This manual contains detailed operating instructions for
all aspects of the D901/M instrument. The following
condensed instructions are provided to assist the
operator in getting the instrument started up and running
as quickly as possible. This pertains to basic operation
only. If specific instrument features are to be used or if
the installer is unfamiliar with this type of instrument,
refer to the appropriate section in the manual for
complete details.
1. TRANSDUCER LOCATION
A. Determine the appropriate mounting location for
the transducers by referring to Figure 1.
Receiving
Transducer
Transmitting
Transducer
Solids Bearing or Aerated Liquids Clean Liquids
Pipe Preparation
and Mounting
90° Elbow
Fluid Velocity ∝ Γ1Γ2
Figure 1 Transducer Locations
2. PIPE PREPARATION AND TRANSDUCER
MOUNTING
A. The piping surface, where the transducers are to
be mounted, needs to be clean and dry. Remove
loose scale, rust and paint to ensure satisfactory
acoustical bonds.
B. Connect the mounting straps around the pipe.
Leave the strap loose enough to slip the
transducers underneath.
C. Apply a liberal amount of silicone rubber
(enclosed) onto the transducer faces and the
prepared areas of the pipe.
Rev. 04/02 -1- D901/M
QUICK-START OPERATING INSTRUCTIONS
D. Place each transducer under the mounting strap,
180° apart on the pipe. Ensure that the transducer
cables are facing the same direction. See Figure 2.
Connections
Receiving
Transducer
Transmitting
Transducer
Figure 2 Transducer
E. Route the transducer cable back to the transmitter,
avoiding locations near high voltage supply wires.
3. TRANSDUCER CONNECTION
A. Do not
transducers.
B. Connect the spade terminals to the appropriate
terminal block within the transmitter.
4. INITIAL SETTINGS AND POWER UP
attempt to add additional cable to the
A. Set the SENSITIVITY control to - 2.
B. Apply AC power. The POWER indicator will
Startup
illuminate.
C. If the pipe is full of a flowing liquid, the SIGNAL
STRENGTH meter will indicate and the READ
indicator will illuminate.
D. Adjust the SENSITIVITY control so that the right-most
green LED just comes ON.
E. The default display indicates fluid velocity as either
FPS or MPS. Refer to the appropriate place in this
manual for specific features and options.
Instrument Startup and Configuration
Initial Settings
Modes of Operation
Pipe I.D. Input
Full Scale Input
Totalizer Exponent Input
Engineering Units Input
13
13-15
16-17
17-19
20
21
22
23
24
25
TABLE OF CONTENTS
Part 4 - Troubleshooting
Instrument Startup and Configuration
CAL. Constant Input
Display Damping
System Damping
TEST Diagnostic Key
System and Totalizer RESET
Totalizer Reset
Trouble Shooting Guide
Appendices
Face Plate Drawing
Intrinsically Safe Installation
Pages
26
27
27
27
28
28
29-30
31+
High-Temperature Transducers
Clean Liquid Installation Guide
Multiple Unit Cross-talk
Pipe Dimension Chart: Cast Iron
Pipe Dimension Chart: ST, SS, PVC
Velocity to Volumetric Conversion
Statement of Warranty
Customer Service
Rev. 04/02 -4- D901/M
PART 1 - INTRODUCTION
General
Application Versatility
The D901/M ultrasonic flow meter is designed to measure
the fluid velocity of liquid within closed conduit. The
transducers are a non-contacting, clamp-on type, which
will provide benefits of non-fouling operation and ease of
installation.
The flow meter operates by transmitting an ultrasonic
sound from its transmitting transducer through the pipe
wall into the flowing liquid. The sound will be reflected by
suspended particles or bubbles within the liquid and
recorded by the receiving transducer. A frequency shift
(Doppler effect) will occur that is directly related to the
speed of the moving particle or bubble. This shift in
frequency is interpreted by the instrument and converted
to various user defined measuring units.
A unique feature of this product is that it employs a
proprietary digital filtering system and recognition circuit.
This feature allows the instrument to measure fluid
velocities of clean liquids if the transducers are mounted
downstream from a 90° elbow. The non-symmetrical
hydraulic turbulence which occurs downstream of an
elbow is captured, linearized and can be displayed as
liquid velocity and volume. This capability is not available
in conventional Doppler technology.
The D901/M flow meter can be successfully applied on a
wide range of metering applications. The simple to
program transmitter allows the standard product to be
used on pipe sizes ranging from 1 - 120 inch [ 25 - 3050
mm ] pipe I.D. (With the small pipe transducer option, the
pipe size range is 0.25 - 1 inch [ 6 - 25 mm]). A variety of
liquid applications can be accommodated: raw sewage,
reclaimed water, river water, plant effluent, mining slurries,
sludge, etc. Because the transducers are non-contacting
and have no moving parts, the flow meter is not affected
by system pressure, fouling or wear. Standard
transducers are rated to 250°F [121°C]. Optional high
temperature transducers are rated to operate to 400°F
[204°C].
