POSSIBLE PROBE BLOW OUT. INSERTING COTTER PINS IS A FURTHER SAFETY MEASURE.
7. Slowly open the isolation valve. When the valve is fully open, use the proper size wrench on the insertion nuts, alternately
tightening each nut about two complete turns to avoid uneven seal loading.
Page 17 August 2019DPP-UM-00256-EN-03
Transmitter Installation
TRANSMITTER INSTALLATION
Unpacking and Inspection
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such
as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:NIf damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
Mounting Location
The enclosure should be mounted in an area that is convenient for servicing, calibration and for observation of the
LCD readout.
1. Locate the transmitter within the length of transducer cable that was supplied with the DFX system. If this is not possible,
exchange the cable for one that is of proper length. While transducer cable extension is not generally recommended,
if additional transducer cable length is required, use cable and connectors of the correct type and impedance. In many
cases, especially if a splice my be exposed to water or other liquids, it may be more eective to replace the entire cable.
Transducers use RG59,75 Ohm coaxial cable or Twinax (Belden #9463) or
(Belden # 9463DB) 78 Ohm two-conductor cable.
2. Mount the DFX ow meter in a location that is:
• Free of vibration
• Protected from falling corrosive fluids
• Within ambient temperature limits – 40…185° F (– 40…85° C)
• Out of direct sunlight. Direct sunlight may increase transmitter temperature to above the maximum limit
3. See Figure 12 for enclosure and mounting dimension details. Make sure there is enough room for door swing, maintenance
and conduit entrances. Secure the enclosure to a at surface with four appropriate fasteners.
4. Use conduit hubs where cables enter the enclosure. Seal unused holes with plugs.
OTE:NUse NEMA 4 (IP-65) rated fittings/plugs to maintain the watertight integrity of the enclosure. Generally, the left
conduit hole (viewed from front) is used for line power, the center conduit hole for transducer connections and the
right hole is used for ISO-MOD I/O wiring.
5. If additional holes are required, drill the appropriate size hole in the enclosure’s bottom. Use extreme care not to run the
drill bit into the wiring or circuit cards.
To access terminal strips for electronic connectors, loosen the two screws in the enclosure door and open the door.
1. Guide the transducer connectors through the middle conduit hole located of the transmitter enclosure. Secure the
transducer cable with the supplied conduit nut (See Figure 13).
JP1
J3
J4
J2
Figure 13: Transducer cable installation
The terminals within the DFX flow meter are removable. They can be unplugged, wired and then plugged back in.
2. Connect the wires to J4 at the corresponding screw terminals in the transmitter. See Figure 14 or the Wiring Diagram
located inside the door of the transmitter.
OTE:NThe transducer cable carries low level, high frequency signals. While transducer cable extension is not generally
recommended, if additional transducer cable length is required, use cable and connectors of the correct type and
impedance. In many cases, especially if a splice my be exposed to water or other liquids, it may be more effective to
replace the entire cable. Transducers use RG59, 75 Ohm coaxial cable or Twinax (Belden #9463) or (Belden # 9463DB)
78 Ohm two conductor cable. Cable lengths up to 990 feet (300 meters) are available.
+
C3
Transducer
Connections
JP3
1
7
241
VPP12-800
3
9
CLASS B
3
R
®
4
10
6
12
VDE
JP2
JP1
J3
J4
J2
+
C3
Grounding
Wire
Lock Nut
Figure 14: Transducer connections
Page 20 August 2019DPP-UM-00256-EN-03
Transmitter Installation
Power Supply Wiring Connections
Connect power to the screw terminal block marked J2 through the conduit hole on the left side of the enclosure. See Figure 15
for AC power supplies and Figure 16 for DC power supplies. Use wiring practices that conform to local and national codes (for
example, The National Electric Code Handbook in the U.S.).
CAUTION
ANY OTHER WIRING METHOD MAY BE UNSAFE OR CAUSE IMPROPER OPERATION OF THE INSTRUMENT.
TO AVOID SERIOUS INJURY OR DAMAGE, DISCONNECT ELECTRICAL POWER BEFORE SERVICING THIS METER.
OTE:NThis instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (such
as fluorescent lights, relays, compressors or variable frequency drives). Do not run line power with other signal wires
within the same wiring tray or conduit.
WIRING DIAGRAM
CAUTION! To avoid serious injury or damage,
disconnect electrical power before servicing this meter
LINE VOLTAGES MAY BE PRESENT WITHIN THE ENCLOSURE. THERE IS A RISK OF SHOCK, SPARKS AND DEATH IF THIS
PRODUCT IS HANDLED IN AN UNSAFE WAY. SERVICE SHOULD ONLY BE DONE BY QUALIFIED PERSONNEL.
1. Verify that the jumpers at JP3 are properly oriented for the power supply. See Figure 15.
2. Verify that the jumpers at JP1 and JP2 are not present.
3. Connect L1, L2 and EARTH to the terminals referenced in Figure 15. Phase and neutral connections to L1 and L2 are not
polarized. Do not operate without an earth ground connection.
4. See Figure 16 for AC connection schematic. Wire gauges up to 14 AWG can be accommodated in the DFX ow meter’s
terminal blocks.
OTE:NA switch or circuit breaker is required in the installation. The switch or circuit breaker must be in close proximity
of the DFX flow meter and within easy reach of the operator. The switch or circuit breaker must be marked as the
disconnect device for the DFX flow meter.
JP1
J3
J4
J2
AC Power
Connections
Figure 16: DFX flow meter AC power connection
50/60 Hz
17 Watts Maximum
DC Power Supply Connections
The DFX flow meter may be operated from a 12…28V DC source, as long as the source is capable of supplying 7 Watts.
