11 1 0 4 W . A i r p o rt Blvd , S u i t e 1 0 8 & 1 4 8
Staf f o r d , T e x as 77 4 7 7 U S A
(2 81 ) 5 6 5 -1118
Fa x ( 2 8 1 ) 5 6 5 -11 1 9
Date: 8/1/2019
WARRANTY
Dynamic Flow Computers warrants to the owner of the Smart Flow Computer that the
product delivered will be free from defects in material and workmanship for one (1) year
following the date of purchase.
This warranty does not cover the product if it is damaged in the process of being installed
or damaged by abuse, accident, misuse, neglect, alteration, repair, disaster, or improper
testing.
If the product is found otherwise defective, Dynamic Flow Computers will replace or
repair the product at no charge, provided that you deliver the product along with a return
material authorization (RMA) number from Dynamic Flow Computers.
Dynamic Flow Computers will not assume any shipping charge or be responsible for
product damage due to improper shipping.
THE ABOVE WARRANTY IS IN LIEU OF ANY OTHER WARRANTY EXPRESS
IMPLIED OR STATUTORY. BUT NOT LIMITED TO ANY WARRANTY OF
MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY
WARRANTY ARISING OUT OF ANY PROPOSAL, SPECIFICATION, OR SAMPLE.
LIMITATION OF LIABILITY:
DYNAMIC FLOW COMPUTERS SHALL HAVE NO LIABILITY FOR ANY
INDIRECT OR SPECULATIVE DAMAGES (INCLUDING, WITHOUT LIMITING
THE FOREGOING, CONSEQUENTIAL, INCIDENTAL AND SPECIAL DAMAGES)
ARISING FROM THE USE OF, OR INABILITY TO USE THIS PRODUCT.
WHETHER ARISING OUT OF CONTRACT, OR UNDER ANY WARRANTY,
IRRESPECTIVE OF WHETHER DFM HAS ADVANCED NOTICE OF THE
POSSIBILITY OF ANY SUCH DAMAGE INCLUDING, BUT NOT LIMITED TO
LOSS OF USE, BUSINESS INTERRUPTION, AND LOSS OF PROFITS.
NOTWITHSTANDING THE FOREGOING, DFM’S TOTAL LIABILITY FOR ALL
CLAIMS UNDER THIS AGREEMENT SHALL NOT EXCEED THE PRICE PAID
FOR THE PRODUCT. THESE LIMITATIONS ON POTENTIAL LIABILITY WERE
AN ESSENTIAL ELEMENT IN SETTING THE PRODUCT PRICE. DFM NEITHER
ASSUMES NOR AUTHORIZES ANYONE TO ASSUME FOR IT ANY OTHER
LIABILITIES
Parts List .................................................................................................................................................. 1-3
Verifying Digital Inputs and Outputs .................................................................................................... 1-40
CHAPTER 2: Data Entry ............................................................................................................................ 2-1
Introduction to the SFC332L Computer Software ................................................................................... 2-1
Configuration File through Window Program ......................................................................................... 2-1
New ..................................................................................................................................................... 2-1
Open .................................................................................................................................................... 2-1
Close .................................................................................................................................................... 2-1
Save ..................................................................................................................................................... 2-1
Save As ................................................................................................................................................ 2-1
Com Settings ....................................................................................................................................... 2-3
Date: 8/1/2019
Meter Configuration ............................................................................................................................ 2-4
Alpha T E-6 Override ........................................................................................................................ 2-35
Wedge Fa Override and Wedge Kd2 Override .................................................................................. 2-35
Venturi C Override ............................................................................................................................ 2-35
End Batch .......................................................................................................................................... 2-35
SYSTEM ........................................................................................................................................... 2-35
HISTORICAL DATA ........................................................................................................................... 2-36
VIEW, CAPTURE AND STORE ..................................................................................................... 2-36
API 14.3................................................................................................................................................... 3-2
User friendly
Flexible
Easy to understand and configure
Rugged
Economical to install and maintain
Accurate
The model SFC332L Smart Flow Computer incorporates all these features. We hope that your experience
with the Smart Flow Computer will be a very pleasant and friendly experience and not intimidating in any
way.
