Dynasonics 901 User Manual

Series 901
Enhanced Ultrasonic Flow Meter
Operations & Maintenance
Manual
REV 4/02
Location
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the D901/M instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation only. If specific instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
1. TRANSDUCER LOCATION
A. Determine the appropriate mounting location for
the transducers by referring to Figure 1.
Receiving
Transducer
Transmitting
Transducer
Solids Bearing or Aerated Liquids Clean Liquids
Pipe Preparation and Mounting
90° Elbow
Fluid Velocity ∝ Γ1Γ2
Figure 1 Transducer Locations
2. PIPE PREPARATION AND TRANSDUCER MOUNTING
A. The piping surface, where the transducers are to
be mounted, needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Connect the mounting straps around the pipe.
Leave the strap loose enough to slip the transducers underneath.
C. Apply a liberal amount of silicone rubber
(enclosed) onto the transducer faces and the prepared areas of the pipe.
QUICK-START OPERATING INSTRUCTIONS
D. Place each transducer under the mounting strap,
180° apart on the pipe. Ensure that the transducer cables are facing the same direction. See Figure 2.
Connections
Receiving
Transducer
Transmitting
Transducer
Figure 2 Transducer
E. Route the transducer cable back to the transmitter,
avoiding locations near high voltage supply wires.
3. TRANSDUCER CONNECTION
A. Do not
transducers.
B. Connect the spade terminals to the appropriate
terminal block within the transmitter.
4. INITIAL SETTINGS AND POWER UP
attempt to add additional cable to the
A. Set the SENSITIVITY control to - 2. B. Apply AC power. The POWER indicator will
Startup
illuminate.
C. If the pipe is full of a flowing liquid, the SIGNAL
STRENGTH meter will indicate and the READ indicator will illuminate.
D. Adjust the SENSITIVITY control so that the right-most
green LED just comes ON.
E. The default display indicates fluid velocity as either
FPS or MPS. Refer to the appropriate place in this manual for specific features and options.
TABLE OF CONTENTS
Part 1 - Introduction
Part 2 - Installation
Quick-Start Operating Instructions
Introduction General Applications Model Matrix
Product Specifications
Bench Test Procedure
Installation Transducer Mounting Locations
Pages
1-2
5 5 6
7-8
9
10-12
Pipe Preparation Transducer Mounting Transmitter Mounting Electrical Connections
Part 3 - Startup and Configuration
Instrument Startup and Configuration Initial Settings Modes of Operation Pipe I.D. Input Full Scale Input Totalizer Exponent Input Engineering Units Input
13 13-15 16-17 17-19
20
21
22
23
24
25
TABLE OF CONTENTS
Part 4 - Troubleshooting
Instrument Startup and Configuration CAL. Constant Input Display Damping System Damping TEST Diagnostic Key System and Totalizer RESET Totalizer Reset
Trouble Shooting Guide
Appendices Face Plate Drawing Intrinsically Safe Installation
Pages
26
27
27
27
28
28
29-30
31+
High-Temperature Transducers Clean Liquid Installation Guide Multiple Unit Cross-talk Pipe Dimension Chart: Cast Iron Pipe Dimension Chart: ST, SS, PVC Velocity to Volumetric Conversion Statement of Warranty Customer Service
PART 1 - INTRODUCTION
General
Application Versatility
The D901/M ultrasonic flow meter is designed to measure the fluid velocity of liquid within closed conduit. The transducers are a non-contacting, clamp-on type, which will provide benefits of non-fouling operation and ease of installation.
The flow meter operates by transmitting an ultrasonic sound from its transmitting transducer through the pipe wall into the flowing liquid. The sound will be reflected by suspended particles or bubbles within the liquid and recorded by the receiving transducer. A frequency shift (Doppler effect) will occur that is directly related to the speed of the moving particle or bubble. This shift in frequency is interpreted by the instrument and converted to various user defined measuring units.
A unique feature of this product is that it employs a proprietary digital filtering system and recognition circuit. This feature allows the instrument to measure fluid velocities of clean liquids if the transducers are mounted downstream from a 90° elbow. The non-symmetrical hydraulic turbulence which occurs downstream of an elbow is captured, linearized and can be displayed as liquid velocity and volume. This capability is not available in conventional Doppler technology.
The D901/M flow meter can be successfully applied on a wide range of metering applications. The simple to program transmitter allows the standard product to be used on pipe sizes ranging from 1 - 120 inch [ 25 - 3050 mm ] pipe I.D. (With the small pipe transducer option, the pipe size range is 0.25 - 1 inch [ 6 - 25 mm]). A variety of liquid applications can be accommodated: raw sewage, reclaimed water, river water, plant effluent, mining slurries, sludge, etc. Because the transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Standard transducers are rated to 250°F [121°C]. Optional high temperature transducers are rated to operate to 400°F [204°C].
PART 1 - INTRODUCTION
User Safety
Battery Backup
Product Identification
The D901/M employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 9 Vdc and the metal work is electrically connected to Earth Ground. The display face swings open to allow access to user connections.
A rechargeable nickel-cadmium battery on the back of the display board retains all user-entered configuration values in memory for several years (at 25°C), even if power is lost or turned off. The ten year battery is continually trickle charged whenever line power is applied. A completely discharged battery recharges fully after 48 hours of instrument operation.
The serial number and complete model number of your D901/M is located on the inside of the transmitter’s front cover. Should technical assistance be required, please provide the Dynasoncs’ Customer Service Department with this information.
Product Matrix
PART 1 - SPECIFICATIONS
Ambient Conditions
Display
Transducer to Transmitter Distance
Power Requirements
Pipe Sizes
Transmitter - -22 to 160°F [ - 30 to 70 °C], 0-95% relative humidity, non-condensing.
Transducers - - 40° to 250°F [ -40° to 121° C] Standard. Optional: - 40° to 400°F [ - 40° to 204°C]
2 line x 20 character alphanumeric LCD, back lit. Digit height 0.2 inches [ 5 mm]
Standard: 20 feet [ 6.09 meters ], flexible armored conduit. Optional lengths to 300 feet [ 100 meters ]
115/230 VAC 50/60 Hz ± 10%. Optional: 100/200 VAC 50/60 Hz ± 10% and 12VDC. Power consumption less than 12 VA.
1 - 120 inches [ 25 - 3050 mm ] Pipe I.D. Optional: 0.25 - 1 inch [6 – 25 mm ], Small
Pipe Transducer
Velocity
Measuring Units
Indicators
Liquid Requirements
0.5 - 20 FPS [ 0.15 - 6.08 MPS]
FPS, GPM, MGD [ MPS, LPM, M3/Hr ]
Power, Signal Strength, Fault, Over-range, Read, Flow Analyzer
25 ppm of 30 micron* suspended solids or bubbles.
* Less than this minimum will require transducer mount downstream of a 90°
PART 1 - SPECIFICATIONS
Outputs
Non-linearity
Sensitivity
Repeatability
Response Time
Enclosure
Size
4-20 mA, 600 Ohms max., Isolated. 12 Vdc pulse, 50 mS duration, 0-0.15 Hz to
0-2.5 Hz, user adjustable. ±2 % Full Scale
0.4 % of Full Scale
±0.4% of Full Scale
5-50 seconds, user configured adjustable, to 90% of value, step change in flow.
NEMA 4X, [IP-65] Fiberglass w/SS hardware.
