Dynasonics 902, 903 User Manual

Series 902/903
Portable Doppler Ultrasonic Flow Meter
Operations & Maintenance
Manual
REV 10/08
BEFORE OPERATING THE D902/3
Important Notice!
The D902/3 flow meter is equipped with a Lead Acid Gel Cell battery. This battery will require charging before initial operation.
Apply AC power, utilizing the enclosed line power cord, to the D902/3 for a period of 16-24 hours prior to using the product for the first time. The line cord connects to the socket connection located on the side of the enclosure.
Do not allow the battery to completely discharge. (Discharging the battery to the point where the LOW BATTERY indicator illuminates will not damage the battery. Allowing the battery to stay discharged for long periods of time can degrade the storage capacity of the battery.) When not in use, continually charge the battery by keeping it plugged into line power. The D902/3 has an integral charging circuit that prevents overcharging. The instrument can be permanently connected to AC line power without damaging the flow meter or the battery.
Rev. 10/08 - 1 - D902/3
TABLE OF CONTENTS
Part 1 - Introduction
Part 2 - Installation
Quick-Start Operating Instructions 4-5
Introduction
General 6
Applications 6
Model Matrix 7
Product Specifications 8
Bench Test Procedure 9
Installation
Transducer Mounting Locations 11-12
Pages
Pipe Preparation 13
Transducer Mounting 13-15
Electrical Connections 16-17
Battery Charging and Maintenance 18-19
Part 3 - Startup and Configuration
Rev. 10/08 - 2 - D902/3
Instrument Startup and Configuration
Initial Settings 20
Modes of Operation 21
Pipe I.D. Input 22
Full Scale Input 23
Totalizer Exponent Input 24
Engineering Units Input 25
TABLE OF CONTENTS
Part 4 - Troubleshooting
Instrument Startup and Configuration
CAL. Constant Input 25
Display Damping 26
TEST Diagnostic Key 26
System and Totalizer RESET 27
Totalizer Reset 27
FLOW ANALYZER Indicator 27
Troubleshooting Guide 28-29
Appendices 31+
Spare Parts Listing
Mechanical Drawing
Pages
Fluid Sound Speed Conversion Chart
Clean Liquid Installation Guide
Pipe Dimension Chart: Cast Iron
Pipe Dimension Chart: ST, SS, PVC
Velocity to Volumetric Conversion
Statement of Warranty
Customer Service
Rev. 10/08 - 3 - D902/3
Location
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the D902/3 instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
1. TRANSDUCER LOCATION
A. Determine the appropriate mounting location for the
transducers by referring to Figure 1.
TOP VIEW OF PIPE
Pipe Preparation and Mounting
RECEIVING
TRANSDUCER
TRANSMITTING
TRANSDUCER
90° ELBOW
Fluid Velocity Г - Г2
Clean, Non-aerated Liquids Liquids with Suspended Solids or Aeration
Figure 1 Transducer Locations
2. PIPE PREPARATION AND TRANSDUCER MOUNTING
A. The piping surface, where the transducers are to be
mounted, needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Connect the elastic mounting strap around the pipe.
Leave the strap just loose enough to slip the transducers underneath.
C. Apply a liberal amount of silicone grease (enclosed)
onto the transducer faces and the prepared areas of the pipe.
Rev. 10/08 - 4 - D902/3
QUICK-START OPERATING INSTRUCTIONS
D. Place each transducer under the mounting strap, 180°
apart on the pipe. Ensure that the transducer cables are facing the same direction. See Figure 2.
FLOW DIRECTION
Figure 2 Transducer Cable Direction
E. Route the transducer cable back to the transmitter,
avoiding locations near high voltage supply wires.
Connections
Startup
3. TRANSDUCER CONNECTION
A. Connect the transducer plug to the appropriate mating
socket on the side the D902/3 enclosure.
4. INITIAL SETTINGS AND POWER UP
A. Set the SENSITIVITY control to -2.
B. Press the POWER button. The POWER indicator will
illuminate.
C. If the pipe is full of a flowing liquid
STRENGTH meter will indicate and the READ indicator will illuminate.
D. Adjust the SENSITIVITY control so that the right-most
green LED just comes ON.
E. The default display indicates fluid velocity as either
FPS or MPS. Refer to the appropriate place in this manual for specific features and options.
, the SIGNAL
Rev. 10/08 - 5 - D902/3
PART 1 - INTRODUCTION
General
Application Versatility
The D902/3 ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non-contacting, clamp-on type, which will provide benefits of non-fouling operation and ease of installation.
The flow meter operates by transmitting an ultrasonic sound from its transmitting transducer through the pipe wall into the flowing liquid. The sound will be reflected by suspended particles or bubbles within the liquid and recorded by the receiving transducer. A frequency shift (Doppler effect) will occur that is directly related to the speed of the moving particle or bubble. This shift in frequency is interpreted by the instrument and converted to various user defined measuring units.
A unique feature of this product is that it employs a proprietary digital filtering system and recognition circuit. This feature allows the instrument to measure fluid velocities of clean liquids if the transducers are mounted downstream from a 90° elbow. The non-symmetrical hydraulic turbulence which occurs downstream of an elbow is captured, linearized and can be displayed as liquid velocity and volume. This capability is not available in conventional Doppler technology.
The D902/3 flow meter can be successfully applied on a wide range of metering applications. The simple to program transmitter allows the standard product to be used on pipe sizes ranging from 1 - 120 inch (25 - 3048 mm) pipe I.D. With the small pipe transducer option, the pipe size range is 0.25 - 1 inch (6 - 25 mm). A variety of liquid applications can be accommodated: raw sewage, reclaimed water, cooling water, river water, plant effluent, mining slurries, sludge, etc. Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Standard transducers are rated to 250 °F (121 °C). Optional high temperature transducers are rated to operate to 400 °F (204 °C).
Rev. 10/08 - 6 - D902/3
PART 1 - INTRODUCTION
User Safety
Battery Backup
Product Identification
The D902/3 employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 9 Vdc and the metal work is electrically connected to earth ground. All user connections are made through sealed, bulk-head plugs located on the side of the D902/3 enclosure.
A rechargeable nickel-cadmium battery on the back of the display board retains all user-entered configuration values in memory for several years (at 25 °C), even if power is lost or turned off. The ten year battery is continually trickle charged whenever line power is applied. A completely discharged battery recharges fully after 48 hours of instrument operation.
The serial number and complete model number of the D902/3 are located on the inside of the transmitter cover. Should technical assistance be required, please provide the Dynasonics Customer Service Department with this information.
Product Matrix
D 9
Measuring Units/ Transducer Type
02) U.S.
03) Metric
12) U.S. (High Temp)
13) Metric (High Temp)
22) U.S. (Small Pipe)
23) Metric (Small Pipe)
32) U.S. (High Temp &
Small Pipe)
33) Metric (High Temp & Small Pipe)
* High Temp (+400 °F) Small Pipe (1/4" - 1")
*
Power Supply
A) 115 VAC B) 230 VAC C) 100 VAC D) 200 VAC E) 12 VDC
1 N A
Output 2
N) None
Output 1
1) 4-20 mA
Totalizer
A) Six digit
resettable
NOTE: The Series D902 is shipped with one set of standard transducers, acoustic couplant, two mounting straps, power cord and a 4-20 mA cable.
Rev. 10/08 - 7 - D902/3
N
Approvals
N) None
Options
N) U.S. Power Cord E) U.K. Power Cord G) Euro Power Cord
PART 1 - SPECIFICATIONS
TRANSMITTER
DESCRIPTION SPECIFICATION
Power Requirements
Flow Range
Outputs
Indicators
Display
Units
Rate U.S. (Metric) FPS, GPM, MGD (MPS, LPM, M
Totalizer U.S. (Metric) Gallons (liters, M3)
Ambient Conditions
Enclosure
Internal Lead Acid Gel Cell battery provides 8 hours of continuous operation. AC charging: (Std) 115/230 VAC 50/60 Hz ±10%. (Opt) 100/200 VAC 50/60 Hz ±10%. (Opt) 12 VDC.
