Dynasonics D300, D301 User Manual

Series
Series D300/301
Series Series
Doppler Ultrasonic Flow Meter
Operations & Maintenance
D300/301
D300/301D300/301
Manual
REV 2/00
PART 1 - TABLE OF CONTENTS
Description Pages
Quick Start Installation 1.2-1.3 Operating Theory 1.4 Product Limitations 1.5 Model Number Matrix 1.6 Specifications 1.7
Pre-Installation Bench Test 2.1 Transducer Installation 2.2-2.6
Transmitter Installation 3.1-3.2 Electrical Connections 3.2-3.5
Power Up and Configuration 4.1 Field Calibration 4.2-4.5 Relay Adjustment 4.5 Changing Pipe Size or Flow Span 4.6-4.7
Appendix Fluid Sound Speed Conversions Ductile Iron Pipe Data Cast Iron Pipe Data Steel, SS, PVC Pipe Data FPS to GPM Conversion Chart Intrinsic Safety Installation Troubleshooting Waveform s Ref. Statement of Warranty Service Information
Rev. 2/00 -1.1- 300/301
PART 1 - QUICK START
General
This manual contains detailed operating instructions for all aspects of the D300/301 instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. Thi s pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section i n the manual for complete details.
1. TRANSDUCER LOCATION
A. In general, select a mounting location on the
piping system with a minimum of 10 pipe diameters (10 X the pipe inside diameter) of straight pipe upstream and 5 straight diameters downsteam. See Table 2.1 for additional configurations.
B. On horizontal pipe, select a position that is
between 2 and 4 o’clock on the pipe, with 12 o’clock representing the top.
Transducer Cable
FLOW
Figure 1.1
Top View of Pipe
2. PIPE PREPARATION AND TRANSDUCER MOUNTING
A. The piping surface, where the transducers are
to be mounted, needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Loosely wrap the appropriate length of strap
around the pipe at the l ocation determined in Step 1. Refer to Figure 1.1 for proper orientation.
C. Apply a liberal amount of couplant onto the
transducer face. Pl ace the transducer onto the pipe ensuring square and true placement. If an RTV type of couplant (requiring curing time) was utilized, allow sufficient time for curing before applying power to the instrument.
Rev. 2/00 -1.2- 300/301
PART 1 - QUICK START
3. TRANSDUCER/POWER CONNECTIONS
A. Do not attempt to add additional cable to the
transducers.
B. Refer to the WIRING DIAGRAM in Figure 1.2
for proper power and transducer connections. Verify proper jumper selections are in place for the power source. See Figures 2.2 and 2.3.
4. INITIAL SETT INGS AND POWER UP
Power Connections Transducer Connections
IMPORTANT!
In order to successfully complete the configuration of the D300/301 flow meter, the transducer must be mounted on a pipe which is full of a flowing liquid. I t is normal to have zero readings and no si gnal indica­tor LED with empty pipes or zero flow rate.
Figure 1.2
Power and Transducer
Connections
A. Adjust the GAIN control [R10] to 1/4 turn from
full counter-clockwise rotati on. Set the DAMP
control R110 to 1/2 turn from either stop. B. Apply power to the instrument. C. If the pipe is full of a flowing liquid, the LED
located on the bottom of the main circuit card
[D21] should begin flashing. If the LED does
not flash, gradually turn the GAIN control [R10]
clockwise until the LED just begins to flash
steadily. (Do not over adjust this setting as
ambient noise can influence readings.) D. If possible, turn off the flow to the pipe. Verify
that the LED [D21] ceases to flash. If the LED
continues to flash when flow rate is zero, the
GAIN control [R10] is set too far clockwise and
ambient noise is influencing the readings.
Turn the control counter-clockwise until the
flashing ceases. E. If the instrument passes steps 4C and 4D, the
basic setup of the instrument is complete.
Rev. 2/00 -1.3- 300/301
PART 1 - GENERAL
General
Operating Theory
The Dynasonics D300/301 flowmeter is designed to measure the flow of liquids and slurries in full-pipe closed systems. The transmitter is factory configured to measure flow on a specific, customer specified, pipe, where flow range and measuring units have been supplied to the Dynasonics factory during assembly and factory calibration. The standard product is typically used on pipe sizes ranging from 1 - 120 inch [ 25 - 1524 mm ] pipe I.D. (With the small pipe transducer option, the pipe size range is
0.25 - 1 inch [ 6 - 25 mm]). A variety of liquid applications can be accommodated: sewage, sludges, concrete, mining slurries, dredging, etc. Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Standard transducers are rated to 250°F [121°C]. Optional high temperature transducers are rated to operate to 400°F [204°C].
