DynaGen GSC300 User Manual

Installation and User Manual for the GSC300 Auto Start Engine Controller
Auto Start Engine Controller
GSC300
File: GSC300rev2.4.doc Dec. 08, 2005
Thank You For Purchasing This DynaGen Product
Please Read Manual Before Installing Unit
Receipt of Shipment and Warranty Return Information
Upon receipt of shipment, carefully remove the unit from the shipping container and thoroughly examine the unit for shipping damage. In case of damage, immediately contact the carrier and request that an inspection report be filed prior to contacting DynaGen.
All returned items are to be shipped prepaid and include a Return Material Authorization (RMA) number issued by DynaGen. RMA forms are available by contacting DynaGen Technical Support through the contact methods listed below.
2
Limited Warranty
DynaGen will repair or replace any GSC300 controller which proves to be defective under normal and proper use within Three Years from the date of shipment. This constitutes the only warranty and no other warranty shall be implied.
We welcome your comments and suggestions. Please contact us at:
DynaGen Technologies Inc. Phone: 1-888-396-2436
(902) 562 0133 Fax: (902) 567 0633 Email: support@dynagen.ca WEB SITE: www.dynagen.ca
Operating & Installation Manual for the GSC300 Engine Controller
SPECIFICATIONS FOR THE GSC300
Operating Voltage: 7 to 30VDC continuous, with zero volts cranking dropout protection
Operating Temperature: -40 to +85ºC
Physical Dimensions: 4.5"(H) x 5.5"(W) x 1.25"(D)
Actual Unit Weight: 0.458 lbs
Enclosure: High Impact Resistant, Injection Molded Plastic Enclosure
Front Panel Indications
-High intensity LED’s with regulated brightness
LCD Display:
-Ultra-bright, Backlight LCD display with optimum viewing angle of 0 to -25º from perpendicular
-Display Size (mm): 8 (W) x 32 (H) x 12.8 (D) x 16 characters
Adjustments
Warm-up: 0 - 200 seconds (After Oil Bypass Feature)
Cool-Down: 0 - 255 seconds
Crank Disconnect: 12 to 140Hz (Generator Output Version)
44 to 300Hz (Magnetic Pick-up Version)
Overspeed: 60 - 4156Hz (Generator Output Version)
300 - 8492Hz (Magnetic Pick-up Version)
Crank Rest: 3 - 32 seconds
Delay on Start: 0 – 59 seconds
Crank Tries: 1 to 10
Oil Bypass: 15 – 55 seconds
Low Battery Indication: 7 – 35 VDC
3
Operating & Installation Manual for the GSC300 Engine Controller
Timer adjustments
Glow Plug/Preheat: 0 - 255 seconds
Energize To Stop (ETS): Energizes for 15 seconds on failures, or energizes until 5 seconds after
engine speed goes to zero upon removing power from Start/Stop terminal or removing the unit from manual mode using the front panel buttons.
Inputs
Speed Sensing:
-Optional Generator Output Speed Sensing or Magnetic Pick-Up Model (Specified by customer at time of order)
Maximum Input Voltage: 300Vrms
Minimum Input Voltage: 0.7Vrms(Generator Output Sensing),
0.1Vrms(Magnetic Pick-Up version)
-60Hz Rejection Filter Included
-Loss of Speed Signal Included
Sender/Failure Inputs:
-Oil Pressure, Coolant Temperature, Fuel Level/Auxiliary Input
-Accepts standard industry low impedance (0-500 ohm) sender inputs (VDO, Stewart-Warner, Datcom, Murphy, etc.)
-Data entry available for custom sender inputs
-Can be configured to accept a switched gauge failure through the PC interface
-Failure points adjustable
4
Operating & Installation Manual for the GSC300 Engine Controller
Protection
-Three on-board replaceable 40A fuses protect Fuel, Crank, and Timer Outputs
-Reverse polarity protected
-Short circuit & overload protection on annunciation outputs
-Inputs are electrostatic discharge protected
-Maximum power supply surge before damage: 1500V for 250us
Outputs
-All outputs positive switched (sourcing)
-Fuel, Crank, and Timer Outputs: 40A each, using standard 40A automotive relays
-Annunciation Outputs: 300mA individually, 350mA combined
Connections
-Removable terminal block for annunciation outputs and low power connections
-0.25" spade terminals for quick connections on all other connections
Programming
-Intuitive windows based software interface utilizing the parallel port of your PC
-Option of programming through 3-button interface (limited parameter adjustment) on the front panel or the PC Interface that has full parameter programming ability.