General Description: The SFC332L is a dual meter run bi-directional flow computer for the measurement
of liquid products. Using orifice plate, Venturi, turbine/PD/ultrasonic mass meter, or wedge devices, it can
meter a wide variety of products, such as crude, refined product, LPG/NGL products, products that use
table 24C, ethylene, propylene, and water. Fifty days of previous daily data, fifty previous batch data, and
fifty previous hourly data are stored in the full format type reports. The previous 100 audit trail reports and
100 alarm reports are stored. User formatted reports and user formatted ticket reports are available.
Sixteen different product files are user-configurable with easy switch feature and product scheduling for
batch operation.
Inputs/Outputs: 2 serial connections, RS-232 and RS-485, both of them Modbus ready. The RS-232 can
also be used with serial printer. Inputs: two 4 wire RTD, 4 single ended analog inputs, 4 status inputs and
1 density frequency. Outputs: 2 pulse/switch outputs; 3 switch outputs; and 2 analog outputs. Also
includes a programmable plasma display.
In order to install this software product the following requirements must be met:
Windows Operating System (Win95, Win98, Win98SE, win2000, WinNT, WinXP, Vista,
Windows 7, Windows 8, Windows 10)
For Windows NT, 2000, XP or Vista: Administrator level access to create an ODBC system DNS.
Minimum disk space available: 16 MB.
1 Serial Communication Port
If your computer meets these requirements, you can run the setup file downloaded from our website
Step 1. Go to our website WWW.DYNAMICFLOWCOMPUTERS.COM
Step 2. Click on the “Downloads”
Step 3. Select either Windows or
DOS software based on Step 2.
Step 4. On the new screen
presented to you click on the
application that you are trying to
download. Once you hit the link it
will ask you if you want to run or
save the file in your computer.
Select SAVE. (See illustration 1)
Step 5. The file will start to
transfer to your computer. The
download time depends on your
Internet connection speed and the
type of application that being
downloaded.
Step 6. When the download if
finish. Press the OPEN button to
start the setup process. (See
Illustration)
Step 7. Follow the steps in the
application setup.
The back terminal wiring indicates the overall positions of the terminal plugs and their functions. Though
the back panel’s jumpers are also shown, refer to the next drawing, “Back Panel Jumpers”, for information
on their settings and functions.
The Smart Flow Computer receives its power via the two topmost pins on Terminal P1, on the left of the
terminal board. Also on Terminal P1 are, from top to bottom, inputs from the two turbines and the RS-485
serial connection.
To the right (P4), from top to bottom, are status input 1, density frequency input, and switch output 1 and 2.
Terminal P3, at the lower bottom, handles analog inputs and outputs. These are, in order from right to left,
analog inputs 1-4 and analog outputs 1 and 2.
Terminal P5, top middle, is the RTD terminal block, "100 platinum RTD input".
We will now configure your SFC332L Flow Computer’s inputs and outputs. The flow computer allows the
user to configure the inputs and outputs. (I.e. Analog #1 is pressure for Meter #1). The flow computer will
not use the unassigned inputs.
How to assign a transmitter to an I/O point
1 Click “Configure Device”, configuration menu is prompted
2 On configuration menu, click “Input Assignment”
3 Enter assignments for DP, temperature, pressure, density and spare inputs.
4 Assignment (1-n). Assignments 1-4 are analog inputs attached
to terminal of the back panel. These inputs accept 4-20mA or 1-5
volts input and are suitable for temperature, pressure, density, or spare inputs. An assignment
5 is strictly RTD (temperature) input only for the meter, densitometer or spare. Assignment 7
indicates a density frequency input; it is assigned automatically once you choose live density
frequency input in the setup menu at density type Assignment 10 (module 1) is for
Rosemount multi-variable module only. DP, pressure, and temperature for the meter can be
assigned. When a frequency type primary element is hooked to the flow computer, the Multi
Variable pressure and temperature can be used and the DP becomes a spare input that could
be assigned for strainer differential.