• 12V DC Supply @ 600 mA minimum
• 24V DC Supply @ 300 mA minimum
1. Verify that the jumpers are properly placed. See the wiring diagram inside the door of the DFX ow meter enclosure or see
Figure 15. The jumpers at JP3 should not be present and the jumpers at JP1 and JP2 should be in place.
2. Connect the DC power source as illustrated in the schematic in Figure 17 on page 23. Wire up to 14 AWG can be
accommodated in the DFX ow meter terminal blocks.
OTE:NA switch or circuit breaker is required in the installation. The switch or circuit breaker must be in close proximity
of the DFX flow meter and within easy reach of the operator. The switch or circuit breaker must be marked as the
disconnect device for the DFX flow meter.
Page 22 August 2019DPP-UM-00256-EN-03
Transmitter Installation
JP1
J3
J4
J2
DC Power
Connections
12 to 28 VDC
7 Watts Maximum
Figure 17: DC power connection
Multiple Meter Installations
The DFX flow meter contains a provision for synchronizing multiple DFX flow meters together. Synchronization is required
when more than one DFX flow meter is mounted on a common pipe or header system. If the meters are not synchronized, a
phenomena called “cross-talk” can occur between meters, which can lead to erroneous readings or no readings at all.
Cross-talk results from the small differences in transmitted frequency generated from two or more different ultrasonic
flow meters. By synchronizing the transmitted ultrasonic energy, cross-talk caused by differences in transmitted frequency
is eliminated.
The DFX flow meter synchronization circuit is designed to interconnect up to four DFX flow meters over a cable length of 100
feet (30 meters). Use 20-22 AWG twisted-pair shielded interconnection wire for this purpose. See Figure 18.
2. Daisy-chain connect the EXTernal SYNChronization and GND terminal blocks together between the meters to be
synchronized, using the twisted-pair cable described previously. The terminal block is located on the circuit board that is
mounted on the door of the meter’s monitor. See Figure 15 on page 21 or the Wiring Diagram inside the door of the
DFX monitor.
3. At a single point, connect the shield drain wire from the interconnection cable to earth ground.
4. Congure the SYNC SELECT jumpers on the DFX ow meters. One DFX ow meter should be congured for INT and the
remaining units congured for EXT (see Figure 19).
Figure 19: DFX flow meter synchronization connections
ISO Modules
The DFX flow meter uses ISO-MODs for input and output functions. ISO-MODs are epoxy encapsulated electronic input/
output modules that are simple to install and replace in the field. See Figure 20. All modules are 2500 V optically isolated from
the DFX flow meter’s power and earth grounds. This eliminates the potential for ground loops and reduces the chance of
severe damage in the event of an electrical surge.
Three ISO-MOD options are available: 4…20 mA, dual-relay and rate pulse. The DFX flow meter supports any two ISO-MOD
input/output modules. All modules are field-configurable by using the keyboard interface. Field wiring connections to
ISO-MODs are quick and easy using removable wiring terminals. Configuration and connection of the various ISO-MODs are
described on the following pages.
ISO Module Replacement
To remove an ISO-MOD, remove the two machine screws that secure the module in place and pull the module straight out of
the enclosure. A 10-pin connection is on the bottom of the module that mates with the circuit board underneath. To install
and ISO-MOD, push the module into the 10-pin connector and tighten the two machine screws. Re-calibrate the parameters if
the 4…20 mA modules are replaced. See “Module Configuration Parameters” on page 35 for instructions.
WIRING DIAGRAM
CAUTION! To avoid serious injury or damage,
disconnect electrical power before servicing this meter
The 4…20 mA Output Module interfaces with most recording and logging systems by transmitting an analog current signal
that is proportional to system flow rate. Configure the 4…20 mA ISO-MOD via jumper selections for an internally powered
(Figure 22) or externally powered (Figure 23) module. Do not exceed the maximum load for a particular supply voltage.
See Figure 21.
Supply Voltage - 7 VDC
1100
1000
900
800
700
600
500
400
Loop Load (Ohms)
300
200
100
121416182022242628
0.02
Supply Voltage (VDC)
Figure 21: Maximum 4…20 mA loads
= Maximum Loop Resistance
Operate in the
Shaded Regions
Internal Power Conguration
Verify that jumpers are in place at JP1 and JP2 on the module. See Figure 22 . In this configuration, the 4…20 mA output
is driven from a +24V DC source located within the DFX flow meter. The 24V DC source is isolated from the DC ground
and earth ground connections within the DFX flow meter. The module can accommodate loop loads up to 800 Ohms in
this configuration.
OTE:NThe +24V internal supply, if configured to power the 4…20 mA output, shares a common ground with another
ISO-MOD (if installed). If another module is connected to earth ground, a ground loop may occur. The solution to this
problem is to configure the 4…20 mA module for external power and use an external isolated supply to power the
4…20 mA loop.