0.5 to 20 FPS (0.15 to 6 MPS)
4-20 mA, 600 Ohms max. isolated
Power, Signal Strength, Flow Analyzer, Read Fault, Overrange, Charging and Low Battery
2 line × 20 character alphanumeric LCD (backlit). Digit height 0.2 inches (5 mm), 6 digit rate, 6 digit totalizer (resettable)
User configured
-20 to +160 °F (-30 to +70 °C), 0-95% relative humidity, non-condensing
NEMA 4, (IP-65) ABS with SS hardware. 11W × 17L × 8D inches (279W × 432L × 203D mm)
3
/hr)
Accuracy
Sensitivity
Repeatability
Response Time
±2% Full Scale
0.4% of Full Scale
±0.4% of Full Scale
5-50 seconds, user configured, to 90% of value, step change in flow
TRANSDUCERS
DESCRIPTION SPECIFICATION
Liquid Requirements
Transducer Cable
Pipe Sizes
Housing Material
25 ppm of 30 micron size suspended solids or entrained gases.
(Std) 20 feet (6 m), retractable cord.
(Std) 1 inch (25 mm) and above (Small pipe) 1/4 to 1 inch (6 to 25 mm)
Standard Clamp-On: NEMA 6P (IP-68) - 40 °F to +210 °F (- 40 °C to +100 °C) CPVC, Ultem
High Temp Clamp-On: NEMA 4 (IP-65) - 40 °F to +400 °F (- 40 °C to +200 °C) Vespel
®
, Nylon, PVC (Cable Jacket), Aluminum (small pipe)
®
, Anodized Aluminum, Nickel-plated brass, Teflon® (Cable Jacket)
Rev. 10/08 - 8 - D902/3
PART 2 - PRE-INSTALLATION CHECKOUT
Unpacking
Functional Test
Transducer Connection
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The D902/3 flow meter can be checked for basic functionality using the following Bench Test procedure. It is recommended that this operation be performed before each day of operation.
Procedure:
1. Open the D902/3 transmitter cover.
2. Connect the transducer cable connector plug to the corresponding connector socket located on the side of the D902/3 enclosure. See Figure 3.
3. Set the transmitter SENSITIVITY control (located on the front panel) to -2.
4. Apply power.
5. Hold the transducers, the flat sides facing each other, approximately 6 - 8 inches (150 - 200 mm) apart.
6. Move the transducers towards and away from each other 1 inch (25 mm) for several cycles at approximately 1 second intervals.
7. If unit is functioning properly, the READ LED will illuminate and the rate display will indicate flow readings.
Bench Test is Complete
Figure 3
Rev. 10/08 - 9 - D902/3
PART 2 - TRANSDUCER INSTALLATION
Transducer Mounting Considerations
Step A - Mounting Locations
CASE 1:
Figure 4
The transducers that are utilized by the D902/3 contain piezoelectric crystals for transmitting and receiving ultrasonic sound energy through the pipe wall.
The transducers can be mounted in three different configurations. The selection of the proper configuration is dependent on the characteristics of the liquid to be measured.
The three liquid characteristics, which will affect mounting location and orientation, are as follows:
CASE 1: Liquid that contains 25 to 10,000 PPM (1%) of 30 micron or larger suspended solids or aeration.
CASE 2: Liquid that contains greater than 10,000 PPM (1%) of 30 micron or larger suspended solids or aeration.
CASE 3: Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration and suspended solids and aeration content which is smaller than 30 microns.
Liquid that contains 25 to 10,000 PPM (1%) of 30 micron or larger suspended solids or aeration.
Select a transducer mounting location with adequate straight runs of pipe, both upstream and downstream, to achieve stable readings. Examples of minimum upstream and downstream requirements are included in Table 1.
Mount the transducers 180° apart and facing each other on the pipe. If the pipe is horizontal, the preferred mounting orientation is 3 and 9 o’clock, with 12 o’clock being the top of the pipe. Orientation on vertical pipes does not matter. See Figure 4.
Rev. 10/08 - 10 - D902/3
PART 2 - TRANSDUCER INSTALLATION
Table 1
1
1
The D902/3 system will provide repeatable measurements on piping systems that do not meet these requirements, but the accuracy of these readings may be influenced to various degrees.
Rev. 10/08 - 11 - D902/3
PART 2 - TRANSDUCER INSTALLATION
CASE 2:
Liquid that contains greater than 10,000 PPM (1%) of 30 micron or greater suspended solids or aeration.
The mounting location and straight pipe requirements for CASE 2 liquid characteristics are the same as those described in CASE 1. The difference will be in the location of the transducers on the pipe. As the discontinuities (suspended solids or aeration) reach a level of approximately 1% or 10,000 PPM, sound can no longer be reliably transmitted through the liquid as it has a tendency to scatter and absorb into the high concentration of discontinuity. To compensate for this, the D902/3 transducers can be located on the same region of the pipe. In a horizontal pipe, mount the transducers at 2 o’clock and 4 o’clock positions. (Assuming 12 o’clock as the top of the pipe.) See Figure 5.
Figure 5
CASE 3:
Rev. 10/08 - 12 - D902/3
Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration. Or, liquid that contains solids or aeration which is smaller than 30 microns.
The transducers will be mounted 1 to 3 pipe diameters downstream from a 90° elbow. The orientation of the transducers on the pipe will be 180° apart and facing each other and 90° out of the plane of the elbow. See Figure 6 on page 13.
PART 2 - TRANSDUCER INSTALLATION
Step B - Pipe Surface Preparation
Step C - Transducer Mounting
Figure 6
Before the transducer heads are bonded to the pipe surface, an area slightly larger than the flat surface of the transducer must be cleaned to bare metal on the pipe. (Plastic pipes do not require preparation beyond removal of paint.) Remove all scale, rust and paint. Thoroughly dry and degrease the mounting surfaces.
NOTE: Small pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception.
After selecting the applicable mounting location and preparing the piping surface as detailed in Steps A and B, the transducer can be mounted to the pipe.
NOTE: High Temperature transducer installations require specialized mounting hardware and instructions. For drawings detailing installation of this option, contact the factory.
Steps A and B, Mounting Locations and Pipe Preparation sections of this manual apply to the High Temperature option. Reference these sections as required.
Rev. 10/08 - 13 - D902/3
PART 2 - TRANSDUCER INSTALLATION
To assure an acoustically conductive path between the transducer face and the prepared piping surface, a coupling compound is employed. Enclosed with the D902/3 system is a tube of Dow Corning 111, silicone grease. This couplant is satisfactory for temporarily mounting the transducers to the pipe. If the installation is long-term (more than a few days), Dynasonics recommends utilizing a silicone-based RTV such as Dow Corning RTV-732. If alternate couplants are utilized, the grease chosen must be rated to not flow at the temperature of the pipe.
1. Wrap the elastic strap (enclosed) around the pipe in the area where the transducers are to be mounted. Mount the strap snuggly, but leave the strap just loose enough to allow the transducers to be placed underneath.
2. Spread an even layer of coupling compound, approximately 1/8 inch (3 mm) thick, to the prepared transducer mounting areas of the pipe. Utilize Dow 111 for temporary mounting or Dow 732 for permanent mounting.
3. Spread an even layer of the coupling compound, approximately 1/8 inch (3 mm) thick, to the flat face of the two transducers.
FLOW DIRECTION
Figure 7
Rev. 10/08 - 14 - D902/3
4. Place each transducer under the strap with the flat face positioned towards the pipe. The notch on the back of the transducer will provide a mounting surface for the strap. The transducer cables must be facing in the same direction for proper operation. See Figure 7. NOTE: Large pipes may require two people for this procedure.
5. Tighten the strap tight enough to hold the transducers in place, but not so tight that all of the couplant squeezes out of the gap between the transducer face and pipe. Ensure that the transducers are squarely aligned on the pipe.
PART 2 - TRANSDUCER INSTALLATION
6. Route the transducer cable back to the transmitter mounting area avoiding high voltage cable trays and conduits. Do not attempt to add additional cable to the factory supplied transducer cable. The D902/3 processes very small signals, so the cable shield must be continuous.
