Dynasonics 901 User Manual

Series 901
Enhanced Ultrasonic Flow Meter
Operations & Maintenance
Manual
REV 4/02
Location
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the D901/M instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
1. TRANSDUCER LOCATION
A. Determine the appropriate mounting location for
the transducers by referring to Figure 1.
Receiving
Transducer
Transmitting
Transducer
Solids Bearing or Aerated Liquids Clean Liquids
Pipe Preparation and Mounting
90° Elbow
Fluid Velocity ∝ Γ1Γ2
Figure 1 Transducer Locations
2. PIPE PREPARATION AND TRANSDUCER MOUNTING
A. The piping surface, where the transducers are to
be mounted, needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Connect the mounting straps around the pipe.
Leave the strap loose enough to slip the transducers underneath.
C. Apply a liberal amount of silicone rubber
(enclosed) onto the transducer faces and the prepared areas of the pipe.
QUICK-START OPERATING INSTRUCTIONS
D. Place each transducer under the mounting strap,
180° apart on the pipe. Ensure that the transducer cables are facing the same direction. See Figure 2.
Connections
Receiving
Transducer
Transmitting
Transducer
Figure 2 Transducer
E. Route the transducer cable back to the transmitter,
avoiding locations near high voltage supply wires.
3. TRANSDUCER CONNECTION
A. Do not
transducers.
B. Connect the spade terminals to the appropriate
terminal block within the transmitter.
4. INITIAL SETTINGS AND POWER UP
attempt to add additional cable to the
A. Set the SENSITIVITY control to - 2. B. Apply AC power. The POWER indicator will
Startup
illuminate.
C. If the pipe is full of a flowing liquid, the SIGNAL
STRENGTH meter will indicate and the READ indicator will illuminate.
D. Adjust the SENSITIVITY control so that the right-most
green LED just comes ON.
E. The default display indicates fluid velocity as either
FPS or MPS. Refer to the appropriate place in this manual for specific features and options.
TABLE OF CONTENTS
Part 1 - Introduction
Part 2 - Installation
Quick-Start Operating Instructions
Introduction General Applications Model Matrix
Product Specifications
Bench Test Procedure
Installation Transducer Mounting Locations
Pages
1-2
5 5 6
7-8
9
10-12
Pipe Preparation Transducer Mounting Transmitter Mounting Electrical Connections
Part 3 - Startup and Configuration
Instrument Startup and Configuration Initial Settings Modes of Operation Pipe I.D. Input Full Scale Input Totalizer Exponent Input Engineering Units Input
13 13-15 16-17 17-19
20
21
22
23
24
25
TABLE OF CONTENTS
Part 4 - Troubleshooting
Instrument Startup and Configuration CAL. Constant Input Display Damping System Damping TEST Diagnostic Key System and Totalizer RESET Totalizer Reset
Trouble Shooting Guide
Appendices Face Plate Drawing Intrinsically Safe Installation
Pages
26
27
27
27
28
28
29-30
31+
High-Temperature Transducers Clean Liquid Installation Guide Multiple Unit Cross-talk Pipe Dimension Chart: Cast Iron Pipe Dimension Chart: ST, SS, PVC Velocity to Volumetric Conversion Statement of Warranty Customer Service
PART 1 - INTRODUCTION
General
Application Versatility
The D901/M ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non-contacting, clamp-on type, which will provide benefits of non-fouling operation and ease of installation.
The flow meter operates by transmitting an ultrasonic sound from its transmitting transducer through the pipe wall into the flowing liquid. The sound will be reflected by suspended particles or bubbles within the liquid and recorded by the receiving transducer. A frequency shift (Doppler effect) will occur that is directly related to the speed of the moving particle or bubble. This shift in frequency is interpreted by the instrument and converted to various user defined measuring units.
A unique feature of this product is that it employs a proprietary digital filtering system and recognition circuit. This feature allows the instrument to measure fluid velocities of clean liquids if the transducers are mounted downstream from a 90° elbow. The non-symmetrical hydraulic turbulence which occurs downstream of an elbow is captured, linearized and can be displayed as liquid velocity and volume. This capability is not available in conventional Doppler technology.