4-20 mA IN (+)
4-20 mA OUT (-)
RTU/PLC
MONITOR
Figure 22: Internally powered 4…20 mA
OUT (-)
IN (+)
INT PWR EXT PWR
JP2
JP1
Use Both
Jumpers
I/O: 4-20 mA
P.N. D020-1045-100
ISO-MOD
Page 25 August 2019DPP-UM-00256-EN-03
Transmitter Installation
External Power Conguration
Remove the two jumpers located at JP1 and JP2 on the module. See Figure 23. In this configuration, the 4…20 mA module
requires power from an external DC power supply. The voltage of the external power source must be sufficient to power the
module and drive the loop load. The loop loss attributed to the ISO-MOD is 7V DC, so the minimum voltage required to power
a loop can be calculated using the following formula: Loop voltage (min) = (loop load Ohms × 0.02) + 7
I/O: 4-20 mA
OUT (-)
IN (+)
INT PWR EXT PWR
JP2
JP1
Jumpers
P.N. D020-1045-100
ISO-MOD
Remove
4-20 mA IN (+)
4-20 mA OUT (-)
RTU/PLC
MONITOR
Figure 23: Externally powered 4…20 mA
Page 26 August 2019DPP-UM-00256-EN-03
Transmitter Installation
Control Relay Output Module
Two independent SPDT (single-pole, double-throw, Form C) relays are contained in this module. The relay operations are user
configured via the front panel to act in either a flow rate alarm, error alarm or totalizing pulse. The relays are rated for 200V AC
maximum and have a current rating of 0.5 A resistive load (175V DC @ 0.25 A resistive). Use a secondary relay whenever the
Control Relay ISO-MOD is used to control inductive loads such as solenoids and motors.
Typical relay connections are illustrated in Figure 24. The reed relays located within the relay module can interface directly
with small pilot lights, PLCs, electronic counters and SCADA systems.
Figure 25 shows the connection of an external power relay to the Relay ISO-MOD. Use external power relays whenever the
load to be switched exceeds the switch rating of the reed relays, or if the load is inductive in nature.
FLOW OK
LOW F LOW
P
EXTERNAL
TOTALIZER/SAMPLER
Figure 24: Typical relay connections
INTERNAL
CURCUIT
b NO
b CM
b NC
a NO
a CM
a NC
I/O: RE L A Y
P.N. D020-1045-102
ISO-MOD
POWER
RELAY
b NO
b CM
b NC
a NO
a CM
a NC
POWER
SOURCE
Figure 25: External relay connections
I/O: RELAY
P.N. D020-1045-102
ISO-MOD
Page 27 August 2019DPP-UM-00256-EN-03
Instrument Programming
Rate Pulse Output Module
The Rate Pulse Output Module is used to transmit information to external counters and PID systems via a frequency output
that is proportional to system flow rate. The frequency output range of the Rate Pulse Module is 0…2500 Hz. This module has
two types of outputs: one simulates the output of the coil of a turbine flow meter and the other is an open-collector type that
does not source voltage at its output. Both outputs may be connected simultaneously.
The turbine meter output creates a 500 mV peak-to-peak saw-tooth waveform that is not referenced to ground. This output
can be run to electronic monitors that are compatible with variable reluctance outputs from coils, such as those found in
turbine and paddle-wheel flow meters. The input impedance of the receiving device should not be smaller than 2000 Ohms.
The standard pulse output does not output a voltage, but acts as an open-collector output requiring an external power
source and pull-up resistor. See Figure 26. The MOSFET in the Rate Pulse Module can support loads of 100V @ 1 A. Resistor
selection is based on the input impedance of the receiving device. Select a resistor that is a maximum of 10% of the input
impedance of the receiving device, but does not exceed 10k Ohms.
500 mV
+V
p-p
TURBINE IN
TURBINE IN
RTU/PLC
MONITOR
+V EXT SENSOR
RTU/PLC
MONITOR
0
0
500 mVpp
R
PULSE IN
GND
Figure 26: Rate pulse module
+V
I/O: 0-2.5KHz
P.N. D020-1045-207
TURBINE - B
TURBINE - A
OUT (-)
IN (+)
ISO-MOD
0
TIME
Page 28 August 2019DPP-UM-00256-EN-03
Instrument Programming
INSTRUMENT PROGRAMMING
General
The DFX flow meter is configured through the keypad interface. All entries are saved in non-volatile FLASH memory that is
retained indefinitely in the event of power loss.
Keypad Operation
The DFX flow meter contains a four-key tactile feedback keypad interface that lets you view and change configuration
parameters used by the meter’s operating system.
Figure 27: Keypad layout
The DFX flow meter has two basic sets of programming procedures: list item selection and numeric value entry.
OTE:NWhile in RUN mode, simultaneously press the UP and DOWN keys to display the current firmware version.
List Item Selection Procedure
OTE:NIf you are in PROGRAM mode and the selection to be viewed or changed is displayed, proceed to step 3 below. If
you are in PROGRAM mode and the selection to be viewed or changed is not displayed, press UP or DOWN until the
selection appears. Proceed to step 3.
1. Press MENU. PROGRAM appears in the lower left-hand corner and ID UNITS appears on the lower line of the display.
2. Press DOWN to move to the selection.
3. Press ENTER to view the current selection.
4. If the current selection is correct, press ENTER to conrm. The unit automatically advances to the next selection.
5. To change the current selection, press UP to scroll through the available choices. Press ENTER to conrm your selection.
The unit automatically advances to the next selection.
6. To exit the programming mode, press MENU. Depending on your position in the programming mode, up to three MENU
presses may be required to exit. The display changes to RUN mode.
OTE:NWhile in RUN mode, simultaneously press the UP and DOWN keys to display the current firmware version.
Numeric Value Entry Procedure
OTE:NIf you are in PROGRAM mode and the selection to be viewed or changed is displayed, proceed to step 3 below. If
you are in PROGRAM mode and the selection to be viewed or changed is not displayed, press UP or DOWN until the
selection appears. Proceed to step 3.
1. Press MENU. PROGRAM displays in the lower left corner and ID UNITS displays on the lower line.
2. Press DOWN until the correct selection displays. The current numeric value for this selection displays on the upper line.
3. If the current value is correct, press ENTER. The left-most programmable number ashes. Press ENTER again to conrm
and keep the current numeric value. The unit automatically advances to the next menu selection.
4. To change the current selection, press ENTER. The left-most programmable number ashes. Press UP to scroll through the
digits 0…9. Press DOWN to move the active digit to the right. Continue until all digits are selected.