7. If the transducers are to be permanently mounted using Dow 732, the RTV must be completely cured proceeding to Instrument Startup. Ensure that no relative motion between the transducer and pipe occurs during the 24 hour curing process. If Dow 111 grease was used for temporary operation of the D902/3 system, proceed with the Instrument Startup procedures.
Transducer Installation is complete.
before
Rev. 10/08 - 15 - D902/3
PART 2 - ELECTRICAL CONNECTIONS
Transmitter Location
Transducer Connection
Figure 8
The D902/3 enclosure should be located in an area that is convenient for observation of the LCD readout and keypad operations. To prolong the life of the keypad and controls, the enclosure cover should be left closed when the unit is unattended.
Place the D902/3 transmitter in a location that is:
Where little vibration exists.
Protected from falling corrosive fluids.
Within ambient temperature limits -22 to +160 °F (+30
to +70 °C)
Out of direct sunlight. Direct sunlight may increase
temperatures within the transmitter to above maximum limit.
Connect the transducer plug to the socket connection located on the side of the D902/3 enclosure. Refer to Figure 8. Ensure that tension on the retractable cables has not pulled either of the transducers out of position on the pipe. The transducers must be squarely mounted to achieve greatest accuracy.
NOTE: The transducer cable carries low level signals. Do not attempt to add additional cable to the factory supplied transducer cable.
Rev. 10/08 - 16 - D902/3
PART 2 - ELECTRICAL CONNECTIONS
4-20 mA Output
Battery Charging and AC Power Operation
4-20 mA Output
Figure 9
AC Power Connection
Figure 10
The 4-20 mA output is proportional to the flow rate measuring scale and can drive a load of up to 600 Ohms. The output is isolated from earth ground and circuit low. Connect the load to the 4-20 mA connection socket located on the side of the D902/3 enclosure, matching polarity as indicated. See Figure 9. A mating plug for the connection socket has been included.
To recharge the internal battery of the D902/3 or to operate the meter for periods of time greater than 8 hours, connect the meter to AC line power. Line power is connected by plugging the enclosed line cord into the appropriate connector socket located on the side of the D902/3 enclosure. See Figure 10. Use wiring practices that conform to local codes (National Electric Code Handbook in the USA). Use only the standard three wire connection. The ground terminal grounds the instrument, which is mandatory for safe operation.
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (i.e. Fluorescent lights, relays, compressors, variable frequency drives, etc.).
®
Rev. 10/08 - 17 - D902/3
PART 2 - SERVICE AND MAINTENANCE
Battery Care and Maintenance
The D902/3 flow meter is equipped with a Lead Acid Gel Cell battery. This battery will require charging before initial operation. Apply AC power, utilizing the enclosed line power cord, to the D902/3 for a period of 16-24 hours prior to using the product for the first time. The line cord connects to the socket connection located on the side of the enclosure.
The D902/3’s integral battery provides continuous operation for up to 8 hours on a full-charge. The battery is “maintenance free”, but it still requires a certain amount of attention to prolong its useful life. To obtain the greatest capacity and longevity from the battery, the following practices are recommended:
Do not allow the battery to completely discharge. (Discharging the battery to the point where the LOW BATTERY indicator illuminates will not damage the battery. Allowing the battery to stay discharged for long periods of time can degrade the storage capacity of the battery.) When not in use, continually charge the battery by keeping it plugged into line power. The D902/3 battery management circuitry will not allow the battery to become “over-charged”.
NOTE: The D902/3 will automatically enter a low power consumption mode approximately 1-1/2 minutes after the LOW BATTERY indicator illuminates. This circuit prevents excessive discharge of the internal battery.
If the D902/3 is stored for prolonged periods of time, monthly charging is recommended.
If the D902/3 is stored for prolonged periods of time, store at a temperature below 70 ºF (21 ºC).
The CHARGING indicator will always be illuminated when the D902/3 is connected to line power and the flow meter is turned ON. If the D902/3 is turned OFF and line power is connected, the CHARGING indicator will illuminate only when the internal circuit is charging the battery. During storage, the CHARGING indicator will cycle as necessary.
Rev. 10/08 - 18 - D902/3
PART 2 - SERVICE AND MAINTENANCE
Desiccant Cartridge
The D902/3 is equipped with a DESICCANT CARTRIDGE, which is located in the face plate of the meter. The purpose of the cartridge is to absorb the humidity that was present inside of the enclosure when the product was manufactured and to absorb moisture that may seep into the enclosure during field operation. Observing the color indicator of the DESICCANT CARTRIDGE and replacing it when it turns PINK will decrease the chance of corrosion and resulting failure of the internal components of the D902/3.
Procedure:
1. Obtain a new DESICCANT CARTRIDGE from Dynasonics (Dynasonics P.N. D005-9909-001).
2. Replace the cartridge in a temperature and humidity controlled environment. Allow the meter to reach the same ambient temperature as the area in which the cartridge will be replaced. (Do not attempt to change the cartridge if the meter is below the Dew Point Temperature.)
3. Remove the old cartridge with a 1-3/8" open-end wrench or appropriate adjustable wrench.
4. Insert the new cartridge and tighten with the wrench.
5. Discard the used cartridge.
Rev. 10/08 - 19 - D902/3
PART 3 - STARTUP AND CONFIGURATION
Before Starting the Instrument
Instrument Startup
Important!
NOTE: The D902/3 flow meter system requires a full pipe of flowing liquid before a successful startup can be
completed. Do not attempt to make adjustments or change configurations until both a full pipe and liquid flow are verified.
NOTE: If Dow 732 RTV was utilized to couple the transducers to the pipe, the adhesive must fully cure before power is applied to the instrument. Dow 732 requires 24 hours to cure satisfactorily. If Dow 111 silicone grease was utilized as a couplant, the curing time is not required.
Procedure:
1. Verify that all wiring is properly connected and routed.
2. Set the SENSITIVITY Control to -2. This control is located on the D902/3 front panel.
3. Apply power. The POWER indicator will illuminate.
4. Adjust the SENSITIVITY control so that the right-most LED on the SIGNAL STRENGTH bar meter just illuminates or SIGNAL STRENGTH is at least in the yellow/green region.
NOTE: It is undesirable to adjust the SENSITIVITY control to a position higher than necessary, as ambient noise can also be amplified. This noise can cause false readings to occur.
5. If the pipe is full of a flowing liquid, the READ indicator will illuminate and the display will begin reading fluid velocity as FPS (Feet per Second) or MPS (Meters per Second). It is normal to have low SIGNAL STRENGTH and FAULT indication at ZERO flow.
6. If a SIGNAL STRENGTH reading in the green portion of the bar meter or a FLOW ANALYZER indication could not be obtained, refer to the troubleshooting section of this manual.
Rev. 10/08 - 20 - D902/3
PART 3 - STARTUP AND CONFIGURATION
Keypad Configurations
Modes of Operation
Default Configuration
After a successful flow meter installation and startup (covered in the previous sections of this manual) the D902/3 can be keypad configured to provide select engineering unit readings of flow and a scaled 4-20 mA output. Configuration inputs are made via the keypad and are stored by the microprocessor. The entries are retained by the flow meter’s backup battery in the event of power failure. If fluid velocity readings in FPS or MPS are the only required measurement, keypad configuration is not required.
The RUN/ENT key toggles the flow meter between the two modes of operation.
RUN Mode: This is the primary operating mode of the flow meter. The meter is in RUN mode when the readout is displaying flow as velocity (FPS, MPS) or volume (GPM, LPM, LPS). In RUN mode the outputs are active and transmitting signals proportional to flow rate.
ENTRY Mode: This mode is used to view or change the configuration of the flow meter. When the D902/3 ships from the Dynasonics factory, it contains the following Default configuration:
PARAMETER U.S. METRIC
ID
UNITS
DAMP
Volume/PLS
FULL SCALE
CAL
Each of these parameters may be viewed and/or modified in the ENTRY Mode. Changes are processed when the RUN/ENT is pressed and the meter returns to RUN MODE. In ENTRY Mode flow totalization is suspended and process outputs are frozen at the last value recorded.