Rev. 04/02 -5- D901/M
PART 1 - INTRODUCTION
User Safety
Battery Backup
Product Identification
The D901/M employs modular construction and provides
electrical safety for the operator. The display face
contains voltages no greater than 9 Vdc and the metal
work is electrically connected to Earth Ground. The
display face swings open to allow access to user
connections.
A rechargeable nickel-cadmium battery on the back of
the display board retains all user-entered configuration
values in memory for several years (at 25°C), even if
power is lost or turned off. The ten year battery is
continually trickle charged whenever line power is
applied. A completely discharged battery recharges fully
after 48 hours of instrument operation.
The serial number and complete model number of your
D901/M is located on the inside of the transmitter’s front
cover. Should technical assistance be required, please
provide the Dynasoncs’ Customer Service Department
with this information.
Product Matrix
Rev. 04/02 -6- D901/M
PART 1 - SPECIFICATIONS
Ambient Conditions
Display
Transducer to Transmitter Distance
Power Requirements
Pipe Sizes
Transmitter - -22 to 160°F [ - 30 to 70 °C],
0-95% relative humidity, non-condensing.
Transducers - - 40° to 250°F [ -40° to 121°
C] Standard. Optional: - 40° to 400°F [ - 40°
to 204°C]
2 line x 20 character alphanumeric LCD,
back lit. Digit height 0.2 inches [ 5 mm]
After unpacking, it is recommended to save the shipping
carton and packing materials in case the instrument is
stored or re-shipped. Inspect the equipment and carton
for damage. If there is evidence of shipping damage,
notify the carrier immediately.
The D901/M flow meter can be checked for basic
functionality using the following Bench Test procedure.
It is recommended that this operation be performed
before installing the transducers or transmitter
permanently.
Procedure:
1. Open the D901/M transmitter enclosure and the inner
display door.
2. Connect the transducer cable terminals to the
corresponding terminal block locations within the
transmitter. See Figure 3.
3. Set the transmitter SENSITIVITY control [located on
the display door] to -2.
4. Apply power.
5. Hold the transducers, the flat sides facing each other,
approximately 6-8 inches [150-200 mm] apart.
6. Move the transducers towards and away from each
other 1 inch [25mm] for several cycles at
approximately 1 second interval.
7. If unit is functioning properly, the READ LED will
illuminate and the rate display will indicate flow
readings.
Figure 3
Bench Test is Complete
Rev. 04/02 -9- D901/M
PART 2 - TRANSDUCER INSTALLATION
Transducer Mounting
Considerations
Step A - Mounting
Locations
CASE 1:
The transducers that are utilized by the D901/M contain
piezo electric crystals for transmitting and receiving
ultrasonic sound energy through the pipe wall.
The transducers can be mounted in three different
configurations. The selection of the proper configuration
is dependent on the liquid to be measured characteristics.
The three liquid characteristics, which will affect mounting
location and orientation, are as follows:
CASE 1: Liquid that contains 25 to 10,000 PPM [1%] of 30
micron or larger suspended solids or aeration.
CASE 2: Liquid that contains greater than 10,000 PPM
[1%] of 30 micron or larger suspended solids or aeration.
CASE 3: Liquid that contains fewer than 25 PPM of 30
micron or larger suspended solids or aeration and
suspended solids and aeration content which is smaller
than 30 microns.
Liquid that contains 25 to 10,000 PPM [1%] of 30
micron or larger suspended solids or aeration.
Select a transducer mounting location with adequate
straight runs of pipe, both upstream and downstream, to
achieve stable readings. Examples of minimum upstream
and downstream requirements are included in Table 1.
Mount the transducers 180° apart and facing each other
on the pipe. If the pipe is horizontal, the preferred
mounting orientation is 3 and 9 o’clock, with 12 o’clock
being the top of the pipe. Orientation on vertical pipes
does not matter. See Figure 4.
Rev. 04/02 -10- D901/M
PART 2 - TRANSDUCER INSTALLATION
1
2
3
4
5
Table 1
1
Example Upstream Pipe
Diameters
* **
1 24 4
2 14 3
3 9 3
4 8 3
5 8 3
6 24 4
Downstream
Pipe Diameters
6
1
The D901/M system will provide repeatable measurements on piping systems that do not
meet these requirements, but the accuracy
Liquid that contains greater than 10,000 PPM [1%] of
CASE 2:
30 micron or greater suspended solids or aeration.
may be influenced to various degrees.