13.5H x 11.3W x 5.60D inches [343H x 287W x 141D mm]
Mounting
Weather Shield
Net Weight
Wall mount
Optional weather visor; Dynasonics P.N. D003-899-001
15 lbs. [ 6.8 Kg ]
PART 2 - PRE-INSTALLATION CHECKOUT
Unpacking
Functional Test
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The D901/M flow meter can be checked for basic functionality using the following Bench Test procedure. It is recommended that this operation be performed before installing the transducers or transmitter permanently.
Procedure:
1. Open the D901/M transmitter enclosure and the inner display door.
2. Connect the transducer cable terminals to the corresponding terminal block locations within the transmitter. See Figure 3.
3. Set the transmitter SENSITIVITY control [located on the display door] to -2.
4. Apply power.
5. Hold the transducers, the flat sides facing each other, approximately 6-8 inches [150-200 mm] apart.
6. Move the transducers towards and away from each other 1 inch [25mm] for several cycles at approximately 1 second interval.
7. If unit is functioning properly, the READ LED will illuminate and the rate display will indicate flow readings.
Figure 3
Bench Test is Complete
PART 2 - TRANSDUCER INSTALLATION
Transducer Mounting Considerations
Step A - Mounting Locations
CASE 1:
The transducers that are utilized by the D901/M contain piezo electric crystals for transmitting and receiving ultrasonic sound energy through the pipe wall.
The transducers can be mounted in three different configurations. The selection of the proper configuration is dependent on the liquid to be measured characteristics.
The three liquid characteristics, which will affect mounting location and orientation, are as follows:
CASE 1: Liquid that contains 25 to 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
CASE 2: Liquid that contains greater than 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
CASE 3: Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration and suspended solids and aeration content which is smaller than 30 microns.
Liquid that contains 25 to 10,000 PPM [1%] of 30 micron or larger suspended solids or aeration.
Select a transducer mounting location with adequate straight runs of pipe, both upstream and downstream, to achieve stable readings. Examples of minimum upstream and downstream requirements are included in Table 1.
Mount the transducers 180° apart and facing each other on the pipe. If the pipe is horizontal, the preferred mounting orientation is 3 and 9 o’clock, with 12 o’clock being the top of the pipe. Orientation on vertical pipes does not matter. See Figure 4.
PART 2 - TRANSDUCER INSTALLATION
1
2
3 4
5
Table 1
1
Example Upstream Pipe
Diameters
* ** 1 24 4 2 14 3 3 9 3 4 8 3 5 8 3 6 24 4
Downstream
Pipe Diameters
6
1
The D901/M system will provide repeatable measurements on piping systems that do not
meet these requirements, but the accuracy
Liquid that contains greater than 10,000 PPM [1%] of
CASE 2:
30 micron or greater suspended solids or aeration.
may be influenced to various degrees.
Top View of Pipe
Figure 4
PART 2 - TRANSDUCER INSTALLATION
The mounting location and straight pipe requirements for CASE 2 liquid characteristics are the same as those describe in CASE 1. The difference will be in the location of the transducers on the pipe. As the discontinuities (suspended solids or aeration) reach a level of approximately 1% or 10,000 PPM, sound can no longer be reliably transmitted through the liquid as it has a tendency to scatter and absorb into the high concentration of
CASE 3:
Figure 5
discontinuity. To compensate for this, the D901/M transducers can be located on the same region of the pipe. In a horizontal pipe, mount the transducers at 2 o’clock and 4 o’clock positions. (Assuming 12 o’clock as the top of the pipe.) See Figure 5.
Liquid that contains fewer than 25 PPM of 30 micron or larger suspended solids or aeration. Or, liquid that contains solids or aeration which is smaller than 30 microns.
The transducers will be mounted 1 to 3 pipe diameters downstream from a 90° elbow. The orientation of the transducers on the pipe will be 180° apart and facing each other and 90° out of the plane of the elbow. See Figure 6.
PART 2 - TRANSDUCER INSTALLATION
STEP B - PIPE SURFACE PREPARATION
STEP C - TRANSDUCER MOUNTING
Figure 6
Before the transducer heads are bonded to the pipe surface, an area slightly larger than the flat surface of the transducer must be cleaned to bare metal on the pipe. (Plastic pipes do not require preparation beyond removal of paint.) Remove all scale, rust and paint. Thoroughly dry and degrease the mounting surfaces.
NOTE: Small pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception.
After selecting the applicable mounting location and preparing the piping surface as detailed in A and B, the transducer can be mounted to the pipe.
To assure an acoustically conductive path between the transducer face and the prepared piping surface, a coupling compound is employed. Enclosed with the D901/ M system is tube of Dow Corning RTV-732. This couplant is satisfactory for permanently mounting the transducers to the pipe. If the installation is temporary (less than a few days), Dynasonics recommends utilizing a silicone-based grease such as Dow Corning 111. The grease chosen must be rated to not flow at the temperature of the pipe.
PART 2 - TRANSDUCER INSTALLATION
PROCEDURE:
1. Select the proper number of transducer straps to allow a complete strap to go around the circumference of the pipe. See Table 2 - The straps can be connected together to make a continuous length.
Table 2 Pipe Sizes Straps Required
1” to 9” 10” to 19” 20” to 29” 30” to 39”
2. Wrap the strap around the pipe in the area where the transducers are to be mounted. Leave the strap loose enough to allow the transducers to be placed underneath. If multiple straps are being used, it can be beneficial to wrap electrical tape around all but one strap connection to secure the strap worm screws in place.
3. Spread an even layer of coupling compound, approximately 1/8 inch [3mm] thick, to the prepared transducer mounting areas of the pipe. Utilize Dow 732 for permanent mounting or Dow 111 for temporary mounting,
25 to 225 mm 1 250 to 480 mm 2 500 to 740 mm 3 760 to 1000 mm 4
4. Spread an even layer of coupling compound, approximately 1/8 inch [ 3mm ] thick, to the flat face of the two transducers.
5. Place each transducer under the strap with the flat face positioned towards the pipe. The notch on the back of the transducer will provide a mounting surface for the strap. The transducer cables must be facing in
PART 2 - TRANSDUCER INSTALLATION
the same direction for proper operation. See Figure 7. NOTE: Large pipes may require two people for this procedure.
6. Tighten the strap tight enough to hold the transducers in place, but not so tight that all of the couplant squeezes out of the gap between the transducer face and pipe. Ensure that the transducers are squarely aligned on the pipe.
Figure 7
7. Route the transducer cable back to the transmitter mounting area avoiding high voltage cable trays and conduits. Do not attempt to add additional cable to the factory supplied transducer cable. The D901/M processes very small signals, so the cable shield must be continuous. Excess cable may be coiled to take up extra length.
8. If the transducers are to be permanently mounted using Dow 732, the RTV must be completely cured before proceeding to Instrument Start up. Ensure that no relative motion between the transducer and pipe occurs during the 24 hour curing process. If Dow 111 grease was used for temporary operation of the D901/ M system, proceed with the Instrument Start-up procedures.
Transducer Installation is complete
PART 2 - TRANSMITTER INSTALLATION
Transmitter Installation
The enclosure should be mounted in an area that is convenient for servicing, calibration or for observation of the LCD readout.
1. Locate the transmitter within the length of transducer cable that was supplied with the D901/M system. If this is not possible, do not attempt to add additional cable to the transducer. Contact the Dynasonics factory to coordinate an exchange for the proper cable length. Transducer cables that are up to 300 feet [90 meters] are available.
