Powered From The DyNet Network - Mains supply not required
Optically Isolated between the two communication Ports – 2.5KV
surge isolation.
Allows KNX integration to Philips Dynalite lighting control
system
Powerful Internal PLC - Custom scripts can be written to provide
process control based on conditional logic. Feature allows the
gateway to before logical calculation from messages received and
then peform the required reaction.
DIN Rail Mounting - 6 Units wide.
Warning – This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be required to take
adequate measures.
Read Instructions – We recommend that you read this Instruction Manual prior
to commencement of installation.
Special Programming – This device will only operate in basic modes unless
programmed via a computer. If programming is required, contact your local
agent for details. Once the data cable is connected to the devices, the factory
default settings will allow any control panel to operate all channels in all
controllers.
Mounting Location – Install in a dry, well-ventilated location.
Data Cable – Use screened, stranded RS485 data cable with three twisted
pairs. Segregate from mains cables by 300mm. Connect devices in a ‘daisy
chain’Do not cut or terminate liv e data cables.
Correct cabling – Insure that correct polarity of the KNX and DyNet ports are
maintained and that only approved cables are used for each port.
1. Mount the device on a DIN rail inside an appropriate enclosure.
2. Ensure the both Dynet and KNX networks are powered down before beginning termination
3. Connect data cables to the device as per diagrams. Note that the device is powered from the DyNet network segment that is connected to Port 1.
4. Connect KNX network to second port of gateway. Ensure that correct polarity is maintained.
5. Power up both Dynet and KNX networks.
6. The gateway is now ready to be commissioned.
DDNG-KNX
Network Gateway
Installation Manual

example net work topology
RS485 Serial Port 1: 1 x RS485 un-terminated, consisting of 1 x 6 way terminal block
1 x AUX programmable dry contact input
KNX Serial Port 2: 1 x KNX consisting of 1 x 2 pole polarized connector
Serial Port Isolation: Opto Isolated to 2.5KV Surge
User Controls: Service Switch, Diagnostic LED for Dynet and KNX network
Internal Controls: Programmable Logic Controller, 64 Tasks
Operating Environment: 0º to 40ºC ambient temperature, 0% to 90% RH non condensing
Power Consumption: Max15mA from the DyNet network at 12-15VDC
Max 5mA from KNX/EIB
Compliance: CE, C-Tick, CISPR22 Class B emissions, immunity as per IEC 60335 / 730
Construction: Polycarbonate DIN Rail enclosure (6 unit)
Dimensions: H 86mm x W 105mm x D 66mm
Weight: 0.8kg
DDNG-KNX Instruction Manual Rev A.doc Specifications subject to change without notice
Philips Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333