Top View of Pipe
Figure 4
Rev. 04/02 -11- D901/M
PART 2 - TRANSDUCER INSTALLATION
The mounting location and straight pipe requirements for
CASE 2 liquid characteristics are the same as those
describe in CASE 1. The difference will be in the location
of the transducers on the pipe. As the discontinuities
(suspended solids or aeration) reach a level of
approximately 1% or 10,000 PPM, sound can no longer be
reliably transmitted through the liquid as it has a tendency
to scatter and absorb into the high concentration of
CASE 3:
Figure 5
discontinuity. To compensate for this, the D901/M
transducers can be located on the same region of the
pipe. In a horizontal pipe, mount the transducers at 2
o’clock and 4 o’clock positions. (Assuming 12 o’clock as
the top of the pipe.) See Figure 5.
Liquid that contains fewer than 25 PPM of 30 micron
or larger suspended solids or aeration. Or, liquid that
contains solids or aeration which is smaller than 30
microns.
The transducers will be mounted 1 to 3 pipe diameters
downstream from a 90° elbow. The orientation of the
transducers on the pipe will be 180° apart and facing each
other and 90° out of the plane of the elbow. See Figure 6.
Rev. 04/02 -12- D901/M
PART 2 - TRANSDUCER INSTALLATION
STEP B -
PIPE SURFACE
PREPARATION
STEP C -
TRANSDUCER
MOUNTING
Figure 6
Before the transducer heads are bonded to the pipe
surface, an area slightly larger than the flat surface of the
transducer must be cleaned to bare metal on the pipe.
(Plastic pipes do not require preparation beyond removal
of paint.) Remove all scale, rust and paint. Thoroughly
dry and degrease the mounting surfaces.
NOTE: Small pits in the piping surface typically do not
significantly impact ultrasonic transmission or signal
reception.
After selecting the applicable mounting location and
preparing the piping surface as detailed in A and B, the
transducer can be mounted to the pipe.
To assure an acoustically conductive path between the
transducer face and the prepared piping surface, a
coupling compound is employed. Enclosed with the D901/
M system is tube of Dow Corning RTV-732. This couplant
is satisfactory for permanently mounting the transducers
to the pipe. If the installation is temporary (less than a few
days), Dynasonics recommends utilizing a silicone-based
grease such as Dow Corning 111. The grease chosen
must be rated to not flow at the temperature of the pipe.
Rev. 04/02 -13- D901/M
PART 2 - TRANSDUCER INSTALLATION
PROCEDURE:
1. Select the proper number of transducer straps to allow
a complete strap to go around the circumference of the
pipe. See Table 2 - The straps can be connected
together to make a continuous length.
Table 2
Pipe Sizes Straps Required
1” to 9”
10” to 19”
20” to 29”
30” to 39”
2. Wrap the strap around the pipe in the area where the
transducers are to be mounted. Leave the strap loose
enough to allow the transducers to be placed
underneath. If multiple straps are being used, it can be
beneficial to wrap electrical tape around all but one
strap connection to secure the strap worm screws in
place.
3. Spread an even layer of coupling compound,
approximately 1/8 inch [3mm] thick, to the prepared
transducer mounting areas of the pipe. Utilize Dow
732 for permanent mounting or Dow 111 for temporary
mounting,
25 to 225 mm 1
250 to 480 mm 2
500 to 740 mm 3
760 to 1000 mm 4
4. Spread an even layer of coupling compound,
approximately 1/8 inch [ 3mm ] thick, to the flat face of
the two transducers.
5. Place each transducer under the strap with the flat
face positioned towards the pipe. The notch on the
back of the transducer will provide a mounting surface
for the strap. The transducer cables must be facing in
Rev. 04/02 -14- D901/M
PART 2 - TRANSDUCER INSTALLATION
the same direction for proper operation. See Figure 7.
NOTE: Large pipes may require two people for this
procedure.
6. Tighten the strap tight enough to hold the transducers
in place, but not so tight that all of the couplant
squeezes out of the gap between the transducer face
and pipe. Ensure that the transducers are squarely
aligned on the pipe.
Figure 7
7. Route the transducer cable back to the transmitter
mounting area avoiding high voltage cable trays and
conduits. Do not attempt to add additional cable to the
factory supplied transducer cable. The D901/M
processes very small signals, so the cable shield must
be continuous. Excess cable may be coiled to take up
extra length.
8. If the transducers are to be permanently mounted
using Dow 732, the RTV must be completely cured
before proceeding to Instrument Start up. Ensure that
no relative motion between the transducer and pipe
occurs during the 24 hour curing process. If Dow 111
grease was used for temporary operation of the D901/
M system, proceed with the Instrument Start-up
procedures.