2. Mount the D901/M transmitter in a location that is:
Figure 8
PART 2 - TRANSMITTER INSTALLATION
ELECTRICAL CONNECTIONS
Where little vibration exist. Protected from falling corrosive fluids. Within ambient temperature limits - 22 to 160°F [30 to
70°C]
Out of direct sunlight. A sun and weather shield is
available from Dynasonics. P.N. D003-899-001. Direct sunlight may increase temperatures within the transmitter to above maximum limit.
3. Mounting: Refer to Figure 8 for enclosure and mounting dimension details. Ensure that enough room is available to allow for door swing, maintenance and conduit entrances. Secure the enclosure to a flat surface with four appropriate fasteners.
4. Conduit holes. Conduit hubs should be used where cables enter the enclosure. Holes not used for cable entry should be sealed with plugs.
NOTE: Use NEMA 4 [ IP65 ] rated fittings plugs to maintain the water tight integrity of the enclosure. Generally, the left conduit hole (viewed from front) is used for line power; the right conduit hole for transducer connections.
5. If additional holes are required, (analog outputs, etc.) drill the appropriate size hole in the enclosure’s bottom. Use extreme care not to run the drill bit into the wiring or circuits cards.
To access terminal strips for electronic connectors, loosen the two screws in the enclosure door and open the door. Loosen the two thumb-screws on the inner display door and open the door.
1. Guide the transducer terminations through the transmitter conduit hole located on the right side of the
PART 2 - ELECTRICAL INSTALLATION
Transducer Connections
Figure 9
4-20 mA Output
Pulse Output
enclosure. Secure the transducer cable with the supplied conduit nut.
2. The terminals on the transducer cable are coded with wire markings. Connect the appropriate wires to the corresponding screw terminals in the transmitter. See
Figure 9.
NOTE: The transducer cable carries low level signals.
Do not attempt to add additional cable to the factory supplied transducer cable. If additional cable is required, contact the Dynasonics factory to arrange for an exchange transducer with the appropriate length of cable. Cables to 300 feet [ 90 meters ] are available.
The 4-20mA output is proportional to the flow rate measuring scale and can drive a load of up to 600 ohms. The output is isolated from earth ground and circuit low. Connect the load to the 4-20 mA screw terminals on the transmitter terminal block, matching polarity as indicated.
NOTE: An additional hole in the transmitter enclosure is required for outputs. Drill the hole in the the enclosure bottom taking care not to drive the drill bit into wiring or the circuit boards with the transmitter.
The pulse output is proportional to the flow rate measuring scale. This output may be used one of two ways:
To drive a 12V logic device. To drive a low impedance, 12V device. Minimum
resistance 50 ohms.
The pulse output is adjustable from a range of 0 - 600 Hz to 0 - 10kHz via control R29 [CTR] located on the left side of the signal processing PCB in the back of the enclosure. The pulse width is fixed at 50 µ seconds. CTR “ - ” represents circuit low. CTR “ + “ represents 12 Vdc pulse output.
PART 2 - ELECTRICAL INSTALLATION
Optional 0 - 1 mA Output
Line Power
Figure 10
If the 0-1mA output has been installed on the D901/M, the connections are available on the screw terminal block in the transmitter. Connect a load of not more than 4 K ohms to the terminals. Adjust control R20 [1 mA] to fine tune the output to match the load impedance.
Connect line power to the screw terminals marked AC, AC and GND in the transmitter. See Figure 10. Utilize the conduit hole on the left side of the enclosure for this purpose. Use wiring practices that conform to local codes (National Electric Code Hand book in the USA). Use only the standard three wire connection. The ground terminal grounds the instrument, which is mandatory for safe operation.
CAUTION: Any other wiring method may be unsafe or cause improper operation of the instrument.
It is recommended not to run line power with other signal wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line power. Do not operate this unit on circuits with noisy components (i.e. Fluorescent lights, relays, compressors, variable frequency drives, etc.).
If this option is installed, the D901/M can be operated from a 12 Vdc source, as long as it is capable of supplying 1 Ampere. Observe proper polarity.
Optional 12 Vdc power
PART 3 - STARTUP AND CONFIGURATION
Before Starting the Instrument
Instrument Startup
Sensitivity Adjustment Control
Note: The D901/M flow meter system requires a full pipe
of liquid before a successful startup can be completed. Do not attempt to make adjustments or change configurations until a full pipe is verified.
Note: If Dow 732 RTV was utilized to couple the transducers to the pipe, the adhesive must fully cure before power is applied to the instrument. Dow 732 requires 24 hours to cure satisfactorily. If Dow 111 silicone grease was utilized as a couplant, the curing time is not required.
Procedure:
1. Verify that all wiring is properly connected and routed.
2. Set the SENSITIVITY Control to -2. This control is located on the inner door.
3. Apply power. The POWER indicator will illuminate.
4. Adjust the SENSITIVITY control so that the right-most LED on the SIGNAL STRENGTH bar meter just illuminates.
Note: It is undesirable to adjust the SENSITIVITY control to a position higher than necessary, as ambient noise can also be amplified. This noise can cause false readings to occur.
5. If the pipe is full of a flowing liquid, the READ indicator will illuminate and the display will begin reading fluid velocity as FPS (Feet per Second) or MPS (Meters per Second). It is normal to have low SIGNAL STRENGTH and FAULT indication at ZERO flow.
6. If a SIGNAL STRENGTH reading in the green portion of the bar meter could not be obtained, refer to the troubleshooting section of this manual.
After a successful flow meter installation and startup
PART 3 - STARTUP AND CONFIGURATION
Keypad Configurations
Modes of Operation
(covered in the previous sections of this manual) the D901/M can be keypad configured to provide select engineering unit readings of flow and a scaled 4-20mA output. Configuration inputs are made via the keypad and are stored by the microprocessor. The entries are retained by the flow meter’s backup battery in the event of power failure. If fluid velocity readings, FPS or MPS, are the only required measurement keypad configuration is not required.
The RUN/ENT key toggles the flow meter between the two modes of operation.
RUN Mode: This is the primary operating mode of the flow meter. The meter is in RUN mode when the readout is displaying flow as velocity (FPS, MPS) OR volume (GPM, LPM, LPS). In RUN mode the outputs are active and transmitting signals proportional to flow rate.
ENTRY Mode: This mode is used to view or change the configuration of the flow meter. When the D901/M ships from the Dynasonics factory, it contains the following Default configuration:
Each of these parameters may be viewed and/or modified
Default Configuration
PARAMETER US METRIC ID UNITS DAMP Volume/PLS FULL SCALE CAL
in the ENTRY Mode. Changes are processed when the RUN/ENT is pressed and the meter returns to RUN MODE. In ENTRY Mode flow totalization is suspended and process outputs are frozen at the last value recorded.
1 Inch 25 mm
1 [FPS] 1 [MPS]
1 Sec 1 Sec
φ φ
20 FPS 6.08 MPS
100% 100%
PART 3 - STARTUP AND CONFIGURATION
Pipe I.D. Input
The ID key allows the entry of a pipe’s Internal Diameter. The D901/M utilizes the I.D. constant to process volumetric flow rates such as GPM (Gallons per Minute) or LPM (Liters per Minute). The entry is made as either inches or mm, dependent on whether the unit is configured as U.S. units or Metric units.
Press the I.D. key from the ENTRY MODE. The display will show
This is the present I.D. constant. Enter a new I.D. based on information obtained from the pipe manufacturer, a physical measurement or a pipe chart. Some common pipe sizes and dimensions are located on a series of charts located in the Appendix of this manual. The acceptable input range for the I.D. constant is shown in Table 3.