-Needs no power to program using the PC Interface –uses power from parallel port of PC
-Specifications May Change Without Notification
5
Operating & Installation Manual for the GSC300 Engine Controller
GSC300 Product Number Identification
The GSC300 series product numbering scheme provides significant information pertaining to a specific model. The Product Number Identification Table (see Table 1) provides the required interpretation information. An example is offered to initially simplify the process.
A product number GSC300-X-XX-XX would consist of a combination of information from the following table.
TABLE1: IDENTIFICATION TABLE
Position 1-6
Series
GSC300=GSC300
Position 8
Speed Range
L=Low
H=High
Position 10-11 Position 13-14
DC Voltage
12=12VDC 24=24VDC
LX=Customized
Labeling
LS=Standard
6
Example: The product number GSC300-L-12-LS would be described as follows:
A GSC300 series automatic engine controller configured for a 12 VDC system. The controller is factory configured for low speed range (generator speed range) which includes standard labeling.
A GSC300 serial number would be displayed as:
GSC300-L-12-LS-00000
Operating & Installation Manual for the GSC300 Engine Controller
WIRING INSTALLATION GUIDELINES
Danger: Never work on the engine while its power is on. This controller does
not generate a warning signal prior to automatic engine start. Warning signs should be placed on engine equipment indicating this important safety measure.
INSTRUCTIONS
Following these instructions will help avoid common installation problems during wiring and setup.
Battery must be disconnected before any wiring connections are made.
Wire length from the engine to the controller should not exceed 6 meters (20 feet).
Wiring size and type should be as specified below. Use stranded wire, since solid wire has a tendency to crack, break and loosen over time.
TYPES AND SIZES
Terminal Wire Size
(AWG)
1 12 40A Fuel Output Terminal 2 12 40A Auto(Battery +) Terminal Connection 3 12 40A Auto(Battery +) Terminal Connection 4 12 40A Crank Output Terminal 5 12 40A Ground Terminal Connection 6 12 40A Ground Terminal Connection 7 12 40A Preheat/ETS Terminal 8 12 40A Preheat/ETS Terminal
9 18 100mA Speed Signal Connection 10 18 100mA Speed Signal Connection 11 18 300mA Overcrank Output 12 18 300mA Overspeed Output 13 18 300mA High Temp Output 14 18 300mA Low Oil Output 15 18 300mA Low Battery Output 16 18 300mA Engine Run Output 17 18 100mA Not in Auto Output 18 18 300mA General Failure Output 19 18 7mA Start/Stop Input 20 18 7mA Oil Pressure Sender/Switch Input 21 18 7mA Temperature Sender/Switch Input 22 18 7mA Fuel Level/Auxiliary Sender/Switch
Current max. Function
Input
7
Operating & Installation Manual for the GSC300 Engine Controller
WIRING GUIDELINES
1. DO NOT use wire smaller than 18 AWG.
IMPORTANT: The connections supplying DC power to the GSC300 panel should preferably run directly
2.
from the battery posts with no splices or other connections. Avoid using chassis (aluminum or iron engine parts), as return conductor for battery negative voltage. Copper wiring is recommended. Failure to follow the above may result in erratic operation due to large voltage drops across wiring connections. A small fuse should be placed at the battery terminal to provide 12 volts to the Remote Start Contacts to ensure that a short along this line will not cause any damage.
3. DO NOT exceed the maximum rated current and voltage on each of the controller outputs. Do not exceed 40A each for the Fuel Output, Crank Output or Preheat Output. Do not exceed 300mA individually, or 350mA combined, for the General Fault Output or Annunciation Outputs.
4. DO NOT short Crank Output or Fuel Output to ground. This will cause damage to the unit.
To verify the operation of engine controller outputs, measure voltage (i.e. meter in volts) when outputs
5.
should be ON.