Transducer Installation is complete
Rev. 04/02 -15- D901/M
PART 2 - TRANSMITTER INSTALLATION
Transmitter Installation
The enclosure should be mounted in an area that is
convenient for servicing, calibration or for observation of
the LCD readout.
1. Locate the transmitter within the length of transducer
cable that was supplied with the D901/M system. If
this is not possible, do not attempt to add additional
cable to the transducer. Contact the Dynasonics
factory to coordinate an exchange for the proper cable
length. Transducer cables that are up to 300 feet [90
meters] are available.
2. Mount the D901/M transmitter in a location that is:
Figure 8
Rev. 04/02 -16- D901/M
PART 2 - TRANSMITTER INSTALLATION
ELECTRICAL
CONNECTIONS
♦ Where little vibration exist.
♦ Protected from falling corrosive fluids.
♦ Within ambient temperature limits - 22 to 160°F [30 to
70°C]
♦ Out of direct sunlight. A sun and weather shield is
available from Dynasonics. P.N. D003-899-001. Direct
sunlight may increase temperatures within the
transmitter to above maximum limit.
3. Mounting: Refer to Figure 8 for enclosure and
mounting dimension details. Ensure that enough room
is available to allow for door swing, maintenance and
conduit entrances. Secure the enclosure to a flat
surface with four appropriate fasteners.
4. Conduit holes. Conduit hubs should be used where
cables enter the enclosure. Holes not used for cable
entry should be sealed with plugs.
NOTE: Use NEMA 4 [ IP65 ] rated fittings plugs to
maintain the water tight integrity of the enclosure.
Generally, the left conduit hole (viewed from front) is used
for line power; the right conduit hole for transducer
connections.
5. If additional holes are required, (analog outputs, etc.)
drill the appropriate size hole in the enclosure’s
bottom. Use extreme care not to run the drill bit into
the wiring or circuits cards.
To access terminal strips for electronic connectors, loosen
the two screws in the enclosure door and open the door.
Loosen the two thumb-screws on the inner display door
and open the door.
1. Guide the transducer terminations through the
transmitter conduit hole located on the right side of the
Rev. 04/02 -17- D901/M
PART 2 - ELECTRICAL INSTALLATION
Transducer Connections
Figure 9
4-20 mA Output
Pulse Output
enclosure. Secure the transducer cable with the
supplied conduit nut.
2. The terminals on the transducer cable are coded with
wire markings. Connect the appropriate wires to the
corresponding screw terminals in the transmitter. See
Figure 9.
NOTE: The transducer cable carries low level signals.
Do not attempt to add additional cable to the factory
supplied transducer cable. If additional cable is required,
contact the Dynasonics factory to arrange for an exchange
transducer with the appropriate length of cable. Cables to
300 feet [ 90 meters ] are available.
The 4-20mA output is proportional to the flow rate
measuring scale and can drive a load of up to 600 ohms.
The output is isolated from earth ground and circuit low.
Connect the load to the 4-20 mA screw terminals on the
transmitter terminal block, matching polarity as indicated.
NOTE: An additional hole in the transmitter enclosure is
required for outputs. Drill the hole in the the enclosure
bottom taking care not to drive the drill bit into wiring or the
circuit boards with the transmitter.
The pulse output is proportional to the flow rate measuring
scale. This output may be used one of two ways:
♦ To drive a 12V logic device.
♦ To drive a low impedance, 12V device. Minimum
resistance 50 ohms.
The pulse output is adjustable from a range of 0 - 600 Hz
to 0 - 10kHz via control R29 [CTR] located on the left side
of the signal processing PCB in the back of the enclosure.
The pulse width is fixed at 50 µ seconds. CTR “ - ”
represents circuit low. CTR “ + “ represents 12 Vdc pulse
output.
Rev. 04/02 -18- D901/M
PART 2 - ELECTRICAL INSTALLATION
Optional 0 - 1 mA
Output
Line Power
Figure 10
If the 0-1mA output has been installed on the D901/M, the
connections are available on the screw terminal block in
the transmitter. Connect a load of not more than 4 K
ohms to the terminals. Adjust control R20 [1 mA] to fine
tune the output to match the load impedance.
Connect line power to the screw terminals marked AC, AC
and GND in the transmitter. See Figure 10. Utilize the
conduit hole on the left side of the enclosure for this
purpose. Use wiring practices that conform to local codes
(National Electric Code Hand book in the USA). Use only
the standard three wire connection. The ground terminal
grounds the instrument, which is mandatory for safe
operation.
CAUTION: Any other wiring method may be unsafe or
cause improper operation of the instrument.
It is recommended not to run line power with other signal
wires within the same wiring tray or conduit.
NOTE: This instrument requires clean electrical line
power. Do not operate this unit on circuits with noisy
components (i.e. Fluorescent lights, relays, compressors,
variable frequency drives, etc.).