The D901/M flow meter can be successfully applied on a wide range of metering applications. The simple to program transmitter allows the standard product to be used on pipe sizes ranging from 1 - 120 inch [ 25 - 3050 mm ] pipe I.D. (With the small pipe transducer option, the pipe size range is 0.25 - 1 inch [ 6 - 25 mm]). A variety of liquid applications can be accommodated: raw sewage, reclaimed water, river water, plant effluent, mining slurries, sludge, etc. Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Standard transducers are rated to 250°F [121°C]. Optional high temperature transducers are rated to operate to 400°F [204°C].
PART 1 - INTRODUCTION
User Safety
Battery Backup
Product Identification
The D901/M employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 9 Vdc and the metal work is electrically connected to Earth Ground. The display face swings open to allow access to user connections.
A rechargeable nickel-cadmium battery on the back of the display board retains all user-entered configuration values in memory for several years (at 25°C), even if power is lost or turned off. The ten year battery is continually trickle charged whenever line power is applied. A completely discharged battery recharges fully after 48 hours of instrument operation.
The serial number and complete model number of your D901/M is located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasoncs’ Customer Service Department with this information.
Product Matrix
PART 1 - SPECIFICATIONS
Ambient Conditions
Display
Transducer to Transmitter Distance
Power Requirements
Pipe Sizes
Transmitter - -22 to 160°F [ - 30 to 70 °C], 0-95% relative humidity, non-condensing.
Transducers - - 40° to 250°F [ -40° to 121° C] Standard. Optional: - 40° to 400°F [ - 40° to 204°C]
2 line x 20 character alphanumeric LCD, back lit. Digit height 0.2 inches [ 5 mm]
Standard: 20 feet [ 6.09 meters ], flexible armored conduit. Optional lengths to 300 feet [ 100 meters ]
115/230 VAC 50/60 Hz ± 10%. Optional: 100/200 VAC 50/60 Hz ± 10% and 12VDC. Power consumption less than 12 VA.
1 - 120 inches [ 25 - 3050 mm ] Pipe I.D. Optional: 0.25 - 1 inch [6 – 25 mm ], Small
Pipe Transducer
Velocity
Measuring Units
Indicators
Liquid Requirements
0.5 - 20 FPS [ 0.15 - 6.08 MPS]
FPS, GPM, MGD [ MPS, LPM, M3/Hr ]
Power, Signal Strength, Fault, Over-range, Read, Flow Analyzer
25 ppm of 30 micron* suspended solids or bubbles.
* Less than this minimum will require transducer mount downstream of a 90°
PART 1 - SPECIFICATIONS
Outputs
Non-linearity
Sensitivity
Repeatability
Response Time
Enclosure
Size
4-20 mA, 600 Ohms max., Isolated. 12 Vdc pulse, 50 mS duration, 0-0.15 Hz to
0-2.5 Hz, user adjustable. ±2 % Full Scale
0.4 % of Full Scale
±0.4% of Full Scale
5-50 seconds, user configured adjustable, to 90% of value, step change in flow.
NEMA 4X, [IP-65] Fiberglass w/SS hardware.
13.5H x 11.3W x 5.60D inches [343H x 287W x 141D mm]
Mounting
Weather Shield
Net Weight
Wall mount
Optional weather visor; Dynasonics P.N. D003-899-001
15 lbs. [ 6.8 Kg ]
PART 2 - PRE-INSTALLATION CHECKOUT
Unpacking
Functional Test
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The D901/M flow meter can be checked for basic functionality using the following Bench Test procedure. It is recommended that this operation be performed before installing the transducers or transmitter permanently.
Procedure:
1. Open the D901/M transmitter enclosure and the inner display door.
2. Connect the transducer cable terminals to the corresponding terminal block locations within the transmitter. See Figure 3.
