Dynalite DDNG-KNX Installation Manual

features
Powered From The DyNet Network - Mains supply not required Optically Isolated between the two communication Ports – 2.5KV
surge isolation.
Allows KNX integration to Philips Dynalite lighting control
system
Powerful Internal PLC - Custom scripts can be written to provide
process control based on conditional logic. Feature allows the gateway to before logical calculation from messages received and then peform the required reaction.
DIN Rail Mounting - 6 Units wide.
Warning – This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Read Instructions We recommend that you read this Instruction Manual prior to commencement of installation.
Special Programming This device will only operate in basic modes unless programmed via a computer. If programming is required, contact your local agent for details. Once the data cable is connected to the devices, the factory default settings will allow any control panel to operate all channels in all controllers.
Mounting Location – Install in a dry, well-ventilated location. Data Cable – Use screened, stranded RS485 data cable with three twisted
pairs. Segregate from mains cables by 300mm. Connect devices in a ‘daisy chain’Do not cut or terminate liv e data cables.
Correct cabling Insure that correct polarity of the KNX and DyNet ports are maintained and that only approved cables are used for each port.
electrical diagram
1. Mount the device on a DIN rail inside an appropriate enclosure.
2. Ensure the both Dynet and KNX networks are powered down before beginning termination
3. Connect data cables to the device as per diagrams. Note that the device is powered from the DyNet network segment that is connected to Port 1.
4. Connect KNX network to second port of gateway. Ensure that correct polarity is maintained.
5. Power up both Dynet and KNX networks.
6. The gateway is now ready to be commissioned.
DDNG-KNX
Network Gateway
Installation Manual
installation steps
example net work topology
product specifications
RS485 Serial Port 1: 1 x RS485 un-terminated, consisting of 1 x 6 way terminal block 1 x AUX programmable dry contact input
KNX Serial Port 2: 1 x KNX consisting of 1 x 2 pole polarized connector Serial Port Isolation: Opto Isolated to 2.5KV Surge User Controls: Service Switch, Diagnostic LED for Dynet and KNX network Internal Controls: Programmable Logic Controller, 64 Tasks Operating Environment: 0º to 40ºC ambient temperature, 0% to 90% RH non condensing Power Consumption: Max15mA from the DyNet network at 12-15VDC
Max 5mA from KNX/EIB
Compliance: CE, C-Tick, CISPR22 Class B emissions, immunity as per IEC 60335 / 730 Construction: Polycarbonate DIN Rail enclosure (6 unit) Dimensions: H 86mm x W 105mm x D 66mm Weight: 0.8kg
DDNG-KNX Instruction Manual Rev A.doc Specifications subject to change without notice
Philips Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333