To verify the operation of the Preheat Output, measure the resistance between the Preheat terminals when
6.
the Preheat Output should be ON. At this time there should be a closed circuit. When the output is supposed to be OFF there should be an open circuit between the terminals.
8
Operating & Installation Manual for the GSC300 Engine Controller
GSC300 12/24VDC SYSTEM OPERATION
9
The GSC300 controller is designed to operate in either 12 or 24 VDC system voltages. When operating in 12VDC systems the fuel, crank and preheat/ets relays need to be the proper 12VDC relay type. When operating in 24VDC systems these relays need to be the proper 24VDC relay type. Contact the factory if relays are required.
Approved relays for 12 or 24VDC system operation are as follows:
AZETTLER – AZ973-1C-12DC for 12VDC operation
AZETTLER – AZ973-1C-24DC for 24VDC operation
Operating & Installation Manual for the GSC300 Engine Controller
TERMINAL DESCRIPTION
Term # Description
1 Fuel Output provides 40A maximum. Fuel Output closes to +12/24 VDC when start signal is
actuated, and opens when either an engine failure is detected or when Cool-Down period has
ended. 2 Auto Terminal. Connection point on the unit for +V Battery power connection 3 Auto Terminal. Connection point on the unit for +V Battery power connection 4 Crank Output provides 40A maximum. Crank Output closes to +12/24VDC during cranking,
and opens when the engine has started, or during Crank Rest. 5
6
7 Preheat/ETS Output closes to terminal 8 during Preheat or ETS period. (Dry contacts between
8 Preheat/ETS Output closes to terminal 8 during Preheat or ETS period. (Dry contacts between
9 Speed 1. Speed Signal Input for Crank Disconnect, Engine Run, and Overspeed sensing. 300
10 Speed 2. Speed Signal Input for Crank Disconnect, Engine Run, and Overspeed sensing. 300
11 Overcrank Annunciation Output closes to +12/24VDC on Overcrank Failure. 300mA max. 12 Overspeed Annunciation Output closes to +12/24VDC on Overspeed Failure. 300mA max. 13 High Temp Output closes to +12/24VDC upon High Temp Failure. 300mA max. 14 Low Oil Output closes to +12/24VDC upon Low Oil Failure. 300mA max. 15 Low Battery Output closes to +12/24VDC on Low Battery Condition. 300mA max. 16 Engine Run Output closes to +12/24VDC on Engine Run Condition. 300mA max. 17 Not In Auto Output closes to +12/24VDC when unit is not in auto. 300mA max. 18 General Failure Output closes to +12/24VDC on a General Failure. 300mA max. 19 Start Stop Input. Apply +12/24VDC to this terminal while unit is in Auto Mode to start engine.
20 Oil pressure sender/switch. This oil pressure sender/switch can be N.O. or N.C., meaning that
21 Temperature sender/switch. For proper operation, this input must be connected to ground via a
22 Fuel Level/Auxiliary Failure Input. For proper operation, this input must be connected to
Battery Ground connection for the controller module. A good ground connection, directly from
the battery, is required for proper operation.
Battery Ground connection for the controller module. A good ground connection, directly from
the battery, is required for proper operation.
terminals 7 & 8)
terminals 7 & 8)
VAC max. input voltage.
VAC max. input voltage.
Remove +12/24VDC to stop engine or enter Cool-Down mode.
for N.O., ground is a failure while +Vbatt is Engine OK, for N.C., ground means engine OK,
and +Vbatt means failure. The operation (failure point) of the output in response to the sender
can be set using the PC Interface.
sender/switch. The operation (failure point) of the output in response to the sender can be set
using the PC Interface.
ground via a sender/switch. The operation (failure point) of the output in response to the sender
can be set using the PC Interface.