5. Press ENTER to conrm your selection. The unit automatically advances to the next selection.
6. To exit the programming mode, press MENU. Depending on your position in the programming mode, up to three MENU
presses may be required to exit. The display changes to RUN mode.
Totalizer Reset
Press ENTER and MENU simultaneously when in the RUN mode to reset the totalizer. The message TOTAL RST displays for a
few seconds to indicate that the totalizer had been cleared. If a password has been set, you must enter the password to clear
the totalizer.
Page 29 August 2019DPP-UM-00256-EN-03
Menu Structure
MENU STRUCTURE
Hierarchy
The DFX flow meter has a hierarchical menu structure. See “Menu Maps” on page31 for a visual path to the configuration
parameters. Use the table below as a quick reference guide to the pages with detailed information on each parameter.
Setup
Parameters
ID UNIT → INCH33AD SETUP → YES 36CFG MOD1 → YES34
DISPLAY → RAT E33HIGH36NO35
RATE UNT → GALLONS33LOW36RELAY27, 35
RATE INT → SEC33FLOW 0HZ → (numeric entry)35
TOTL UNT → GALLONS33
TOTL MUL → X PT 0133
SP GRAV → (numeric entry)33
FL C OFF → (numeric entry)33
LITERS33
MGAL33
CUBIC FT33
M CU FT33
CUBIC ME33
MEG LTRS33
ACRE FT33
OIL BARR33
LIQ BARR33
LBS33
KGS33
VEL FT33
VEL MTRS33
X PT 133
X 133
X 1033
X 10033
X 100033
X 1000033
X 10000033
X 1000000033
For Details,
see page
Advanced
Setup
Parameters
Options
For Details,
see page
Module
Configuration
Parameter
Options
For Details,
see page
Page 30 August 2019DPP-UM-00256-EN-03
Menu Maps
Menu Structure
To Module Conguration
NUM PTS
Number of Linearization Points
Numeric Entry (0 to 10)
AGC MODE
Automatic Gain Control
NORMAL
FL C-OFF
Low Flow Cuto
Numeric Entry
HIGH
FREQ n
MANUAL
SCALE F
COEFF n
Frequency of Point (n)
Numeric Entry
depending on the number
May require up to 10 cycles
of linear points chosen.
Coecient of Point (n)
Numeric Entry
From Module Conguration
Numeric Entry
DAMPING
Damping Percentage
Numeric Entry
FILTER
Hardware Filter
NONE
CFG MOD 1
Congure Module 1
LOW
MEDIUM
YES
NO
HIGH
XDCR TYP
Transducer Type
CFG MOD 2
Congure Module 2
YES
GAIN POT
4 mA Flow Value
Scale Factor
Numeric Entry
DT90
NO
PROBE
C FACTOR
Correction Factor
PASSWORD
LINEAR
Linearization?
YES
AD SETUP
Advanced Setup
NO
YES
NO
Numeric Entry
Password Entry
Numeric Entry
RATE INT
START
V1.16
SETUP MENU
Rate Inter val
SEC
MIN
I D UNIT
Pipe Measurement Units
HOUR
DAY
INCH (Inches)
MM (Millimeters)
TOTL UNT
Totalizer Units
ID
Pipe Inside Diameter
GALLONS
LITERS
NUMERIC ENTRY
MGAL
CUBIC FT
M CU FT
CUBIC ME
DISPLAY
Display Choices
(42 Gal)
MEGL TRS
ACRE FT
OIL BARR
LIQ BARR (31.5 Gal)
LBS
KGS
RATE UNT
BOTH
DIAGNOSTICS
RAT E
TOTA L
Figure 28: Menu Map 1
VEL FEET
Flow Rate Units
VEL MTRS
GALLONS
LITERS
MGAL
TOTL MUL
Totalizer Multiplier
X PT 01(÷100)
CUBIC FT
M CU FT
X PT 1 (÷10)
X 1 (X1)
CUBIC ME
MEGL LTRS
ACRE FT
X 10 (X10)
X 100 (X1,00)
(42 Gal)
OIL BARR
LIQ BARR (31.5 Gal)
X 1000 (X1,000)
LBS
X 10000 (X10,000)
X 100000 (X100,000)
KGS
X 1000000 (X1,000,000)
VEL FEET
VEL MTRS
SP GRAV
Specic Gravity
Numeric Entry
Specic Gravity only appears
when LBS or KGS are selected
in either Rate Unit or Total Unit
Page 31 August 2019DPP-UM-00256-EN-03
Menu Structure
MOD TYPE
Numeric Entry
RATE TST
n OFF <
Relay (n) O
Select Rate Test Function
FLOW 0HZ
Flow Rate at 0 Hz
RELAY n
Relay Functions
Numeric Entry
TOTAL
NONE
FLOW
FL MAXHZ
Flow Rate at 2500 Hz
ERRORS
Numeric Entry
Module Type
4-20 MA
NONE
RATE
RELAY
For Test Press Enter
n ON >
Relay (n) On
RATE PCT
10% Increments
Numeric Entry
Numeric Entry
1 & 2 are in
n = the relay
number 1, 2, 3 ,4
module 1.
3 & 4 are in
module 2.
To Password
4MA OUT
FLOW 4MA
4 mA Flow Value
FLOW 20MA
20 mA Flow Value
Numeric Entry
4-20 CAL?
4-20 Calibration?