I.D. US METRIC Max Min *
* Pipe sizes less than 1 inch [ 25 mm ] require a Small Pipe Transducer.
Note: If a decimal value of less than 1 is to be entered, enter 0 . X X . The zero must precede the decimal value.
Note: If an entered value is out of the acceptable range of the instrument, an UNDER! or OVER! indication will be displayed. The meter will not allow any other entries to be made until a legitimate value is entered.
INSIDE DIAMETER
Table 3
120 Inches 3050 mm
0.25 Inches 6 mm
PART 3 - STARTUP AND CONFIGURATION
Full Scale Input
Important!
Volume to Velocity Conversion
The FULL SCALE key allows the entry of the highest anticipated fluid velocity. The entry is made as either FPS (Feet per Second) or MPS (Meters per Second), dependent on whether the unit is configured as US units or Metric units. The FULL SCALE input is used by the D901/M microprocessor to scale the 4-20mA output and adjust the resolution of the flow rate display.
Acceptable input range for the FULL SCALE constant is shown in Table 4.
I.D. US METRIC Max Min *
* Note: FULL SCALE values below 1.5 FPS [ 0.5 MPS] are not recommended.
Note: If a decimal value is to be entered, enter 0 The zero must precede the decimal value and no more than two numbers should be entered after the decimal value.
Note: If an entered value is out of the acceptable range of the instrument, a RANGE! indication will be displayed. The meter will not allow any additional entries to be made until a legitimate value is entered.
Two useful equations which relate volumetric flow in round pipes to flow velocity are as follows:
FPS = U.S. GPM X 0.409 ID2 (inches)
MPS = LPM X 21.23 ID
Table 4
40 FPS 8 MPS n/a n/a
2
(mm)
. X X .
PART 3 - STARTUP AND CONFIGURATION
Totalizer Exponent Input
The VOL. PULSE key allows the entry of a totalizer exponent. This feature is useful for accommodating a large accumulated flow. The exponent is a “ X 10 “ multiplier, which can be from 0 (no multiplier) to 2 (X 100). For example, to totalize in GAL X 100, a VOL. PULSE value of 2 would be used (10² or 100).
Acceptable input range for the VOL. PULSE constant is shown in Table 5.
I.D. US METRIC Max Min *
* Note: If an entry greater than 2 is attempted, the meter will display OVER!. If a non- whole number value is attempted, the meter will display RANGE!. A legitimate value will need to be entered.
After a VOL. PULSE value is entered, the display will reflect the unit as 0=10º=X1, 10¹=X10 and 2=10²=X100.
Table 6 illustrates various codes and their display results.
Table 5
2 2 0 0
Table 6
VOL. PULSE CODE
0 1 2
ENG. NOTATION DISPLAY MAXIMUM
10E0 999,999 10E1 999,999 10E2 999,999
PART 3 - STARTUP AND CONFIGURATION
Important Note for MGD Configurations
Engineering Units Input
When utilizing the MGD engineering UNITS, the totalizer defaults to a VOL. PULSE multiplier of 10E3. This is not reflected on the display. Example: In MGD mode, a VOL. PULSE entry of 3 will result in an effective accumulation of E106 gallons (millions of gallons).
The UNITS key allows the selection of measuring units. Table 7 shows applicable codes for the engineering units available.
UNITS CODE U.S. METRIC
Table 7
Altering the CALibration of the D901/M
1 2 3
Attempting to enter values other than 1, 2 or 3 will result in an UNDER! or OVER! to be displayed. Non-whole number values will result in a RANGE! display. A legitimate value must be entered.
A few factors can influence the readings of the D901/M flow meter. The CAL entry allows the user to compensate for flow discrepancies without affecting the factory calibration. Examples of situations that can cause reading discrepancies are:
Operation on liquids with sonic velocity carrying properties that are different than water.
FPS MPS GPM LPM MGD LPS
Transducers mounted in non-recommended locations.
Operation on fluids with a large amount of suspended
solids.
PART 3 - STARTUP AND CONFIGURATION
By applying a CAL value other than 100%, the factory calibrated readings will be altered by the percentage entered. This CAL value will not 20mA or pulse outputs.
For example, if a reading of 175 GPM is displayed and the known flow rate is 160 GPM, a CAL value of
160 GPM 175 GPM
The D901/M will not allow decimal values to be entered as a CAL constant, so round to the nearest whole number. In this case 91%.
Acceptable input ranges for the CAL constant are shown in Table 8.
I.D. US METRIC Max Min
Values outside of this range will result in an OVER! or UNDER! Display. Non-whole number entries will result in a RANGE! Display. Enter an appropriate value.
X 100 = 91.4%
Table 8
200% 200% 3% 3%
be reflected in the 4-
PART 3 - STARTUP AND CONFIGURATION
Display Damping
System Damping
The TEST Diagnostic Key
The DAMP key allows the selection of time duration between display updates. The value selected and entered will result in display updates of
n x 2 = seconds between updates
Acceptable input ranges for the DAMP constant are shown in Table 9.
I.D. US METRIC Max Min
Values outside of this range will result in an OVER! or UNDER! display. Entry of an appropriate value is required.
Note: The D901/M circuit is calibrated at the factory to provide stable flow readings and outputs under normal flow conditions and liquid turbulence. In conditions where stability of readings and/or outputs are unsatisfactory, the response of the instrument can be changed by adjusting R17 (DAMP) control located left center on the main circuit card. Open the inner door of the flow meter and adjust with a small screwdriver.
The TEST key is used for diagnostic purposes. It displays the operand presently available at the analog to digital converter. This value will always be in the range of 0 to
255.
Table 9
5 5
0.5 0.5
PART 3 - STARTUP AND CONFIGURATION
System and Totalizer RESET
Reset the Flow Totalizer
The RESET key is used for generating a system reset or to reset the accumulated (totalized) flow. Press the RESET button from the ENTER Mode. A choice is then made to :
RESET Reset the system VOL. MULT Press VOL PULSE to
re-set the totalizer to zero.
If the RESET key is pressed again, all configuration constants will return to default values.
If the VOL. PULSE key is pressed, the accumulated flow will be erased and the display will return to zero.
In RUN Mode, pressing the decimal point once will suspend totalizer accumulation. Pressing the decimal point again will clear the total. Pressing it a third time will restart the accumulation from zero.
PART 4 - TROUBLE SHOOTING
CONDITION
Unit does not turn “ON” when power is applied
OVERRANGE light is ON
FAULT light is ON; low SIGNAL STRENGTH indication
POSSIBLE CAUSE
Check AC connections.
Test the fuse
Ensure the terminal block located in the
upper left corner of the main PCB is secure
Verify that ribbon cables between PCBs are connected.
Increase the value of the FULL SCALE constant.
Verify that fluid velocity is not greater than 20 FPS [6.08 MPS]
Ensure that the transducers are properly mounted to the pipe.
Verify that transducer connections are correct
Ensure that the pipe is full of moving liquid.
Increase SENSITIVITY so that right­most SIGNAL STRENGTH light just comes ON.
On cleaner liquids, move the transducers closer to a 90
On dirtier liquids, mount the transducers as described in CASE 3 of Part 2 of this manual.
If the pipe has a polyethylene liner, move the transducers to another area. The liner may contain an air void at this location.
(continued)
o
pipe elbow.
PART 4 - TROUBLE SHOOTING
FAULT light is ON; low SIGNAL STRENGTH indication (continued)
Stability of flow readings are unsatisfactory
Erroneous Reading
If GND connection and pipe are at different potentials, ground D901/M to pipe potential.