If this option is installed, the D901/M can be operated from
a 12 Vdc source, as long as it is capable of supplying 1
Ampere. Observe proper polarity.
Optional 12 Vdc power
Rev. 04/02 -19- D901/M
PART 3 - STARTUP AND CONFIGURATION
Before Starting the
Instrument
Instrument Startup
Sensitivity Adjustment
Control
Note: The D901/M flow meter system requires a full pipe
of liquid before a successful startup can be completed.
Do not attempt to make adjustments or change
configurations until a full pipe is verified.
Note: If Dow 732 RTV was utilized to couple the
transducers to the pipe, the adhesive must fully cure
before power is applied to the instrument. Dow 732
requires 24 hours to cure satisfactorily. If Dow 111
silicone grease was utilized as a couplant, the curing time
is not required.
Procedure:
1. Verify that all wiring is properly connected and routed.
2. Set the SENSITIVITY Control to -2. This control is
located on the inner door.
3. Apply power. The POWER indicator will illuminate.
4. Adjust the SENSITIVITY control so that the right-most
LED on the SIGNAL STRENGTH bar meter just
illuminates.
Note: It is undesirable to adjust the SENSITIVITY control
to a position higher than necessary, as ambient noise can
also be amplified. This noise can cause false readings to
occur.
5. If the pipe is full of a flowing liquid, the READ indicator
will illuminate and the display will begin reading fluid
velocity as FPS (Feet per Second) or MPS (Meters per
Second). It is normal to have low SIGNAL
STRENGTH and FAULT indication at ZERO flow.
6. If a SIGNAL STRENGTH reading in the green portion
of the bar meter could not be obtained, refer to the
troubleshooting section of this manual.
After a successful flow meter installation and startup
Rev. 04/02 -20- D901/M
PART 3 - STARTUP AND CONFIGURATION
Keypad
Configurations
Modes of Operation
(covered in the previous sections of this manual) the
D901/M can be keypad configured to provide select
engineering unit readings of flow and a scaled 4-20mA
output. Configuration inputs are made via the keypad and
are stored by the microprocessor. The entries are
retained by the flow meter’s backup battery in the event of
power failure. If fluid velocity readings, FPS or MPS, are
the only required measurement keypad configuration is
not required.
The RUN/ENT key toggles the flow meter between the two
modes of operation.
RUN Mode: This is the primary operating mode of the
flow meter. The meter is in RUN mode when the readout
is displaying flow as velocity (FPS, MPS) OR volume
(GPM, LPM, LPS). In RUN mode the outputs are active
and transmitting signals proportional to flow rate.
ENTRY Mode: This mode is used to view or change the
configuration of the flow meter. When the D901/M ships
from the Dynasonics factory, it contains the following
Default configuration:
Each of these parameters may be viewed and/or modified
Default Configuration
Rev. 04/02 -21- D901/M
PARAMETER US METRIC
ID
UNITS
DAMP
Volume/PLS
FULL SCALE
CAL
in the ENTRY Mode. Changes are processed when the
RUN/ENT is pressed and the meter returns to RUN
MODE. In ENTRY Mode flow totalization is suspended
and process outputs are frozen at the last value recorded.
1 Inch 25 mm
1 [FPS] 1 [MPS]
1 Sec 1 Sec
φφ
20 FPS 6.08 MPS
100% 100%
PART 3 - STARTUP AND CONFIGURATION
Pipe I.D. Input
The ID key allows the entry of a pipe’s Internal Diameter.
The D901/M utilizes the I.D. constant to process
volumetric flow rates such as GPM (Gallons per Minute) or
LPM (Liters per Minute). The entry is made as either
inches or mm, dependent on whether the unit is
configured as U.S. units or Metric units.
Press the I.D. key from the ENTRY MODE. The display
will show
This is the present I.D. constant. Enter a new I.D. based
on information obtained from the pipe manufacturer, a
physical measurement or a pipe chart. Some common
pipe sizes and dimensions are located on a series of
charts located in the Appendix of this manual. The
acceptable input range for the I.D. constant is shown in
Table 3.
I.D. US METRIC
Max
Min *
* Pipe sizes less than 1 inch [ 25 mm ] require a Small
Pipe Transducer.
Note: If a decimal value of less than 1 is to be entered,
enter 0 . X X . The zero must precede the decimal value.
Note: If an entered value is out of the acceptable range of
the instrument, an UNDER! or OVER! indication will be
displayed. The meter will not allow any other entries to be
made until a legitimate value is entered.
INSIDE DIAMETER
Table 3
120 Inches 3050 mm
0.25 Inches 6 mm
Rev. 04/02 -22- D901/M
PART 3 - STARTUP AND CONFIGURATION
Full Scale Input
Important!