3. Set the transmitter SENSITIVITY control [located on the display door] to -2.
4. Apply power.
5. Hold the transducers, the flat sides facing each other, approximately 6-8 inches [150-200 mm] apart.
6. Move the transducers towards and away from each other 1 inch [25mm] for several cycles at approximately 1 second interval.
7. If unit is functioning properly, the READ LED will illuminate and the rate display will indicate flow readings.
Figure 3
Bench Test is Complete
PART 2 - TRANSDUCER INSTALLATION
Transducer Mounting Considerations
Step A - Mounting Locations
CASE 1:
The transducers that are utilized by the D901/M contain piezo electric crystals for transmitting and receiving ultrasonic sound energy through the pipe wall.
The transducers can be mounted in three different configurations. The selection of the proper configuration is dependent on the liquid to be measured characteristics.
The three liquid characteristics, which will affect mounting location and orientation, are as follows:
CASE 1: Liquid that contains 25 to 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
CASE 2: Liquid that contains greater than 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
CASE 3: Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration and suspended solids and aeration content which is smaller than 30 microns.
Liquid that contains 25 to 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
Select a transducer mounting location with adequate straight runs of pipe, both upstream and downstream, to achieve stable readings. Examples of minimum upstream and downstream requirements are included in Table 1.
Mount the transducers 180° apart and facing each other on the pipe. If the pipe is horizontal, the preferred mounting orientation is 3 and 9 o’clock, with 12 o’clock being the top of the pipe. Orientation on vertical pipes does not matter. See Figure 4.
PART 2 - TRANSDUCER INSTALLATION
1
2
3 4
5
Table 1
1
Example Upstream Pipe
Diameters
* ** 1 24 4 2 14 3 3 9 3 4 8 3 5 8 3 6 24 4
Downstream
Pipe Diameters
6
1
The D901/M system will provide repeatable measurements on piping systems that do not
meet these requirements, but the accuracy
Liquid that contains greater than 10,000 PPM [1%] of
CASE 2:
30 micron or greater suspended solids or aeration.
may be influenced to various degrees.
Top View of Pipe
Figure 4
PART 2 - TRANSDUCER INSTALLATION
The mounting location and straight pipe requirements for CASE 2 liquid characteristics are the same as those describe in CASE 1. The difference will be in the location of the transducers on the pipe. As the discontinuities (suspended solids or aeration) reach a level of approximately 1% or 10,000 PPM, sound can no longer be reliably transmitted through the liquid as it has a tendency to scatter and absorb into the high concentration of
CASE 3:
Figure 5
discontinuity. To compensate for this, the D901/M transducers can be located on the same region of the pipe. In a horizontal pipe, mount the transducers at 2 o’clock and 4 o’clock positions. (Assuming 12 o’clock as the top of the pipe.) See Figure 5.
Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration. Or, liquid that contains solids or aeration which is smaller than 30 microns.
The transducers will be mounted 1 to 3 pipe diameters downstream from a 90° elbow. The orientation of the transducers on the pipe will be 180° apart and facing each other and 90° out of the plane of the elbow. See Figure 6.
PART 2 - TRANSDUCER INSTALLATION
STEP B - PIPE SURFACE PREPARATION
STEP C - TRANSDUCER MOUNTING
Figure 6
Before the transducer heads are bonded to the pipe surface, an area slightly larger than the flat surface of the transducer must be cleaned to bare metal on the pipe. (Plastic pipes do not require preparation beyond removal of paint.) Remove all scale, rust and paint. Thoroughly dry and degrease the mounting surfaces.
NOTE: Small pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception.
After selecting the applicable mounting location and preparing the piping surface as detailed in A and B, the transducer can be mounted to the pipe.
To assure an acoustically conductive path between the transducer face and the prepared piping surface, a coupling compound is employed. Enclosed with the D901/ M system is tube of Dow Corning RTV-732. This couplant is satisfactory for permanently mounting the transducers to the pipe. If the installation is temporary (less than a few days), Dynasonics recommends utilizing a silicone-based grease such as Dow Corning 111. The grease chosen must be rated to not flow at the temperature of the pipe.
Loading...
+ 31 hidden pages