1. Enter the range values: after assigning the inputs scroll down the transducer inputs
assignment menu to scale the 4-20mA. Enter the value at @4mA and @20mA. Enter both
values similar to the way the transmitter is ranged. 1-5 volts is equivalent to 4-20mA. Enter
the 1 volt value at the 4mA, and 5 volt value at 20mA. When the Multi Variable is used the 420 ma scale has no effect on anything and does not need to be configured for that input. The
reason is simply that the flow computer gets the data via digital communication from the
transmitter in engineering units, and therefore a scale is not needed. Normal pressure range is
0-3626, temperature –40 to 1200, DP –250 to 250, or -830 to 830 inches of water.
2. Enter the high and low limits: high limits and low limits are simply the alarm points in
which you would like the flow computer to flag as an alarm condition. Enter these values
with respect to the upper and lower range conditions. Try to avoid creating alarm log when
conditions are normal. For example: If the line condition for the pressure is between 0 to 500
PSIG, then you should program less than zero for low pressure alarm, and 500 or more for
high pressure alarm. High limits are also used in the SCALE for the Modbus variables. The
high limit is equalent to 32767 or 4095. The low limit is not used for calculating the scale.
The scale starts at zero to wherever the high limit value.
3. Set up the fail code:Maintenance and Failure Code values tell the flow computer
to use a default value in the event the transmitter fails. The default value is stored in
Maintenance. There are three outcomes: the transmitter value is always used, no matter
what (Failure Code = 0); the Maintenance value is always used, no matter what
(Failure Code = 1); and the Maintenancevalue is used only when the transmitter’s
value indicates that the transmitter has temporarily failed (Failure Code = 2).
RTD inputs will skip 4-20 mA assignment because RTD is a raw signal of 50 (ohms) to 156. Readings
beyond that range require a 4-20 mA signal to the flow computer or using the built in Rosemount Multi
Variable transmitter. The Rosemount Multivariable has a range of –40-1200 degrees Fahrenheit.
Density coefficients for raw frequency inputs are programmed in this menu. The menu will only show
parameters relevant to the live density selected (i.e., Solartron or UGC, etc.).
Wiring to the flow computer is very straightforward and simple. But still it is very important to get familiar
with the wiring diagram.
Wiring the Analog Inputs:
Typical wiring for analog inputs 1 and 2 are shown in the drawing. Analog inputs 3 and 4 are to the left of
analog 1 and 2. Note that the analog input has only one common return, which is the -Ve signal of power
supply powering the transmitters.
When wiring 1-5 volts, make sure to calibrate the flow computer for the 1-5 volt signal because the flow
computer calibration defaults for the 4-20mA, which is different from the 1-5 volts. JP5 must be cut for 15 volt inputs. The jumpers for analog 1-4 are in order from right to left. It is possible to cut the first two
jumpers for analog 1 & 2 in for 1-5 volts signal and have analog in 3 & 4 as 4-20mA signal. Signal line
impedance provided by our flow computer is less than 250. Therefore, when using a smart transmitter
that requires a minimum of 250 resistance in the loop, an additional resistor at the flow computer end
needs to be installed in series with the 4-20mA loop in order to allow the hand held communicator to talk to
the transmitter.
NOTE: The 4-20mA or 1-5 volt DOES NOT source power to the transmitters. You can use the DC
power feeding the flow computer to power the 4-20mA loop IF that power supply is
FILTERED.
The flow computer shows wiring to RTD 1 and RTD 2. 100 platinum can be used; a temperature range
of -43F to +300F can be measured. RTD 1 is to the right where P5 designation is. In the figure below
notice that each side of the RTD requires two wire connections. When using less than 4 wires a jumper
must be used to make up for the missing lead. Internal excitation current source generated is approximately
7mA. .
RTD can be wired to multi-variable directly through specially provided cable. This wiring diagram
describes wiring directly into the flow computer and not into the multi-variable.