The basic principle of operation is the measurement of the frequency shift “Doppler” of a reflected ultrasonic signal from discontinuity in the flowing liquid. In theory, these di scontinuities can be virtuall y any amount of suspended bubbles, solids, or interfaces caused by turbulent flow. In practice the degree to which this can be reliably accomplished is a function of the sensitivity and frequency of the transducer and associated transmitter. The D300/301 design requires greater than 100 PPM of suspended solids or bubbles over 100 microns in size. Should your application be cleaner than this, please check with factory for information on transit time ultrasonic flowmeters. The transducer which generates and receives the ultrasoni c signal supplies the data to the transmitter. The transmitter processes the signal and provides an analog and pulse output for velocity indicating and volumetric totalizing. In addition, the transmitter contains a signal light which determines satisfactory operation.
Rev. 2/00 -1.4- 300/301
PART 1 - GENERAL
Measuring Limits
The flowmeter is typically used as a unidirectional meter and is most accurate when the transducer is mounted in the orientation detailed in this manual. But, the meter will measure flow in both directions — although flow direction will not be indicated or totalized properly. The flowmeter will operate from signals returned from turbulence alone (such as installation directly at pump discharges or downstream from elbows and valves); however, it should be noted that turbulence may vary with flow rates and result in non-linear results. The repeatability of the device is not dependent on most process liquids.
The flowmeter is designed to measure the flow of liquids and slurries, as long as a small, homogeneous quantity of entrained air or suspended solids are present. Without the presence of continuing supply of air or solids, the transmitted pulses are not reflected back to the transducer and the indicator will indicate zero flow. Also, the LED signal indicator will be extinguished.
The signal strength light will indicate (continuously blink) when a minimum size and concentration of suspended particles are available for a reliable flow reading (100 micron and 100 PPM minimum) and the liquid is moving at least 0.1 FPS [0.03 MPS]. Most water-based liquids can be measured from a factory calibrated flowmeter. However, liquids with a heavy solids level (i.e. over 2%), liquids with sound speeds that vary from water (see Appendix of alternate liquids list) or pipes with liners may have to be field calibrated. This is done by adjusting the span pot (R30 on circuit board) to make the indicator agree with a known flow velocity or a mathematically corrected fluid velocity. All standard indicator scales are calibrated to customer specified units. If the scale range or units need to changed, the process to do so is covered in detail later in this manual.
Rev. 2/00 -1.5- 300/301
Serial Number
PART 1 - GENERAL
The D300/301 employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 9 Vdc and the metal work is electrically connected to Earth Ground. The display face swings open to allow access to user connections.
The serial number and complete model number of your D300/301 is located on the inside of the transmitter’s front cover. Shoul d technical assistance be required, please provide the Dynasoncs’ Customer Service Department with this information.
A part number breakdown of the transducer and transmitter portions of the flowmeter are described below.
Transmitter Transducer
Rev. 2/00 -1.6- 300/301
PART 1 - GENERAL
Rev. 2/00 -1.7- 300/301
PART 2 - TRANSDUCER INSTALLATION
Unpacking
Bench Test
Power Connections
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The D300/301 flow meter can be checked for basic functionality using the following
Bench Test
procedure. It is recommended that this operation be performed before installing the transducers or transmitter permanently.
Procedure:
1. Open the D300/301 transmitter enclosure.
2. Connect the transducer cable terminals to the corresponding terminal block locations within the transmitter. The R, T and corresponding G termi­nals are marked on the coaxial transducer cables. See
Figure 2.1
.
3. Set the transmitter SENSE control [R10] to ap­proximately 1/4 turn from full clockwise position.
4. Apply power.
5. Rub the face of the transducer lengthwise back and forth with your thumb using moderate pres­sure. The cycle time should be 1-2 times per sec-
Transducer Connections
ond.