YES
Numeric Entry
NO
From Module Conguration
Figure 29: Menu map 2
Page 32 August 2019DPP-UM-00256-EN-03
4 mA DAC Value
20MA OUT
20 mA DAC Value
Numeric Entry
4-20TEST
4-20 mA Output Test
Numeric Entry
Numeric Entry
PARAMETERS
The following tables list and explain the parameters. The tables are divided into three main sections:
• Setup parameters
• Module configuration parameters
• Advanced setup parameters
Setup Parameters
The setup menu contains all of the configuration parameters necessary to make the transmitter operational.
Parameter FunctionOptionsDescription
ID UNITS
ID
DISPLAYDisplay mode
RATE UNT
RATE INT
TOTL UNTTotalizer units
TOTL MUL
SP GRAV
FL COFFLow flow cutoff(Enter a numeric value)
Measurement
standard
Pipe inside
diameter
Engineering units
for flow rate
Time interval for
flow rate
Flow totalizer
multiplier value
Fluid specific
gravity
ENGLSH (Inches)
METRIC (Millimeters)
(Enter a numeric value)
RAT E
TOTAL
BOTH
DIA
Select an engineering unit for flow rate measurements. When Pounds (LBS) or Kilograms (KGS) is selected, the specific
gravity for the fluid type must be entered for the SP GRAV setup parameter.
MeasurementSelectionMeasurementSelection
PoundsLBSCubic MetersCUBIC ME
KilogramsKGSMillions of Metric LitersMEGLTRS
GallonsGALLONSAcre FeetACRE FT
LitersLITERSOil Barrels (42 Gallons)OIL BARR
Millions of GallonsMGALLiquor Barrels (31.5 Gallons)LIQ BARR
Cubic FeetCUBIC FTVelocity in Linear FeetVEL FEET
Millions of Cubic FeetM CU FTVelocity in Linear MetersVEL MTRS
SEC Seconds
MIN Minutes
HOUR Hours
DAY Days
Select an engineering unit for flow totalizer measurements. When Pounds (LBS) or Kilograms (KGS) is selected, the specific
gravity for the fluid type must be entered for the SP GRAV setup parameter.
MeasurementSelectionMeasurementSelection
PoundsLBSCubic MetersCUBIC ME
KilogramsKGSMillions of Metric LitersMEGLTRS
GallonsGALLONSAcre FeetACRE FT
LitersLITERSOil Barrels (42 Gallons)OIL BARR
Millions of GallonsMGALLiquor Barrels (31.5 Gallons)LIQ BARR
Cubic FeetCUBIC FTVelocity in Linear FeetVEL FEET
Millions of Cubic FeetM CU FTVelocity in Linear MetersVEL MTRS
0.01…1,000,000
(Enter a numeric value)
Selects the unit of measure for pipe ID entry.
Enter the pipe inside diameter in inches if ENGLSH was selected as UNITS; in millimeters if METRIC
was selected.
To display only the Flow Rate, select R ATE . To display only the Flow Total, select TOTAL . To
alternately display the Flow Rate and the Total, select BOTH. By selecting BOTH, the display
switches between RATE and TOTAL every 7 seconds.
The DIA selection places the display in the diagnostics mode. When selected, the display shows
the measured frequency, the gain setting and the signal strength.
Select a time interval for flow rate measurements.
Used for setting the flow totalizer exponent. This feature is useful for accommodating a very
large accumulated flow. The exponent is a ×10n multiplier, where “n” can be from -2 (×0.01) to +6
(×1,000,000). Reference the table below for valid entries and their influence on the DFX meter
display.
ExponentDisplay Multiplier
× PT 01 2× 0.01
× PT 1 1× 0.1
×1 0× 1
×10 1× 10
×100 2× 100
×1000 3× 1000
×10000 4× 10,000
×100000 5× 100,000
×1000000 6× 1,000,000
Allows adjustments to be made to the specific gravity (density relative to water) of the liquid.
If Pounds (LBS) or Kilograms (KGS) is selected for either the RATE UNT or the TOTL UNT, a specific
gravity must be entered for the correct mass flow to be calculated. A list of fluids and their
associated specific gravities is located in “Specifications” on page40.
A Low Flow Cutoff entry is provided to allow very low flow rates (that can be present when
pumps are off and valves are closed) to be displayed as Zero flow. The value entered is in actual
rate units.
Parameters
Page 33 August 2019DPP-UM-00256-EN-03
Parameters
Parameter FunctionOptionsDescription
The SCALE F function applies a correction factor/multiplier to the readings and outputs so
the DFX system can agree with a different or reference flow meter, or to compensate for an
installation where there is inadequate straight pipe to obtain a laminar flow profile. A factory
SCALE FScale factor value (Enter a numeric value)
DAMPING
CFG MOD1
CFG MOD2
System damping
percentage
Configure I/O
Module
Configure I/O
Module
(Enter a numeric value
0…99%)
YES or NO
YES or NO
calibrated system should be set to 1.000. The range of settings for this entry is 0.5000…5.000. The
following example describes using the SCALE F entry.
The DFX meter is indicating a flow rate that is 4% higher than another flow meter located in the
same pipe line. To have the meter indicate the same flow rate as the other meter, enter a SCALE F
of 0.960, to lower the readings by 4%.
Flow Filter Damping establishes a maximum adaptive filter value. Under stable flow conditions
(flow varies less than 10% of reading), this adaptive filter increases the number of successive flow
readings that are averaged together up to this maximum value. If flow changes outside of the
10% window, the Flow Filter adapts by decreasing and allows the meter to react faster. Increasing
this value tends to provide smoother steady-state flow readings and outputs.
This prompt lets you access the setup parameters associated with installation of the optional
ISO-MOD interface modules. If NO is selected, the unit skips ahead to CFG MOD2. If YES is
selected, configuration and calibration of the module installed in the first position is accessible.