Rev. 10/08 - 21 - D902/3
1 Inch 25 mm
1 (FPS) 1 (MPS)
1 Sec 1 Sec
φ φ
20 FPS 6.08 MPS
100% 100%
PART 3 - STARTUP AND CONFIGURATION
Pipe I.D. Input
The ID key allows the entry of a pipe’s Internal Diameter. The D902/3 utilizes the I.D. constant to process volumetric flow rates such as GPM (Gallons per Minute) or LPM (Liters per Minute). The entry is made as either inches or mm, dependent on whether the unit is configured as U.S. units or Metric units.
Press the I.D. key from the ENTRY MODE. The display will show
This is the present I.D. constant. Enter a new I.D. based on information obtained from the pipe manufacturer, a physical measurement or a pipe chart. Some common pipe sizes and dimensions are located on a series of charts located in the Appendix of this manual. The acceptable input range for the I.D. constant is shown in
Table 3.
I.D. U.S. METRIC
Max
Min *
* Pipe sizes less than 1 inch (25 mm) require a Small Pipe Transducer. Dynasonics P.N. D070-1004-003.
INSIDE DIAMETER
Table 3
120 Inches 3050 mm
0.25 Inches 6 mm
NOTE: If a decimal value of less than 1 is to be entered, enter 0
NOTE: If an entered value is out of the acceptable range of the instrument, an UNDER! or OVER! indication will be displayed. The meter will not allow any other entries to be made until a legitimate value is entered.
Rev. 10/08 - 22 - D902/3
. X X. The zero must precede the decimal value.
PART 3 - STARTUP AND CONFIGURATION
Full Scale Input
Important!
The FULL SCALE key allows the entry of the highest anticipated fluid velocity. The entry is made as either FPS (Feet per Second) or MPS (Meters per Second) dependent on whether the unit is configured as U.S. units or Metric units. The FULL SCALE input is used by the D902/3 microprocessor to scale the 4-20 mA output and adjust the resolution of the flow rate display.
Acceptable input range for the FULL SCALE constant is shown in Table 4.
Table 4
I.D. U.S. METRIC
Max
Min *
* NOTE: FULL SCALE values below 1.5 FPS (0.5 MPS)
are not recommended.
NOTE: If an entered value is out of the acceptable range of the instrument, a RANGE! indication will be displayed. The meter will not allow any additional entries to be made until a legitimate value is entered.
20 FPS 8 MPS
n/a n/a
NOTE: If a decimal value is to be entered, enter 0 . X X. The zero must precede the decimal value (if less than 1) and only two numbers should be entered after the decimal value.
Volume to Velocity Conversion
Rev. 10/08 - 23 - D902/3
Two useful equations which relate volumetric flow in round pipes to flow velocity are as follows:
FPS = U.S. GPM × 0.409 ID
MPS = LPM × 21.23 ID
2
(inches)
2
(mm)
PART 3 - STARTUP AND CONFIGURATION
Totalizer Exponent Input
The VOL. PULSE key allows the entry of a totalizer exponent. This feature is useful for accommodating a very large accumulated flow. The exponent is a “×10” multiplier, which can be from 0 (no multiplier) to 2 (×100). For example, to totalize in GAL × 100, a VOL. PULSE value of 2 would be used (10² or 100).
Acceptable input range for the VOL. PULSE constant is shown in Table 5.
I.D. U.S. METRIC
Max
Min *
* NOTE: If an entry greater than 2 is attempted, the meter will display OVER!. If a non-whole number value is attempted, the meter will display RANGE!. A legitimate value will need to be entered.
After a VOL. PULSE value is entered, the display will reflect the unit as 0=10º=×1, 1=10¹=×10 and 2=10²=×100.
Table 6 illustrates various codes and their display results.
Table 5
2 2
0 0
Table 6
VOL. PULSE
CODE
0
1
2
Rev. 10/08 - 24 - D902/3
ENG. NOTATION
10E0 999,999
10E1 999,999
10E2 999,999
DISPLAY
MAXIMUM
PART 3 - STARTUP AND CONFIGURATION
Engineering Units Input
Altering the CALibration of the D902/3
The UNITS key allows the selection of measuring units. Table 7 shows applicable codes for the engineering units available.
UNITS CODE U.S. METRIC
1
2
3
Attempting to enter values other than 1, 2 or 3 will result in an UNDER! or OVER! to be displayed. Non-whole number values will result in a RANGE! display. A legitimate value must be entered.
A few factors can influence the readings of the D902/3 flow meter. The CAL entry allows the user to compensate for flow discrepancies without affecting the factory calibration. Examples of situations that can cause reading discrepancies are:
Operation on liquids with sonic velocity carrying properties that are different than water. Please refer to the Fluid Sound Speed correction chart located in the Appendix of this manual.
Table 7
FPS MPS
GPM LPM
MGD LPS
Transducers mounted in non-recommended locations.
Operation on fluids with a large amount of suspended
solids.
By applying a CAL value other than 100%, the factory calibrated readings will be altered by the percentage entered. This CAL value will not output.
For example, if a reading of 175 GPM is displayed and the known flow rate is 160 GPM, a CAL value of
160 GPM 175 GPM
Rev. 10/08 - 25 - D902/3
× 100 = 91.4%
be reflected in the 4-20 mA
PART 3 - STARTUP AND CONFIGURATION
Display Damping
The TEST Diagnostic Key
The D902/3 will not allow decimal values to be entered as a CAL constant, so round to the nearest whole number. In this case 91%.
Acceptable input ranges for the CAL constant are shown in Table 8. Values outside of this range will result in an OVER! or UNDER! display. Non-whole number entries will result in a RANGE! display. Enter an appropriate value.
I.D. U.S. METRIC
Max
Min
The DAMP key allows the selection of time duration between display updates. The value selected and entered will result in display updates of
n × 2 = seconds between updates
Acceptable input ranges for the DAMP constant are shown in Table 9. Values outside of this range will result in an OVER! or UNDER! display. Entry of an appropriate value is required.
I.D. U.S. METRIC
Max
Min
The TEST key is used for diagnostic purposes. It displays the operand presently available at the analog to digital converter. This value will always be in the range of 0 to
255.
Table 8
200% 200%
3% 3%
Table 9
5 5
0.5 0.5
Rev. 10/08 - 26 - D902/3
PART 3 - STARTUP AND CONFIGURATION
System and Totalizer RESET
Reset the Flow Totalizer
FLOW ANALYZER
The RESET key is used for generating a system reset or to reset the accumulated flow. Press the RESET button from the ENTER Mode. A choice is then made to:
RESET Reset the system
VOL. MULT Press VOL. PULSE to reset the totalizer to zero
If the RESET key is pressed again, all configuration constants will return to default values.
If the VOL. PULSE key is pressed, the accumulated flow will be erased and the display will return to zero.
In RUN Mode, pressing the decimal point once will suspend totalizer accumulation. Pressing the decimal point again will clear the total. Pressing it a third time will restart the accumulation from zero.
NOTE: In RUN mode, the key presses are processed and displayed at the interval defined by the DAMP constant setting. (i.e. If the DAMP constant is set to 10, the key presses will be acknowledged only every 20 seconds.)
The FLOW ANALYZER bar meter indicates the relative condition of the Doppler signal that is being processed by the D902/3. When the instrument is utilized on liquids with suspended solids or aeration, the FLOW ANALYZER will indicate within the two right segments — an ideal Doppler condition. When the D902/3 is used to measure cleaner liquids, the FLOW ANALYZER bar meter will search its discrete filter banks and adjust to match the particular liquid parameters that are present. The bar meter will indicate these changes when they occur. If no segments are illuminated on the FLOW ANALYZER, the level of liquid discontinuity or hydraulic turbulence is inadequate and the transducers will have to be relocated. Typically, moving the transducers closer to a 90º elbow will provide adequate liquid conditions.
Rev. 10/08 - 27 - D902/3
PART 4 - TROUBLESHOOTING
CONDITION
Unit does not turn “ON” when power is applied
These procedures require the face plate to be removed from the enclosure.