Volume to Velocity
Conversion
The FULL SCALE key allows the entry of the highest
anticipated fluid velocity. The entry is made as either FPS
(Feet per Second) or MPS (Meters per Second),
dependent on whether the unit is configured as US units
or Metric units. The FULL SCALE input is used by the
D901/M microprocessor to scale the 4-20mA output and
adjust the resolution of the flow rate display.
Acceptable input range for the FULL SCALE constant is
shown in Table 4.
I.D. US METRIC
Max
Min *
* Note: FULL SCALE values below 1.5 FPS [ 0.5 MPS]
are not recommended.
Note: If a decimal value is to be entered, enter 0
The zero must precede the decimal value and no more
than two numbers should be entered after the decimal
value.
Note: If an entered value is out of the acceptable range of
the instrument, a RANGE! indication will be displayed.
The meter will not allow any additional entries to be made
until a legitimate value is entered.
Two useful equations which relate volumetric flow in round
pipes to flow velocity are as follows:
FPS = U.S. GPM X 0.409
ID2 (inches)
MPS = LPM X 21.23
ID
Table 4
40 FPS 8 MPS
n/a n/a
2
(mm)
. X X .
Rev. 04/02 -23- D901/M
PART 3 - STARTUP AND CONFIGURATION
Totalizer Exponent
Input
The VOL. PULSE key allows the entry of a totalizer
exponent. This feature is useful for accommodating a
large accumulated flow. The exponent is a “ X 10 “
multiplier, which can be from 0 (no multiplier) to 2 (X 100).
For example, to totalize in GAL X 100, a VOL. PULSE
value of 2 would be used (10² or 100).
Acceptable input range for the VOL. PULSE constant is
shown in Table 5.
I.D. US METRIC
Max
Min *
* Note: If an entry greater than 2 is attempted, the meter
will display OVER!. If a non- whole number value is
attempted, the meter will display RANGE!. A legitimate
value will need to be entered.
After a VOL. PULSE value is entered, the display will
reflect the unit as 0=10º=X1, 10¹=X10 and 2=10²=X100.
Table 6 illustrates various codes and their display results.
Table 5
2 2
0 0
Table 6
VOL. PULSE
CODE
0
1
2
Rev. 04/02 -24- D901/M
ENG. NOTATION DISPLAY MAXIMUM
10E0 999,999
10E1 999,999
10E2 999,999
PART 3 - STARTUP AND CONFIGURATION
Important Note for
MGD Configurations
Engineering Units
Input
When utilizing the MGD engineering UNITS, the totalizer
defaults to a VOL. PULSE multiplier of 10E3. This is not
reflected on the display. Example: In MGD mode, a VOL.
PULSE entry of 3 will result in an effective accumulation of
E106 gallons (millions of gallons).
The UNITS key allows the selection of measuring units.
Table 7 shows applicable codes for the engineering units
available.
UNITS CODE U.S. METRIC
Table 7
Altering the
CALibration of the
D901/M
1
2
3
Attempting to enter values other than 1, 2 or 3 will result in
an UNDER! or OVER! to be displayed. Non-whole
number values will result in a RANGE! display. A
legitimate value must be entered.
A few factors can influence the readings of the D901/M
flow meter. The CAL entry allows the user to compensate
for flow discrepancies without affecting the factory
calibration. Examples of situations that can cause reading
discrepancies are:
• Operation on liquids with sonic velocity carrying
properties that are different than water.
FPS MPS
GPM LPM
MGD LPS
• Transducers mounted in non-recommended locations.
• Operation on fluids with a large amount of suspended
solids.
Rev. 04/02 -25- D901/M
PART 3 - STARTUP AND CONFIGURATION
By applying a CAL value other than 100%, the factory
calibrated readings will be altered by the percentage
entered. This CAL value will not
20mA or pulse outputs.
For example, if a reading of 175 GPM is displayed and the
known flow rate is 160 GPM, a CAL value of
160 GPM
175 GPM
The D901/M will not allow decimal values to be entered as
a CAL constant, so round to the nearest whole number. In
this case 91%.
Acceptable input ranges for the CAL constant are shown
in Table 8.
I.D. US METRIC
Max
Min
Values outside of this range will result in an OVER! or
UNDER! Display. Non-whole number entries will result in
a RANGE! Display. Enter an appropriate value.
X 100 = 91.4%
Table 8
200% 200%
3% 3%
be reflected in the 4-
Rev. 04/02 -26- D901/M
PART 3 - STARTUP AND CONFIGURATION
Display Damping
System Damping
The TEST Diagnostic
Key
The DAMP key allows the selection of time duration
between display updates. The value selected and entered
will result in display updates of
n x 2 = seconds between updates
Acceptable input ranges for the DAMP constant are
shown in Table 9.