10
Operating & Installation Manual for the GSC300 Engine Controller
Wiring Connection Diagram
11
Operating & Installation Manual for the GSC300 Engine Controller
Back Panel Layout
12
Operating & Installation Manual for the GSC300 Engine Controller
CONTROLLER OVERVIEW
The GSC300 Features the Following Functions:
1. Controller Programming Adjustability
2. General Fault Conditions
3. Not In Auto
4. Low Battery Voltage Alarm
5. Oil Pressure Input
6. Coolant Temperature Input
7. Fuel Level/Auxiliary Input
8. Speed Signal Sensing
9. Adjustable Input Programming
10. Magnetic Pick-Up Capability Option
1: CONTROLLER PROGRAMMING ADJUSTABILITY: Adjustable Parameter Ranges:
Crank Disconnect: 12 to 140Hz (Generator Output Version)
44 to 300Hz (Magnetic Pick-up Version)
Overspeed: 60 - 4156Hz (Generator Output Version) -OR DISABLED BY PC INTERFACE
300 - 8492Hz (Magnetic Pick-up Version) -OR DISABLED BY PC INTERFACE
Crank Tries: 1 to 10
Crank/Rest: 3 to 32 seconds
NOTE: If the engine speed seen by the controller does not go to zero during Crank Rest, the controller will
wait until the speed goes to zero before re-initiating the cranking sequence.
2: GENERAL FAULT CONDITIONS: The following scenarios can cause the unit to enter the
general fault condition:
Low Fuel/Auxiliary Failure (“XTR_FAIL”) Low Oil High Coolant Temperature Overcrank Overspeed Loss of Speed (“SPDLOSS”)
The General Fault output is rated 300mA Max.
13
Operating & Installation Manual for the GSC300 Engine Controller
14
3: NOT IN AUTO: When the controller is in the OFF Mode, the NOT IN AUTO LED will illuminate and
the NOT IN AUTO Output will close to +Vbatt, indicating the controller is not in the AUTO Mode. The LCD display will read “OFF”, however the backlight on the LCD display will not be ON.
NOTE: and LED indications to function properly.
+ Battery must be permanently connected to the AUTO terminal for the NOT IN AUTO condition
4: LOW BATTERY VOLTAGE ALARM: In the event the battery voltage drops below the user
defined set point which can be between 7 and 35VDC, the engine controller displays a Low Battery Condition. The Low Battery Voltage condition can occur when the controller is in the AUTO or MANUAL/TEST Mode, but will only occur in the running state or while in standby in AUTO. The LCD display will show the message: “LOW_BATT”
5: LOW OIL INPUT: The Low Oil Input can accept data from a sender or signal from a N.O. or N.C. type
switch. N.O. means that ground would be a failure, +5V would be “Engine OK”. N.C. means that ground would be “Engine OK”, and +5V would be a failure. The operation of the oil input is set in PSI by the PC Interface and is the only input which has selectable operation in this manner.
Note:
The oil input failure is disabled during the Oil Bypass time.
6: HIGH TEMPERATURE INPUT: For proper operation this must be of the standard N.O. type where
with a switch or sender, a ground would be seen as a failure, and a +5V would be seen as “Engine OK”. This can be used with a sender or switch and when using a sender the failure point in degree Fahrenheit can be adjusted using the PC Interface.
7: FUEL LEVEL/AUXILIARY INPUT: For proper operation while using a switch, the switch must
be the N.O. type which closes to ground upon failure. If this input is used as a sender, no failure will be indicated. The sender option is solely for Fuel Level/Auxiliary Level Display on the LCD.
8: SPEED SIGNAL SENSITIVITY: The controller will accept to a maximum of 300 VAC, 60 Hz from
direct generator output for speed sensing. The following values are minimal recommended voltages for speed signal sensing: 20 HZ - .075 V (75mV) 60 HZ - .6V (600mV)
9: HOUR METER: The controller can display a log of generator run times. Run times will be displayed on
the controllers display screen. The display represents both hours and minutes in the form 123456:7. The last digit on the hour meter will represent the time in 1/10 of an hour. Each increment would represent 6 minutes. For example if the hour meter displays 000010:5 than the generator had ran for 10 hours and 30 minutes. Please note that although the hour meter displays time in hours and minutes, it will record up to the nearest second. If the generator was operated for only 3 minutes, the display may not increment but this time would be stored and added to the next generator run time.