If NO was selected at CFG MOD1, CFG MOD2 becomes active. This prompt lets you access the
setup parameters associated with installation of the optional ISO-MOD interface modules. If NO
is selected, the unit skips ahead to PASSWORD. If YES is selected, configuration and calibration of
the module installed in the second position is accessible.
Page 34 August 2019DPP-UM-00256-EN-03
Module Conguration Parameters
When YES is selected at CFG MOD1 or CFG MOD2, these MOD TYPE parameters become available:
• NONE
• 4…20 mA
• RATE
• RELAY
Once the module is configured, the menu moves to the PASSWORD parameter.
MOD TYPE FunctionOptionsDescription
NONE
420MA
RAT E
RELAY
No module is
installed
4…20 mA type
module
Rate pulse output
module
Relay 1 and Relay
2 configuration
NONESelect NONE (no module installed) to move to the PASSWORD parameter.
FLOW 4MAEnter the flow rate that corresponds to 4 mA. The units are equal to the units set in RATE UNT.
FLOW 20MAEnter the flow rate that corresponds to 20 mA. The units are equal to the units set in RATE UNT.
Select NO to move to the PASSWORD parameter.
Select YES to adjust the “zero” and span of the 4…20 mA output.
To adjust either the 4 mA or 20 mA output, connect a milliammeter or reliable
4MA OUT
4-20 CAL?
20MA OUT
4-20TEST
FLOW 0HzEnter the flow rate that corresponds to 0 Hz. The units are equal to the units set in RATE UNT.
FL MAXHZEnter the flow rate that corresponds to 2500 Hz. The units are equal to the units set in RATE UNT.
RATE TSTSimulate a pulse output. Moves to RATE PCT entry.
Allows a simulated value to be output from the rate pulse output. By incrementing this value,
the rate pulse output transmits the indicated frequency in terms of percentage of the maximum
RATE PCT
NONESelect NONE (no Relay 1 installed) to move to the Relay 2 parameter.
TOTAL
FLOW
ERRORS
output frequency.
For example, if the maximum output frequency is 2500 Hz, increment the displayed value to 50 to
output a test frequency of 1250 Hz.
TOTAL mode configures the relay to output a 50 m/s pulse (contact changeover) each time the
display totalizer increments. Select TOTAL to configure the relay for Totalizer Relay and move to
the PASSWORD menu.
Flow Rate Relay configuration permits relay changeover at two separate flow rates allowing
operation with an adjustable switch deadband. Figure 30 on page 37 illustrates how the setting
of the two set points influences Rate Alarm operation.
A single-point flow rate alarm would place the ON> setting slightly higher than the OFF<
setting—allowing a switch deadband to be established. If a deadband is not established, switch
chatter (rapid switching) may result if the flow rate is very close to the switch point.
When a relay is set to ERROR mode, the relay activates when any error occurs in the flow meter
that has caused the meter to stop measuring reliably. See “Startup and Troubleshooting” on
page38 for a list of potential errors.
reference to the output.
1. Disconnect one side of the current loop and connect the milliammeter
in series (disconnect either wire at the terminals labeled +/– on the ISOMOD 4…20 mA module).
2. Using the arrow keys, increase the numerical value to increase the
current in the loop to the output. Decrease the value to decrease the
current in the loop to output. The value range for 4MA OUT is 40…80
counts. The value range for 20MA OUT is 3700…3900 counts.
3. Re-connect the 4…20 mA output circuitry as required.
Outputs a simulated value from the 4…20 mA output. By incrementing this
value, the 4…20 mA output transmits the indicated current value.
Parameters
Page 35 August 2019DPP-UM-00256-EN-03
Parameters
Advanced Conguration Parameters
Parameter FunctionOptionsDescription
By changing the Security Password from 0000 to some other value (any value between
0001…9999), configuration parameters are not accessible without first entering that value when
prompted. If the value is left at 0000, no security is invoked and unauthorized changes could be
made. Access to resetting of the Totalizer is also protected by this password.
PASSWORD
AD SETUP
(continued
on next
page)
Change the
security password
Advance
setup mode
Select YES to
access these
parameters:
AGC MODE
GAIN POT
FILTER
LINEAR
(continued on
next page)
0…9999
AGC MODE – Automatic Gain Control Mode of OperationNORMAL – Standard Configuration
HIGH – Used for low signal strength
MANUAL – AGC disabled
GAIN POT – Digital Gain Control
FILTER – Hardware Filter Control
Select the mode of operation. A basic understanding of the AGC logic is required in order to know when to use any
selection other than NORMAL.
When the unit is powered up, there is a delay before the unit begins transmitting sound into the pipe. During this time,
the signal strength is measured and a base signal level is obtained. Typically this is a value of about 20. The unit measures
flow by measuring the Doppler frequency shift. The frequency shift is approximately 70 Hz per foot per second. For every
foot per second increase in velocity, the signal strength should increase by 1. The unit automatically adjusts the gain and
selects the proper hardware filter for the measured velocity. The control can be observed when the DISPLAY mode is set to
DIAG. See Figure 31 on page 38.
Manual Operations
When NORMAL is selected, the unit automatically controls the gain and front end hardware filter for optimum
measurement of the Doppler signal.
Select HIGH for applications where the unit reads flow rates consistently, but much lower than the actual flow rate. This
may be required when sound is not getting through the pipe as well. Selecting HIGH causes the unit to look for the
signal strength to increase by 2 for every foot per second increase in flow rate. Basically, the gain is doubled, but still
automatically controlled.
Select the MANUAL mode for applications where the flow is constant but there is extraneous noise to filter out. Typically,
this would only be required at very low flow rates. When MANUAL mode is selected, the GAIN POT and FILTER settings are
manually set. Automatic control is disabled.