If Variable Frequency Drives are being utilized, verify that the D901/M obtains a READ light when the pump turn OFF. If it does, contact the Dynasonics factory.
Increase the DAMP constant from keypad.
Increase the system time constant by
turning R17 (DAMP) clockwise till readings are satisfactory.
Move transducers to a location further from piping tees, elbows, valves, filters, etc.
Transducers mounted incorrectly.
Another local ultrasonic instrument is
operating at about the same frequency [ consult the Dynasonics factory].
Presence of large amounts of suspended solids or aeration. Use CAL constant to compensate.
Sources of radiated interference are present. Apply appropriate shielding.
An electrically noisy power supply is powering the D901/M. Power the meter with a circuit that does not power motors, ballasts or switching supplies.
Readings of flow at zero fluid velocity
Verify that residual leakage and flow is not present. [I.e. leaking check valves]
Verify that SENSITIVITY is not adjusted too high. With nominal flow running through the pipe, adjust SENSITIVITY control till the right-most bar meter light just comes ON.
PART 5 - APPENDICES
Appendices
Relay Alarm Module Addendum Pipe Dimension Chart: Cast Iron Pipe Dimension Chart: Steel, SS, PVC Velocity to Volumetric Conversion Chart Statement of Warranty Customer Service
Addendum — Relay Alarm Module
General
This addendum supplies information not covered in the standard Installation and Operation Manual supplied with the Series D901/D90M Ultrasonic Flowmeter Product.
The Series D901/D90M product enclosed in this carton was purchased with an external relay alarm module. The module is enclosed and will need to be mounted seperately from the D901/D90M enclosure.
Supplemental Specifications - Alarm Module Loop Load equivalent 200 Ohms
Alarm Trip Point Activated by setting trip point proportional to full scale FPS
(example: to trip alarm at 2 FPS when FULL SCALE on the D901 is set to 10 FPS. Set alarm to 2/10 = 20%.)
Contact Rating SPDT, 3 AMPS @ 28Vdc or 117 VAC resistive. Dead Band DIP switch selectable, see chart below
Connections
Termination Inside the D901/D90M
Terminations at the Alarm Relay
Description: Installation and Operation Manual Addendum Series D901/D90M Alarm Relay Option
Origin Date: 7-20-98 Revision: none Revision date: none Page 1 of 2
Addendum — Relay Alarm Module
Dead Band and Relay Operation Programming
Description: Installation and Operation Manual Addendum Series D901/D90M Alarm Relay Option
Origin Date: 7-20-98 Revision: none Revision date: none Page 2 of 2
Cement Lining
Ductile Iron Pipe
Standard Classes
Pipe
Size
(inches)
3 3.96 3.46 0.25 3.40 0.28 3.34 0.31 3.28 0.34 3.22 0.37 3.14 0.41 4 4.80 4.28 0.26 4.22 0.29 4.16 0.32 4.10 0.35 4.04 0.38 3.93 0.44 6 6.90 6.40 0.25 6.34 0.28 6.28 0.31 6.22 0.34 6.16 0.37 6.10 0.40 6.04 0.43 .123/.250
8 9.05 8.51 0.27 8.45 0.30 8.39 0.33 8.33 0.36 8.27 0.39 8.21 0.42 8.15 0.45 10 11.10 10.32 0.39 10.46 0.32 10.40 0.35 10.34 0.38 10.28 0.41 10.22 0.44 10.16 0.47 12 13.20 12.58 0.31 12.52 0.34 12.46 0.37 12.40 0.40 12.34 0.43 12.28 0.46 12.22 0.49
14 15.30 14.64 0.33 14.58 0.36 14.52 0.39 14.46 0.42 14.40 0.45 14.34 0.48 14.28 0.51 16 17.40 16.72 0.34 16.66 0.37 16.60 0.40 16.54 0.43 16.48 0.46 16.42 0.49 16.36 0.52 18 19.50 18.80 0.35 18.74 0.38 18.68 0.41 18.62 0.44 18.56 0.47 18.50 0.50 18.44 0.53 .1875/.375 20 21.60 20.88 0.36 20.82 0.39 20.76 0.42 20.70 0.45 20.64 0.48 20.58 0.51 20.52 0.54 24 25.80 25.04 0.38 24.98 0.41 24.92 0.44 24.86 0.47 24.80 0.50 24.74 0.53 24.68 0.56
30 32.00 31.22 0.39 31.14 0.43 31.06 0.47 30.98 0.51 30.90 0.55 30.82 0.59 30.74 0.63
Outside
Diameter
(inches)
Class 53
ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall
Class 54 Class 55 Class 56Class 50 Class 51 Class 52
Std./Double
Thickness
36 38.30 37.44 0.43 37.34 0.48 37.06 0.62 37.14 0.58 37.40 0.45 36.94 0.68 36.84 0.73 42 44.50 43.56 0.47 43.44 0.53 43.32 0.59 43.20 0.65 43.08 0.71 42.96 0.77 42.84 0.83 .250/.500 48 50.80 49.78 0.51 49.64 0.58 49.50 0.65 49.36 0.72 49.22 0.79 49.08 0.86 48.94 0.93 54 57.10 55.96 0.57 55.80 0.65 55.64 0.73 55.48 0.81 55.32 0.89 55.16 0.97 55.00 1.05
March, 2000
Cast Iron Pipe
Standard Classes
CLASS B CLASS C CLASS D CLASS E CLASS F CLASS G CLASS HCLASS A
Size
(Inches)
10 11.10 10.10 0.50 11.10 9.96 0.57 11.40 10.16 0.62 11.40 10.04 0.68 11.60 10.12 0.74 11.60 10.00 0.80 11.84 10.12 0.86 11.84 10.00 0.92
12 13.20 12.12 0.54 13.20 11.96 0.62 13.50 12.14 0.68 13.50 12.00 0.75 13.78 12.14 0.82 13.78 12.00 0.89 14.08 12.14 0.97 14.08 12.00 1.04 14 15.30 14.16 0.57 15.30 13.98 0.66 15.65 14.17 0.74 15.65 14.01 0.82 15.98 14.18 0.90 15.98 14.00 0.99 16.32 14.18 1.07 16.32 14.00 1.16 16 17.40 16.20 0.60 17.40 16.00 0.70 17.80 16.20 0.80 17.80 16.02 0.89 18.16 16.20 0.98 18.16 16.00 1.08 18.54 16.18 1.18 18.54 16.00 1.27 18 19.50 18.22 0.64 19.50 18.00 0.75 19.92 18.18 0.87 19.92 18.00 0.96 20.34 18.20 1.07 20.34 18.00 1.17 20.78 18.22 1.28 20.78 18.00 1.39 20 21.60 20.26 0.67 21.60 20.00 0.80 22.06 20.22 0.92 22.06 20.00 1.03 22.54 20.24 1.15 22.54 20.00 1.27 23.02 20.24 1.39 23.02 20.00 1.51
24 25.80 24.28 0.76 25.80 24.02 0.89 26.32 24.22 1.05 26.32 24.00 1.16 26.90 24.28 1.31 26.90 24.00 1.45 27.76 24.26 1.75 27.76 24.00 1.88 30 31.74 29.98 0.88 32.00 29.94 1.03 32.40 30.00 1.20 32.74 30.00 1.37 33.10 30.00 1.55 33.46 30.00 1.73 36 37.96 35.98 0.99 38.30 36.00 1.15 38.70 35.98 1.36 39.16 36.00 1.58 39.60 36.00 1.80 40.04 36.00 2.02 42 44.20 42.00 1.10 44.50 41.94 1.28 45.10 42.02 1.54 45.58 42.02 1.78 48 50.50 47.98 1.26 50.80 47.96 1.42 51.40 47.98 1.71 51.98 48.00 1.99
O.D.