10: MAGNETIC PICK-UP CAPABILITY OPTION: The Magnetic Pick-Up Capability Option can
be provided on the GSC300 upon request. Frequency will not be displayed on the LCD if this option is chosen.
Operating & Installation Manual for the GSC300 Engine Controller
LED LAYOUT
Front View of GSC300
15
Operating & Installation Manual for the GSC300 Engine Controller
LED INDICATIONS
FRONT PANEL LED INDICATIONS
LED Appearance Condition/Failure Not in Auto LED is ON. No LED’s ON Steady Low Oil LED Flashing Low Oil LED Steady High Temperature LED Steady Overcrank LED
Steady Overspeed LED
Flashing Overspeed LED
Was Engine Cranking?
Was Engine Running?
Steady Engine Running LED
Flashing Engine Running LED
Unit is in OFF state. “OFF”, no +12/24VDC to “Auto” terminal. Low Oil Pressure Failure Auxiliary Input Failure Over Temperature Failure Engine would not start after specified Crank tries. Speed Signal present above Overspeed setting
No speed signal available while Cranking
The speed signal was Zero while running. The engine has stalled, or the speed signal has been lost. Engine Controller is in running mode of operation. Crank Rest period. Cranking will resume soon.
16
Operating & Installation Manual for the GSC300 Engine Controller
17
Programming The GSC300 Settings
Using the Front Panel Interface:
The following table shows the LED’s that correspond to the various settings of the various parameters. To enter the controller into Program Mode, you need to turn the small switch at the bottom edge of the controller to the program position. This Mode Switch can be set using a ballpoint pen or such to allow the controller to be put into Program Mode. The first three LED’s (3, 2 & 1) correspond to which parameter is being adjusted, and the next three (6, 5 & 4) LED’s show the setting for that particular parameter. The picture on the next page shows the LED numbering and the location of the Mode Switch.
LED's 6, 5 & 4
Parameter
LED's 3, 2 & 1
○○○ ○○● ○●○ ○●● ●○○ ●○● ●●○ ●●●
Crank Tries
Crank Time
Rest Time
Preheat Time
Cool-Down
Preheat/ETS/
Warm-Up Warm-Up
○○○ 1 2 3 4 5 6 7 8
○○● 5 10 15 20 25 30 35 40
○●○ 0 5 10 15 20 25 30 35
○●● 0 5 10 15 20 25 30 35
●○○ 0 32 64 96 128 160 192 224
●○●
Preheat ETS Warm-Up
N/A N/A N/A N/A N/A
●●○ 0 28 56 84 112 140 168 196
To scroll through the parameters simply press the Auto button on the front panel of the GSC300. To scroll through the range of values for that parameter simply press the Manual Start button. To set the value into the controller’s memory, press the OFF button. In this manner the settings of the controller can be adjusted by simply using the three buttons on the front panel of the controller. Be sure to press the OFF button when you have selected the parameter value wanted. By not pressing the off button to set the value, the value of that parameter will not be stored into memory and remain at it’s previous setting.
Operating & Installation Manual for the GSC300 Engine Controller
Numbering Of LED’s and Location of Mode Switch
18
Programming Using the PC Interface
The GSC300 can also be programmed using the PC interface. Detailed instructions on the PC interface are included with the GSC300 Configurator software. A sample interface screen is illustrated on the following page.
Operating & Installation Manual for the GSC300 Engine Controller
Sample Screen From PC Interface
19
Operating & Installation Manual for the GSC300 Engine Controller
TROUBLESHOOTING GUIDELINES
TROUBLE POSSIBLE CAUSE SUGGESTED ACTION
Unit does not operate when powered to test mode
Engine starts and immediately goes into Overspeed shutdown
Engine does not crank
Engine cranks but does not start
Power leads to unit are reversed Confirm correct wiring for ground and +bat,
and re-attempt testing. Bad ground connection from engine to controller unit. Improper speed range Check to ensure that the speed sensing
Battery is low or terminals are dirty Clean terminals and re-charge battery Crank circuitry wiring improperly connected Bad ground connection from engine to controller Crank relay damaged. Or on board fuse is blown
Out of fuel Check fuel level, add fuel if necessary Ignition control wiring not installed properly Fuel relay damaged Check fuel relay and replace if damaged.