Gain Control
GAIN POT – Digital Gain Pot
0…64
Using the arrow keys, increase or decrease the numerical value to set the signal gain level. Typically, optimum flow
measurement is made when this value is 10…50. Use the lowest value that provides an accurate and stable flow reading.
This adjustment must be made in conjunction with the FILTER setting.
Page 36 August 2019DPP-UM-00256-EN-03
Parameter FunctionOptionsDescription
Hardware Filter
FILTER – Hardware Filter SelectionNONE – No Filter
LOW – (1600 Hz Cutoff)
MEDIUM – (350 Hz Cutoff)
HIGH – (250 Hz Cutoff)
Select the hardware filter with a cutoff frequency that is above the Doppler shift frequency to be measured. The Doppler
shift frequency is found by multiplying the flow velocity (in FPS) by 80.
For example, if the flow velocity is 4 FPS then the cutoff frequency is 4 × 80 or 320 Hz. The filter with the next highest
frequency would be 350 Hz.
Transducer Type
Select the appropriate transducer type to be connected to the DFX transmitter. The selection invokes optimum hardware
and software settings unique to the transducer architecture.
Correction Factor
C FACTOR – Transducer Type
0.01…5.00
This value is established at the factory during calibration. If a new set of transducers or insertion probe is connected , the
new correction factor should be entered. The correction factor values can be found on transducers or probes labels.
Linearization
LINEAR – Entry of Linearization Data
The Linearization feature corrects flow readings influenced by non-linear flow measurement. This typically occurs when
there is insufficient straight piping before or after the location where the transducers are mounted.
Up to 10 linearization points may be entered. The microprocessor performs a linear interpolation between data points
entered in the linearization table and apply the associated correction factor to the measured flow rate.
AD SETUP
(continued
from
previous
page)
Advance
setup mode
Advance
setup mode
Select YES to
access these
parameters:
AGC MODE
GAIN POT
FILTER
LINEAR
(continued from
previous page)
1. Enter the number of linearization points at the NUM PTS prompt. If a value of 00 is entered, linearization is disabled.
The unit prompts for FREQ 1 to be entered.
2. Enter the measured frequency corresponding to the ow rate for the rst point. This can be obtained by running
actual ow with the DISPLAY mode set to DIAG and reading the measured frequency, or by calculating the frequency
if the ow rate in feet per second is known using the following formulas:
The unit prompts for COEFF 1 to be entered. This is the multiplication factor for the measured flow rate.
3. Enter the coecient or correction factor to be applied. The value entered must be between 0.5…1.5.
4. Repeat this procedure for all of the linearization points. When all of the points have been entered, the unit returns to
the NUM PTS prompt.
5. Press MENU to return to the main menu LINEAR prompt. Then press UP or DOWN to move to the next setup
parameter.
Parameters
Minimum
Flow
Set OFF
Set ON
Output OFF
Deadband
Figure 30: Single point alarm operation
Maximum
Flow
Output ON
Page 37 August 2019DPP-UM-00256-EN-03
Startup and Troubleshooting
Gain
RUN
Frequency
Signal
Strength
51000
00
MEM
AUTO
AutoHOLD FAST MIN MX LOGGING YES
HOLD MIN MAX REL
CANCEL SAVE NO
Hz % ms RANGE
SETUP
nS
W
°F
mV
°C
ac+dc
V
ac+dc
mV
dB
V
dB
OFF
VIEW MEM
CLEAR MEM
mA
A
COM
µA
10A MAX
CAT III
400mA
FUSED
FUSED
I/O: 4-20 mA
P.N. D020-1045-100
OUT (-)
IN (+)
INT PWR EXT PWR
JP2
JP1
MANUAL
A
mA
µA
A
mA
ac+dc
µA
ac+dc
TEMPERATURE
W
V
1000V
ISO-MOD
Figure 31: Diagnostic display
Figure 32: 4…20 mA calibration setup
STARTUP AND TROUBLESHOOTING
OTE:NThe DFX flow meter system requires a full pipe of flowing liquid before a successful startup evaluation can be
completed. Do not attempt to make adjustments or make manual configuration changes until a full pipe of flowing
liquid is verified.
OTE:NIf an RTV sealant was used to couple the transducers to the pipe, the sealant must fully cure before power is applied
to the instrument. Most RTVs require 24 hours to cure satisfactorily. It is very important that the transducers are not
moved during the curing process. Air bubbles can form between the transducer and the pipe wall and influence
performance. If silicone grease was used as a couplant, the curing time is not required.
Startup
1. Verify that the DT9 or DP7 transducer has been properly installed and wired. See “Transducer Installation” on page 10.
2. Verify that the power supply jumper settings are properly congured for the power supply. See “Power Supply Wiring
Connections” on page 21.
3. Verify that the meter is properly programmed. See “Instrument Programming” on page 29.
4. Apply power.
5. On initial powerup, the DFX meter’s microprocessor conducts a series of self-diagnostic tests, baseline measurements and
begins to buer liquid velocity data. During this 30-second startup, ow rate readings and outputs are inhibited.
6. After the startup routine has completed running, the meter begins to display ow rate and/or total as congured.
7. If an ERROR appears on the monitor’s lower display, see “Troubleshooting” on page 39.
Page 38 August 2019DPP-UM-00256-EN-03
Troubleshooting
SymptomCause/Resolution
• Insufficient power to monitor. Measure voltage at J2.
• Power supply not properly wired to J2. See “Power Supply Wiring Connections” on page 21.
Display does not light up
ERROR on the
DFX flow meter display
Unstable flow reading
Inaccurate flow reading
Analog output does not match
data collection
system
Rate Pulse output does not
match data collection system
DFX flow meter does not
capture short flow pulses
• Fuse F1 is open or not installed.