OVERRANGE light is ON
FAULT light is ON; low SIGNAL STRENGTH indication
POSSIBLE CAUSE
Verify that the battery is charged. Plug into an AC power source.
Test the fuse.
Ensure the terminal block located in the
upper left corner of the main PCB is secure.
Verify that ribbon cables between PCBs are connected.
Increase the value of the FULL SCALE constant.
Verify that fluid velocity is not greater than 20 FPS (6.08 MPS).
Ensure that the transducers are properly mounted to the pipe.
Verify that transducer connections are correct.
Ensure that the pipe is full of moving liquid.
Increase SENSITIVITY so that right-most SIGNAL STRENGTH light just comes ON.
On cleaner liquids, move the transducers
o
closer to a 90
pipe elbow.
On dirtier liquids, mount the transducers as described in CASE 3 in Part 2 of this manual.
If the pipe has a polyethylene liner, move the transducers to another area. The liner may contain an air void at this location.
(continued)
Rev. 10/08 - 28 - D902/3
PART 4 - TROUBLESHOOTING
FAULT light is ON; low SIGNAL STRENGTH indication (continued)
Stability of flow readings are unsatisfactory
This procedure requires the face plate to be removed from the enclosure.
Erroneous Reading
If GND connection and pipe are at different potentials, ground D902/3 to pipe potential.
If Variable Frequency Drives are being utilized, verify that the D902/3 obtains a READ light when the pump is turned OFF. If possible, increase the carrier frequency of the drive.
Increase the DAMP constant from keypad.
Increase the system time constant by
turning R17 (DAMP) clockwise till readings are satisfactory.
Move transducers to a location further from piping tees, elbows, valves, filters, etc.
Transducers mounted incorrectly.
Another local ultrasonic instrument is
operating at about the same frequency (consult the Dynasonics factory).
The D902/3 display indicates flow, when true fluid velocity is zero
Presence of large amounts of suspended solids or aeration. Use CAL constant to compensate.
Sources of radiated interference are present. Apply appropriate shielding.
An electrically noisy power supply is powering the D902/3. Power the meter with a circuit that does not power motors, ballasts or switching supplies.
Verify that residual leakage and flow are not present (i.e. leaking check valves).
Verify that SENSITIVITY is not adjusted too high. With nominal flow running through the pipe, adjust SENSITIVITY control till the right-most bar meter light just comes ON.
Rev. 10/08 - 29 - D902/3
NOTES
Rev. 10/08 - 30 - D902/3
PART 5 - APPENDICES
Appendices
Spare Parts List Mechanical Drawing Fluid Sound Speed Conversion Chart Clean Liquid Installation Guide Pipe Dimension Chart: Cast Iron Pipe Dimension Chart: Steel, SS, PVC Velocity to Volumetric Conversion Chart Statement of Warranty Customer Service
Rev. 10/08 - 31 - D902/3
SPARE PARTS - D902/3
PART NUMBER
D070-1004-001 Series D902 Std. Temp./Std. Pipe Transducer
D040-0402-001 Series D902 High Temp./Std. Pipe Transducer
D070-1004-003 Series D902 Std. Temp./Small Pipe Transducer
D902 O&M Series D902 Installation and Operations Manual
D005-1003-100 Two conductor, 20 AWG, unshielded cable
D003-0825-001 Stainless Steel Identification Tag
D005-9909-001 Series 902 Desiccant Cartridge
DESCRIPTION
D005-1201-001 Series 902 Gel Cell Battery
D002-2011-002 Couplant, RTV (for permanent mounting)
D002-2011-001 Couplant, Silicone (for temporary mounting)
D005-2109-002 Series 902 U.S. Line Cord (Two spades and ground)
D005-2109-011 Series 902 U.K. Line Cord (Three rectangular spades)
D005-2109-021 Series 902 German Line Cord (Two round spades)
D010-0200-100 Series 902 Transducer Extension Cable, 20 ft. (6 m)
D005-1301-002 Fuse, 0.125A Slow Blow, 250V
D005-1301-004 Fuse, 0.75A Slow Blow, 250V
D002-2009-046 Elastic Pipe Strap, 46" (1100 mm)
D002-2009-076 Elastic Pipe Strap, 76" (2000 mm)
D005-0904-001 4-20 mA MIL Connector
Rev. 10/08 - 32 - D902/3
MECHANICAL DRAWING - D902/3
Rev. 10/08 - 33 - D902/3
Fluid Properties
Original Date: 7/30/1999 Revision: A Revision Date: 9/10/2003 File: I:/dynasonics/dyna_code/tables/fluid_ss.xls
Fluid Specific Gravity Sound Speed delta-v/degree C Kinematic Viscosity Absolute Viscosity
20 degrees C m/s ft/s m/s/degree C Centistokes Centipoise
Acetate, Butyl 1270 4163.9 Acetate, Ethyl 0.901 1085 3559.7 4.4 0.489 0.441 Acetate, Methyl 0.934 1211 3973.1 0.407 0.380 Acetate, Propyl 1280 4196.7 Acetone 0.79 1174 3851.7 4.5 0.399 0.316 Alcohol 0.79 1207 3960.0 4.0 1.396 1.101 Alcohol, Butyl 0.83 1270 4163.9 3.3 3.239 2.688 Alcohol, Ethyl 0.83 1180 3868.9 4 1.396 1.159 Alcohol, Methyl 0.791 1120 3672.1 2.92 0.695 0.550 Alcohol, Propyl 1170 3836.1 Alcohol, Propyl 0.78 1222 4009.2 2.549 1.988 Ammonia 0.77 1729 5672.6 6.7 0.292 0.225 Anlline 1.02 1639 5377.3 4.0 3.630 3.710 Benzene 0.88 1306 4284.8 4.7 0.711 0.625 Benzol, Ethyl 0.867 1338 4389.8 0.797 0.691 Bromine 2.93 889 2916.7 3.0 0.323 0.946 n-Butane 0.60 1085 3559.7 5.8 Butyrate, Ethyl 1170 3836.1 Carbon dioxide 1.10 839 2752.6 7.7 0.137 0.151 Carbon tetrachloride 1.60 926 3038.1 2.5 0.607 0.968 Chloro-benezene 1.11 1273 4176.5 3.6 0.722 0.799 Chloroform 1.49 979 3211.9 3.4 0.550 0.819 Diethyl ether 0.71 985 3231.6 4.9 0.311 0.222 Diethyl Ketone 1310 4295.1 Diethylene glycol 1.12 1586 5203.4 2.4 Ethanol 0.79 1207 3960.0 4.0 1.390 1.097 Ethyl alcohol 0.79 1207 3960.0 4.0 1.396 1.101 Ether 0.71 985 3231.6 4.9 0.311 0.222 Ethyl ether 0.71 985 3231.6 4.9 0.311 0.222 Ethylene glycol 1.11 1658 5439.6 2.1 17.208 19.153 Freon R12 774.2 2540 Gasoline 0.7 1250 4098.4 Glycerin 1.26 1904 6246.7 2.2 757.100 953.946 Glycol 1.11 1658 5439.6 2.1 Isobutanol 0.81 1212 3976.4 Iso-Butane 1219.8 4002 Isopentane 0.62 980 3215.2 4.8 0.340 0.211 Isopropanol 0.79 1170 3838.6 2.718 2.134 Isopropyl alcohol 0.79 1170 3838.6 2.718 2.134 Kerosene 0.81 1324 4343.8 3.6 Linalool 1400 4590.2 Linseed Oil .925-.939 1770 5803.3 Methanol 0.79 1076 3530.2 2.92 0.695 0.550 Methyl alcohol 0.79 1076 3530.2 2.92 0.695 0.550 Methylene chloride 1.33 1070 3510.5 3.94 0.310 0.411 Methylethyl Ketone 1210 3967.2 Motor Oil (SAE 20/30) .88-.935 1487 4875.4 Octane 0.70 1172 3845.1 4.14 0.730 0.513