Wiring diagram shows typical Analog output wiring. Notice that analog output will regulate 4-20 mA
current loop but DOES NOT source the power for it. External power is required.
ASSIGN ING/R ANGING THE 4-20MAAN ALOG OUT PUTS :
Go to the I/O assignment main menu and click Analog Output Assignment. A selection menu
is prompted. Select the analog output number, and then enter what the 4-mA output will indicate and the
20 mA. Make sure that the 20 mA assignment value exceeds the upper range limit of what you assigned
the Analog output for, otherwise the analog output will not update beyond 20 mA.
Scroll to Turbine under Wiring and press ENTER. Two drawings above each other will show
typical wiring for turbine meter 1 and turbine meter 2. When dual pickups from the same turbine are
connected, use the inputs for turbine 1 for pickup 1 and turbine 2 for the second pickup coil. When
connecting sine wave directly from the pickup coil make sure the distance from the pickup coil to the flow
computer is very short--less than 50 feet with shielded cable. In the event there is presence of noise, the
distance must be shortened. When connecting sine wave signal, the R11 jumper for meter 1 must be
installed and R3 jumper for meter 2 must be installed. (JP3 and JP2 must be off when using sine wave).
On the other hand, when using square wave, the square wave signal can be sinusoidal but has to be above 5
volts peak to peak with less than 0.4 volts offset in order for the flow computer to read it. R11 and R3 must
be off and JP3 on for meter 1; JP2 must be on for meter 2.
Note: When connecting square wave input, the JP3 and JP2 connect the turbine return to the
flow computer power return. Therefore, signal polarity is very important. Reverse polarity
could result in some damage or power loss. When sine wave is used the signal polarity is
usually of no significance.
The turbine input is immediately under the power input on terminal P1. The third pin down from the top is
Turbine/PD "minus", and below it is Turbine plus. The second pulse input for Turbine/PD meter 2 or the
second pickup coil is below turbine one input on P1. The fifth pin down from the top is turbine 2 "minus"
signal and below it is Turbine/PD 2 plus signal.
Turbine input wiring for passive (dry contact) pulse generators
Some mass flow meters have pulse outputs that do not provide power but instead require
external power, they are referred to as passive outputs, dry outputs, open collector, etc. (For
example the Krohne UFM 3030 Mass meter).
In these cases the wiring should be as shown on the below diagram. The pull up resistor can be
adjusted to limit the current sink by the Mass meter. For Turbine Input 1 JP3 must be ON and
R11 OFF and if using Turbine Input 2 then JP2 must be ON and R3 OFF.
When using a live densitometer input with frequency signal, the signal can be brought into the Smart Flow
Computer in its raw form. The Smart Flow Computer accepts a sine wave or square with or without DC
offset. Example for density wiring can be seen in the wiring diagram. Three are two drawings, one with
barrier and the other without. Barriers are used for area classification. Notice that the RTD wiring is also
drawn to show how to hook the density RTD signal.
Note: When wiring the density input polarity is of significance and reverse polarity could
result in some damage or power loss. The density signal is on connector P4, the
third and fourth pin down from the top. The third pin down is density plus, the
fourth down is density minus. When Density input is 4-20mA it should be
connected as a regular 4-20mA signal to the analog input and not the density
frequency input.
The RS-232 is not located on the terminal board. The RS-232 is a green 5-pin terminal block with screw
type connector located on the display side of the enclosure. Go to Wiring | RS-232. Termination
jumpers for the RS-232 are located at the top corner of the board on the same side of the RS-232 connector.
The two jumpers at the top are for terminating the transmit line and below it is the receive line.
The RS-232 port can be used for printing reports, Modbus communication, or interfacing
to the configuration program. If the port is configured as printer port in the flow
computer Note: Twisted shielded cable is required.
WARNING: When the RS-232 terminal is used with a modem, external protection on the
phone line is required. Jumper DTR to DSR, RTS to CTS, and disable software
handshake on the modem RS232 connection
Date: 8/1/2019
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.