I.D. US METRIC
Max
Min
Values outside of this range will result in an OVER! or
UNDER! display. Entry of an appropriate value is
required.
Note: The D901/M circuit is calibrated at the factory to
provide stable flow readings and outputs under normal
flow conditions and liquid turbulence. In conditions where
stability of readings and/or outputs are unsatisfactory, the
response of the instrument can be changed by adjusting
R17 (DAMP) control located left center on the main circuit
card. Open the inner door of the flow meter and adjust
with a small screwdriver.
The TEST key is used for diagnostic purposes. It displays
the operand presently available at the analog to digital
converter. This value will always be in the range of 0 to
255.
Table 9
5 5
0.5 0.5
Rev. 04/02 -27- D901/M
PART 3 - STARTUP AND CONFIGURATION
System and Totalizer
RESET
Reset the Flow
Totalizer
The RESET key is used for generating a system reset or
to reset the accumulated (totalized) flow. Press the
RESET button from the ENTER Mode. A choice is then
made to :
RESETReset the system
VOL. MULTPress VOL PULSE to
re-set the totalizer to
zero.
If the RESET key is pressed again, all configuration
constants will return to default values.
If the VOL. PULSE key is pressed, the accumulated flow
will be erased and the display will return to zero.
In RUN Mode, pressing the decimal point once will
suspend totalizer accumulation. Pressing the decimal
point again will clear the total. Pressing it a third time will
restart the accumulation from zero.
Rev. 04/02 -28- D901/M
PART 4 - TROUBLE SHOOTING
CONDITION
Unit does not turn “ON” when power is
applied
OVERRANGE light is ON
FAULT light is ON; low SIGNAL
STRENGTH indication
POSSIBLE CAUSE
• Check AC connections.
• Test the fuse
• Ensure the terminal block located in the
upper left corner of the main PCB is
secure
• Verify that ribbon cables between PCBs
are connected.
• Increase the value of the FULL SCALE
constant.
• Verify that fluid velocity is not greater
than 20 FPS [6.08 MPS]
• Ensure that the transducers are properly
mounted to the pipe.
• Verify that transducer connections are
correct
• Ensure that the pipe is full of moving
liquid.
• Increase SENSITIVITY so that rightmost SIGNAL STRENGTH light just
comes ON.
• On cleaner liquids, move the
transducers closer to a 90
• On dirtier liquids, mount the transducers
as described in CASE 3 of Part 2 of this
manual.
• If the pipe has a polyethylene liner,
move the transducers to another area.
The liner may contain an air void at this
location.
(continued)
Rev. 04/02 -29- D901/M
o
pipe elbow.
PART 4 - TROUBLE SHOOTING
FAULT light is ON; low SIGNAL
STRENGTH indication (continued)
Stability of flow readings are
unsatisfactory
Erroneous Reading
• If GND connection and pipe are at
different potentials, ground D901/M to
pipe potential.
• If Variable Frequency Drives are being
utilized, verify that the D901/M obtains a
READ light when the pump turn OFF. If it
does, contact the Dynasonics factory.
• Increase the DAMP constant from keypad.
• Increase the system time constant by
turning R17 (DAMP) clockwise till
readings are satisfactory.
• Move transducers to a location further
from piping tees, elbows, valves, filters,
etc.
• Transducers mounted incorrectly.
• Another local ultrasonic instrument is
operating at about the same frequency
[ consult the Dynasonics factory].
• Presence of large amounts of suspended
solids or aeration. Use CAL constant to
compensate.
• Sources of radiated interference are
present. Apply appropriate shielding.
• An electrically noisy power supply is
powering the D901/M. Power the meter
with a circuit that does not power motors,
ballasts or switching supplies.
Readings of flow at zero fluid velocity
Rev. 04/02 -30- D901/M
• Verify that residual leakage and flow is not
present. [I.e. leaking check valves]
• Verify that SENSITIVITY is not adjusted
too high. With nominal flow running
through the pipe, adjust SENSITIVITY
control till the right-most bar meter light
just comes ON.
PART 5 - APPENDICES
Appendices
Relay Alarm Module Addendum
Pipe Dimension Chart: Cast Iron
Pipe Dimension Chart: Steel, SS, PVC
Velocity to Volumetric Conversion Chart
Statement of Warranty
Customer Service
Rev. 04/02 -31- D901/M
Addendum — Relay Alarm Module
General
This addendum supplies information not covered in the standard Installation and
Operation Manual supplied with the Series D901/D90M Ultrasonic Flowmeter Product.
The Series D901/D90M product enclosed in this carton was purchased with an
external relay alarm module. The module is enclosed and will need to be mounted
seperately from the D901/D90M enclosure.