6. If unit is functioning properly, the RED LED lo­cated on the bottom of the main circuit card will begin to flash and the rate display will indicate flow readings.
7. Verify that the LED ceases to flash when the rub­bing stops.
Figure 2.1
Power and Transducer
Connections
8. If the meter does not respond, increase the SENSE control [R10] to approximately 1/2 turn from full clockwise position. Attempt Step 5 agai n.
Bench Test is Complete
Rev. 2/00 -2.1- 300/301
PART 2 - TRANSDUCER INSTALLATION
Transducer Mounting Locations
The following list outlines how to install the DT6 transducer for optimal performance, highest reliability and greatest accuracy:
1. Select a transducer site at least 10 pipe diameters downstream from bends, or fittings and 5 pipe diameters upstream. A symmetrical flow pattern is necessary for accuracy and repeatability over the
Table 2.1
1
1
The D300/301 syst em will provide repeatable measurements on piping systems that do not meet
these requirement s , but the accuracy
Rev. 2/00 -2.2- 300/301
of these readings may be inf luenc ed to various degrees.
PART 2 - TRANSDUCER INSTALLATION
Transducer Cable
FLOW
Figure 2.2
Top View of Pipe
operating range of the meter. Down stream from pump or orifices, etc., locate at least 20 diameters. See
Table 2.1
2. On horizontal pipe, select a position that is between 2 and 4 o’clock on the pipe, with 12 o’clock representing the top. If the transducer is to be mounted on a verti cal pipe, sel ect a section of pipe where the flow is moving from bottom to top (flow moving vertically down a pipe tends to cavitate and provide unreliable operation.)
3. Mount the transducer in the orientation shown in Figure 2.2. The flow meter will read flow in both directions, but will be most accurate if the cable is mounted in the orientation shown—pointing in the primary flow direction.
4. If totalization of the measured fluid is required, the pipe must remain full. The meter will read when the liquid level is greater than the placement of the transducer, but the volumetric measurement will be based on a full pipe, so totalization will be higher than actual.
5. The flowmeter wi ll achieve proper Doppler signals off of turbulence; however, it I should be noted that turbulence may not be linear with pump speed changes, nor is the reading necessarily accurate due to the non-uniformity of turbulence.
6. When a liquid has less than 100 PPM of 100 micron or larger particles, try mounting the transducer within 12 inches of a pump discharge or other source of flow turbulence or cavitation. A reading obtained under these circumstances will be repeatable, but not necessarily accurate or linear.
7. It is a good practice to test the flow meter on the piping system before permanently mounting the transducer using RTV. Function can be verified by applying a water soluble lubricant, such as KY­Jelly, and holding the transducer by hand on the pipe in the location where the transducer will be
Rev. 2/00 -2.3- 300/301
PART 2 - TRANSDUCER INSTALLATION
permanently mounted. Under flowing liquid conditions, adequate signal is indicated when the Signal LED (D21) flashes steadily.
Acoustic Couplant Types
Small Pipe Transducers
Intrinsic Safety Installations
For proper operation, there cannot be air voids between the traducer face and pipe. The space must be filled with a materi al which is a good transmitter of sound energy such as:
SILICONE GREASE: Dow Corning 111 R or comparable (-100 to +450 F.) T he material must be suitable not to fl ow at temperature of pipe. Used for temporary survey installations and portable flow meters.
SILICONE RUBBER: Dow Corning 732-RTV R. Excellent for permanent bonding. This adhesi ve is a recommended bonding agent and easily removable.
INSTALLATION AND PIPE PREPARATION
The cable from the DT6 transducer is provided with either dual-coaxial cables, flexible nylon conduit or PVC coated steel conduit with a 1/2” NPT fitting. The coaxial cable was ordered from the factory at a specific length
should the coaxial cable be lengthened as this may de-tune the circuitry and influence performance
Installation of the DT61 and DT63 small-pipe transducers follow the same procedures as the DT60 and DT62 standard pi pe type. The only difference is that the small pipe transducers utilize an integral clamping mechanism for pipe mounting and the standard pipe units use a stainless steel strap.
Installations requiring intrinsic safety should refer to the Appendix drawings covering these applications.
UNDER NO CIRCUMSTANCES
.
Rev. 2/00 -2.4- 300/301
Loading...
+ 26 hidden pages