Inch
3 3.80 3.02 0.39 3.96 3.12 0.42 3.96 3.06 0.45 3.96 3.00 0.48 4 4.80 3.96 0.42 5.00 4.10 0.45 5.00 4.04 0.48 5.00 3.96 0.52 6 6.90 6.02 0.44 7.10 6.14 0.48 7.10 6.08 0.51 7.10 6.00 0.55 7.22 6.06 0.58 7.22 6.00 0.61 7.38 6.08 0.65 7.38 6.00 0.69 8 9.05 8.13 0.46 9.05 8.03 0.51 9.30 8.18 0.56 9.30 8.10 0.60 9.42 8.10 0.66 9.42 8.10 0.66 9.60 8.10 0.75 9.60 8.00 0.8
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D.
Inch
I.D.
Inch
Wall
O.D. Inch
I.D.
Inch
Wall
54 56.66 53.96 1.35 57.10 54.00 1.55 57.80 54.00 1.90 58.40 53.94 2.23 60 62.80 60.02 1.39 63.40 60.06 1.67 64.20 60.20 2.00 64.82 60.06 2.38 72 75.34 72.10 1.62 76.00 72.10 1.95 76.88 72.10 2.39 84 87.54 84.10 1.72 88.54 84.10 2.22
March, 2000
Steel, Stainless Steel, P.V.C.
Standard Schedules
Nominal
Pipe Size
Inches
OUTSIDE DIAMETER
1 1.315 1.185 0.065 1.097 0.109 1.049 1.049 0.133 0.957 0.179 0.957 0.179 0.815 0.250
1.25 1.660 1.530 0.065 1.442 0.109 1.380 1.380 0.140 1.278 0.191 1.278 0.191 1.160 0.250
1.5 1.900 1.770 0.065 1.682 0.109 1.610 1.610 0.145 1.500 0.200 1.500 0.200 1.338 0.281 2 2.375 2.245 0.065 2.157 0.109 2.067 2.067 0.154 1.939 0.218 1.939 0.218 1.687 0.344
2.5 2.875 2.709 0.083 2.635 0.120 2.469 2.469 0.203 2.323 0.276 2.323 0.276 2.125 0.375 3 3.500 3.334 0.083 3.260 0.120 3.068 3.068 0.216 2.900 0.300 2.900 0.300 2.624 0.438
3.5 4.000 3.834 0.083 3.760 0.120 3.548 3.548 0.226 3.364 0.318 3.364 0.318 4 4.500 4.334 0.083 4.260 0.120 4.026 0.237 4.026 0.237 3.826 0.337 3.826 0.337 3.624 0.438 3.624 0.438 3.438 0.531 5 5.563 5.345 0.109 5.295 0.134 5.047 0.258 5.047 0.258 4.813 0.375 4.813 0.375 4.563 0.500 4.563 0.500 4.313 0.625 6 6.625 6.407 0.109 6.357 0.134 6.065 0.280 6.065 0.280 5.761 0.432 5.761 0.432 5.501 0.562 5.501 0.562 5.187 0.719 8 8.625 8.407 0.109 8.329 0.148 8.125 0.250 8.071 0.277 7.981 0.322 7.981 0.322 7.813 0.406 7.625 0.500 7.625 0.500 7.437 0.594 7.187 0.719 7.187 0.719 6.183 1.221
10 10.750 10.482 0.134 10.42 0.165 10.25 0.250 10.13 0.310 10.02 0.365 10.020 0.365 9.750 0.500 9.750 0.500 9.562 0.594 9.312 0.719 9.062 0.844 9.062 0.844 8.500 1.125
12 12.750 12.420 0.165 12.39 0.180 12.25 0.250 12.09 0.330 12.00 0.375 11.938 0.406 11.626 0.562 11.750 0.500 11.370 0.690 11.060 0.845 10.750 1.000 10.750 1.000 10.120 1.315 14 14.000 13.50 0.250 13.37 0.315 13.25 0.375 13.25 0.375 13.124 0.438 12.814 0.593 13.000 0.500 12.500 0.750 12.310 0.845 11.810 1.095 11.810 1.095 11.180 1.410 16 16.000 15.50 0.250 15.37 0.315 15.25 0.375 15.25 0.375 15.000 0.500 14.688 0.656 15.000 0.500 14.310 0.845 13.930 1.035 13.560 1.220 13.560 1.220 12.810 1.595 18 18.000 17.50 0.250 17.37 0.315 17.12 0.440 17.25 0.375 16.876 0.562 16.564 0.718 17.000 0.500 16.120 0.940 15.680 1.160 15.250 1.375 15.250 1.375 14.430 1.785 20 20.000 19.50 0.250 19.25 0.375 19.25 0.375 19.25 0.375 18.814 0.593 18.376 0.812 19.000 0.500 17.930 1.035 17.430 1.285 17.000 1.500 17.000 1.500 16.060 1.970 24 24.000 23.50 0.250 23.25 0.375 23.25 0.375 23.25 0.375 22.626 0.687 22.126 0.937 23.000 0.500 21.560 1.220 20.930 1.535 20.930 1.535 20.930 1.535 19.310 2.345
30 30.000 29.37 0.315 29.00 0.500 29.00 0.500 29.25 0.375 29.250 0.375 29.000 0.500 36 36.000 35.37 0.315 35.00 0.500 35.00 0.500 35.25 0.375 35.250 0.375 35.000 0.500 42 42.000 41.25 0.375 41.250 0.375 41.000 0.500 48 48.000 47.25 0.375 47.250 0.375 47.000 0.500
SCH.
5
ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall
SCH. 10
(LTWALL)
SCH. 20 SCH. 30 STD. SCH. 40 SCH. 60 SCH. 140 SCH. 180
X STG. SCH. 80 SCH. 100 SCH. 120
March, 2000
FPS TO GPM CROSS - REFERENCE (Schedule 40)
Nominal
Pipe
(Inches)
1 1.05 2.6989 4.0484 5.3978 6.7473 8.097 9.4462 10.796 12.145 13.490 14.844 16.190 17.540 18.890 20.240 21.590 22.941 24.290
1.25 1.38 4.6620 6.9929 9.3239 11.655 13.99 16.317 18.648 20.979 23.310 25.641 27.970 30.300 32.630 34.960 37.300 39.627 41.958
1.5 1.61 6.3454 9.5182 12.691 15.864 19.04 22.209 25.382 28.555 31.730 34.900 38.070 41.250 44.420 47.590 50.760 53.936 57.109 2 2.07 10.489 15.734 20.979 26.224 31.47 36.713 41.958 47.202 52.450 57.692 62.940 68.180 73.430 78.670 83.920 89.160 94.405
2.5 2.47 14.935 22.402 29.870 37.337 44.80 52.272 59.740 67.207 74.670 82.142 89.610 97.080 104.50 112.00 119.50 126.95 134.41 3 3.07 23.072 34.608 46.144 57.680 69.22 80.752 92.288 103.82 115.40 126.90 138.40 150.00 161.50 173.00 184.60 196.11 207.65
3.5 3.55 30.851 46.276 61.702 77.127 92.55 107.98 123.40 138.83 154.30 169.68 185.10 200.50 216.00 231.40 246.80 262.23 277.66 4 4.03 39.758 59.636 79.515 99.394 119.3 139.15 159.03 178.91 198.80 218.67 238.50 258.40 278.30 298.20 318.10 337.94 357.82 5 5.05 62.430 93.645 124.86 156.07 187.3 218.50 249.72 280.93 312.10 343.36 374.60 405.80 437.00 468.20 499.40 530.65 561.87 6 6.06 89.899 134.85 179.80 224.75 269.7 314.65 359.60 404.55 449.50 494.45 539.40 584.30 629.30 674.20 719.20 764.14 809.09 8 7.98 155.89 233.83 311.78 389.72 467.7 545.61 623.56 701.50 779.40 857.39 935.30 1013.0 1091.0 1169.0 1247.0 1325.1 1403.0
10 10.02 245.78 368.67 491.56 614.45 737.3 860.23 983.12 1106.0 1229.0 1351.8 1475.0 1598.0 1720.0 1843.0 1966.0 2089.1 2212.0
I.D.