1. PAYMENT – Terms of payment are effective from the actual date of invoice. If, in the Seller’s
opinion, the financial condition of the Buyer at any time – or any other circumstances – do not justify
the incurrence of production costs of shipment on the terms of payment specified, the Seller may
require partial or full payment in advance. Payment terms are net 30 days unless otherwise stated on
invoice.
2. F.O.B. – All shipments are from Racine, Wisconsin, USA, unless otherwise other stated, and title
transfers to the buyer upon leaving factory.
3. QUOTATION AND PRICES – Quoted prices are firm for 30 days unless s t at ed in the quot at i on a n d
are subject to change without notice after expiration of this period.
4. TAXES – Any applicable sales, use, revenue, excise or other taxes not specifically stated in the
quotation are to be remitted by the Buyer directly to the appropriate regulatory agency.
5. WARRANTY – Seller’s standard published warranty in effect at the time of shipment shall apply.
This warranty is exclusive and is in lieu of all other warranties, express, implied, or statutory, including
the warranty of merchantability.
6. DELIVERY – The Seller shall not be liable for loss or damage of any kind resulting from delay or
inability to deliver on account of flood, fire, labor trouble, riots, civil disturbances, accidents, acts or
orders or regulations of civil or military authorities, sh ortages of material, or any other causes beyond
Seller’s control.
7. PRODUCT CHANGES – In keeping with our continu ing policy of product improvement, we reserve
the right to make changes in our products at any time, without incurring an obligation to change,
replace or upgrade equipment previously shipped.
8. CANCELLATIONS – An order placed by Buyer and accepted by Seller may be cancelled only with
the Seller’s consent and upon terms that will indemnify the Seller against loss.
9. RESTOCKING CHARGE – On standard equipment, the charge is 25%, provided the equipment is
returned within 30 days in acceptable condition with a RGA number. Restocking charges for special
equipment may vary from standard equipment, and will be handled on a case-by-case basis. No
returns will be taken after one year.
Limited Warranty and Disclaimer
Dynasonics, div. of Racine Federated Inc. warrants to the end purchaser, for a period of
one year from the date of shipment from our factory, that all new transmitters and
transducers manufactured by it are free from defects in materials and workmanship.
This warranty does not cover products that have been damaged due to normal use,
misapplication, abuse, lack of maintenance, or improper installation. Dynasonics’
obligation under this warranty is limited to the repair or replacement of a defective
product, at no charge to the end purchaser, if the product is inspected by Dynasonics
and found to be defective. Repair or replacement is at Dynasonics’ discretion. An
authorization number must be obtained from Dynasonics before any product may be
returned for warranty repair or replacement. The product must be thoroughly cleaned
and any process chemicals removed before it will be accepted for return.
The purchaser must determine the applicability of the product for its desired use and
assumes all risks in connection therewith. Dynasonics assumes no responsibility or
liability for any omissions or errors in connection with the use of its products.
Dynasonics will under no circumstances be liable for any incidental, consequential,
contingent or special damages or loss to any person or property arising out of the failure
of any product, component or accessory.
All expressed or implied warranties, including the implied warranty of
merchantability and the implied warranty of fitness for a particular purpose or
application are expressly disclaimed and shall not apply to any products sold or
services rendered by Dynasonics.
The above warranty supersedes and is in lieu of all other warranties, either expressed or
implied and all other obligations or liabilities. No agent or representative has any
authority to alter the terms of this warranty in any way.
RETURN OF EQUIPMENT/SALES INFORMATION
CONTACTS AND PROCEDURES
Customer Service/Application Engineer:
If you have a question regarding order status, placing an order, reviewing applications for
future purchases, or wish to purchase a new flowmeter, please contact our new National
Sales and Marketing Headquarters:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800)535-3569 or
(262)639-6770
FAX: (262)639-2267
Service/Repair Department:
If you already purchased equipment and have an operation problem, require service, or
need to schedule field service, please contact our Service Department:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
PHONE: (800)535-3569 or
(262)639-6770
FAX: (262)639-2267
Return Goods Authorization:
When returning equipment, it is necessary for you to contact our Service Department at
(800)535-3569 or (262)639-6770 to obtain an RGA number for the authority and proper
tracking of your material and its prompt inspection and return. The RGA number should
be noted on the outside of the box. All returns of equipment go to the following address:
DYNASONICS
Division of Racine Federated, Inc.
8635 Washington Avenue
Racine, WI 53406
Attn: RGA #
8635 WASHINGTON AVENUE
RACINE, WI 53406
TOLL-FREE IN NORTH AMERICA.:
TEL: (800) 535-3569 FAX: (800) 732-8354
TEL: (262) 639-6770 FAX: (262) 639-2267
URL: www.dynasonics.com
D901/M O&M REV 04/02
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.