Oil, Castor 0.97 1477 4845.8 3.6 0.670 0.649 Oil, Diesel 0.80 1250 4101 Oil (Lubricating X200) 1530 5019.9 Oil (Olive) 0.91 1431 4694.9 2.75 100.000 91.200 Oil (Peanut) 0.94 1458 4783.5 Paraffin Oil 1420 4655.7 Pentane 0.626 1020 3346.5 0.363 0.227 Petroleum 0.876 1290 4229.5 1-Propanol 0.78 1222 4009.2 Refrigerant 11 1.49 828.3 2717.5 3.56 Refrigerant 12 1.52 774.1 2539.7 4.24 Refrigerant 14 1.75 875.24 2871.5 6.61 Refrigerant 21 1.43 891 2923.2 3.97 Refrigerant 22 1.49 893.9 2932.7 4.79 Refrigerant 113 1.56 783.7 2571.2 3.44 Refrigerant 114 1.46 665.3 2182.7 3.73 Refrigerant 115 656.4 2153.5 4.42 Refrigerant C318 1.62 574 1883.2 3.88 Silicone (30 cp) 0.99 990 3248 30.000 29.790 Toluene 0.87 1328 4357 4.27 0.644 0.558 Transformer Oil 1390 4557.4 Trichlorethylene 1050 3442.6 1,1,1-Trichloro-ethane 1.33 985 3231.6 0.902 1.200 Turpentine 0.88 1255 4117.5 1.400 1.232 Water, distilled 0.996 1498 4914.7 -2.4 1.000 0.996 Water, heavy 1 1400 4593 Water, sea 1.025 1531 5023 -2.4 1.000 1.025 Wood Alcohol 0.791 1076 3530.2 2.92 0.695 0.550 m-Xylene 0.868 1343 4406.2 0.749 0.650 o-Xylene 0.897 1331.5 4368.4 4.1 0.903 0.810 p-Xylene 1334 4376.8 0.662
Cast Iron Pipe
Standard Classes
CLASS B CLASS C CLASS D CLASS E CLASS F
Size
(Inches)
10 11.10 10.10 0.50 11.10 9.96 0.57 11.40 10.16 0.62 11.40 10.04 0.68 11.60 10.12 0.74 11.60 10.00 0.80 11.84 10.12 0.86 11.84 10.00 0.92
12 13.20 12.12 0.54 13.20 11.96 0.62 13.50 12.14 0.68 13.50 12.00 0.75 13.78 12.14 0.82 13.78 12.00 0.89 14.08 12.14 0.97 14.08 12.00 1.04 14 15.30 14.16 0.57 15.30 13.98 0.66 15.65 14.17 0.74 15.65 14.01 0.82 15.98 14.18 0.90 15.98 14.00 0.99 16.32 14.18 1.07 16.32 14.00 1.16 16 17.40 16.20 0.60 17.40 16.00 0.70 17.80 16.20 0.80 17.80 16.02 0.89 18.16 16.20 0.98 18.16 16.00 1.08 18.54 16.18 1.18 18.54 16.00 1.27 18 19.50 18.22 0.64 19.50 18.00 0.75 19.92 18.18 0.87 19.92 18.00 0.96 20.34 18.20 1.07 20.34 18.00 1.17 20.78 18.22 1.28 20.78 18.00 1.39 20 21.60 20.26 0.67 21.60 20.00 0.80 22.06 20.22 0.92 22.06 20.00 1.03 22.54 20.24 1.15 22.54 20.00 1.27 23.02 20.24 1.39 23.02 20.00 1.51
24 25.80 24.28 0.76 25.80 24.02 0.89 26.32 24.22 1.05 26.32 24.00 1.16 26.90 24.28 1.31 26.90 24.00 1.45 27.76 24.26 1.75 27.76 24.00 1.88 30 31.74 29.98 0.88 32.00 29.94 1.03 32.40 30.00 1.20 32.74 30.00 1.37 33.10 30.00 1.55 33.46 30.00 1.73 36 37.96 35.98 0.99 38.30 36.00 1.15 38.70 35.98 1.36 39.16 36.00 1.58 39.60 36.00 1.80 40.04 36.00 2.02 42 44.20 42.00 1.10 44.50 41.94 1.28 45.10 42.02 1.54 45.58 42.02 1.78 48 50.50 47.98 1.26 50.80 47.96 1.42 51.40 47.98 1.71 51.98 48.00 1.99
O.D. Inch
3 3.80 3.02 0.39 3.96 3.12 0.42 3.96 3.06 0.45 3.96 3.00 0.48 4 4.80 3.96 0.42 5.00 4.10 0.45 5.00 4.04 0.48 5.00 3.96 0.52 6 6.90 6.02 0.44 7.10 6.14 0.48 7.10 6.08 0.51 7.10 6.00 0.55 7.22 6.06 0.58 7.22 6.00 0.61 7.38 6.08 0.65 7.38 6.00 0.69 8 9.05 8.13 0.46 9.05 8.03 0.51 9.30 8.18 0.56 9.30 8.10 0.60 9.42 8.10 0.66 9.42 8.10 0.66 9.60 8.10 0.75 9.60 8.00 0.8
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D. Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
CLASS G CLASS HCLASS A
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
54 56.66 53.96 1.35 57.10 54.00 1.55 57.80 54.00 1.90 58.40 53.94 2.23 60 62.80 60.02 1.39 63.40 60.06 1.67 64.20 60.20 2.00 64.82 60.06 2.38 72 75.34 72.10 1.62 76.00 72.10 1.95 76.88 72.10 2.39 84 87.54 84.10 1.72 88.54 84.10 2.22
March, 2000
Steel, Stainless Steel, P.V.C.
Standard Schedules
Nominal
Pipe Size
Inches
1.25 1.660 1.530 0.065 1.442 0.109 1.380 1.380 0.140 1.278 0.191 1.278 0.191 1.160 0.250
OUTSIDE
DIAMETER
1 1.315 1.185 0.065 1.097 0.109 1.049 1.049 0.133 0.957 0.179 0.957 0.179 0.815 0.250
1.5 1.900 1.770 0.065 1.682 0.109 1.610 1.610 0.145 1.500 0.200 1.500 0.200 1.338 0.281 2 2.375 2.245 0.065 2.157 0.109 2.067 2.067 0.154 1.939 0.218 1.939 0.218 1.687 0.344
2.5 2.875 2.709 0.083 2.635 0.120 2.469 2.469 0.203 2.323 0.276 2.323 0.276 2.125 0.375 3 3.500 3.334 0.083 3.260 0.120 3.068 3.068 0.216 2.900 0.300 2.900 0.300 2.624 0.438
3.5 4.000 3.834 0.083 3.760 0.120 3.548 3.548 0.226 3.364 0.318 3.364 0.318 4 4.500 4.334 0.083 4.260 0.120 4.026 0.237 4.026 0.237 3.826 0.337 3.826 0.337 3.624 0.438 3.624 0.438 3.438 0.531 5 5.563 5.345 0.109 5.295 0.134 5.047 0.258 5.047 0.258 4.813 0.375 4.813 0.375 4.563 0.500 4.563 0.500 4.313 0.625 6 6.625 6.407 0.109 6.357 0.134 6.065 0.280 6.065 0.280 5.761 0.432 5.761 0.432 5.501 0.562 5.501 0.562 5.187 0.719 8 8.625 8.407 0.109 8.329 0.148 8.125 0.250 8.071 0.277 7.981 0.322 7.981 0.322 7.813 0.406 7.625 0.500 7.625 0.500 7.437 0.594 7.187 0.719 7.187 0.719 6.183 1.221
10 10.750 10.482 0.134 10.42 0.165 10.25 0.250 10.13 0.310 10.02 0.365 10.020 0.365 9.750 0.500 9.750 0.500 9.562 0.594 9.312 0.719 9.062 0.844 9.062 0.844 8.500 1.125
12 12.750 12.420 0.165 12.39 0.180 12.25 0.250 12.09 0.330 12.00 0.375 11.938 0.406 11.626 0.562 11.750 0.500 11.370 0.690 11.060 0.845 10.750 1.000 10.750 1.000 10.120 1.315 14 14.000 13.50 0.250 13.37 0.315 13.25 0.375 13.25 0.375 13.124 0.438 12.814 0.593 13.000 0.500 12.500 0.750 12.310 0.845 11.810 1.095 11.810 1.095 11.180 1.410 16 16.000 15.50 0.250 15.37 0.315 15.25 0.375 15.25 0.375 15.000 0.500 14.688 0.656 15.000 0.500 14.310 0.845 13.930 1.035 13.560 1.220 13.560 1.220 12.810 1.595 18 18.000 17.50 0.250 17.37 0.315 17.12 0.440 17.25 0.375 16.876 0.562 16.564 0.718 17.000 0.500 16.120 0.940 15.680 1.160 15.250 1.375 15.250 1.375 14.430 1.785 20 20.000 19.50 0.250 19.25 0.375 19.25 0.375 19.25 0.375 18.814 0.593 18.376 0.812 19.000 0.500 17.930 1.035 17.430 1.285 17.000 1.500 17.000 1.500 16.060 1.970 24 24.000 23.50 0.250 23.25 0.375 23.25 0.375 23.25 0.375 22.626 0.687 22.126 0.937 23.000 0.500 21.560 1.220 20.930 1.535 20.930 1.535 20.930 1.535 19.310 2.345
30 30.000 29.37 0.315 29.00 0.500 29.00 0.500 29.25 0.375 29.250 0.375 29.000 0.500 36 36.000 35.37 0.315 35.00 0.500 35.00 0.500 35.25 0.375 35.250 0.375 35.000 0.500 42 42.000 41.25 0.375 41.250 0.375 41.000 0.500 48 48.000 47.25 0.375 47.250 0.375 47.000 0.500
SCH.