Run wire directly from battery - to the
ground terminal #11on controller unit.
wires of the controller are connected to the
generator output.
Refer to engine control wiring section and
check crank connections
Run wire directly from battery - to the
ground terminal #5 & 6, on controller unit.
Check wiring, in line fuse and slave relay.
Replace fuse, relay and re-test controller
again
Refer to engine control wiring section and
check ignition connections
20
Engine starts but shuts
down after “Oil Bypass
period” due to low oil/high temp/Aux input
Fault LED works OK, but general fault output does not activate Flashing Overspeed LED
Flashing Run LED & Solid Oil LED
Solid Oil LED immediately on start-up, without engine actually cranking or starting.
Display Parameter for Temperature, Oil or Fuel displayed as >>> or <<<
TM
Oil/Temp/Auxiliary input wiring improperly connected.
Fault (short or overload) on general fault output.
Speed signal improperly connected, missing, or damaged. Crank output damaged, not working Check wiring and replace controller if
Starter or starter solenoid damaged Replace/repair damaged starter or starter
Oil switch not closed as it should be Check oil switch wiring and switch to make
False speed signal being detected by controller. This problem can sometimes occur in installations where there is AC power from inverters near generator output lines connected to the speed signal cable.
Parameter is >>> ABOVE or <<< BELOW specified manufacturer sender range.
Check wiring for proper connections.
Check for fault, once fault is corrected then
output operation resumes.
Check speed signal wiring; replace
damaged speed signal source.
necessary
solenoid.
sure the switch is closing when there is no
oil pressure
Install a small step down transformer
between the speed sensing wires and the
generator output.
If the neutral from the generator output is
not grounded, attach it to ground
Install sender with proper range
specifications.
Warm-Up Feature appears longer then time setting.
Warm-Up Feature time setting does not begin until the Oil Bypass Time has expired.
Operating & Installation Manual for the GSC300 Engine Controller
Re-adjust Oil Bypass and/or Warm-Up
timing.
21
TECHNICAL NOTES ON FREQUENTLY ASKED QUESTIONS
1. Controller Memory Clear Time
The GSC300 needs 10 seconds for its memory to clear. When the power to the controller is turned off and then back on again without waiting a few seconds to clear the memory, a loss of speed will be indicated by the GSC300 because the controller remains in run mode and senses that the generator has stopped. This would be indicated by a Flashing Overspeed LED. By leaving the GSC300 OFF for 10 seconds before it is returned to the Auto setting the memory will be cleared and it will function as intended.
2. Step-Down Transformer Use On Speed Sensing Cable With Inverter Systems
In some applications engine controllers are used on generators where there is no utility connection and inverters are used to provide AC power instead of a utility. Inverters can produce harmonics that can cause small AC signals to appear on wires that are near any power lines being fed by the inverter. If the generator output wires are located close to a line being powered by an inverter, a small AC signal can appear on the generator output lines when the inverter is on. This signal can cause the engine controller to react as if the generator is running if the speed sensing wires are connected to the generator output lines. This small AC signal can cause the controller to appear to have a Low Oil Failure when the remote start contacts are closed or the controller is put in the manual/test mode. The controller may think the generator is already running and immediately check to make sure there is oil pressure. Since the engine really hasn’t started yet, there is no oil pressure and the controller sees a low oil fault. This is seen as the Oil LED turning on solid even before the engine starts to engage the starter.
Without this false speed signal the controller will not look for oil pressure until the engine has started to run and the crank disengages if oil verification is disabled. Simply installing a small transformer between the generator output and the speed sensing terminals on the controller can eliminate this false speed signal. This transformer should be rated for 120 or 240 volts on the input or primary coil (depending on the generator output voltage you are using for speed sensing), and have an output voltage of around 12VAC on the secondary of the transformer. The two wires from the secondary of the transformer are connected to the two wires of the speed sensing terminals on the GSC300 controller. The step-down transformer acts to reduce the false speed signal on the line to a level that the engine controller will not recognize as the engine running. A common size transformer that would serve this purpose would be 24VA
.
Operating & Installation Manual for the GSC300 Engine Controller
Loading...