INCH
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9
12 11.94 348.99 523.49 697.99 872.49 1047.0 1221.5 1396.0 1570.5 1745.0 1919.5 2094.0 2268.0 2443.0 2617.0 2792.0 2966.5 3141.0 14 13.13 422.03 633.04 844.05 1055.1 1266.0 1477.1 1688.1 1899.1 2110.0 2321.1 2532.0 2743.0 2954.0 3165.0 3376.0 3587.2 3798.2 16 15.00 550.80 826.20 1101.6 1377.0 1652.0 1927.8 2203.2 2478.6 2754.0 3029.4 3305.0 3580.0 3856.0 4131.0 4406.0 4681.8 4957.2
FPS TO GPM: GPM = (PIPE ID)² X VELOCITY IN FPS X 2.45 FPS X .3048 = MPS GPM TO FPS: FPS =
GPM
(ID)² X 2.45
GPM X .0007 = GPD GPM X 3.7878 = LPM
FPS TO GPM CROSS - REFERENCE (Schedule 40)
Nominal
Pipe
(Inches)
18 16.88 697.52 1046.3 1395.0 1743.8 2093.0 2441.3 2790.1 3138.8 3488.0 3836.3 4185.0 4534.0 4883.0 5231.0 5580.0 5928.9 6277.7 20 18.81 866.14 1299.0 1732.0 2165.3 2598.4 3031.5 3464.6 3897.6 4330.7 4763.8 5196.8 5629.9 6063.0 6496.0 6929.1 7362.2 7795.3 24 22.63 1253.7 1880.0 2507.0 3134.1 3761.0 4387.8 5014.6 5641.5 6268.3 6895.1 7522.0 8148.8 8775.6 9402.4 10029 10656 11283 26 25.25 1560.7 2341.0 3121.0 3901.9 4682.2 5462.6 6243.0 7023.4 7803.7 8584.1 9364.5 10145 10925 11706 12486 13266 14047 28 27.25 1817.8 2727.0 3636.0 4544.5 5453.4 6362.3 7271.2 8180.0 9088.9 9997.8 10907 11816 12725 13633 14542 15451 16360 30 29.25 2094.4 3142.0 4189.0 5236.0 6283.2 7330.4 8377.6 9424.9 10472 11519 12566 13614 14661 15708 16755 17803 18850 32 31.25 2390.6 3586.0 4781.0 5976.5 7171.9 8367.2 9562.5 10758 11953 13148 14344 15539 16734 17930 19125 20320 21516 34 33.25 2706.4 4060.0 5413.0 6766.0 8119.2 9472.4 10826 12179 13532 14885 16238 17592 18945 20298 21651 23004 24358 36 35.25 3041.8 4563.0 6084.0 7604.5 9125.4 10646 12167 13688 15209 16730 18251 19772 21292 22813 24334 25855 27376 42 41.25 4165.4 6248.0 8331.0 10414 12496 14579 16662 18744 20827 22910 24992 27075 29158 31241 33323 35406 37489 48 47.99 5637.8 8457.0 11276 14095 16913 19732 22551 25370 28189 31008 33827 36646 39465 42284 45103 47922 50740 54 53.98 7133.1 10700 14266 17833 21399 24966 28532 32099 35665 39232 42798 46365 49931 53498 57065 60631 64198
I.D.
INCH
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9
60 60.09 8839.2 13259 17678 22098 26518 30937 35357 39777 44196 48616 53035 57455 61875 66294 70714 75134 79553 72 72.10 12726 19089 25451 31814 38177 44540 50903 57266 63628 69991 76354 82717 89080 95443 101805 108168 114531 84 84.10 17314 25971 34628 43285 51943 60600 69257 77914 86571 95228 103885 112542 121199 129856 138514 147171 155828
FPS TO GPM: GPM = (PIPE ID)² X VELOCITY IN FPS X 2.45 FPS X .3048 = MPS GPM TO FPS: FPS =
GPM
(ID)² X 2.45
GPM X .0007 = GPD GPM X 3.7878 = LPM
Fluid Sound Speeds
g
Original Date: 10/19/99 Revision: none Revision Date: none File: I:/dynasonics/dyna_code/tables/doppler ss conversions.xls
120.0176921
Doppler
Fluid Specific Gravity Sound Speed Calibration Entry
20 de
Acetate, Butyl (n) 1270 4163.9 85 Acetate, Ethyl 0.901 1085 3559.7 72 Acetate, Methyl 0.934 1211 3973.1 81 Acetate, Propyl 1280 4196.7 85 Acetone 0.79 1174 3851.7 78 Alcohol 0.79 1207 3960.0 81 Alcohol, Butyl (n) 0.83 1270 4163.9 85 Alcohol, Ethyl 0.83 1180 3868.9 79 Alcohol, Methyl 0.791 1120 3672.1 75 Alcohol, Propyl (I) 1170 3836.1 78 Alcohol, Propyl (n) 0.78 1222 4009.2 82 Ammonia (35) 0.77 1729 5672.6 115 Anlline (41) 1.02 1639 5377.3 109 Benzene (29,40,41) 0.88 1306 4284.8 87 Benzol, Ethyl 0.867 1338 4389.8 89 Bromine (21) 2.93 889 2916.7 59 n-Butane (2) 0.60 1085 3559.7 72 Butyrate, Ethyl 1170 3836.1 78 Carbon dioxide (26) 1.10 839 2752.6 56 Carbon tetrachloride 1.60 926 3038.1 62 Chloro-benezene 1.11 1273 4176.5 85 Chloroform (47) 1.49 979 3211.9 65 Diethyl ether 0.71 985 3231.6 66 Diethyl Ketone 1310 4295.1 87 Diethylene glycol 1.12 1586 5203.4 106 Ethanol 0.79 1207 3960.0 81 Ethyl alcohol 0.79 1207 3960.0 81 Ether 0.71 985 3231.6 66 Ethyl ether 0.71 985 3231.6 66 Ethylene glycol 1.11 1658 5439.6 111 Freon R12 774.2 2540 52 Gasoline 0.7 1250 4098.4 83 Glycerin 1.26 1904 6246.7 127 Glycol 1.11 1658 5439.6 111 Isobutanol 0.81 1212 3976.4 81 Iso-Butane 1219.8 4002 81 Isopentane (36) 0.62 980 3215.2 65 Isopropanol (46) 0.79 1170 3838.6 78 Isopropyl alcohol (46) 0.79 1170 3838.6 78 Kerosene 0.81 1324 4343.8 88 Linalool 1400 4590.2 93
rees C m/s ft/s relative to 25C water
Linseed Oil .925-.939 1770 5803.3 118
(
)
Methanol (40,41) 0.79 1076 3530.2 72 Methyl alcohol (40,44) 0.79 1076 3530.2 72 Methylene chloride (3) 1.33 1070 3510.5 71 Methylethyl Ketone 1210 3967.2 81 Motor Oil (SAE 20/30) .88-.935 1487 4875.4 99 Octane (23) 0.70 1172 3845.1 78 Oil, Castor 0.97 1477 4845.8 99 Oil, Diesel 0.80 1250 4101 83 Oil (Lubricating X200) 1530 5019.9 102 Oil (Olive) 0.91 1431 4694.9 96 Oil (Peanut) 0.94 1458 4783.5 97 Paraffin Oil 1420 4655.7 95 Pentane 0.626 1020 3346.5 68 Petroleum 0.876 1290 4229.5 86 1-Propanol (46) 0.78 1222 4009.2 82 Refrigerant 11 (3,4) 1.49 828.3 2717.5 55 Refrigerant 12 (3) 1.52 774.1 2539.7 52 Refrigerant 14 (14) 1.75 875.24 2871.5 58 Refrigerant 21 (3) 1.43 891 2923.2 59 Refrigerant 22 (3) 1.49 893.9 2932.7 60 Refrigerant 113 (3) 1.56 783.7 2571.2 52 Refrigerant 114 (3) 1.46 665.3 2182.7 44 Refrigerant 115 (3) 656.4 2153.5 44 Refrigerant C318 (3) 1.62 574 1883.2 38 Silicone (30 cp) 0.99 990 3248 66 Toluene (16,52) 0.87 1328 4357 89 Transformer Oil 1390 4557.4 93 Trichlorethylene 1050 3442.6 70 1,1,1-Trichloro-ethane 1.33 985 3231.6 66 Turpentine 0.88 1255 4117.5 84 Water, distilled Water 0 degrees C 1402 4596.7 94 Water 20 degrees C 1482 4859.0 99 Water 40 degrees C 1529 5013.1 102 Water 60 degrees C 1551 5085.2 103 Water 80 degrees C 1554 5095.1 104 Water 100 degrees C 1543 5059.0 103 Water 120 degrees C 1519 4980.3 101 Water 140 degrees C 1485 4868.9 99 Water 160 degrees C 1440 4721.3 96 Water 180 degrees C 1390 4557.4 93 Water 200 degrees C 1333 4370.5 89 Water, heavy 1 1400 4593 93 Water, sea 1.025 1531 5023 102 Wood Alcohol (40,41) 0.791 1076 3530.2 72 m-Xylene (46) 0.868 1343 4406.2 90 o-Xylene (29,46) 0.897 1331.5 4368.4 89 p-Xylene (46) 1334 4376.8 89