5
ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall
SCH. 10
(LTWALL)
SCH. 20 SCH. 30 STD. SCH. 40 SCH. 60
X STG. SCH. 80 SCH. 100 SCH. 120
SCH. 140 SCH. 180
March, 2000
Ductile Iron Pipe
Standard Classes
Cement Lining
Pipe
Size
(inches)
3 3.96 3.46 0.25 3.40 0.28 3.34 0.31 3.28 0.34 3.22 0.37 3.14 0.41 4 4.80 4.28 0.26 4.22 0.29 4.16 0.32 4.10 0.35 4.04 0.38 3.93 0.44 6 6.90 6.40 0.25 6.34 0.28 6.28 0.31 6.22 0.34 6.16 0.37 6.10 0.40 6.04 0.43 .123/.250
8 9.05 8.51 0.27 8.45 0.30 8.39 0.33 8.33 0.36 8.27 0.39 8.21 0.42 8.15 0.45 10 11.10 10.32 0.39 10.46 0.32 10.40 0.35 10.34 0.38 10.28 0.41 10.22 0.44 10.16 0.47 12 13.20 12.58 0.31 12.52 0.34 12.46 0.37 12.40 0.40 12.34 0.43 12.28 0.46 12.22 0.49
14 15.30 14.64 0.33 14.58 0.36 14.52 0.39 14.46 0.42 14.40 0.45 14.34 0.48 14.28 0.51 16 17.40 16.72 0.34 16.66 0.37 16.60 0.40 16.54 0.43 16.48 0.46 16.42 0.49 16.36 0.52 18 19.50 18.80 0.35 18.74 0.38 18.68 0.41 18.62 0.44 18.56 0.47 18.50 0.50 18.44 0.53 .1875/.375
Outside
Diameter
(inches)
Class 54 Class 55 Class 56Class 50 Class 51 Class 52 Class 53
ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall
Std./Double
Thickness
20 21.60 20.88 0.36 20.82 0.39 20.76 0.42 20.70 0.45 20.64 0.48 20.58 0.51 20.52 0.54 24 25.80 25.04 0.38 24.98 0.41 24.92 0.44 24.86 0.47 24.80 0.50 24.74 0.53 24.68 0.56
30 32.00 31.22 0.39 31.14 0.43 31.06 0.47 30.98 0.51 30.90 0.55 30.82 0.59 30.74 0.63 36 38.30 37.44 0.43 37.34 0.48 37.06 0.62 37.14 0.58 37.40 0.45 36.94 0.68 36.84 0.73 42 44.50 43.56 0.47 43.44 0.53 43.32 0.59 43.20 0.65 43.08 0.71 42.96 0.77 42.84 0.83 .250/.500 48 50.80 49.78 0.51 49.64 0.58 49.50 0.65 49.36 0.72 49.22 0.79 49.08 0.86 48.94 0.93 54 57.10 55.96 0.57 55.80 0.65 55.64 0.73 55.48 0.81 55.32 0.89 55.16 0.97 55.00 1.05
March, 2000
FPS TO GPM CROSS - REFERENCE (Schedule 40)
Nominal
Pipe
(Inches)
1 1.05 2.6989 4.0484 5.3978 6.7473 8.097 9.4462 10.796 12.145 13.490 14.844 16.190 17.540 18.890 20.240 21.590 22.941 24.290
1.25 1.38 4.6620 6.9929 9.3239 11.655 13.99 16.317 18.648 20.979 23.310 25.641 27.970 30.300 32.630 34.960 37.300 39.627 41.958
1.5 1.61 6.3454 9.5182 12.691 15.864 19.04 22.209 25.382 28.555 31.730 34.900 38.070 41.250 44.420 47.590 50.760 53.936 57.109 2 2.07 10.489 15.734 20.979 26.224 31.47 36.713 41.958 47.202 52.450 57.692 62.940 68.180 73.430 78.670 83.920 89.160 94.405
2.5 2.47 14.935 22.402 29.870 37.337 44.80 52.272 59.740 67.207 74.670 82.142 89.610 97.080 104.50 112.00 119.50 126.95 134.41 3 3.07 23.072 34.608 46.144 57.680 69.22 80.752 92.288 103.82 115.40 126.90 138.40 150.00 161.50 173.00 184.60 196.11 207.65
3.5 3.55 30.851 46.276 61.702 77.127 92.55 107.98 123.40 138.83 154.30 169.68 185.10 200.50 216.00 231.40 246.80 262.23 277.66 4 4.03 39.758 59.636 79.515 99.394 119.3 139.15 159.03 178.91 198.80 218.67 238.50 258.40 278.30 298.20 318.10 337.94 357.82 5 5.05 62.430 93.645 124.86 156.07 187.3 218.50 249.72 280.93 312.10 343.36 374.60 405.80 437.00 468.20 499.40 530.65 561.87 6 6.06 89.899 134.85 179.80 224.75 269.7 314.65 359.60 404.55 449.50 494.45 539.40 584.30 629.30 674.20 719.20 764.14 809.09 8 7.98 155.89 233.83 311.78 389.72 467.7 545.61 623.56 701.50 779.40 857.39 935.30 1013.0 1091.0 1169.0 1247.0 1325.1 1403.0
10 10.02 245.78 368.67 491.56 614.45 737.3 860.23 983.12 1106.0 1229.0 1351.8 1475.0 1598.0 1720.0 1843.0 1966.0 2089.1 2212.0
I.D.