• Power supply jumpers are not installed properly. See “Power Supply Wiring Connections” on page 21..
• Ribbon cable between the door and enclosure back is not fully engaged into the two sockets.
• Transducers not properly coupled to the pipe. Couplant is not present or pipe not properly prepared.
• Transducer not properly wired to the J4 Terminal block inside the meter. Review the Wiring Diagram
on the inside door of the DFX meter.
• More than one DFX meter is installed on the piping system.
See “Multiple Meter Installations” on page 23.
• Insufficient particles over 35 microns. Inject air upstream of the transducers.
• Too many particles that are smaller than 35 micron prevent ultrasonic meters from operating.
• Transducer failure. Unplug transducer cable from J4, measure capacitance between blue/clear or red/
black Receive and Transmit. Verify that the capacitance on each set is approximately 2 nF (nano Farads)
and within 0.02 nF of each other.
• Relocate transducer to a pipe position with less hydraulic disturbance.
• Increase Damping value.
• Ensure that ground connection is properly connected to meters earth ground. See Figure 13.
• Verify that pipe ID is entered correctly.
• Verify that an erroneous Scale Factor has not been entered.
• Verify that erroneous Linearization values have not been entered.
• Verify that AGC is set to Normal.
• Verify that the transducers are mounted square and 180 degrees apart on the pipe.
• Relocate transducer to a pipe position with greater straight run length.
• DP7 Probe not aligned in the pipe.
• Verify 4…20 mA calibration.
• Verify 4 mA and 20 mA flow settings. Verify that the loop load is within the supply voltage range
• Run 4…20mA TEST feature to verify that mA outputs coincide with expected data collection
system readings.
• Verify 0 Hz and MAX Hz flow settings.
• Place oscilloscope or frequency counter on the Rate Pulse module outputs and verify
frequency output.
• Run output TEST feature to verify that the Hz output coincides with expected data collection
system readings.
• Verify that the K-factor has been calculated correctly:
K-factor = Hz/(flow/second)
Example:
Max Hz (2500 Hz) = 10,000 Gallons/Minute
K-factor = 2,500 Hz / 166.7 Gallons/Second
K-factor = 15 pulses/gallon
• Verify that the data collection system is accepting the pulses from the meter. Connect to Turbine OUT
or OUT/IN as required.
When run in AUTO mode, the meter uses a series of filters that optimize readings for a particular flow
range. The flow meter takes several seconds to adjust to a step change in flow. To make the flow meter
respond quickly to changes in flow, decrease DAMPING, place the meter into MANUAL AGC and lock the
FILTER at NONE.
Startup and Troubleshooting
Page 39 August 2019DPP-UM-00256-EN-03
Specications
SPECIFICATIONS
Velocity Range0.15…30 fps (0.05…9 mps)
Accuracy±2% full scale, over calibrated span
Liquid Types
Monitor Enclosure
Power Supply115/100/230V AC 50/60 Hz ±15% @ 17V A max; 12…28V DC @ 7V A max
Display2-line × 8 character LCD; LED backlighting; 8-digit rate, 8-digit total (resettable)
Units
Rate IntervalSecond, minute, hour, day. Totalizer exponent: E-2 to E+6 (x ¹/100 to x 1,000,000)
Response TimeUser selectable: 6…60 seconds
Output Options
Multiple Meters
Keypad4-key, tactile
Ambient Conditions–40…185º F (–40…85º C); 0…95% relative humidity (non-condensing)
Approvals(Std.) General Safety US and Canada. Certified to UL 61010-1 and CSA C22.2 No. 61010-1
Transducer TypeCompression-mode Ultrasonic; 625 kHz
Construction
Pipe Sizes
Liquids containing a minimum of 100 ppm of useful sonic suspended reflectors greater than 35 micron size, and
at least 25% of the overall particle volume is larger than 100 microns
NEMA 4X (IP 66), polycarbonate, stainless steel, brass,
plated-steel mounting brackets 7.00 in. H × 5.75 in. W × 3.88 in. D (178 mm × 146 mm × 99 mm)
User configured: Feet, US gallons, ft³, Mil-gal, meters, liters, Mil-ft³, m³, Mil-liters, acre-feet, oil barrels (42 US
gallons), liquid barrel (32.5 US gallons), lb, Kg
4…20 mA800 ohms max, internal or external power supply, 12-bit resolution
Optically Isolated Dual Relay
Rate Pulse
Synchronization provision included—utilized for multiple meter, single pipe/manifold system. Up to four meters
may be interconnected, up to 100 feet (30 meters) apart
Standard Clamp-On
Optional Flexible Armored ConduitZinc-plated steel, PVC
Standard Clamp-On Transducers1 inch (25 mm) and above
Small Pipe Clamp-On Transducers0.25…1 inch (6…25 mm)
Standard Lengths20, 50 and 100 foot (6.1, 15 and 30 meter), 78 Ohm twinax cable
Optional LengthsTo 990 feet (297 meters), 75 Ohm RG59 cable
500 mV AC2500 Hz max, 12-bit resolution, 500 mV AC into 2 K Ohm minimum;
Open collector2500 Hz max, 1 A at 100 V max
Independently configured; Form C, 200V AC @ 0.5 A resistive; rate alarm,
totalizer pulse, error
Type 6* (IP 67) –40…194º F (–40…90º C) CPVC, Ultem®, Nylon, PVC (Cable
Jacket), Aluminum (small pipe) *Depth of 1 meter for 30 minutes
Page 40 August 2019DPP-UM-00256-EN-03
NORTH AMERICAN PIPE SCHEDULES
Steel, Stainless Steel, PVC Pipe, Standard Classes