49,50
0.996 1498 4914.7 100
GENERAL TERMS AND CONDITIONS OF SALES
1. PAYMENT – Terms of payment are effective from the actual date of invoice. If, in the Seller’s
opinion, the financial condition of the Buyer at any time – or any other circumstances – do not justify the incurrence of production costs of shipment on the terms of payment specified, the Seller may require partial or full payment in advance. Payment terms are net 30 days unless otherwise stated on invoice.
2. F.O.B. – All shipments are from Racine, Wisconsin, USA, unless otherwise other stated, and title
transfers to the buyer upon leaving factory.
3. QUOTATION AND PRICES – Quoted prices are firm for 30 days unless s t at ed in the quot at i on a n d
are subject to change without notice after expiration of this period.
4. TAXES – Any applicable sales, use, revenue, excise or other taxes not specifically stated in the
quotation are to be remitted by the Buyer directly to the appropriate regulatory agency.
5. WARRANTY – Seller’s standard published warranty in effect at the time of shipment shall apply.
This warranty is exclusive and is in lieu of all other warranties, express, implied, or statutory, including the warranty of merchantability.
6. DELIVERY – The Seller shall not be liable for loss or damage of any kind resulting from delay or
inability to deliver on account of flood, fire, labor trouble, riots, civil disturbances, accidents, acts or orders or regulations of civil or military authorities, sh ortages of material, or any other causes beyond Seller’s control.
7. PRODUCT CHANGES – In keeping with our continu ing policy of product improvement, we reserve
the right to make changes in our products at any time, without incurring an obligation to change, replace or upgrade equipment previously shipped.
8. CANCELLATIONS – An order placed by Buyer and accepted by Seller may be cancelled only with
the Seller’s consent and upon terms that will indemnify the Seller against loss.
9. RESTOCKING CHARGE – On standard equipment, the charge is 25%, provided the equipment is
returned within 30 days in acceptable condition with a RGA number. Restocking charges for special equipment may vary from standard equipment, and will be handled on a case-by-case basis. No returns will be taken after one year.
Limited Warranty and Disclaimer
Dynasonics, div. of Racine Federated Inc. warrants to the end purchaser, for a period of one year from the date of shipment from our factory, that all new transmitters and transducers manufactured by it are free from defects in materials and workmanship. This warranty does not cover products that have been damaged due to normal use, misapplication, abuse, lack of maintenance, or improper installation. Dynasonics’ obligation under this warranty is limited to the repair or replacement of a defective product, at no charge to the end purchaser, if the product is inspected by Dynasonics and found to be defective. Repair or replacement is at Dynasonics’ discretion. An authorization number must be obtained from Dynasonics before any product may be returned for warranty repair or replacement. The product must be thoroughly cleaned and any process chemicals removed before it will be accepted for return.
The purchaser must determine the applicability of the product for its desired use and assumes all risks in connection therewith. Dynasonics assumes no responsibility or liability for any omissions or errors in connection with the use of its products. Dynasonics will under no circumstances be liable for any incidental, consequential, contingent or special damages or loss to any person or property arising out of the failure of any product, component or accessory.
All expressed or implied warranties, including the implied warranty of
merchantability and the implied warranty of fitness for a particular purpose or application are expressly disclaimed and shall not apply to any products sold or
services rendered by Dynasonics.
The above warranty supersedes and is in lieu of all other warranties, either expressed or implied and all other obligations or liabilities. No agent or representative has any authority to alter the terms of this warranty in any way.
RETURN OF EQUIPMENT/SALES INFORMATION
CONTACTS AND PROCEDURES
Customer Service/Application Engineer:
If you have a question regarding order status, placing an order, reviewing applications for future purchases, or wish to purchase a new flowmeter, please contact our new National Sales and Marketing Headquarters:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800)535-3569 or
(262)639-6770
FAX: (262)639-2267
Service/Repair Department:
If you already purchased equipment and have an operation problem, require service, or need to schedule field service, please contact our Service Department:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800)535-3569 or
(262)639-6770
FAX: (262)639-2267
Return Goods Authorization:
When returning equipment, it is necessary for you to contact our Service Department at (800)535-3569 or (262)639-6770 to obtain an RGA number for the authority and proper tracking of your material and its prompt inspection and return. The RGA number should be noted on the outside of the box. All returns of equipment go to the following address:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
Attn: RGA #
8635 WASHINGTON AVENUE
RACINE, WI 53406
TOLL-FREE IN NORTH AMERICA.: TEL: (800) 535-3569 FAX: (800) 732-8354 TEL: (262) 639-6770 FAX: (262) 639-2267
URL: www.dynasonics.com
D901/M O&M REV 04/02
Loading...