INCH
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9
12 11.94 348.99 523.49 697.99 872.49 1047.0 1221.5 1396.0 1570.5 1745.0 1919.5 2094.0 2268.0 2443.0 2617.0 2792.0 2966.5 3141.0 14 13.13 422.03 633.04 844.05 1055.1 1266.0 1477.1 1688.1 1899.1 2110.0 2321.1 2532.0 2743.0 2954.0 3165.0 3376.0 3587.2 3798.2 16 15.00 550.80 826.20 1101.6 1377.0 1652.0 1927.8 2203.2 2478.6 2754.0 3029.4 3305.0 3580.0 3856.0 4131.0 4406.0 4681.8 4957.2
FPS TO GPM: GPM = (PIPE ID)² X VELOCITY IN FPS X 2.45 FPS X .3048 = MPS GPM TO FPS: FPS =
GPM
(ID)² X 2.45
GPM X .0007 = GPD GPM X 3.7878 = LPM
FPS TO GPM CROSS - REFERENCE (Schedule 40)
Nominal
Pipe
(Inches)
18 16.88 697.52 1046.3 1395.0 1743.8 2093.0 2441.3 2790.1 3138.8 3488.0 3836.3 4185.0 4534.0 4883.0 5231.0 5580.0 5928.9 6277.7 20 18.81 866.14 1299.0 1732.0 2165.3 2598.4 3031.5 3464.6 3897.6 4330.7 4763.8 5196.8 5629.9 6063.0 6496.0 6929.1 7362.2 7795.3 24 22.63 1253.7 1880.0 2507.0 3134.1 3761.0 4387.8 5014.6 5641.5 6268.3 6895.1 7522.0 8148.8 8775.6 9402.4 10029 10656 11283 26 25.25 1560.7 2341.0 3121.0 3901.9 4682.2 5462.6 6243.0 7023.4 7803.7 8584.1 9364.5 10145 10925 11706 12486 13266 14047 28 27.25 1817.8 2727.0 3636.0 4544.5 5453.4 6362.3 7271.2 8180.0 9088.9 9997.8 10907 11816 12725 13633 14542 15451 16360 30 29.25 2094.4 3142.0 4189.0 5236.0 6283.2 7330.4 8377.6 9424.9 10472 11519 12566 13614 14661 15708 16755 17803 18850 32 31.25 2390.6 3586.0 4781.0 5976.5 7171.9 8367.2 9562.5 10758 11953 13148 14344 15539 16734 17930 19125 20320 21516 34 33.25 2706.4 4060.0 5413.0 6766.0 8119.2 9472.4 10826 12179 13532 14885 16238 17592 18945 20298 21651 23004 24358 36 35.25 3041.8 4563.0 6084.0 7604.5 9125.4 10646 12167 13688 15209 16730 18251 19772 21292 22813 24334 25855 27376 42 41.25 4165.4 6248.0 8331.0 10414 12496 14579 16662 18744 20827 22910 24992 27075 29158 31241 33323 35406 37489 48 47.99 5637.8 8457.0 11276 14095 16913 19732 22551 25370 28189 31008 33827 36646 39465 42284 45103 47922 50740 54 53.98 7133.1 10700 14266 17833 21399 24966 28532 32099 35665 39232 42798 46365 49931 53498 57065 60631 64198
I.D.
INCH
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9
60 60.09 8839.2 13259 17678 22098 26518 30937 35357 39777 44196 48616 53035 57455 61875 66294 70714 75134 79553 72 72.10 12726 19089 25451 31814 38177 44540 50903 57266 63628 69991 76354 82717 89080 95443 101805 108168 114531 84 84.10 17314 25971 34628 43285 51943 60600 69257 77914 86571 95228 103885 112542 121199 129856 138514 147171 155828
FPS TO GPM: GPM = (PIPE ID)² X VELOCITY IN FPS X 2.45 FPS X .3048 = MPS GPM TO FPS: FPS =
GPM
(ID)² X 2.45
GPM X .0007 = GPD GPM X 3.7878 = LPM
Limited Warranty and Disclaimer
Dynasonics, division of Racine Federated Inc. warrants to the end purchaser, for a period of one year from the date of shipment from the factory, that all new transmitters and transducers manufactured by it are free from defects in materials and workmanship. This warranty does not cover products that have been damaged due to misapplication, abuse, lack of maintenance, or improper installation. Dynasonics’ obligation under this warranty is limited to the repair or replacement of a defective product, at no charge to the end purchaser, if the product is inspected by Dynasonics and found to be defective. Repair or replacement is at Dynasonics’ discretion. A return goods authorization (RGA) number must be obtained from Dynasonics before any product may be returned for warranty repair or replacement. The product must be thoroughly cleaned and any process chemicals removed before it will be accepted for return.
The purchaser must determine the applicability of the product for its desired use and assumes all risks in connection therewith. Dynasonics assumes no responsibility or liability for any omissions or errors in connection with the use of its products. Dynasonics will under no circumstances be liable for any incidental, consequential, contingent or special damages or loss to any person or property arising out of the failure of any product, component or accessory.
All expressed or implied warranties, including the implied warranty of
merchantability and the implied warranty of fitness for a particular purpose or application are expressly disclaimed and shall not apply to any products sold or
services rendered by Dynasonics.
The above warranty supersedes and is in lieu of all other warranties, either expressed or implied and all other obligations or liabilities. No agent or representative has any authority to alter the terms of this warranty in any way.
GENERAL TERMS AND CONDITIONS OF SALES
1. PAYMENT – Terms of payment are effective from the actual date of invoice. If, in the Seller’s
opinion, the financial condition of the Buyer at any time – or any other circumstances – do not justify the incurrence of production costs of shipment on the terms of payment specified, the Seller may require partial or full payment in advance. Payment terms are net 30 days unless otherwise stated on invoice.
2. F.O.B. – All shipments are from Racine, Wisconsin, USA, unless otherwise other stated, and title
transfers to the buyer upon leaving factory.
3. QUOTATION AND PRICES – Quoted prices are firm for 30 days unless stated in the quotation and
are subject to change without notice after expiration of this period.
4. TAXES – Any applicable sales, use, revenue, excise or other taxes not specifically stated in the
quotation are to be remitted by the Buyer directly to the appropriate regulatory agency.
5. WARRANTY – Seller’s standard published warranty in effect at the time of shipment shall apply.
This warranty is exclusive and is in lieu of all other warranties, express, implied, or statutory, including the warranty of merchantability.
6. DELIVERY – The Seller shall not be liable for loss or damage of any kind resulting from delay or
inability to deliver on account of flood, fire, labor trouble, riots, civil disturbances, accidents, acts or orders or regulations of civil or military authorities, shortages of material, or any other causes beyond Seller’s control.
7. PRODUCT CHANGES – In keeping with our continuing policy of product improvement, we reserve
the right to make changes in our products at any time, without incurring an obligation to change, replace or upgrade equipment previously shipped.
8. CANCELLATIONS – An order placed by Buyer and accepted by Seller may be cancelled only with
the Seller’s consent and upon terms that will indemnify the Seller against loss.
9. RESTOCKING CHARGE – On standard equipment, the charge is 25%, provided the equipment is
returned within 30 days in acceptable condition with a RGA number. Restocking charges for special equipment may vary from standard equipment, and will be handled on a case-by-case basis. No returns will be taken after one year.
RETURN OF EQUIPMENT/SALES INFORMATION
CONTACTS AND PROCEDURES
Customer Service/Application Engineer:
If you have a question regarding order status, placing an order, reviewing applications for future purchases, or wish to purchase a new flow meter, please contact our new National Sales and Marketing Headquarters:
DYNASONICS
Division of Racine Federated Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800) 535-3569 or
(262) 639-6770
FAX: (262) 639-2267
Service/Repair Department:
If you already purchased equipment and have an operation problem, require service, or need to schedule field service, please contact our Service Department:
DYNASONICS
Division of Racine Federated Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800) 535-3569 or
(262) 639-6770
FAX: (262) 639-2267
Return Goods Authorization:
When returning equipment, it is necessary for you to contact our Service Department at (800) 535-3569 or (262) 639-6770 to obtain an RGA number for the authority and proper tracking of your material and its prompt inspection and return. The RGA number should be noted on the outside of the box. All returns of equipment go to the following address:
DYNASONICS
Division of Racine Federated Inc.
8635 Washington Avenue
Racine, WI 53406
Attn: RGA #
8635 WASHINGTON AVENUE
RACINE, WI 53406
TOLL-FREE IN NORTH AMERICA TEL: (800) 535-3569 FAX: (800) 732-8354 TEL: (262) 639-6770 FAX: (262) 639-2267
URL: www.dynasonics.com
DYNASONICS is a registered trademark of Racine Federated Inc. Ultem is a registered trademark of General Electric Co. Vespel is a registered trademark of E.I. DuPont de Nemours and Company. National Electric Code is a registered trademark of NFPA. UL is a registered trademark of Underwriters Laboratories.
© 2008 Racine Federated Inc.
All rights reserved.
Printed in USA
D902/903 O&M REV 10/08
Loading...